Loading...
HomeMy WebLinkAbout23-23520 837 Pole Line Rd-Heaven Scent Laundrymat-City Approved plans OF TMNvMLIS �INYFAUfj City of Twin Falls �0 � General Inspection Notes �0ERVtN0 SERV►NG UP) a) NOTE: This is not a complete list and is not inclusive of all construction methods, materials or practices. These checklists are intended to serve as a guide for the items that cause the most issues during inspections and promote +=, consistency in the application of the codes & standard practices. Compliance with all the provisions of applicable codes shall be required. O The information in the checklists is not, or was it ever intended to be, all inclusive. It does not include all code or individual plan requirements. It is intended to reflect local policies, procedures & practices within the City of Twin Falls. These checklists do not waive any specific code requirements not listed or allow for the decrease in the requirements of an engineered design. It also does not add requirements where the minimum of the code has been met. Z This page and all approved plans, associated documents, revisions & changes to the plans must be maintained on site and available for review at all times. FIRE BUILDING FINAL INSPECTION INFORMATION O Fire Alarm Inspection: Footing/Foundation Inspection: COMMERCIAL OCCUPANCY • * Fire alarm plans must be approved by the State Fire Marshal's office or if applicable the Twin Falls * All re-bar must be tied in place at time of inspection. Fire Marshal prior to installation and inspection. * All hold down anchors installed properly. Final inspections are required by multiple City Departments/Inspectors prior t0 * Fire alarm system must be wired to call out from a land line, or with a cell dialer. (Voice over IP is not allowed). Shear Inspection: getting your Certificate of Occupancy. * Fire alarm system must be live and capable of calling the Twin Falls Dispatch Center on the day of * All hold downs must be installed per approved plans and manufacturers installation guide. testing. * Fasteners should not be overdriven and shiners should be removed and/or replaced. Make sure to have the approved set of plans and inspection card on site for all inspections. * Install the correct type of fastener at the correct spacing. Fire Sprinkler Inspection: If you have Special Inspections: Once the required special inspections have been completed a final * Fire sprinkler plans must be approved by the State Fire Marshal's office prior to installation and Framing Inspection: report needs to be submitted to the building department certifying corrections of any discrepancies inspection. Underground fire sprinkler line must be inspected by the Twin Falls Fire Department prior * Accessibility standards are in compliance. (ICC A117.1-2009) noted in the special inspection reports.This final report can be submitted any time before requesting [ ^ to be covered. * Required load paths to footing for all load points are installed. occupancy. �+ * Pipe or hose used for flushing the underground sprinkler line must be secure, incapable of * Stair rise and treads must meet code requirements. * Required Site Work inspections may be requested and completed as the work is done or as required movement, and is deemed safe by the inspector. *Min rise 4", Max rise 7", Max tread 11" by the specific department by contact the following: * Rough to cover inspection and hydro testing must be completed before covering or tenting the *Min nosing is 3/4", Max nosing is 1 1/4" and cannot differ in length by more than 3/8" above ground fire sprinkler system. * Provide required up-lift protection for all trusses. - Planning&Zoning (parking and landscaping) Planner-208-735-7270 or Office-208-735-7267 Kitchen Hood Inspections: Final Inspection: - Engineering (Retention, curb, gutter, sidewalk, drive approaches) * Fire suppression system must be installed and ready for trip test (trip link, balloons, etc.) prior to * Landings to meet minimum code requirements. (Doors 1010.1.6, Ramps 1012.6, Stairs 1011.6) Lab inspection line 208-735-3446 inspection. * Accessibility Standards are in compliance.(ICC A117.1-2009) -Street Department (road cuts) * Kitchen hood must be wired to initiate the fire alarm upon activation of the fire suppression system. * Egress door sign-age is posted and correct verbiage is used. Office- 208-736-2226 (The only exception to this is if the building does not require a fire alarm to be installed) * "DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED" * All electrical outlets, lighting, and appliances under the kitchen hood must shut down upon *Correct hardware has been installed on all doors. * When you are ready for any Fire Department inspections please call (extinguishers, activation of the fire suppression system. *Panic hardware is installed where required. fire/alarm/sprinkler systems): * Main gas valve must be installed and must shut down upon activation of the fire suppression *Accessible hardware is installed where required. Fire Inspection Line-208-735-7338 system. * Handrails shall be installed where required. * Exhaust fan must be capable of running continuously upon activation of the fire suppression * Stairways shall have handrails on each side. * When you are ready for a building final inspection on the structure: system. * All racking and shelving to be in place. Make sure you have the final inspections on the plumbing, electrical, and mechanical work. * Make up air must be capable of running continuously upon activation of the fire suppression system. * All Exit signs are field verified. (must be visible—nothing can block the line of sight) Call the building inspection line 208-735-7333 * Maximum Occupancy signs posted where required. All departments will be notified by this office to go do their final inspection. Final Inspection: * Special Inspection reports and balance reports need to be received by our office. * Address must be posted as outlined on the approved set of plans or previously approved by the If there is an elevator in the building please contact the Division of Building Safety at the following link Twin Falls Fire Marshal. PLANNING &ZONING for any permits/inspections: http://dbs.idaho.gov/programs/industrial/fagEL.html I ENGINEERING Landscaping: Once ALL the departments have signed the Certificate of Occupancy the Building Official will sign and * Our code allows for us to issue a TCO with landscaping incomplete; however, we cannot extend the then it will be ready to be picked-up or emailed. (All In order to streamline and eliminate confusion in regards to the engineering department commercial TCO beyond the current planting season.This means that we will work with the applicant on a permit inspections,the following will need to be inspected prior to signing the Certificate of definitive date of their choosing, but not typically beyond 2-3 months. If you need a Temporary Certificate of Occupancy there is a $1,000 refundable deposit required. All Occupancy. All inspections will be completed using the City of Twin Falls approved (stamped) plans. departments are required to sign and give a list of outstanding issues. Once the temporary is all signed Trash Enclosures: &the list made you will need to come in and sign stating you know what those issue are, that you will Storm Water Facility Inspections: (3 phases) * Trash enclosures should be finished before a final inspection is requested,this includes the front have them completed by the specified time, and will call for inspection as those items are completed. * Inspection of excavation, including dimensions and geotextile fabric. All adjoining trenches leading gate on the enclosure. Per our code, we cannot issue a TCO if this item is not completed. It is up to each department to determine if you meet their qualification for temporary occupancy. to storm water facilities also need to be excavated and inspected. * Inspection of storm drain pipes (per plans) need to be in place (not covered)for visual inspection. Note: If a building was originally done as a shell, the shell building permit is required to be finaled The drain rock must meet ISPWC section 801 Drain Rock requirements. All pipe connections to storm prior the tenant improvement permits can be finaled. In addition, if Temporary Occupancy is needed water facilities must be completed. Please have Address posted on site for all I there will be $1,000 refundable deposit for each permit. * Inspection of completed storm water facilities with the above referenced drain rock and geotextile fabric showing proper cover and overlap. Inspections. • Site Inspections: Please have a printed color copy of City * Verify that the parking lot layout (design) &striping matches the plans * Verify that the parking lot surface is an approved "hard" surface Approved Plans & Inspection Cards on site for * Verify that there is ADA compliant access from the Right-of-Way(ROW)to the building envelope all inspections. Right-Of-Way Inspections. * Verify driveway approach widths & locations according to plans * Verify ADA compliance of Curb/Gutter, Sidewalks, and Sidewalk/Driveway combinations O Verify ROW connections to other Agencies/Entities meet's ADA tolerances CITY APPROVED PLANS Flood Plain Inspections: * Verify flood plain location and compare plans to the site Reviewed for Code Compliance * Verify the commercial buildings are one foot above base flood elevation PLANS MUST BE ON JOB SITE When ready for inspection please call the Engineering inspection line at (208) 735-3446 for same day inspections call before 7:30 am. Having these inspections approved when the work has been FOR ALL INSPECTIONS • completed will ensure the Certificate of Occupancy is issued in a timely manner. __J 2018 IBC Section 105.4 Validity of Permit: The issuance or granting of a permit shall not be a permit for, or approval of, any violation of any of the provisions of this code or of any other ordinances of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the building official from requiring the correction of errors in the construction documents and other data. The building official is authorized to prevent occupancy or use of a structure where in violation of this code or of any other ordinance of this jurisdiction. WHILE EVERY EFFORT HAS BEEN MADE TO PERFORM A CODE REVIEW p L 800rH COMPLETE AND ACCURATE PLAN REVIEW,IT DOES Code: $D1,,8 International Building CodeSpTE 0NOT EXEMPT THE FIRE MARSHAL'S OFFICE FROM Construction Type: (602.2,T-601)"existing" FCODE REQUIREMENTS OMITTED FROM DRAWINGS Occupancy Group: ,Laundry(304.1)"formerly M,retail" THAT ARE CAUGHT DURING FIELD INSPECTIONS. Project Area: 90 sq.ft. Allowable Area: li pus/2)B,51,11-B=92,000 sq.ft.allowed(complies) Fire Sprinkler: Existin provided 1s IDAHD Incidental Areas: laundry<100 s.f. requires FS,FS provided fySfD pft��� Required Separation: (T-508.4)B/A, sprinkled=1 hour reqd.,1 hour provided ADDRESS IDENTIFICATION-IAW 2018 IFC 505.1 (T-508.4)B/M,sprinkled=N/A,2 hour provided Fire Extinguishers: (T-906.3(1) eqd.1 /3,000 sq.ft.,<75',2 regd.,2 provided Occupant Load: (T-1004.5)25 cc' New and existing buildings shall be provided with Required Exits: (T-1006.2.1 regd. <49 occ s.,1 provided approved address identification. Exit Configuration: N/A<49 c Travel Distance: (T-1006.2.1)=s 75'max.,71'provided Plumbing Fixtures: (T-2902.1)25 occupants The address identification shall be legible and (water closets) 25 occ s x 1:25=1 regd.,1 provided o placed in a position that is visible from the street or (lavatories) 25 occ s x 1:40=1 regd.,1 provided Q (drinking fountain) 25 occ's x 1:100=1 regd.,1 provided road fronting the property. (servic sink) 1 eqd.,1 provided z Separate Facilities: N/A=or<25 occ's(2902.2,exc.4) O Characters shall contrast with their background. 2 EXITS REQUIRED BEFORE U Address identification shall be Arabic numbers or TRAVEL DISTANCE EXCEEDS 100' letters.Numbers shall not be spelled out. 00 TF Best Practice;Commercial Buildings should have DRAWING SCALE 12"tall numbers and shall be affixed to the building. APPLIES To Numbers may be affixed to monument signs but as 24N36"SHEET SIZE a secondary address location.Street name not nC) -0 eeded if numbers are displayed facing assigned road. Suite numbers shall be affixed near the main entry door(s),at least 4"tall and shall include"SUITE". CA 7EMERGENCY ACCESS KEY BOX 18 IFC 506 Knox Box:www.knoxbox.com E LL- If no existing(E)Knox Box,one shall be installed to the right of the >✓ main access door(s).All keys shall o PROJECT AREA be identified with a tag indicating E E ❑ what the key unlocks.Box should o o be mounted 5-6 feet from ground ' J level. Alternative locations shall be a >� a approved by the Fire Marshal. 0 z 0 IF there is an(E)Knox Box,all keys/codes shall be updated. CAE 0 2 2 Q U N O N V O L U INDEX OF DRAWING: 2 Architectural w 0 0 b o m E A1.0 Code Plan, Code Review ' a L- N A1.1 Floor Plan A1.2 Reflected Ceiling Plan A2.0 Sections & Details U A3.0 Details & Notes Civil By Others Mechanical M0.0 HVAC Cover Sheet ftil M0.1 HVAC Energy Compliance Forms M2.1 HVAC Plan M2.2 HVAC Roof Sheet M3.0 HVAC Schedules M4.0 HVAC Details P0.0 Plumbing Notes P2.1 Plumbing Waste & Vent Plan P2.2 Plumbing Water & Gas Plan P2.3 Plumbing Roof Gas Plan 91 P3.0 Plumbing Schedules ^A P4.0 Plumbing Details W Electrical EO.0 Electrical Cover Sheet EO.1 Electrical Specifications EO.2 Energy Compliance Forms Area Plan,Notes CITY APPROVED PLANS E2.1L Lighting Plan Reviewed for Code Compliance E2.1 P Power Plan E2.2 Electrical Roof Plan Date BUILDING PLAN W PLANS MUST BE ON JOB SITE E3.0 Electrical Schedules 08-10-2023 SCALE: 1/32"=1'-0" S®NORTH FOR ALL INSPECTIONS E4.0 Electrical Details Sheet No. E A1 .0 Page 2 of 26 A Existing CMU wall to remain Existing wall furring to remain 2.D Adjacent M occupancy Remove portion of non-bearing wall SLATE of 20'-4" 9'-0" 40'-10" 6'-10" Verify portion of existing CMU stability, secure as required,seal existing saw—cut with fire rated caulking. /DANK 1� 1 existing 2—hour CMU wall F�Sf0 P, 271 s.f. 300=1 occ 37-3 DRYER TUNNEL I COUNTER OFFICE 1 G 34"MAX COUNTER �F�.. O F61,�.. J IF F A2AD: "\. HEIGHT J F� ) O DE-6505 DE-6505 DE-650S DE-650S DE-650S DE-650S DE-650S DE-650S DE-650S DE-650S - ? \ � -/ /> RESTR00 .i z New counter—b others,provide power&data change change s°aP r P p II I\ II\ II\ II\ II\ II\ II\ A II\ \ y III —1 1 FIRE RISER 0 I� I1 11 11 11 11 11 11 1 1 101 Walls of 3-5/8"metal studs w/5/8"GWB both sides to I underside of roof joist or above ceiling and braced to joist. JJ JJ —y —y \_u J .I G A2.0 Dryer tunnel wall—see section 7Fire E ment—b others a exist.wood ram DRAWING SCALE Fre extinguisher&cabinet qu'P Y pAPPLIES TO Existing floor receptacle to be removed and floor L— J 24"X36"SHEET SIZE patched,see electrcal(lyp.) extinguisher LAUNDROMAT �a 2,941 s.f./150=20 occ `Lh•� A2.0 H ® Proposed area of concrete saw—cut for sewer line joist - 9 t (see plumbing)Patch back concrete to match Walls of 3-5/8"metal studs w/5/"GWB both sides to existing concrete underside of roof or ab ve cello and braced to ost. Remove existing storefront and provide new motorized door as shown a--+ // II L As.D 118'41/2" e urnis logs— y o ers 34"COUNTER STORAGE HEIGHT 963 of./300=4 occ's O folding Existing E electrical a1 FO-1 0 J Fire extinguisher transformer 2 to —� L 1r---- -----_----- ' - -------------- -- as J o do o 76 N I I I I o Z i 3 Existing storefront windows to remain A20 ~ Equipment—by others Proposed sewer excavation,line,and patch.All site and civil by others MECHANICAL F T F T F T F F T T F D- o- 1r Ir D- o- D- D R 0 0 10J r E II V II V II V II V II V II V II V II V II V II V II V II V II � II � II � II � II � II � II � II � II � II � II � IIII ° --F- -- -- l 11 11 11 11 11 f 1111 11 1 11 1a ELD-685 ELD-685 ELD-685 ELD-685 ELD-685 ELD-685 ELD-665 ELD-665 E -665 ELD-665 ELD—65 ELD-665 rR451 ELD-645 ELD-645 ELD�4� ELD-645 ELD-645 ELD-630 ELD-630 ELD-630 ELD-630 ELD-620E4D-620 ELD-620 ELD-620 a � WN 1 as cc wH r'n 4 cc O - v o L II II � MMM00 p N N above grade trough drain y owner above gr de trough drain by owner above grade 44h drain by owner oc Y L Q ad N d 0 existing 1—hour GWB wall � U 70'-0„ o ca N w N c - existing floor to ceiling partition p co E d d a O DOOR HANDLES,PULLS,LATCHES, Adjacent A-2 occupancy J/ LOCKS,AND OTHER OPERATING A Saw—cut portion of slab as required for new drain Contractor option to replace existing floor to ceiling partitionF_1 B DEVICES ON DOORS REQUIRED TO BE p.p� trench(per plumbing)patch back as required. with new wall,or provide new wall west of existing partition. 0� ACCESSIBLE SHALL NOT REQUIRE TIGHT New wall to be 1-hour construction of metal studs w/ GRASPING,PINCHING,OR TWISTING OF 5/8"type-X GWB from floor to roof deck. THE WRIST TO OPERATE.(IBC SECTION 1010.1.9.1) ANY EXIT DOOR WITH A KEYED LOCK TO FLOOR PLAN W BE READILY DISTINGUISHABLE AS BEING S NORTH SCALE 1/4"=1'-0" LOCKED OR PROVIDE A PANIC, E PUSH-PAD,OR LEVER THAT DEACTIVATES LOCK IN A SINGLE MOTION. SMALL THUMB LOCKS NOT REMODEL:If construction will move or alter the existing Fire REMODEL:If construction alters the paths of egress and/or any ALLOWED. Sprinkler System,it may need to be evaluated by the Idaho existing Fire Extinguishers,ensure that travel distance and correct ANY DOOR OTHER THAN MAIN EXIT State Fire Marshal's(ID SFM)office to ensure code compliance mounting stays consistent with 2018 IFC 906 and NFPA 10. DOOR TO HAVE DOOR HARDWARE THAT and hydraulic calculations. UNLOCKS LOCK IN A SINGLE MOTION. If significant changes need to be made,a state licensed fire Portable fire extinguishers shall have a minimum rating of 2A-10B:C. PROVIDE SIGN ON MAIN EXIT DOOR, Sprinkler contractor shall submit plans to the ID SFM for The travel distance to an extinguisher shall not exceed 75 feet. "THIS DOOR TO REMAIN UNLOCKED acceptance. WHEN BUILDING IS OCCUPIED." Please assess if remodel will require more FE's. Idaho State Fire Marshal sfm.planreview@doi.idaho.gov Fire Riser Room/Fire Pump Access: New work/changes shall not be covered up prior to fire inspection.Fire Inspection Line:208-735-7338 IAW 2018 IFC 901.4.6.2,Markings on access doors:Access doors for automatic sprinkler systems risers'rooms and fire pump rooms shall be labeled with an approved sign. Floor Plan The lettering shall have a minimum height of 2 CITY APPROVED PLANS inches with a minimum stroke of 3/8 inch. Reviewed for Code Compliance Date Red sign with white letters."Fire Riser Room" 08-10-2023 PLANS MUST BE ON JOB SITE Sheet No. A FOR ALL INSPECTIONS Al .1 Page 3 of 26 L 800, A SSPTE OF ° Adjacent M occupancy New suspended GWB ceiling system in reslroom®9' % /DANK 1F� F�Sf0 PRG� 1 I DRY R TUNNEL I I 1__1__1 —i— — newtf9ht qht a isting light (; N DER existi OFFGE xi ew a isting light exis ing light L__ _J —__ — -- J 9 n 9 new li ht —— —— — O III x n w — x—-- -- x l x X g light existing fight X — x ¢� �— —� -- --- — -- XI I o I I II thong change sap --T 7 — -- 1 -- r-- 4 FIRE RISER O new new \ \ 11 \ ` \ u \ u \ II \ III —III\ \y II \y II (�(,,)) L ` `�J `�J ` JJ I �L `�1J_ �JJ —\� ii exislig light exidf' light existing light existing light existing light existing light existing light existing light DRAWING SCALE —— ———— —— APPLIES TO 24"x36"SHEET SIZE new Existing lightlocations(for ref rence) L— —J—— ——I—— ——L—— existing light existing light existing light new light new light new light new light —— new light—— ———— ———— new hl x x x x LAUNDROMAT x x x x x x II I existing light existing light existing light existing light existing light existing light existing light existing light I new existi g ceiling grid to r main (ceilings.It ,extend new existing ceili g to remain or be removed(contract r option) to new all Onew light new light H--+ cl( Existing diffusers(typ.) �V existing light existing light existing light E i' new Existing hea er to be removed STORAGE �\ liiEl existing light existing light existinVV light existing light existing light existinUa light existing light Extend ceilin system new light new light new light new Ii9Ft new li h , O X X X X X X X X X X 2 OExisting spri kler locations,adj st placement as r quired.All L sprinkler wno ok to be performed by licensed fire s rinkler J ——L— contractor submitted to slat as rewired. r— ———-- ———— ———— ———— ———— — —— c --r— I--T— I—_T— existing light existing light o o existing light existing light existing light existing light existing light X L_ I 1 _ — I_ I I d ew light l T- ew 6ghlT T O X 101 X E T \ \ \ T�\ \ T IT \ \ T T \ D r rr lr r n n- T- lr r IDi ' b< _ — _ o dlw light lbw light new light II II p hew ht \ neW li \ \ \ \ new li ht \ —t——I—— — — —r— —T_— I——T— 9 \ II II \ II 9hf II II II II W I � 2 --- i — — ---- --- — -- R ii _ EL7�-685 EL-685 ELD-6 ELD-685 ELD-685 EL-685 ELD-665 LD-665 -665 ELD- 5 EID-65 ELD-665 ELD 645 ELD-65 LD-645 ELD ELD-645 EL-64� ELD-630 ELD-630 END-3° ELD-63(X E -620 E4D-620 LDr620 20 P P a y N co c, WH IWH WE d l n o u� N `m I II existing light a isting light existi g light existing li hl exi t— — ——r— —— — ——t— —1 t— -N v o L X m M M O Y m co oo 0 N 0 O Existing lay-in to be removed O Existing header to be removed LU New suspended ceiling system 9' p h 6 d L E Adjacent A-2 Occupancy After existing ceiling that extends over partition into adjacent OA space as required D 0i 0i REFLECTED CEILING PLAN W S SCALE: NORTH 1/4"=1'-0" E on No 91 CITY APPROVED PLANS Reflected Ceiling Plan Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Date 08-10-2023 Sheet No. Al . Page 4 of 26 Easy access to dryer vent clean-out is Existing roof to remain—properrlylyp Dyer flue—by others,see mechanicalatch as imperative so that regular maintenance can SNTE O,r re aired Roof patching to be by roofer carfified be carried out,prohibiting lint build up. with roofing product h ANK/D CFNS fD PRG��ti I Existing header&lay—in to be removed Existing lay—in ceiling to remain,alter seismic bracing as required. Remove portion of lay in ceiling Provide 45'diagonal bmcing 0 32"o.c. Ll (every—other stud)and to cont track on �I' C Demo existing accent fascia and extend underside of truss.coordinate with flues I� h- ceiling as required New wall of 3-5/8"metal studs w/5/8° Lay—in ceiling in adjacent area to remain U GWB extend to underside of deck and z insulate w/R-13 bolts Z Contractor option to replace existing floor to ceiling partition 0 Washers tunnel cover—by others Dryers—by others with new wall,or provide new wall west of existing partition. U Existing GWB wall to remain New wall to be 1—hour construction of metal studs w/ 5/8"type—X GWB&R-13 butts from floor to roof deck. Washers—by others Existing GWG partition. DRAWING SCALE APPLIES TO 24"x36"SHEET SIZE Saw—cut concrete floor as required for new trench(per plumbing),patch back as A E L E\V./ B E L E\V, required. A2.0 SCALE: —1/4"=l'—O" A2.0 SCALE: Suspended GWB ceiling sysle M"„s"p<„.a u'mo. f Painted GWB 4'x8'FEE 6 7 '��„7� 4'high FRP 2'x3'mirror / Map rack w/shelf a / m / Diaper changing station / x e E s +rr—�' Grab bars w/backing ��-_ �1 $ � E o `V TP dispenser "/� € L J "mw,x"aE","x�,.wwa \ >s / a Padded insulation kit on supply "// � �12• �.m�" ? i Toilet w/left hand flush - - &drain \ " Mop sink � _ L 4"rubber base [sY a"mzwr sal l` O 304.WHEELCHAIR TURNING SPACE o L ELEV. o ELEV. rE ELEV. F ELEV. ELEV. _ _ J m A2.0 A2SCALE: A20 A11 A0 asSCALE: 1/4"=1'-0" " ' " SCALE: 1/4"=1'-0" SCALE: 1/4"=1'-0" SCALE: 1/4"=1'-0" _ m "mmrimxx«wwuw rcm p /11 � LL Q VJ ^ C o � 3 I I P—lam clad countertop,apron, W E \ / and back splash a signal w/raised letters, \ / 4 x6 FEE Sink—per plumbing dwg's symbols,&braille O Dunking fountain w/ P—lam clad countertop w/ optional bottle filler waterfall end panel ,,,,mo, ax 2 / \ e. PROVIDE HI-LOW — r r j a 1Mo / \ DRINKING _ - v o L_ 23"ADA brackets by A&M / \ FOUNTAIN,NOT Center wall of 3-5/8°metal Hardware w/3/4"skirt clad w/ °a e6 M o kJ m N N Q SINGLE UNIT. studs w/5/8°GWB p-lam o L L N d H ELEV. ELEV. ELEV. ELEV. ` I�r"" a = A2.0 SCALE: —1/4"-1' O" A2.0 SCALE: —1/4"'-1' O" A2.0 SCALE: —1/4"—T'—O" A2.0 SCALE: —1/4"-1' 0" 308.CLEAR FLOOR OR GROUND SPACE �,..,K,mxx«mEwa O c E d d a ACCESSIBILITY STANDARDS 56°min.to nearest obstruction xmxw,aura"�,„we«"..ae 306.KNEE CLEARANCE 308.REACH RANGES 60"min.to nearest abstraction dispensers not la be 54°min. I L. located behind grab bars x�wxuwwe 39"-41 18"grab bar 36"min 42"grab bar 4"min. 2"min. min. w� 4 12"max 42"min E j III outside diameter of 1.25"-2° �»R Flush handle shall be located on open side of water closet n GRAB BARS 16"-18° TOILET TISSUE DISPENSER Urinals fe"' 30°min.toe clearance wuroF tY� E 8"min. ❑ 30°06" no— clear flaarl _ x CITY APPROVED PLANS space E e E E E L——_J L J _ XO1N1W6"1°" Reviewed for Code Compliance N — V o PLANS MUST BE ON JOB SITE Insulate all water i, Sinks supply&drainpiping _ _— FOR ALL INSPECTIONS N m 404.DOORS AND DOORWAYS �mxamµ"�ga. 404.DOORS AND DOORWAYS Sheet No. A''.6J Page 5 of 26 Vertical 9T wire at 4'o.c.,e.w.(1)per 16 �D L 800, s.f.,coordinate w/(4)seismic restraint. Zff Provide vertical 90'rigid strut @ 12'o.c.,e.w. 5 Op (1)per 144 s.t,coordinate w/seismic Structure - restraint Seismic splay wire bracing to consist of(4) iOA A Provide 12 go.wire at splay locations - hanger wires each at 45'angle from vertical CFNSfD NRG0�1 wire to structure above.Seismic wire system 4$• set 12'o.c.,e.w.(1)per 144 s.f. 10 Drill&install 1/4"through-bolt and lock nut. Heavy duly T-bar system ps. 1/2"tin wall electrical conduit,ensure Acoustical ceiling file \\ adequate to fit over eye screw above \\ \ O \\ Vertical hanger wire tied to structure above 3/4"thin wall electrical conduit E \\ / 8"max.(typ.) ZO / Main horizontal runner or U Note:tube to be tight to ceiling grid and < _ intermediate cross connector attach to structure above.Connect brace to structure w/(1)strut per 144 s.f. v Intermediate connector \\ Notes: Hanger wire to be 12 ga.(min.),all splay wire to be taut& \ \\ DRAWING SCALE Drill&install 1/4"through-bolt and lack nut. tied Ceiling lile turn min.,all splay wires to be directly attached At fixed side,secure system together w/ APPLIES TO to structure. . 24"x36"SHEET SIZE Slot end of tube to fit over main runner r Suspended ceiling system attachments shall be capable of 1/8"pop rivet resisting 200 lbs.minimum. Allow free movement at opposite side Main channel runner r Areas under 144 of.and w/wall on(4)sides extended to structure need not have seismic bracing.Partition walls must 2"perimeter with wall anchors secure to structure. be braced to structure and independent of ceiling system. Note:all splay(hanger)wires shall be free of obstructions,ie:ducts,pipe,conduit,etc. n LAY-IN CEILING DETAILS A3.0 NO SCALE General Notes: +rr'�' 1. Contractor to verify all dimensions and conditions. V 2. All work to comply with IBC,ADA,and all other local and national codes that may apply. Vert.12 ga.wires @ 4'a.c. 3. Contractor to verify and coordinate all owner provided items for proper size,clearance,and requirements. O conduit compression brace- 4. Provide backing for all grab bars,door stops,cabinetry,partitions,etc.as required. full height-typical at 12'max. 5. All finished by tenant. T� E rs o o Gypsum Wall Board(GWB)Notes: O + 1. All GWB to be 5/8".Provide type-X at all fire rated assemblies. C 12 ga.splay wires @ 12'o.c.in 2. GWB ceilings with lay-in tile covering to be taped to a level 2 over screws&joints. _J m -p 3.0 typ. each plane of each channel 3. Exposed GWB to receive paint to be tape&textured to a level 4 finish. S First line of bracing 4'or less 4. Provide water resistant GWB at rectrooms and wet locations. m r� �\ from wall boundary. p li o ^ c \ Door&Frame Notes: d � 3 \ F 1. Interior 18 ga.hollow metal doors such as Steelcrafl L series. \ Ceiling suspension system ° 2. Interior frames for GAB walls to be such as Steelcraft DW series with(3)non-galvanized anchors per \ 3 side on 7'doors,(4)anchors on 8'doors.Provide 4-1/2"x4-1/2"ball bearing hinges such as Stanley FBB179(3)per 7'door,(4)on 8'and 4'wide doors. 3. Door hardware to be lever handle ADA compliant such as Schlage Saturn.Functions;Entry/Office E \ AL50PD,Classroom AL70PD,Storeroom ALBOPD,Exit AL25D,Privacy AL40S,Passage ALTOS,Dummy o AL170.Verify style with Door Schedule.Keying to be coordinated with owner. ai \\ \ Q U Cabinetry Notes: (n o uro a N s METAL L All cabinetry to be of 3/4"melamine with plastic laminate cladding on all exposed exterior surfaces. N 3 CHANNEL Provide vinyl edge banding(color to be selected). o� M m 00 2. Laminated colors to be selected at later time. p N (V -0 n 3. Provide 3-1/2"wire pulls such as Amerock BP867CS. Y L of of Ud 4. Provide medium duty ball bearing full extension drawer slides such as Accuride 3306DO at all -ad C) N standar yQ\Gp,N. I 5. Provdedheavy duty ball bearing full extension drawer slides such as Accuride 9301E at file drawers. O p' 6. Provide concealed soft close hinges such as Blum CLIP top BLUMOTION at all cabinet doors ca axLu _ 5ti 7. Provide countertops per details.Provide 3/4"particle board beneath p-lam as required. 65 coa5 Metal channel A 0- d L 0 Arcmcecmrm Aooreavenons AN Anchor Boll Tile Notes: L Provide thin-set Tile system where shown. Arch. Architectural 2. At wall areas to receive tile,provide backer bard such as DensShield.Thickness to match wall board. r ` Metal furring channel @ 16"o.c. AFF Above Finish Floor 3. Provide metal caps at tile/wallboard transition points such as Schluter Jolly. V Areas smaller than 144 soft,and with walls on four sides Cntr. Contractor 4. At wood floor areas provide membrane such as Schluter Ditrs.Provide waterproofing and vapor extending to the structure need not be braced.Boundary walls retardant membrane at all tile shower areas with wood construction. must be braced lop and bottom independent of ceiling to qualify. Cone. Concrete 5. See Room Finish Schedule. Cont. Continuous SUSPENDED CEILING SUSPENDED CEILING Else. Electrical n SEISMIC BRACING DETAIL n SEISMIC BRACING DETAIL FUR Existing taRemain B C Exist. Existing Point Notes: 1. Drywall-(1)coal primer such as Sherwin Williams PVA Drywall Primer&Sealer,(2)coals paint A3.0 -NO SCALE - A3.0 -NO SCALE - e.w. Each Way such as Sherwin Williams ProMar 400 Zero VOC Interior Latex. FD Floor Drain 2. CMU-(1)coat primer such as Sherwin Williams LOXON Concrete&Masonry Primer/Sealer,(2) FRP Fiber Reinforced Plastic coals paint such as Sherwin Williams SuperPaint Exterior Acrylic Latex. turn. Furnace 3. Interior Metal(doors,frames,handrails,etc.)-(1)coal primer such as Sherwin Williams am Multi-Purpose Latex Primer,(2)coals paint such as Sherwin Williams Framer 400 Zero VOC Interior ga. Gauge Latex. GWB Gypsum Wall Board 4, Exterior Metal(doors,frames,handrails,etc.)-(1)coat primer such as Sherwin Williams Kem HE Hose Bibb Kromak Universal Metal Primer,(2)coats paint such as Sherwin Williams SuperPoint Exterior Acrylic Horiz. Horizontal Latex. HM Hollow Metal 5. Exposed ceiling structure to be painted with such as;Sherwin Williams Pro Acrylic Dryfoll where noted. HW Hardwood Mech. Mechanical Lay-in Ceiling Notes: o.c. On Center L Provide ceiling tile per Room Finish Schedule. BED Overflow Drain 2. Provide complete 15/16"lay-in ceiling grid system such as Armstrong Prelude ML 15/16'Exposed OSB Oriented Strand Board Tee. p-1 p-lam Plastic Laminate 3. Provide seismic bracing in areas exceeding 144 square feel per ASTM C635&C636,see drawing details. RD Roof Drain ref refrigerator regd. Required Toilet Accessory Notes: SS Stainless Steel L Grab Bars-such as Bradley 812 heavy duly SS with concealed mounting. Struct. Structural 2. Sanitary Napkin Disposal-such as Bradley Diplomat model 4A10. 3. Seat Cover Dispenser-recessed such as Bradley Diplomat 5A40. Details&Notes CITY APPROVED PLANS TL&P Tape,Texture and Paint 4. Toilet Paper Dispenser-dual roll such as Bradley Diplomat model 5A10. lyp. Typical 5. Paper Towel Dispenser-sensor activated such as Bradley model 2499. Reviewed for Code Compliance Vert. Vertical 6. Paper Towel/Waste-sensor activated recessed such as Bradley Diplomat 2A25 w/ with 7. Verify with drawings for contractor provided or owner provided toilet accessories. PLANS MUST BE ON 10B SITE 8. Toilet partitions such as Bradley 72"overhead braced stainless steel partitions.Provide coat hook an WH Water Heater door,hardware&trim,and reinforcements as required mounted grab bars&accessories.Provide Date FOR ALL INSPECTIONS WS Water Softener reinforcing in wall and ceiling as required. 08-10-2023 Sheet No. A3.0 Page 6 of 26 HVAC SPECIFICATIONS MECHANICAL LEGEND PART 1 - GENERAL 1.5 DELIVERY, STORAGE. AND HANDLING 2.5 ACCESS DOORS AND PANELS 3.6 TESTING AND BALANCING EQUIPMENT ® SUPPLY DIFFUSER 1.1 GENERAL INTENT A. DELIVER PRODUCTS TO THE PROJECT PROPERLY IDENTIFIED WITH NAMES,MODEL NUMBERS, A DUCT MOUNTED ACCESS DOORS:DOUBLE WALL,DUCT MOUNTING,AND RECTANGULAR;FABRICATED OF A. INDEPENDENT BALANCING FIRM SHALL PERFORM TESTING AND BALANCING PROCEDURES ON A. THE INTENTION OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND TYPES,GRADES,COMPLIANCE LABELS,AND OTHER INFORMATION NEEDED FOR IDENTIFICATION. GALVANIZED SHEEP METAL WITH INSULATION FILL AND THICKNESS AS INDICATED FOR DUCT PRESSURE EACH SYSTEM ACCORDING TO THE PROCEDURES CONTAINED IN NEBB'S"PROCEDURAL 1JJJJJJ FLEXIBLE DUCTWORK � RETURN GRILLE Z o EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING, B. ALL MECHANICAL EQUIPMENT AND MATERIAL fTEMS SHALL BE PROTECTED FROM WEATHER AND CAS' STANDARDS FOR TESTING,ADJUSTING,AND BALANCING OF ENVIROMENTAL SYSTEMS°OR _ INSTALLATION AND TESTING,COMPLETE AND READY FOR SAFE OPERATION Of THE SYSTEMS DESCRIBED 1. FRAME:GALVANIZED SHEEP STEEL,WITH BEND-OVER TABS AND FOAM GASKETS. o ro VANDALISM PRIOR TO ACTUAL INSTALLATION.FAN WHEELS,PUMPS AND OTHER ROTATING SMACNA'S"HVAC SYSTEMS-TESTING,ADJUSTING,AND BALANCING," L12°x22° LINED RECTANGULAR DUCTWORK HEREIN. ® EXHAUST GRILLE a' y MACHINERY SHALL BE PERIODICALLY ROTATED DURING STORAGE.ANY FACTORY PAINTED 2. PROVIDE NUMBER OF HINGES AND LOCKS AS FOLLOWS: � d B. SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS MADE A B. PREPARE TEST REPORTS FOR EQUIPMENT FANS,AND OUTLETS. CROSSCHECK THE SUMMATION EQUIPMENT SCRATCHED AN MARRED DURING SHIPMENT OR CONSTRUCTION SHALL IDENTIFICATION. A LESS THAN E INCHES SQUARE:SECURE WITH THICKNESS SASH LOCKS. W E THOROUGH EXAMINATION OF THE SITE,AND ALL EXISTING CONDITIONS AND LIMITATIONS WHICH AFFECT OF REQUIRED OUTLET VOLUMES WITH REQUIRED FAN VOLUMES. -------- DEMO THIS WORK.LATER CLAMS SHALL NOT BE MADE FOR LABOR,EQUIPMENT OR MATERIALS REQUIRED RESTORED TO ORIGINAL,"NEW"CONDITION.THIS INCLUDES COMPLETE REPAINTING OF THE b. UP TO 18 INCHES SQUARE:TWO HINGES AND TWO SASH LOCKS. C. ADJUST TERMINAL OUTLETS AND INLETS FOR EACH SPACE TO INDICATED AIRFLOWS WITHIN ROUND DUCTWORK BREAK W >, BECAUSE OF DIFFICULTIES ENCOUNTERED,WHICH COULD HAVE BEEN FORESEEN DURING SUCH AN EQUIPMENT IF NECESSARY TO PROVIDE EXACT PAINT MATCH. c. UP TO 24 BY 48 INCHES:THREE HINGES AND TWO COMPRESSION LATCHES. SPECIFIED TOLERANCES OF INDICATED VALUES. MAKE ADJUSTMENTS USING VOLUME DAMPERS. Op DEHUMIDISTAT � l Z EXAMINATION, C. CONTRACTOR IS RESPONSIBLE FOR RECEIVING AND OFFLOADING EQUIPMENT OF HIS SCOPE. 2.6 EQUIPMENT CURBS AND SUPPORT ADJUST FANS AND EQUIPMENT BLOWERS TO VOLUMES SHOWN IN EQUIPMENT SCHEDULES. C. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT,GENERAL CHARACTER,AND LOCATION OF THE IMMEDIATELY UPON RECEIPT,CONTRACTOR SHALL INSPECT ALL EQUIPMENT AND MATERIAL FOR A ROOF MOUNTED EQUIPMENT:PROVIDE FACTORY CURB TO MATCH EQUIPMENT PROVIDED.CURB TO SET OUTSIDE AIR TO VALUES SHOWN ON MECHANICAL SHEETS. T THERMOSTAT � E a OF FABRICATION WORK TO BE ORRNSTALUTION OFMED.WHERE NOR ITEMA4,ADJUSTMENTS CONTRACTORE WORK ARE NECESSARY FOR SHALL MAKE SUCH ADJUSTMENTS WITHSHIPPING DAMAGE AND REPLACE ANY DEFECTIVE ITEMS AT NO INCREASE TO CONTRACT MALIGN ROOF SLOPE,TYPE,ANO INSULATION OEPTHS FOR PROPER EQUIPMENT MOUNTING(ACCOUNT 3.7 CONTROLS AND ELECTRICAL COMPONENTS O � DUCTWORK BREAK I � W N 3 m AMOUNT. TEMPERATURE SENSOR ®®®® m NO ADDED COMPENSATION.WHERE SUCH ADJUSTMENTS AFFECT FUNCTIONAL OR AESTHETIC DESIGN OF FOR APPLICABLE ACCESSORIES SUCH AS ECONOMIZERS AND ETVS). A CONTRACTOR SHALL PROVIDE A COMPLETE CONTROL SYSTEM TO OPERATE THE EQUIPMENT AS � THE WORK,THEY SHALL FIRST BE SUBMITTED TO THE ARCHITECT FOR RENEW AND APPROVAL. 1.6 SEQUENCING AND SCHEDULING PART 3 - EXECUTION DESCRIBED IN THESE DOCUMENTS.SYSTEM SHALL INCLUDE THERMOSTATS,LOW VOLTAGE WIRING, DUCTWORK RISE (]`m D. SITE UTILITIES:THE MECHANICAL DOCUMENTS INDICATE CONNECTION LOCATION OF VARIOUS BUILDING A, COORDINATE MECHANICAL EQUIPMENT INSTALLATION WITH OTHER BUILDING COMPONENTS PRIOR 3.1 EXAMINATION TRANSFORMERS,AND ASSOCIATED APPURTENANCES REQUIRED TO MEET THE IMIENT OF THESE � SMOKE DETECTOR 0 U SERVICES.COORDINATE WORK WITH THE SITE UTILITIES CONTRACTOR TO ENSURE PROPER INVERT TO ORDERING OR FABRICATION OF ADJOINING WORK. DOCUMENTS. ����DUCTWORK DROP ELEVATION,PIPE SLOPE GRADIENT,PIPE SIZE AND SEPARATION WITHIN TRENCH WORK.NOTIFY A VERIFY FINAL LOCATIONS FOR BE COINS WITH HELD MEASUREMENTS AND WITH THE REQUIREMENTS ARCHITECT OR ENGINEER OF ANY DISCREPANCY BETWEEN DRAWINGS AND FIELD CONDITIONS. B. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET SLEEVES IN OF THE ACTUAL EQUIPMENT TO BE CONNECTED. ®0 CO2 SENSOR E. COMPLY WITH ALL LOCAL AND STATE CODES REGARDING SEISMIC SUPPORT AND ISOLATION.NOT ALL POURED-IN-PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS AS THEY ARE B. LOCATIONS OF EQUIPMENT AND DEVICES,AS SHOWN ON THE DRAWINGS,ARE APPROXIMATE UNLESS (y '�+ SEISMIC REQUIREMENTS ARE SHOWN ON THESE DRAWINGS.CONTRACTOR SHALL MEET THE CONSTRUCTED.ARRANGE FOR CHASES,SLOTS,AND OPENINGS IN BUILDING STRUCTURE DIMENSIONED;DO NOT SCALE DRAWINGS.EXACT LOCATIONS OF SUCH ITEMS SHALL BE DETERMINED BY GENERAL HVAC NOTES o- MOTORIZED DAMPER nuw- DAMPER)SUPPLY(WITH VOLUME REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION FOR SEISMIC SUPPORT/ISOLATION OF HIS DURING PROGRESS OF CONSTRUCTION TO ALLOW FOR MECHANICAL INSTALLATIONS. THE ARCHITECT'S REPRESENTATIVE AND/OR DETERMINED FROM SPECIAL DETAILS AND DRAWINGS. (RE:ALL MECHANICAL SHEETS) WORK. C. SEQUENCE,COORDINATE,AND INTEGRATE INSTALLATIONS EC MECHANICAL MATERIALSAND VERIFY THE PHYSICAL DIMENSIONS EACH ITEM OF MECHANICAL EQUIPMENT TO FIT THE AVAILABLE Bo- BAROMETRIC DAMPER �i SPIN-IN RETURN/EXHAUST 1.2 GENERAL COORDINATION EQUIPMENT FOR EFFICIENT FLOW OF THE WORK.COORDINATE INSTALLATION OF LARGE SPACE AND PROMPTLY NOTIFY THE ARCHITECT PRIOR TO POUCHING-IN IF CONNCTS APPEAR. G1 THE INTENTION Of THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND (WITH VOLUME DAMPER) A. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF A SATISFACTORY,COMPLETE,AND FULLY EQUIPMENT REQUIRING POSITIONING PRIOR TO CLOSING IN THE BUILDING. COORDINATION OF DIVISION 15 EQUIPMENT AND SYSTEMS TO THE AVAILABLE WIRING,EQUIPMENT, EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING, MANUAL VOLUME DAMPER OPERATIONAL PIECE OF WORK IN ACCORDANCE WITH TRUE INTENT OF THE DRAWINGS AND D. COORDINATE CONNECTION OF MECHANICAL SYSTEMS WITH EXTERIOR UNDERGROUND AND DUCTWORK,PIPING,ETC.SHALL BE THE RESPONSIBIUTY OF THE CONTRACTOR.THE INSTALLATION INSTALLATION AND TESTING,COMPLETE AND READY FOR SAFE OPERATION OF THE SYSTEMS h� 45'SQUARE DUCT TAKE-OFF SPECIFICATIONS. OVERHEAD UTILITIES AND SERVICES.COMPLY WITH REQUIREMENTS OF GOVERNING SHALL BE CONCEALED WITHIN BUILDING CONSTRUCTION,OR EXPOSED IN MECHANICAL ROOMS,UNLESS DESCRIBED HERON. v,�RA FROM SQUARE DUCT B. CONTRACTOR SHALL CONSULT ALL DRAWINGS FOR THE PROJECT TO DETERMINE THAT THE WORK AND REGULATIONS,FRANCHISED SERVICE COMPANIES,AND CONTROWNG AGENCIES.COORDINATE OTHERWISE NOTED. FS�-{ COMBINATION SMOKE/FIRE DAMPER EQUIPMENT WILL FIT AS PLANNED. CONNECTION OF ELECTRICAL RVICE ES. .2_GENERAL INSTALLATION G2 THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR T-STAYS AND ALL LOW VOLTAGE WIRING. �� 45 ROUND DUCT TAKE-OFF C. THE LOCATION OF PIPING,DUCTS,EQUIPMENT,ETC.,SHALL BE CHECKED TO ENSURE CLEARANCE FROM CONTROL CONDUIT IS BY ELECTRICAL CONTRACTOR. xA FROM SQUARE DUCT OPENINGS,STRUCTURAL MEMBERS,CABINETS,LIGHTS,OUTLETS AND EQUIPMENT HAVING FIXED E. PROVIDE IDENTIFICATION OF ALL EQUIPMENT.COORDINATE INSTALLATION OF IDENTIFYING A PROVIDE ALL VALVES,DAMPERS AND CONTROL DEVICES REQUIRED TO COMPLETE BALANCING OF FD -{ FIRE DAMPER LOCATIONS. THIS SHALL BE ACCOMPLISHED PRIOR TO FABRICATION OF PIPE OR DUCTS. DEVICES AFTER COMPLETING COVERING AND PAINTING WHERE DEVICES ARE APPLIED TO SYSTEMS AS DESCRIBED IN THESE DOCUMENTS OR AS NORMALLY ASSOCIATED WITH THE SYSTEMS TO G3 ALL OUTSIDE AIR DUCTS TO BE EXTERNALLY INSULATED. 45'ROUND DUCT TAKE-OFF D. IF,AT ANY TIME,AND IN ANY CASE,CHANGES IN LOCATION OF PIPING,DUCTS,EQUIPMENT,ETC., SURFACES.INSTALL IDENTIFYING DEVICES PRIOR TO INSTALLING ACOUSTICAL CEILINGS AND BE INSTALLED WHETHER SPECIFICALLY CALLED FOR ON THE DRAWINGS,DETAILS OR SPECIFICATIONS OR m��" FROM ROUND DUCT BECOMES NECESSARY DUE TO EXISTING OBSTACLES OR INSTALLATION OF OTHER TRADES SHOWN ON SIMILAR CONCEALMENT, NOT.IT SHALL BE UNDERSTOOD,UNLESS SPECIFICALLY STATED OTHERWISE,THAT ALL SYSTEMS G4 ALL SUPPLY DUCTS AND RETURN DUCTS TO BE INSULATED AND INTERNALLY UNED AS SHOWN ON ® EQUIPMENT CALLOLJT ANY OF THE PROJECT DRAWINGS AND SUCH CONFUCT COULD HAVE BEEN AVOIDED BY PROPER 1.7 PROJECT CLOSE-OUT INSTALLED SHALL COMPLY WITH INDUSTRY RECOGNIZED STANDARDS AND FEATURES. DRAWINGS AND SPECIFICATIONS. it T COORDINATION BETWEEN TRADES OR PROPER PRE-PUNNING OF WORK,SUCH REQUIRED CHANGES B. COORDINATE MECHANICAL SYSTEMS,EQUIPMENT,AND MATERIALS INSTALLATION WITH OTHER BUILDING TURNING VANE SHALL BE MADE BY THE CONTRACTOR AT NO EXTRA COST. THESE CHANGES ARE TO BE RECORDED ON A. CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE TO REPLACE OR REPAIR ANY DEFECTS IN COMPONENTS.SEQUENCE,COORDINATE,AND INTEGRATE INSTALLATIONS OF MECHANICAL MATERIALS AND G5 DUCTWORK LAYOUT IS PARTIALLY DIAGRAMMATIC.OFFSETS AND ADJUSTMENTS MAY BE REQUIRED TO ® DETAIL CALLOUT THE RECORD DRAWINGS. WORKMANSHIP OR EQUIPMENT,WHICH DEVELOP WITHIN ONE YEAR FROM ACCEPTANCE BY THE OWNER. EQUIPMENT FOR EFFICIENT FLOW OF THE WORK.GIVE PARTICULAR ATTENTION TO LARGE EQUIPMENT COORDINATE WITH LIGHTS,DUCTS,PLUMBING,FIRE SPRINKLERS AND STRUCTURE. .� ? MITERED CORNER E. THIS CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL INCIDENTAL ELECTRICAL INTERCONNECTIONS, CONTRACTOR MUST ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED TO REPAIR OR REPLACE REQUIRING POSITIONING PRIOR TO CLOSING IN THE BUILDING.GIVE RIGHT-OF-WAY PRIORITY TO 7--' CONTROL WIRING,ETC.,WHICH ARE NECESSARY FOR SYSTEM COMPLETION AND WHICH ME NOT HIS WORK AS WELL AS WORK OF OTHER TRADES THAT MAY BE AFFECTED BY THIS REPLACEMENT. SYSTEMS REQUIRED TO BE INSTALLED AT A SPECIFIED SLOPE. G6 COORDINATE T-STAY LOCATIONS WITH OWNER. O TEMPERATURE GAUGE SPECIFICALLY SHOWN OR OTHERWISE INDICATED ON THE ELECTRICAL DRAWINGS OR SPECIFIED IN B. CONTRACTOR SHALL MAINTAIN A REDLINED SET OF CONSTRUCTION DRAWINGS SHOWING DEVIATIONS C. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED,INSTALL SYSTEMS,MATERIALS,AND DMS T �FLy�7 10 F. ALL ELECTRICAL WORK INCIDENTAL TO OR ACCOMPLISHED UNDER THIS DIVISION SHALL COMPLY WITH AT ACC 26. CEPTANCE ON THE F NGS AND THEWORK. CEILING CONDITIONS.THESE SHALL BE TURNED OVER TO THE OWNER EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM POSSIBLE. G7 CONTCEI NRG SUBCONTRACTOOR SHALL RmMAY FY KNOW WHERE TO SERVICEABLE TEMS NSTALLL ACCESS-TTYPE PANELS SHOUPERS,COILS, LDA THAT POINT OF CONNECTION �/ RADIUS ELBOW ��$y\emu ALL REQUIREMENTS OF DIVISION 26. D. INSTALL SYSTEMS,MATERIALS,AND EQUIPMENT LEVEL AND PLUMB,PARALLEL AND PERPENDICULAR TO �Q C. PROVIDE THREE UIP COMPLETE SETS OF OPERATION AND ECOMME MAINTENANCE MANUALS.THESE ARE TO OTHER BUILDING SYSTEMS AND COMPONENTS,WHERE INSTALLED EXPOSED IN FINISHED SPACES. TYPES SPECIFICALLY NOT BE INSTALLED,THIS CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR HIS WORK G. PLANS ARE DIAGRAMMATIC IN NATURE CONTRACTOR IS RESPONSIBLE FOR REFERRING TO THE DESIGN INCLUDE ALL EQUIPMENT CUT-SHEETS,MANUFACTURERS RECOMMENDED MAINTENANCE PROCEDURES, UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.ARCHITECT SHALL APPROVE LOCATIONS OF ACCESS t� INTAKE OR EXHAUST Q E. INSTALL MECHANICAL EQUIPMENT TO FACILRATE SERVICING,MAMENAICE,AND REPAIR OR V DOCUMENTS FOR ALL OTHER DISCIPLINES FOR PROTECT CONSTRUCTION AND OTHER DETAILS WHICH MANUFACTURERS WARRANTEE INFORMATION,AND CONTRACTORS WARRANTEE LETTER AND CONTACT PANELS PRIOR TO INSTALLATION. INFORMATION. REPLACEMENT OF EQUIPMENT COMPONENTS.AS MUCH AS PRACTICAL,CONNECT EQUIPMENT FOR EASE AFFECT THE MECHANICAL INSTALLATION. CONTRACTOR SHALL CONFER WITH ALL OTHER TRADES FOR F DIRECTION OF AIRFLOW FINISH ADJACENT A ITS WORK AND ARRANGE TO HAVE VISIBLE PORTIONS OF THIS WORK(SUCH AS OF FITTINGS TNECTINC,WITH MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS.EXTEND GREASE G8 ALL PENETRATIONS MADE THROUGH THE RATED ASSEMBLIES S ACCOMMODATE WORK OF THIS SECTION, D. PROVIDE THREE(3)REVIEWED BALANCE REPORTS OF WATER AND AIR SYSTEMS AS APPLICABLE. FITTINGS TO AN ACCESSIBLE LOCATION. ACCESS DOORS,VALVES,SPRINKLER HEADS,ESCUTCHEONS,ETC.)MERGE WITH THE FINISH IN A E. CONTRACTOR SHALL INSTRUCT THE OWNER ON THE OPERATION AND MAINTENANCE OF ALL SYSTEMS F. DRAWINGS ARE NOT DETAILED TO THE EXTENT THAT ALL DUCTWORK AND PIPING OFFSETS,BENDS,AND MUST BE SEALED TO MAINTAIN THE RATING OF SUCH ASSEMBLY BY A U.L RECOGNIZED SEALING O F pF, &"l` MANNER SATISFACTORY NT THE ARCHITECT. METHOD. 9FY ppP H. CONTRACTOR SHALL IDENTIFY ALL SERVICEABLE ITEMS(VALVES,DAMPERS,COILS,ETC.)SO THAT THE PROVIDED UNDER THIS CONTRACT. SPECIAL FITTINGS ARE SHOWN AND EXACT LOCATION INDICATED;HOWEVER,THEY ARE TO BE PROVIDED CEILING SUBCONTRACTOR MAY KNOW WHERE TO INSTALL ACCESS-TYPE PANELS SHOULD A UFT-UP PART 2 - PRODUCTS WHETHER SHOWN OR NOT.REFER TO SCHEDULES FOR ACCESSORIES. G9 CONTRACTOR HAS SOLE RESPONSIBILITY TO COORDINATE ANY SUBSTITUTIONS WITH ALL OTHER 08/10/2023 TYPE CEILING NOT BE INSTALLED.THIS CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR HIS WORK 21 GENERAL G. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY PROTECTING ANY PENETRATION OF A FIRE DISCIPLINES.EQUIPMENT OF GREATER POWER,DIMENSIONS,CAPACITIES,AND RATINGS MAY BE ABBREVIATIONS & DESCRIPTIONS . UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.ARCHITECT SHALL APPROVE LOCATIONS OF ACCESS RATED ASSEMBLY. FIRE SEAL,CAULKING,AND APPURTENANCES SHALL BE UL USTED FOR THE FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT HAS BEEN SUBMITTED FOR REVIEW,IN WRITING AC AIR CONDITIONING HVAC HEATING,VENTILATING,AIR CONDITIONING PANELS PRIOR TO INSTALLATION. A. DUCT DIMENSIONS SHOWN ON PUNS ARE NET FREE AREA ASSEMBLY RAZING IT IS APPLIED TO AND SHALL BE INSTALLED PER THE MANUFACTURERS WRITTEN AND CONNECTING MECHANICAL AND ELECTRICAL SERVICES,CIRCUIT BREAKERS,CONDUIT,MOTORS, I. CEILING HEIGHTS:ARCHITECTURAL DRAWINGS SHALL BE CHECKED FOR CEILING HEIGHTS,WALLS,AND B. ROUND ELBOWS MUST HAVE A CENTERLINE RADIUS OF NO LESS THAN 1.5 TIMES THE DIAMETER OF INSTRUCTIONS.ALL SUCH MATERIALS SHALL MEET STATE,LOCAL,AND AUTHORITIES CODES AND BASES,AND EQUIPMENT SPACES ARE ADJUSTED APPROPRIATELY.NO ADDITIONAL COSTS WILL BE AFF ABOVE FINISHED FLOOR KES KITCHEN EQUIPMENT SUPPLIER YW1 CABINETS THAT ARE INTENDED TO CONCEAL WORK OF THIS SECTION.WHERE CONFlJCTS OCCUR,THE THE ELBOW.SQUARE ELBOWS SHALL HAVE TURNING VANES UNLESS SHOWN AS RPDIUSED ELBOWS. STANDARDS. APPROVED FOR THESE INCREASES,IF LARGER EQUIPMENT IS PROPOSED.IF MINIMUM ENERGY AI1U AR HANDLING UNIT KW KILOWATT F ARCHITECT SHALL E I NOTIFIED PRIOR CONCEAL INSTALLATION THIS THE WORK.LOCATION FU EXPOSED WORK C. ALL DUCTWORK EXPOSED TO VIEW SHALL BE ROUND SPIRAL H. STANDARDS. ARE PROHIBITED IN ANY STRUCTURAL MEMBERS(EXCEPT WHERE NOTED IN DRAWINGS) RATINGS OR EFFICIENCIES OF THE EQUIPMENT ARE SPECIFIED,THE EQUIPMENT MUST MEET THE BTU AIR HA THERMAL UNITS KWH KILOWATT HOUR SUCH AS LIGHTS,DIFFUSERS,SPEAKERS,SPRINKLER HEADS TAKE PRECEDENCE OVER CONCEALED WHICH THE WRITTEN CONSENT OF THE ARCHITECT.OBTAIN APPROVAL FOR OTHER FRAMED OPENINGS DESIGN REQUIREMENTS AND COMMISSIONING REQUIREMENTS. CONTRACTOR N SOLELY RESPONSIBLE CA CBTU'sOMB PER HOUR L ACOUSTICAL DUCT LINER 2.2 DUCTWORK MATERIALS FOR SUBSTITUTED EQUIPMENT MEETING THE INTENT OF THE ORIGINAL DESIGNED EQUIPMENTIN ALL CA COMBUSTION AIR WORK. WHICH NAL U REQUIRED IN ADDITION TO THOSE SHOWN ON DRAWINGS.PAY ALL COSTS FOR LAT LEAVING AR TEMPERATURE J. CONTRACTOR SHALL EXERCISE CARE TO MINIMIZE ANY DISTURBANCE TO ADJACENT AREAS OF THE A. COMPLY WITH SMACNA'S"HVAC DUCT CONSTRUCTION STANDARDS--METAL AND FLEXIBLE"FOR ADDITIONAL CUTTING OF HOLES AS THE RESULT OF INCORRECT LOCATION OF SLEEVES OR FURNISHING AS CC COOLING COIL BUILDING WHICH ARE TO REMAIN IN OPERATION.ISOLATE WORK AREAS BY TEMPORARY PARTITIONS, ACCEPTABLE MATERIALS,MATERIAL THICKNESS,AND DUCT CONSTRUCTION METHODS,UNLESS INCORRECT INFORMATION AS TO THE REQUIREMENTS OF FRAMED OPENINGS. CFF CAP FOR FUTURE MAX MAXIMUM TARPS,ETC.,TO KEEP DUST AND DIRT IN THE CONSTRUCTION AREA OTHERWISE INDICATED.SHEET METAL MATERIALS SHALL BE FREE OF PITTING,SEAM MARKS,ROLLER I. FIRE-RATED ASSEMBLY PENETRATIONS: CFM CUBIC FEET PER MINUTE MCA MINIMUM CIRCUIT AMPS K. PROVIDE ALL NECESSARY FLASHING,SEALING,ETC.,TO MAINTAIN THE WATERPROOF INTEGRITY OF THE MARKS,STAINS,DISCOLORATIONS,AND OTHER IMPERFECTIONS.UNLESS STATED OTHERWISE,ALL CHI CHILLED WATER RETURN MOCP MAXIMUM OVERCURRENT PROTECTION BUILDING AS REQUIRED BY THE INSTALLATION OR REMOVAL OF ITEMS AS REQUIRED BY THIS SCOPE OF DUCTWORK TO BE 26 GAUGE MINIMUM. 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY PROTECTING ANY PENETRATION OF A MIN MINIMUM FIRE RATED ASSEMBLY. FIRE SEAL,CAULKING,AND APPURTENANCES SHALL BE UL LISTED FOR CHWS CHILLED WATER SUPPLY WORK. B. GALVANIZED SHEET STEEL LOCK-FORMING QUALITY;COMPLYING WITH ASTM A 653/A 653M AID THE ASSEMBLY RATING IT IS APPLIED TO AND SHALL BE INSTALLED PER THE MANUFACTURERS CLG CEILING INC NOISE CRITERIA L. INSTALL ALL WORK OF THIS SCOPE TO BE READILY ACCESSIBLE FOR OPERATION,HIS,BUT MAINTENANCE,AND HAVING G90(Z275)COATING DESIGNATION;DUCTS SHALL HAVE MILL-PHOSPHATIZED FINISH FOR WRITTEN INSTRUCTIONS.ALL SUCH MATERIALS SHALL MEET STATE,LOCAL,AND AUTHORITIES CODES CW COLD WATER NFPA NATIONAL FIRE PROTECTION ASSOCIATION REPAIR.MINOR DEVIATIONS FROM THE DRAWINGS MAY BE MADE TO ACCOMPLISH THIS,BUT CHANGES SURFACES EXPOSED TO VIEW. AND STANDARDS. DEG DEGREE NTS NOT TO SCALE INVOLVING OTHER TRADES MAY NOT A MADE WITHOUT PRIOR APPROVAL. C. CARBON-STEEL SHEETS:ASTM A 366/A 366M,COLD-ROLLED SHEETS;COMMERCIAL QUALITY;WITH 2. REFER TO ARCHITECTURAL DRAWINGS FOR ALL FIRE RATED ASSEMBLY LOCATIONS AND RATINGS. M. ALL PENETRATIONS MADE THROUGH RATED ASSEMBLIES TO ACCOMMODATE WORK OF THIS SECTION, DIAL DIAMETER OSA OUTSIDE AR MUST BE SEALED TO MAINTAIN THE RATING OF SUCH ASSEMBLY BY A U.L RECOGNIZED SEALING OILED,MATTE FINISH FOR EXPOSED DUCTS. J. SEISMIC RESTRAINT: DB DRY BULB TEMPERATURE PD PRESSURE DROP METHOD. D. STAINLESS STEEL:ASTM A 48O/A 480M,TYPE 316 OR 304,AND HAVING A NO.2D FINISH FOR 1. THE CONTRACTOR SHALL PROVIDE PROPER MECHANICAL SEISMIC RESTRAINTS FOR ALL INSTALLED EA EXHAUST AIR PH PHASE N. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF THIS WORK.COORDINATE ALL CONCEALED DUCTS AND SUITABLE FINISH FOR EXPOSED DUCTS. HEATS INCLUDING,BUT NOT LIMITED TO,DUCTS,PIPING,EQUIPMENT AND ACCESSORIES.THE EAT ENTERING AIR TEMPERATURE PRV PRESSURE REDUCING VALVE BLOCKING,SUPPORT,ETC.,NECESSARY FOR THE INSTALLATION OF THIS WORK WITH THE GENERAL CONTRACTOR SHALL PROVIDE SEISMIC RESTRAINTS AS LISTED BY THE CODES USED BY THE AM EER ENERGY EFFICIENCY RATIO RA RETURN AR CONTRACTOR. 2.3 INSULATION AND LINER OR AS SHOWN ON THE DRAWINGS(WHICHEVER IS MORE STRINGENT). ESP EXTERNAL STATIC PRESSURE RPM REVOLUTIONS PER MINUTE 1.3 CODES. STANDARDS. PERMITS. AND FEES A. GENERAL: 3.3 DUCT INSTALLATION ENT ENTERING WATER TEMPERATURE BTU ROOFTOP UNIT A. ALL APPUCABLE CODE LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS 1. FIRE-HAZARD CLASSIFICATION:MAXIMUM FlAME-SPREAD INDEX Of 25 AND SMOKE-DEVELOPED FCO FLOOR CLEANOUT SA SUPPLY AIR WORK ARE HEREBY INCORPORATED INTO AND MADE A PART OF THESE SPECIFICATIONS.THEIR INDEX OF 50 WHEN TESTED ACCORDING TO ASTM E 84. A CONSTRUCT AND INSTALL DUCTS ACCORDING TO SMACNA'S"HVAC DUCT CONSTRUCTION FD FIRE DAMPER SEER SEASONAL ENERGY EFFICIENCY RATIO PROVISIONS SWILL BE CARRIED OUT BY THE CONTRACTOR,WHO SHALL INFORM THE ARCHITECT IN 2. INSULATION SCHEDULE: STANDARDS--METAL AND FLEXIBLE.° SFD/FSD COMBINATION SMOKE/FIRE DAMPER WRITING PRIOR TO SUBMITTING A BID,OF ANY WORK OR MATERIALS WHICH VIOLATE ANY OF THE a. INSIDE THE BUILDING THERMAL INSULATION ENVELOPE-ALL INSTALLED VALUES TO BE R-6 B. INSTALL DUCTS WITH FEWEST POSSIBLE JOINTS.INSTALL FABRICATED FITTINGS FOR CHANGES IN FU FULL LOAD AMPS SIP STATIC PRESSURE ENFORCED LAWS,CODES,OR REGULATIONS.IF THE CONTRACTOR PERFORMS ANY WORK CONTRARY TO MINIMUM. DIRECTIONS,SIZE,AND SHAPE AND FOR CONNECTIONS. FLR FLOOR SYM SYMBOL SUCH LAWS,ORDINANCES,RULES AND REGULATIONS,HE SHALL ASSUME FULL RESPONSIBILITY,AND 1) INSULATE ALL RECTANGULAR DUCT WITH 1/2"DUCT LINER MINIMUM UNLESS NOTED C. COORDINATE LAYOUT WITH SUSPENDED CEILING,FIRE-AND SMOKE-CONTROL DAMPERS,LIGHTING FPM FEET PER MINUTEFT FEET TA TRANSFER AIR SHALL BEAR ALL COSTS ASSOCIATED WITH BRINGING WORK INTO COMPLIANCE. OTHERWISE ON THE MECHANICAL SHEETS. LAYOUTS,AND SIMILAR FINISHED WORK. T&P TEMPERATURE AND PRESSURE B. WHERE DRAWINGS OR SPECIFICATIONS CALL FOR MATERIAL ED CONSTRUCTION OF A BETTER QUALITY OR 2) INSULATE ALL ROUND SUPPLY DUCT AND OUTSIDE AIR DUCT WITH 1-1/2"FOIL FACED D. SEAL ALL JOINTS WITH UNITED DUCT SEALANT.APPLY SEALANT TO MALE END CONNECTORS BEFORE GA GRRADE CLEANOUT AUGE TENT TYPICAL HIGHER DRAWING THAN REQUIRED T BY THE ABOVE-MENTIONED CODES AND STANDARDS,THE PROVISIONS TEMP TEMPERATURE OF THE DRAWINGS OR SPECIFICATIONS SHALL TAKE PRECEDENCE OVER THE REQUIREMENTS OF THE DUCT WRAP EXCEPT EXPOSED SPIRAL TO BE UN-INSULATED. ROUND RETURN DUCT INSERTION,AND AFTERWARD TO COVER ENTIRE JOINT AND SHEET META SCREWS. GPM GALLONS PER MINUTE UMC UNIFORM MECHANICAL CODE CODES AND STANDARDS. DOES NOT NEED TO BE INSULATED. E. NON-FIRE-RATED PARTITION PENETRATIONS:WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS AND HC HEATING COIL UPC UNIFORM PLUMBING CODE C. THE RESPECTIVE SUB-CONTRACTOR,AT HIS EXPENSE,SHALL OBTAIN ALL PERMITS AND FEES REQUIRED b. OUTSIDE THE BUILDING THERMAL INSULATION ENVELOPE,BUT INSIDE THE ATTIC SPACE. EXTERIOR WALLS AND ARE EXPOSED TO VIEW,CONCEAL SPACES BETWEEN CONSTRUCTION OPENINGS HP HORSEPOWER VTR VENT THROUGH ROOF 1 INSULATE ALL SUPPLY AND RETURN DUCTS TO R-6 MINIMUM. REFERENCE NOTE ON AND DUCTS OR DUCT INSULATION WITH SHEET METAL FLANGES OF SAME METAL THICKNESS AS DUCTS. V VOLTS FOR THIS SCOPE OF WORK ON THIS PROJECT.THE SUB-CONTRACTORS SHALL ALSO SCHEDULE ALL ) IECC INTERNATIONAL ENERGY REQUIRED INSPECTIONS AND OBTAIN CERTIFICATES FOR HIS WORK,AT HIS EXPENSE. SHEET M2.1 FOR ADDITIONAL INFORMATION. OVERLAP OPENINGS ON 4 SIDES BY AT LEAST 1-1/2 INCHES. CONSERVATION CODE D. THE FOLLOWING SPECIFIC STANDARDS SHALL BE CONSIDERED AS MINIMUM REQUIREMENTS FOR WORK OF 3. ALL DUCTWORK TO BE INSULATED AT A MINIMUM TO MEET 2018 IECC SUPERCEDING THE ABOVE F. FIRE-RATED PARTITION PENETRATIONS:WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS AND WB WET BULB THIS SECTION: SCHEDULE IF CALLED OUT AS LESS THAN CODE. EXTERIOR WALLS,INSTALL APPROPRIATELY RATED FIRE DAMPERS,SLEEVES,AND FlRESTOPPING W/ WITH 1. DUCTWORK:ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED PER THE PUBLISHED STANDARDS B. DUCT INSULATION:MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN.COMPLY WITH SEALANT. OF THE AMERICAN SOCIETY OF HEATING,REFRIGERATION,AND AIR CONDITIONING ENGINEERS ASW C 553,TYPE II AND ASTM C 1290,TYPE III WITH FACTORY-APPUED FSK JACKET. G. PAINT INTERIORS OF METAL DUCTS,THAT DO NOT HAVE DUCT LINER,FOR 24 INCHES UPSTREAM OF SHEET INDEX (ASHRAE)AND THE SHEET METAL AND AIR CONDITIONING NATIONAL ASSOCIATION(SMACNI),AND C. FIBROUS-GLASS LINER:COMPLY WITH NFPA 90A OR NFPA 90B AND WITH NAIMA AH124. REGISTERS AND GRILLES.APPLY ONE COAT OF FLAT,BLACK,LATEX FINISH COAT OVER A COMPATIBLE MEET THE REQUIREMENTS OF NFPA 90 AND NFPA 91. 1. MATERIALS:ASTM C 1071;SURFACES EXPOSED TO AIRSTREAM SHALL BE COATED TO PREVENT GALVANIZED-STEEL PRIMER. 2. FILTERS:ALL FILTER MEDIA SHALL BE UL CLASS 2. EROSION OF GLASS FIBERS. H. PROVIDE BALANCING DAMPERS AT POINTS ON SUPPLY,RETURN,AND EXHAUST SYSTEMS WHERE MO.0 HVAC COVER SHEET BRANCHES LEAD FROM LARGER DUCTS AS REQUIRED FOR AIR BALANCING.INSTALL AT A MINIMUM OF MO.1 HVAC ENERGY COMPLIANCE FORMS 3. FIRE DAMPERS:ALL FIRE DAMPERS SHALL EQ LISTED 1 AND INSTALLED PER IL FOR THE ASSEMBLY a. THICKNESS:1/2",UNLESS NOTED OTHERWISE. TWO DUCT WIDTHS FROM BRANCH TAKEOFF. THEY ARE INSTALLED IN,AND MEET THE REQUIREMENTS OF THE LOCAL BUILDING CODE. M2.1 HVAC PLAN b. LINER ADHESIVE:COMPLY WITH NFPA 90A OR NFPA 90B AND WITH ASTM C 916. I. INSTALL FLEXIBLE CONNECTORS IMMEDIATELY ADJACENT TO EQUIPMENT IN DUCTS ASSOCIATE)WITH M2.2 HVAC ROOF PLAN 1.4 SUBMITTALS AND SUBSTITUTIONS c. MECHANICAL FASTENERS:GALVANIZED STEEL SUITABLE FOR ADHESIVE ATTACHMENT, FANS AND MOTORIZED EQUIPMENT SUPPORTED BY VIBRATION ISOLATORS. M3.0 HVAC SCHEDULES A. SUBMITTAL MATERIALS SHALL BE COMPLETE IN EMERY RESPECT AND SHALL CLEARLY INDICATE MECHANICAL ATTACHMENT,OR WELDING ATTACHMENT TO DUCT WITHOUT DAMAGING UNER WHEN J. CONNECT DIFFUSERS GRILLES TO LOW PRESSURE DUCTS WITH MAXIMUM 8 FEET LENGTHS OF FLEXIBLE M4.0 HVAC DETAILS EQUIPMENT FUTURES,DIMENSIONS,WEIGHTS,PERFORMANCE CHARACTERISTICS,AND CAPACITIES. APPLIED AS RECOMMENDED BY MANUFACTURER AND WITHOUT CAUSING LEAKAGE IN DUCT. DUCT CLAMPED OR STRAPPED IN PLACE.CONNECT FLEXIBLE DUCTS TO METAL DUCTS WITH DRAW CAPACITY AND PERFORMANCE CALCULATIONS SHILL BE ADJUSTED TO INDICATE ACTUAL EQUIPMENT D. REFRIGERANT PIPING INSULATION:SUCTION PIPING-FLEXIBLE ELASTOMERIC,1"THICK. BANDS. PERFORMANCE AT THE PROJECT ELEVATION. LITERATURE OR DRAWINGS THAT DESCRIBE MORE THAN 2.4 DUCT ACCESSORIES K. INSTALL BACKDRAFT DAMPERS ON EXHAUST FANS OR EXHAUST DUCTS NEAREST TO OUTSIDE AND ONE MODEL OR SIZE OF EQUIPMENT SHALL BE MARKED WITH ARROWS OR OTHERWISE CLEARLY WHERE INDICATED. INSCRIBED TO IDENTIFY THE ACTUAL EQUIPMENT THAT WILL BE FURNISHED. ALL OPTIONS AND SPECIAL A. STANDARD VOLUME DAMPERS:SINGLE OR OPPOSED-BLADE DESIGN,STANDARD LEAKAGE RATING,AND PARTS OF FUTURES SHALL ALSO BE CLEARLY IDENTIFIED. ALL SUBMITTED MATERIALS MUST BE CLEAR, SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS.SHAFTS TO BE FULL LENGTH,GALVANIZE) 3.4 HANGING AND SUPPORTING COMPLETE,AND LEGIBLE. ALL SUBMITTALS OF THIS SCOPE MUST BE SUBMITTED AT ONE TIME; STEEL,WITH ZINC-PLATED,DIE-CAST CORE WITH DIAL AND HANDLE MADE OF 3/32-INCH-THICK A SUPPORT HORIZONTAL DUCTS WITHIN 24 INCHES OF EACH ELBOW AND WITHIN 48 INCHES OF EACH �..� MULTIPLE AND VARIED SUBMITTALS WILL BE REJECTED. ZINC-PLATED STEEL,AND A INCH HEXAGON LOCKING NUT.INCLUDE CENTER HOLE TO SUIT BRANCH INTERSECTION. C� B. SUBMITTALS FOR ALL EQUIPMENT SHALL BE ROUTED THROUGH AND REVIEWED BY THE CONTRACTOR. DAMPER OPERATING-ROD SIZE.INCLUDE ELEVATED PLATFORM FOR INSULATED DUCT MOUNTING. B. SUPPORT VERTICAL DUCTS AT MAXIMUM INTERVALS OF 16 FEET AND AT EACH FLOOR. G� THE CONTRACTOR SHALL CHECK ALL SUBMITTALS FOR ADEQUATE IDENTIFICATION,CORRECTNESS,AND B. FIRE DAMPERS:CURTAIN TYPE;FIRE DAMPERS SHALL BE LIBELED ACCORDING TO UL 555. C. SUPPORT ALL DUCTWORK,PIPING,MD EQUIPMENT AS REQUIRED BY THE LOCAL CODES, 4- �y COMPLIANCE WITH CONTRACT DRAWINGS AND SPECIFICATIONS AND APPLY A STAMP OF APPROVAL. FOR 1. FRAME:FABRICATED WITH ROLL-FORMED, SHALL THICK GALVANIZED STEEL;WITH MITERED MANUFACTURERS RECOMMENDATIONS,AND STANDARD INDUSTRY PRACTICE. N O SUBMITTALS THAT ARE REQUIRED TO BE REVIEWED BY THE ENGINEER,A DIGITAL COPY SHALL BE AND INTERLOCKING CORNERS. D. USE MATERIALS COMPATIBLE WITH ITEMS BONG SUPPORTED TO AVOID ELECTROLYTIC ACTION,AND 0 S"I FORWARDED FOR REVIEW AFTER REVIEW AND APPROVAL BY THE CONTRACTOR. THESE SHALL BE 2, BLADES:ROLL-FORMED,INTERLOCKING,0.034-INCH-THICK,GALVANIZED SHEET STEEL.IN PLACE CONFORM TO SMICNA ANSI/ASME B31,NFPA,MSS SP-58,69,89. RETURNED AND SHALL BE REVISED AND RESUBMITTED UNTIL ACCEPTED BY THE ENGINEER. PROVIDE OF INTERLOCKING BLADES,USE FULL-LENGTH,0.034-INCH-THICK,GALVANIZED-STEEL BLADE PRODUCT DATA FOR EACH PIECE OF EQUIPMENT/COMPONENT LISTED IN SCHEDULES. 3.5 ACCESS DOORS AND PANELS C. APPROVED MANUFACTURERS WHICH MAY SUBMIT EQUAL PRODUCT TO THOSE SPECIFIED ARE LISTED IN CONNECTORS. A 3 FUSIBLE LINK REPLACEABLE,165 DEGREE F RATED. : . DUCT ACCESS DOORS:INSTALL DUCT ACCESS DOORS TO ALLOW FOR INSPECTING,ADJUSTING,AND THE EQUIPMENT SCHEDULES.ANY SUBMITTAL FOR CONSIDERATION AS AN EQUAL TO THAT SCHEDULED MAINTAINING ACCESSORIES AND TERMINAL UNITS AS FOLLOWS: MUST CONTAIN ALL INFORMATION REQUIRED TO EVALUATE THIS CLAM.MANUFACTURERS NOT LISTED AS C. CEILING FIRE DAMPERS:LIBELED ACCORDING TO UL SSSC;COMPLY WITH CONSTRUCTION DETAILS FOR ll O EQUAL SUBMIT IN WRITING FOR REVIEW AN W TEN DAYS PRIOR TO BID CLOSING. CONTRACTOR IS TESTS)FLOOR- D ROOF-CEILING ASSEMBLIES AS INDICATED IN UL'S TIRE RESISTANCE DIRECTORY." 1 ADJACENT TO FIRE OR SMOKE DAMPERS,PROVIDING ACCESS TO RESET OR REINSTALL FUSIBLE MUST LINKS. RESPONSIBLE TO ASSURE ANY SU , ,BSTITUTED ITEM MEETS ALL PHYSICAL AND PERFORMANCE 1. FRAME:GALVANIZED SHEET STEEL ROUND OR RECTANGULAR STYLE TO SEAR CEIDNG O B. ARCHITECTURAL ACCESS DOORS OR PANELS:COORDINATE REQUIREMENTS FOR ACCESS PANELS AND HE DESIGN DOCUMENTS.REQUIREMENTS AS INTENDED IN T CONSTRUCTION. U � D. APPROVAL OF SUBMITTALSDOORS WHERE MECHANICAL ITEMS REQUIRING ACCESS ARE CONCEALED BEHIND FINISHED SURFACES. BY THE ENGINEER SHALL NOT RELIEVE THE CONTRACTOR FROM 2. BLADES:GALVANIZED SHEET STEEL WITH REFRACTORY INSULATION. THIS CONTACTOR SHALL PROVIDE ACCESS PANELS OR DOORS OF SUFFICIENT SIZE TO ALLOW ACCESS RESPONSIBILITY FOR DEVIATIONS FROM DRAWINGS OR SPECIFICATIONS,NOR SHALL IT RELIEVE HIM FROM 3. FUSIBLE LINK:REPLACEABLE,165 DEGREE F RATED. TO HIS WORK THAT REQUIRES ACCESS FOR MAINTENANCE OR INSPECTION. RESPONSIBILITY FOR ERRORS IN SHOP DRAWINGS OR OTHER SUBMITTALE. CONTRACTOR HAS SOLE RESPONSIBILITY TO COORDINATE ANY SUBSTIlUT10N5 WITH ALL OTHER AL LITERATURE. D. COMBINATION FIRE/SMOKE DAMPERS:LABELED ACCORDING TO UL$555.COMBINATION FIRE AND � 24c� L 555 FOR 1-1/2-HOUR RATING. QL O L7y DISCIPLINES.EQUIPMENT OF GREATER POWER,DIMENSIONS,CAPACITIES,AND RATINGS MAY BE SMOKE DAMPERS SHALL BE LIBELED ACCORDING TO U a FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING 1. FRAME AND BLADES:0.064-INCH THICK,GALVANIZED SHEET STEEL. � S-I MECHANICAL AND ELECTRICAL SERVICES,CIRCUIT BREAKERS,CONDUIT,MOTORS,BASES,AND EQUIPMENT 2. MOUNTING SLEEVE:FACTORY-INSTALLED,0.052-INCH THICK,GALVANIZED SHEET STEEL;LENGTH TO �1 rTO r SPACES ARE INCREASED.NO ADDITIONAL COSTS WILL BE ACCEPTED FOR THESE INCREASES,IF LARGER SEAR WALL OR FLOOR APPLICATION. FLI F+I � EQUIPMENT IS PROVIDED.IF MINIMUM ENERGY RATINGS OR EFFICIENCIES OF THE EQUIPMENT ARE 3. FUSIBLE LINK:REPLACEABLE,165 DEGREE F RATED. SPECIFIED,THE EQUIPMENT MUST MEET THE DESIGN REQUIREMENTS AND COMMISSIONING REQUIREMENTS. 4. DAMPER MOTORS:MODULATING AND TWO-POSITION ACTION.EQUIP WITH AN INTEGRAL DESIGN OF ELECTRICAL REQUIREMENTS ISL BASED ON MECHANICAL I EQUIPMENT SPECIFIED. MECHANICAL SPIRAL-SPRING MECHANISM WHERE INDICATED.ENCLOSE ENTIRE SPRING MECHANISM IN A SCALE: CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR IF EQUIPMENT PURCHASED IS AS NOTED DIFFERENT FROM THAT SPECIFIED STILL MEETS DESIGN INTENT,INCLUDING BUT NOT LIMITED TO REMOVABLE HOUSING DESIGNED FOR SERVICE OR ADJUSTMENTS. OVERCURRENT PROTECTION,LOCAL DISCONNECTION MEANS,WIRE SIZING,AND DESIGN COSTS. 5. ELECTRICAL CONNECTION:115 V,SINGLE PHASE,60 HZ. DATE: E. FLEXIBLE CONNECTORS:FUME-RETARDANT OR NONCOMBUSTIBLE FABRICS,COATINGS,AND ADHESIVES 08/10/2023 COMPLYING WITH UL 181,CS 1.PROVIDE HEAVY METAL EDGE BANDS,SEALED TO PREVENT DWN BY: LEAKAGE. US RACITY APPROVED PLANS is 1. INDOOR SYSTEM,FLEXIBLE CONNECTOR FABRIC:GLASS FABRIC DOUBLE COATED WITH NEOPRENE. 2. OUTDOOR SYSTEM,FLEXIBLE CONNECTOR FABRIC:GLASS FABRIC DOUBLE COATED WITH Reviewed for Code Compliance CHECKED BY, WEATHERPROOF,SYNTHETIC RUBBER RESISTANT TO UV RAYS AND OZONE. CRA F. FLEXIBLE DUCTS:UL 181,CUSS 1,UL 181,CUSS 1,BLACK POLYMER FILM SUPPORTED BY PLANS MUST BE ON JOB SITE HELICALLY WOUND,SPRING-STEEL WIRE;FIBROUS-GLASS INSULATION;POLYETHYLENE VAPOR BARRIER FILM FOR ALL INSPECTIONS SHEET M0.0 Page 7 of 26 � S Z J REQUIRED OSA CALCULATION W w �i W 5 Q W E c.z OUTDOOR ZONE AIR DIST. ? SYSTEM ZONENAME ZONE CLASSIFICATION AREA(fill[A,]' #OF PEOPLE[l AIRFLOW/PERSON OUTDOOR AIRFLOW BREATHING ZONE EFFECTIVENESS 20181MC REQUIRED O IRP] /SgFt[R,]IF OSA[B,] [Er]a OSA W Laundromat Tl C7 laundromat Dry Cleaners,Laundries:Coin-operated laundries 1,099 sgft 22.0 pe 7.5 cfm 0.06 cfm/sgft 231 cfm 0.8 288cfm 0 I aund romat-partial using natural ventilation-see below 610 sgft O.Ope --- --- --- --- 0Cfm a corrarea Public Spaces:Corridors 696 sgft O.Ope 0.0 Cfm 0.06 cfm/sqft 42cfm 0.8 52 cfm counter Offices:Office space 77 sgft 0.4pe 5.0 cfm 0.06 cfm/sqft 7dm 0.8 8cfm office Offices:Office space 58 sgft 0.3 pe 5.0 cfm 0.06 cfm/sqft 5dm 0.8 6cfm Storage Retail:Storage rooms 358 sgft O.Ope 0.0 cfm 0.12 cfm/sqft 43 cfm 0.8 54 cfm Storage-partial using natural ventilation-see below 520 sgft O.Ope --- --- --- --- Ocfm BUILDING corr area Public Spaces:Corridors 90 sgft O.Ope 0.0 cfm 0.06 cfm/sqft 5don 0.8 7cfm Restroom Publ is Spaces:Toi l et rooms-public 67 sgft O.Ope 0.0 cfm 0.00 cfm/sqft 0cfm 0.8 Ocfm Tl System Total= 1 3,575 sgft 22.7 pe --- --- --- --- 415 cfm Notes:"1.Data from Project 2.Data from 20181 MC Table 403.3.3.1.1 3.Data from 20181 MC Table 403.3.1.1.1.2 NATURAL VENTILATION AIR CALCULATION BALANCE REPORT TO BE PROVIDED BEFORE FINAL SYSTEM ZONE NAME OCC.AREA(ft') 4%of GENERAL OPERABLE AREAS MEETSIMC402.2? MECH.VENT.REQ'D? INSPECTION agp2 9 OCC.AREA OPENINGS d, O Lau nd no mat Tl lau nd romat-partial 610 sgft 24.4 sgft 3.5'x 7'door 24.5 sgft YES NO Storage-partial 520sgft 20.8sgft Tx7'door 21.0sgft YES NO 08/10/2023 EXHAUST CALCULATION SYSTEM ROOM NAME EXHAUST REQUIRED EXHAUST #FIXTURES 20181MC REQUIRED EXHAUST USING CLASSIFICATION EXHAUST EF-1 Restroom Toilet-intermittent 70 cfm/fixture 1 70 cfm 70 cfm Notes:1.Restroom exhaust fan EF-1 to run intermittently,switched with the respective restroom lights. ✓ COMcheck Software Version 4.1.1.0 COMcheck Software Version 4.1.1.0 Mechanical Compliance Certificate Inspection Checklist Energy Code:2018IECC Requirements:100.0%were addressed directly in the COMcheck software Project Information Text in the"Comments/Assumptions"column is Provided by the user In the COMcheck Requirements screen.For each Energy Code: 2018 IECC requirement,the user certifies that a code requirement will be met and how that is documented,or that an exception Project Tide: TF Laundromat TI is being claimed.Where compliance is itemized in a separate table,a reference to that table is provided. Location: Twin Falls,Idaho Section Climate Zone: 5b # It..Review Complies? Comments/Assumptions Project Type: New Construction &Re.ID C103.2 ',Plans,specifications,and/or ❑Complies Requirement will be met. [PR21' calculations provide all information ❑Does Not Construction Site: Owner/A ent: Deal /Contractor: with which compliance can be g goer deter,fined for the mechanical ❑Not Observable', ''^^ Twin Falls,ID Corey Ahrens '.systems and equipment and ❑Not Applicable vI DC Engineering document where exceptions to the Additional Efficiency Package(s) Twin Falls,ID ',standard are claimed.Load cahrens@dcengineering.net calculations per acceptable engineering standards and ',handbooks. O Reduced interior lighting power.Requlr menu are implicitly enforced within interior lighting allowance calculations. C406 Plans,specifications,and/or ',OComplies Requl ement will be met. Mechanical Systems List [PR91' calculations provide all information '17 Does Not w Quantity System with which Compliance can be '�ONot Observable y y Type B Description determined for the additional energy 1 RTU-1(Single Zone): efficiency package options. ',ONot Applicable Heating:1 each-Central Furnace,Gas,Capacity=110 kBtu/h Additional Comments/Assumptions: Proposed Efficiency=83.00%Et,Required Efficiency:80.00%Et ar 80%AFUE F� Cooling:1 each-Single Package DX Unit,Capacity=65 kBtu/h,Alr-Cooled Condenser,Air Economizer Proposed Efficiency-11.00 EER,Required Efficiency:11.00 EER+12.61EER Fan System:None F� Mechanical Compliance Statement FBI Compliance Statement:The proposed mechanical design represented In this document is consistent with the building plans, specifications,and other calculations submitted with this permit application.The proposed mechanical systems have been �..1 designed to meet the 2018 IECC requirements In COMcheck version 4.1.1.0 and to comply with any applicable mandatory (� requirements listed in the Inspection Checklist. O r.l Corey Ahrens � � August 8,23 U Name-Title Signature Date �.,..r � z6 o w f> a O r ' x wO'CH 1 High Impact(Ter 1) Medium Impact(Tier 2) 3 Low Impact(Tier 3) SCALE: AS NOTED Project Title: TF Lau,dmmat Tl Report date: Iof 13 Project Title: TF e\projomat Tl Report date: 2of 13 CITY APPROVED PLANS DATE: Data filename:\\dce\projects\2023\23B0001-Laundromat\Colts\HVAC\Energy Calcs\Laundromat Tl.cck Page 1 of 10 Data filename:\\dce\projects\2023\23B0001-Laundromat\Calcs\HVAC\Energy Calcs\Laundromat Tl.cck Page 2 of 10 08/10/2023 Reviewed for Code Compliance DRAWN BY: JS PLANS MUST BE ON JOB SITE CHECKED BY: CRA FOR ALL INSPECTIONS SHEET M0.1 Page 8 of 26 CONSTRUCTION NOTES: 1. THE HVAC WORK IS PARTIALLY DESIGN/BUILD BY THE HVAC CONTRACTOR. THE INTENT OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS o S 5 --, BEING NECESSARY,FOR FURNISHING,INSTALLATION AND TESTING,COMPLETE DRYER TUNNEL S 5 AND READY FOR OPERATION OF THE WAG SYSTEMS,PER CODE. VERIFY ALL iRES7RPEI DIMENSIONS,SIZES,ETC.ON SITE. COORDINATE ALL WORK WITH THE 6.0SA _ ® ® ® a ® Is ® .._..J O GENERAL CONTRACTOR. �I w E m.Q rrrrrrrrrrrrrrrrrrrr : ' sc-1.10'0 -- 350 CFM 2. ALL WORK ASSOCIATED WITH THE DRYERS AND WASHERS TO BE VERIFIED AS Z 6"OEA UP THROUGH ACCEPTABLE PER THE DRYER AND WASHER MACHINE SUPPLIER,THE 0 �� SG 2.6"0 4 1 THE ROOF EQUIPMENT WRITTEN INSTALLATION INSTRUCTIONS AND THE GENERAL ()� S 80 CFM TYPICAL CONTRACTOR. Z m 3 N LLI N 3 N Fol + RG-1.1s a ITTU-t T T RTu-2Q o FIRE RISER GENERAL NOTES: U II II U " 1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF G \ \ \ \ \ \ \ \ \ \ PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT.PLUMBING VENTS, RC-1. 16"0 REGULATOR VENTS,FLUES,AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM lJJJ 10"0SA OF 10 FEET AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. RTU 2. ALL SUPPLY,RETURN AND OUTSIDE AIR DUCT TO BE INSULATED PER DRAWING 1 CALL OUT OR 2018 IECC AS A MINIMUM. ALL RECTANGULAR DUCTWORK TO SG-1,10.0 LOCATED ON i`® HAVE 1/2"ACOUSTICAL LINER MINIMUM. ALL ROUND SUPPLY AND OUTSIDE 350 CFM ROOF i a SG-1 SO-1 AIR DUCTWORK TO BE WRAPPED WITH A MINIMUM OF 1-1/2'DUCT WRAP ��L���/�L� INSIDE BUILDING INSULATION ENVELOPE. ALL SUPPLY FLEX DUCT TO BE R-6 10 MINIMUM. ROUND RETURN AIR LOCATED BELOW THE BUILDING INSULATION I��I IL�I ENVELOPE MAY BE UNINSULATED. HT 20"ORA 3. RECTANGULAR DUCT SIZES ARE SHOWN AS NET FREE INSIDE DIMENSIONS. ADJUST DUCTWORK SIZES TO MEET SIZING AS REQUIRED WITH ACOUSTICAL � --- - ET LINER THICKNESS AS CALLED FOR IN THE INSULATION SPECIFICATIONS. HET 4. COORDINATE ALL DUCTWORK HEIGHTS CROSSING THROUGH THE TRUSSES AND WALLS. VERIFY FINAL CEILING INSTALLATION HEIGHTS AND TYPES. LAUNDROMAT COORDINATE CEILING GRILLE LOCATIONS WITH THE ELECTRICAL CONTRACTOR. _j=_Cm�j ti RG-1 5. ALL SUPPLY GRILLES TO HAVE EITHER AN OBD OR AN ACCESSIBLE MANUAL DAMPER IN THE RUNOUT. �YONALf�, 460 12'f 9 O 6. GRILLES STYLES TO MATCH CEILING TYPE. 10"0 CFM �� `DUICT DIFFUSERSTING TO EMY AND AIN FROM p lllllllll EXISTING ROOF TOP RTU-36 T 7. COORDINATE FINAL THERMOSTAT LOCATIONS WITH THE OWNER. a, A SG 1 M STORAGE 10'"0SA T' UNIT ON THE ROOF B. COORDINATE ALL ELECTRICAL CONNECTIONS WITH THE ELECTRICAL CONTRACTOR. V02 350 CFM p 35 J 9. GAS PIPING BY THE PLUMBING CONTRACTOR. F y pHQ'� OB/10/2023 Fol a KEYED NOTES: W rc SG-1 �1. ®® F JJrc11JJff 10 ILA 10 1. NEW OPENING THROUGH THE EXISTING ROOF. ROOF PATCH TO BE BY THE ROOFING CONTRACTOR,COORDINATE WITH THE GENERAL CONTRACTOR. SEE SHEET M2.2 FOR CONTINUATION. 2. INSTALL NEW EXHAUST FAN IN THE NEW GYP.COILING. 3. DRYER ROOM TO BECOME UNCONDITIONED SPACE. NO WATER PIPING TO BE SG-1.10110' o INSTALLED IN THIS ROOM. GAP EXISTING SUPPLY AND RETURN DUCT OPENINGS 350 CFM INTO THIS ROOM IF EXISTING. FF- IF F� �� F\� T\� T\� F\x F\� F\� FF Ire IT-� IT-� r� Ire IT-� r� Ire IT'S Ire IT-� T'� r� r� II \ I \ \ \ II \ II \ II \ II \ II \ II \ II \ II \ II II II II II II II II II II MECHANICAL 4. PROVIDE AND INSTALL AN INDMDUAL 8"0 EXHAUST VENT TYPICAL FOR EACH DRYER. VERIFY SIZE WITH DRYER MANUFACTURER. VENTING MATERIAL TO BE PER DRYER MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. 5. OFFSET VENT AS REQUIRED TO MISS MAKE-UP AIR INTAKE. 6. PROVIDE AND INSTALL NEW SEVEN DAY PROGRAMMABLE THERMOSTAT. EXTEND WIRING TO EXISTING ROOFTOP UNIT. 7. NEW 3'X6'MAKE-UP AIR OPENING THROUGH THE ROOF,REFER TO SHEET M2.2 FOR INSTALLATION. O 8. APPROXIMATE LOCATION OF EXISTING ROOFTOP UNIT SUPPLY AND RETURN DROPS,VERIFY ON SITE,EXISTING SUPPLY AIR AND RETURN GRILLES IN THE STORAGE ROOM TO REMAIN. BALANCE THESE SUPPLY AR GRILLES TO 40%OF 1 HVAC PLAN THE TOTAL EXISTING ROOFTOP UNIT CFM. SCALE:1/4"=1'-0" 9. INSTALL NEW RETURN GRILLE IN THE LAUNDROMAT AREA. EXTEND RETURN AIR NORTH DUCT BACK TO THE EXISTING ROOFTOP UNIT RETURN AIR DROP,SIZE AT 60% OF THE TOTAL EXISTING ROOFTOP UNIT CFM. 10. REMOVE EXISTING SUPPLY GRILLES LOCATED IN THE LAUNDROMAT AREA. EXISTING RUNOUTS TO BE EITHER CAPPED OR EXTENDED TO THE NEW SUPPLY GRILLES. INSTALL NEW SUPPLY AIR DUCT WORK AS NECESSARY TO FEED THE NEW SUPPLY GRILLES. SIZE RUNOUTS AT 60%OF THE TOTAL EXISTING ROOFTOP UNIT CFM. BALANCE EACH SUPPLY GRILLE EQUALLY. C� O b z � 3 � z6 o w O r ' x wO'CH SCALE: AS NOTED DATE: 08/10/2023 CITY APPROVED PLANS DRAWN BY: TSM Reviewed for Code Compliance CHECKED BY: PLANS MUST BE ON JOB SITE CRA FOR ALL INSPECTIONS SHEET M2.1 Page 9 of 26 KEYED NOTES: 1. DRYER VENT FROM BELOW. TERMINATE PER THE MANUFACTURER'S WRITTEN INSTRUCTIONS. VENTS TO TERMINATE THREE FEET HIGHER THAN MAKE-UP AIR ED o S INTAKES AND ADJACENT PARAPET. ROOF PATCH TO BE BY THE ROOFING Z CONTRACTOR,COORDINATE WITH THE GENERAL CONTRACTOR. y ® ® ® ® ® ® ® ® 2. INSTALL ROOFTOP UNITS PER DETAILS ON SHEET M4.0. HVAC CONTRACTOR TO I W E a ® ® CUT EXISTING MEMBRANE ROOF FOR NEW CURB PER ROOFING CONTRACTOR'S W c CRITERLA COORDINATE WITH THE GENERAL CONTRACTOR AND ROOFING Z o ` CONTRACTOR. HVAC CONTRACTOR TO CUT OUT EXISTING RIGID INSULATION TO d, 6®EA DUCT FROM SET THE CURB DIRECTLY ON THE ROOF DECK. SHIM THE CURB TO LEVEL WITH I� C7 S TYPICAL RESTROOM BELOW. WOOD STRIPS,DO NOT USE THE INSULATION FOR LEVELING PURPOSES. Z °•' 3 REPLACEMENT OF INSULATION AROUND THE CURB PERIMETER AND MEMBRANE MJ 4 5 ¢ 5 PATCH BACK TO BE BY THE ROOFING CONTRACTOR. COORDINATE PATCH BACK W WORK AND SCHEDULING WITH THE GENERAL AND ROOFING CONTRACTOR. U m G� 3. FULL SIZED LINED SUPPLY AIR AND RETURN AIR DROPS THROUGH THE ROOF. SEE SHEET M2.1 FOR DUCT CONTINUATION. 4. NEW 36'X72°DUCT UP THROUGH ROOF. EXTEND DUCT UP ABOVE SNOW LEVEL INSTALL 135'SHORT THROAT RADIUSED ELBOW AND GOOSE NECK FITRNG WITH 1/4"xl/4"WIRE MESH INSECT SCREEN TERMINATING AT 45' ANGLE. COORDINATE WITH GENERAL CONTRACTOR AND ROOFING CONTRACTOR AS TO WHETHER A FIELD FABBED CURB IS REQUIRED. PROVIDE NECESSARY SUPPORT FOR THE GOOSE NECK. 5. HVAC CONTRACTOR TO CUT EXISTING MEMBRANE ROOF FOR NEW DUCT CURB RTU PER ROOFING CONTRACTOR'S CRITERIA COORDINATE WITH THE GENERAL 1 2 CONTRACTOR AND ROOFING CONTRACTOR. HVAC CONTRACTOR TO CUT OUT --- EXISTING RIGID INSULATION AND ROOF DECK. REPLACEMENT OF INSULATION AROUND THE DUCT MEMBRANE PATCH BACK TO BE BY THE ROOFING -- - CONTRACTOR. COORDINATE PATCH BACK WORK AND SCHEDULING WIN THE GENERAL AND ROOFING CONTRACTOR. 3 EXISTING ROOFTOP EXISTING ROOFTOP UNIT#2 TO REMAIN UNIT#3 TO REMAIN gg\ONAL cA\STEo. i� 8602 A m o 9F Y ANP 08/10/2023 O z � a � CITY APPROVED PLANS w Reviewed for Code Compliance O ll p �I EXISTING ROOFTOP UNIT TO REMAIN PLANS MUST BE ON JOB SITE � 7� FOR ALL INSPECTIONS V r� v o w p M '3 x w � H HVAC ROOF PLAN0 SCALE.AS NOTED 1 SCALE:"¢ -''- OSA BALANCE DATE: NORTH 08/10/2023 DRAWN BY., CISA BALANCE TSM SYSTEM CHECKED BY: CFM CRA RTU-1 230 cfm SHEET (E)RTU-2 100 cfm (E)RTU-3 85 cfm TOTAL= 415 cfm M 2.2 Page 10 of 26 ROOFTOP PACKAGED UNIT SCHEDULE COOLING HEATING-NATURALGAS ELECTRICAL Z o EQUIPMENT NOM. DURING SUPPLY E.S.P. OUTSIDEAIR WEIGHT ; d AREA SERVED ARI AR GROSS SENSIBLE NOMINAL LBS MFG'R MODEL NOTES W E a NO. TON ORIENTATION AIR(CFM) (IN.WC) (CFM) STAGES STAGES VOLT/PH/HZ MCA MOCP EER SEER MBH INPUT(MBH) Z o c RTU-1 LAUNDROMAT 6 VERTICAL 2,4GDCFM 0.60 300CFM 11.0 -- 51.6 1 110 1 208-230/3/60 30.0 45 700 CARRIER 48FCEM07 1THRU8 I� M Z 3 LLl 3 ALTERNATE MANUFACTURERS:DAIKIN,TRANE,AAON,CARRIER,YORK,LENNOX. NOTES: L1 1.UNITCAPACITIES RATED AT3,550 FEET ELEVATION AND COOLING CONDITIONS OF 80/67F DB/WB EAT,95F DB OAT.COOLING CAPACITY IS GROSS SENSIBLE. U 2.PROVIDE PREFABRICATED I4"ROOF CURB. 3.PROVIDE WITH CONDENSATE TRAP AND 2"FILTER RACK WITH 2"MERV 8FILTERS. 4.PROVIDE A CONDENSATE OVERFLOW SWITCH FOR THE EVAP COIL PAN. 5.PROVIDE 7-DAY PROGRAMMABLE STAT WITH TOD FUNCTION,HONEYWELLTH8320 OR EQUAL. 6.PROVIDE WITH I STAGE OF COOLING AND I STAGE OF GAS HEAT. 7.PROVIDE WITH A DRY BULB ECONOMIZER,WITH A BAROMETRIC RELIEF DAMPER. B.PROVIDE WITH RETURN AIR SMOKE DETECTOR(MAYBE FIELD INSTALLED IN THE RA DUCT DROP). RTU OPERATION&SETUP: A.STARTUP AND CHECKOUT UNIT PER MANUFACTURERSWRITTEN INSTRUCTIONS.PROVIDE A COPY OF THE SIGNED START-UP SHEET TO THE OWNER. B.PROVIDE INITIAL THERMOSTAT PROGRAMMING.COORDINATE THE OCCUPIED/UNOCCUPIED SCHEDULE AND TEMPERATURE SET POINTS WITH THE OWNER.FAN TORUN CONTINUOUS DURING OCCUPIED HOURS. C.INSTALL AND WIRE IN A CONDENSATE OVERFLOW SWITCH ON THE EVAP COIL PAN TO SHUTDOWN UNIT ON ACTIVATION. D.ECONOMIZER TO BE AVAILABLE TO PROVIDE COOLING PER THERMOSTAT SCHEDULE AND SET POINTS.FCONOMIZERTOOVERRIDE MINIMUM POSITION OSA.SET OSA DAMPER MINIMUM POSITION TO OUTSIDE AIR AS SHOWN IN THIS SCHEDULE. E.INSTALL AND WIRE THE SMOKE DETECTOR IN THE RETURN AIR DUCT DROP ATAN ACCESSIBLE LOCATION TO SHUTDOWN THE UNIT ON ACTIVATION. AIR DISTRIBUTION DEVICES %ON L 1,2,AND 3-WAY AIR DEVICES ARE DETERMINED BY BLOCKED OFF SECTIONS ON THE DRAWINGS SYMBOL KEY: C y A.FIRST LETTER:S-SUPPLY,E-EXHAUST,T-TRANSFER,R-RETURN (A) (0) 8602 SECOND LETTER:D-DIFFUSER,R-REGISTER,G-GRILLE SD-1,8"0 4 a+ O m ® ® 200 CFM B.LEAD-IN DUCT SIZE,UNLESS NOTED OTHERWISE 1-WAY 2-WAY 2-WAY 3-WAY 4-WAY C.CFM Fy NNQ'�' 08/10/2023 EQUIPMENT SIZE MOUNTING MATERIAL POSED DOOR STEEL OBD MANUFACTURER MODEL NOTES NO. STYLE SURFACE LAY-IN HARD DUCT- STAINLESS ALUMINU FACE NECK SIDEWALL CEILING CEILING SIDEWALL STEEL M 4-WAV DIFFUSER SG-1 24 x 24 6 x 6 IN 2424 PANEL X -- -- -- -- -- X -- -- TUTTLE&BAILEY M 1,2,3,4 SG-2 24x 24 12x 12 4-WAY DIFFUSER -- % -- -- -- -- -- X -- -- TUTTLE&BAILEY M 1,2,3,4 IN 24x24 PANEL RG-1 I 24 x 2 1 22 x 22 35°-3/4"SPACED X -- -- -- -- -- X -- -- TUTTLE&BAILEY T80D 1,2,3,5 ALTERNATE MANUFACTURERS:TITUS,PRICE,METAL-AIRE,NAILOR,CARNES,KRUEGER NOTES: 1.VERIFY ALL INSTALLATION MOUNTING TYPE WITH ARCHITECTURAL REFLECTED CEILING PLAN PRIOR TO ORDERING. 2.FINISH TO BE MODEL'S STANDARD WHITE FINISH. 3.PAINT INSIDE OF DUCT"FLAT BLACK". 4.SUPPLY GRILLE TO BE SQUARE NECK WITH MINIMUM CAN HEIGHT PER DETAIL ON M4.0.SHORTER CANS WILL NOT BE ACCEPTED. 5.MINIMUM HEIGHT OF RETURN CANS TO BE PER DETAIL ON M4.0.SHORTER CANS WILL NOT BE ACCEPTED. EXHAUST FAN SCHEDULE EQUIPMENT STATIC MOTOR NO. AREA SERVED TYPE CFM PRESSURE(IN CONTROL MANUFACTURER MODEL NOTES W.C.) WATTiz P VOLT/PH/HZ SWITCH WITH EF-1 RESTROOM CEILING 70 CFM 0.2" 11.0W -- 120/1/60 RESTROOM LIGHTS PANASONIC FV-0511VQ1 1 ALTERNATE MANUFACTURERS:GREEN HECK,COOK,PEN N BARRY,CARN ES,FANTECH,PAN ISO N I C,S&P NOTES: 1.FAN TO OPERATE WHENEVER THE RESPECTIVE RESTROOM LIGHTS ARE ON.FAN TO BE WIRED TO THE LIGHTS BY THE ELECTRICAL CONTRACTOR,COORDINATE WITH THE ELECTRICAL CONTRACTOR. W � I� A � U � � U Z 6 o w O r ' x wO'CH SCALE: AS NOTED DATE: 08/10/2023 DRAWN BY: CITY APPROVED PLANS TSM CHECKED BY: Reviewed for Code Compliance CRA PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS SHEET M3.0 Page 11 of 26 ROOFTOP UNIT PRE-FAB CURB,PROVIDE DISCONNECT SWITCH AND INSTALL BY THE HVAC . ® OSA OR ECONOMIZER CONTRACTOR. C7 0 BYCONTRAC OR ELECTRICAL HOOD,AS REQUIRED. GRILLE CAN SAME SIZE AS MANUAL GAS SHUT-OFF ® (2)PANDUITS,ONE ON INNER AND F� 120 VOLT POWER CONVENIENCE Lu GRILLE SQUARE NECK ONE ON OUTER LINER,SECURE BANDS VALVE AND DRIP LEG BY II OUTLET,BY ELECTRICAL CONTRACTOR, NAILER STRIP,PROVIDED WITH SHEET METAL SCREWS,TYP. PLUMBING CONTRACTOR. REFER TO ELECTRICAL SHEETS. WITH CURB. 'GLOBE STYLE'VENT CAP W SUPPLY HAND DAMPER TYP.,UNLESS Z❑ A TOP CONNECTION TO THE SHOWN AT AN ALTERNATE LOCATION OR ® - WITH BIRD SCREEN a, GRILLE MAY BE USED IF SPACE GRILLE IS SPECIFIED WffH AN OBD RIGID INSULATION, I C7 c ALLOWS. GRILLE CAN TO BE A TO GAS SUPPLY LINE WRAP DUCTWORK WITHIN ? BY ROOFING CONTRACTOR. VENT DUCT 3 MINIMUM OF 6°TALL FOR TOP SUPPORT FLEX DUCT SUPPLY OR RETURN BY THE PLUMBING ^�� CURB WITH 1-1/2° z Z m i CONNECTION PER SMACNA CONTRACTOR,REFER TO �� DUCTWRAP(TYP.) �— FLASHING,BY HVAC ROOFING CONTRACTOR w DUCT PER DRAWING /� TO PROVIDE AND INSTALL PLUMBING SHEETS. CONTRACTOR. ROUND BOOT,REFER TO STORM COLLAR MEMBRANE ROOF,SEE U m PAINT INSIDE OF GRILLE ca^ ARCHITECTURAL SHEETS. _ (SEAL TO VENT) ARCHITECTURAL SHEETS. 0 v _ ROOFING,BY ROOFING CAN'FLAT BLACK' INSTALL CONDENSATE OVERFLOW \ / CONTRACTOR,REFER FLEX DUCT SIZE SWITCH ON THE EVAP COIL PAN. z uTO FLEX DUCT.MAX. / SHEETS ARCHITECTURAL PER PRINT WIRE SWITCH TO SHUT DOWN UNIT LENGTH 8'-0" /? ON ACTIVATION,BY HVAC U CONTRACTOR. ROOF CURB,SEE CANT STRIP,BY ROOFING COLLAR TO BE MINIMUM RETURN AIR DETAIL 2,THIS CONTRACTOR-IF REQUIRED. T-BAR T-BAR SQUARE NECK OF 3"ABOVE BOTTOM DUCT SHEET. CEILING CEILING DIFFUSER OF GRILLE CAN CONTROL WIRING TO SUPPLY AIR LEVELING STRIP,PROVIDED INDOOR THERMOSTAT DUCT FLEXIBLE CONNECTION AND INSTALLED BY HVAC BY HVAC CONTRACTOR. (TYp.) CONTRACTOR. VENT DUCT NOTES: CONDENSATE DRAIN TRAP,BY HVAC TRIM DUCT OPENINGS AT HVAC CONTRACTOR 1. WHERE GRILLE IS SPECIFIED AS SQUARE NECK BY THE SCHEDULE,FACTORY ROUND CONTRACTOR. BOTTOM OF ROOF DECK TO SECURE CURB NECK GRILLE IS NOT ACCEPTABLE. WITH SHEET METAL,BY AND LEVELING STRIP 2. THE GRILLE CAN AND FLEX DUCT CONNECTION CRITERIA TO REMAIN THE SAME FOR HVAC CONTRACTOR. TO ROOF DECK. INSTALLATION OF GYP.BOARD GRILLES AND/OR RETURN GRILLES. TO POWER SUPPLY BY 3. IF RUNOUT TO THE GRILLE IS LARGER THAN THE GRILLE CAN,INSTALL A REDUCER AT THE ELECTRICAL CONTRACTOR. CONNECTION TO THE GRILLE CAN. 4 GAS RTU DOWNFLOW DETAIL 2 ROOF CURB DETAIL ROOF DECK,REFER TO 4 TYPICAL DIFFUSER CONNECTION DETAIL N ♦`7 ARCHITECTURAL DRAWINGS EXHAUST/OUTSIDE AIR VENT DETAIL I SCALE:NTS SCALE:NTS SCALE:NTS FOR TYPES. SCALE:NTS �%ONAI. �pTSTEo. iT Q86U_20 d,�9r ao9 pN 08/10/2023 O C� O W � � Q 3 z . 6 o w O r ' x wO'CH SCALE: AS NOTED DATE: 08/10/2023 DRAWN BY: CITY APPROVED PLANS TSM CHECKED BY, Reviewed for Code Compliance CRA PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS SHEET M4.0 Page 12 of 26 PLUMBING SPECIFICATIONS PLUMBING LEGEND PART 1 - GENERAL 1.7 PROJECT CLOSE-OUT 2.3PIPE INSULATION M. INSTALL AIR VENTS AT HIGH POINTS OF WATER PIPING. -SD- STORM DRAIN (� o - A. CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE TO REPLACE OR REPAIR ANY DEFECTS IN A ALL INSULATION SHALL MEET FUME SMOKE SPREAD RATING OF 25 50 ACCORDING TO ASTM E84 AND N. INSTAL VENT PIPING FOR GAS PRESSURE REGULATORS AND GAS TRAINS,EXTEND OUTSIDE BUILDING,AND �PRESSURE REDUCING VALVE 1.. GENERAL INTENT / / VENT TO ATMOSPHERE. TERMINATE VENTS WITH TURNED-DOWN,REDUCING-ELBOW FITTINGS WITH -HWS- HEATING WATER SUPPLY LINE Z N, WORKMANSHIP OR EQUIPMENT,WHICH DEVELOP WITHIN ONE YEAR FROM ACCEPTANCE BY THE NFPA 90A. A. THE INTENTION E THE CONTRACT DOCUMENTS A E INCLUDE ALL LABOR AND MATERIALS,AND CORROSION-RESISTANT INSECT SCREENS IN LARGE END. -HOUR- HEATING WATER RETURN LINE F-BOLL VALVE n EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING,INSTALLATION OWNER. CONTRACTOR MUST ASSUME ORKO F OTHER FOR ALL EXPENSES INCURRED TO REPAIR B. INSULATION TYPES: 0. CONNECT GAS PIPING TO APPLIANCES USING GAS SHUT-OFF VALVES,DIRT-LEGS,AND UNIONS. INSTALL AND TESTING,COMPLETE AND READY FOR SAE OPERATION OF THE SYSTEMS DESCRIBED HEREIN. OR REPLACE HIS WORK AS WELL AS WORK OF OTHER TRADES THAT MAY BE AFFECTED BY THIS 1. FLEXIBLE EUSTOMERIC: CLOSED-CELL,SPONGE-OR EXPANDED-RUBBER MATERIALS. COMPLY WITH -CHWS- CHILLED WATER SUPPLY LINE REDUCER W _ .Q B. SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS MADE A REPLACEMENT. ASTIR C 534,TYPE I FOR TUBULAR MATERIALS AND TYPE II FOR SHEET MATERIALS. VALVE UPSTRF L OF AND WITHIN 7 L OF EACH APPLIANCE. INSTALL UNION DOWNSTREAM FROM VALVE. E PROVIDE CALIBRATE CONNECTOR AT ALL EQUIPMENT THAT EXPERIENCES VIBRATION. -CHWR- CHILLED WATER RETURN LANE GATE VALVE W c' TI10ROUGH EXAMINATION OF THE ARE,AND ALL IXISIING CONDITIONS AND UMRATIONS WHICH AFFECT THIS B. CONTRACTOR SHALL MAINTAIN A REDUNEO SET OF CONSTRUCTION DRAWINGS SHOWING DEVIATIONS 2. GLASS-FIBER,PIPE INSULATION: GLASS FIBERS BONDED WITH A THERMOSETTING RESIN. SEMI RIGID P. INSTALL CALIBRATED BALANCING VALVES IN EACH HOT-WATER CIRCULATION RETURN BRANCH AND WORK. LITER CLAIMS SHALL NOT BE MADE FOR LABOR,EQUIPMENT OR MATERIALS REQUIRED BECAUSE BETWEEN THE DRAWINGS AND INSTALLED CONDITIONS. THESE SHALL BE TURNED OVER TO THE BOARD MATERIAL WITH FACTORY-APPUED ASJ JACKET COMPLYING WITH ASIM C 1393.TYPE II OR -CS- CONDENSER WATER SUPPLY UNE D Z 17 OF DIFFICULTIES ENCOUNTERED,WHICH COULD HAVE BEEN FORESEEN DURING SUCH AN DAMINARON. OWNER AT ACCEPTANCE OF THE WORK. TYPE ILIA CATEGORY 2,OR WITH PROPERTIES SIMILAR TO ASTM C 612,TYPE IB. NOMINAL DENSITY DISCHARGE SIDE OF EACH PUMP MO CIRCULATOR. SET CALIBRATED BALANCING VALVES PARRY OPEN TO �+.�GLOBE VALVE c C. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT,GENERAL CHARACTER,AND LOCATIOU OF THE RESTRICT BUT NOT STOP FLOW. -CR- CONDENSER WATER RETURN UNE WORK TO BE PERFORMED. WHERE MINOR ADJUSTMENTS OF THE WORK ARE NECESSARY FOR PURPOSES C. PROVIDE THREE(3)COMPLETE SETS OF OPERATION AND MAINTENANCE MANUALS. THESE ARE IS 2.5 W/CU.E.OR MORE THERMAL CONDUCTIVITY(K-VALUE AT 1 W DEG F IS 0.29 BTU%IN. Q�--TJ���2 WAY CONTROL VALVE 1- Q. INSTALL ESCUTCHEONS FOR PNETRATIONS OF WARS,CEILINGS,AND FLOORS ACCORDING TO THE -CD- CONDENSATE DRAIN LINE : " M m 3 m OF FABRICATION OR INSTALLATION OF ITEMS,THE CONTRACTOR SHALL MAKE SUCH ADJUSTMENTS WITH NO TO INCLUDE ALL EQUIPMENT CUT-SHEETS,MANUFACTURERS RECOMMENDED MAINTENANCE /H%SO.FT.X DEG F OR LESS. FOLLOWING: 3 WAY CONTROL VALVE Z m i - ADDED COMPENSATION. WHERE SUCH ADJUSTMENTS AFFECT FUNCTIONAL OR AESTHETIC DESIGN OF THE PROCEDURES,MANUFACTURERS WARRANTEE INFORMATION,AND CONTRACTORS WARRANTEE LETTER 3. JACKETS: --D--- DEMO LMI- 1. BARE PIPING AT Well AND BOOR PENETRATIONS IN FINISHED SPACES,AND WITHIN CABINETS AND CHECK VALVE � WORK,THEY SHALL FIRST BE SUBMITTED TO THE ARCHITECT FOR REVIEW AND APPROVAL AND CONTACT INFORMATION. a. PROVIDE ALUMINUM JACKET TO COMPLY WITH ASTM B 209,ALLOY 3003,3005,3105 OR 5005, MILLWORK: ONE-PIECE,CAST-BRASS TYPE WITH POUSHED CHROME-PLATED FINISH. -("N- GREASE WASTE R D. SITE UTLRIES: THE MECHANICAL DOCUMENTS INDICATE CONNECTION LOCATION OF VARIOUS BUILDING D. PROVIDE THREE(3)REVIEWED BALANCE REPORTS OF WATER AND AIR SYSTEMS AS APPLICABLE. TEMPER H-14,ON ALL EXTERIOR PIPING WITH INSULATION. PROVIDE 3-MIL VAPOR BARRIER Q. INSTALL MANUFACTURED PIPE MARKERS INDICATING SERVICE ON EACH PIPING SYSTEM. INSTALL WITH �- V m SERVICES. COORDINATE WORK WITH THE SITE UTILITIES CONTRACTOR TO ENSURE PROPER INVERT C. INSULATION SCHEDULE: FLOW INDICATION ARROWS SHOWING DIRECTION OF FLOW. SPACE AT MAXIMUM INTERVALS OF 50 FEET -SS- SANITARY SEWER SOLENOID VALVE 0 U ELEVATION,PIPE SLOPE GRADIENT,PIPE SIZE AND SEPARATION WITHIN TRENCH WORK. NOTIFY ARCHITECT P - P 1. DOMESTIC COLD WATER: ---V--- VENT ALONG EACH RUN. REDUCE INTERVALS TO 25 FEET IN AREAS OF CONGESTED PIPING AND EQUIPMENT. --jQ�---BALANCE VALVE OR ENGINEER OF ANY DISCREPANCY BETWEEN DRAWINGS AND FIELD CONDITIONS. a. ALL SIZES: INSULATION SHALL BE ANY OF THE FOLLOWING: R. ALL VENT-THROUGH-ROOF(VTR)PENETRATIONS SHOWN ON PLANS ARE PRELIMINARY. FINAL LOCATIONS -RID- ROOF DRAIN UNE E. COMPLY WITH ALL LOCAL AND STATE CODES REGARDING SEISMIC SUPPORT AND ISOLATION. NOT ALL ��[-CIS COCK SEISMIC REQUIREMENTS ARE SHOWN ON THESE DRAWINGS. CONTRACTOR SHALL MEET THE REQUIREMENTS A. ABOVE GRADE DOMESTIC WATER PIPING SHALL BE ANY OF THE FOLLOWING: 1) FLEXIBLE ETASTOMERIC: 1/2 INCH THICK. ARE TO BE COORDINATED WITH ALL TRADES. ALL VTRS SHALL BE A MINIMUM OF TEN FEET FROM ANY -OD- OVERFLOW DRAIN LINE OF THE AUTHORITY HAVING JURISDICTION FOR SEISMIC SUPPORT/ISOLATION OF HIS WORK. 1. ALL SIZES:HARD COPPER TUBE CONFORMING TO ASTM B-88,TYPE L;COPPER PRESSURE 2) GLASS-FlBER PIPE INSULATION,TYPE I: 1/2 INCH THICK. FRESH AIR INTAKE THIS CONTRACTOR TO BE RESPONSIBLE FOR THE PROPER FLASHING AND SEALING OF Bl1TTERFLY VALVE 1.2 GENERAL FITTINGS PER ASME B16.18;AND ALLOY SN95 SOWER WITH WATER SOLUBLE FLUX. 2. DOMESTIC HOT WATER VIR PENETRATIONS OF THE ROOF ASSEMBLY. -CAN- DOMESTIC COW WATER OS&Y VALVE S. INDIRECT WASTE PIPING SHALL TERMINATE AT APPROVED RECEPTACLE WITH AIR GAP PER PLUMBING CODE A THE CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF A SATISFACTORY,COMPLETE,AND FULLY 2. NPS 1 AND SMALLER: PEX PER ASTM F 877,STIR 9 TUBING,DISTRIBUTION MANIFOLD, a. SMALLER THAN NPS 2: INSULATION SHALL BE ANY OF THE FOLLOWING: -HW- DOMESTIC HOT WATER AND AW REQUIREMENTS. ORTING STRAINER OPERATIONAL PIECE OF WORK IN ACCORDANCE WITH TRUE INTENT OF THE DRAWINGS AND SPECIFICATIONS. INSERT FITTINGS,AND CRIMPED JOINTS. 1) FlDDBLE SLASTOMERIC: THICKNESS OF NOT LESS TIWN THE DIAMETER OF THE PIPE -HWC- DOMESTIC HOT WATER RECIRC B. CONTRACTOR SHALL CONSULT ALL DRAWINGS FOR THE PROJECT TO DETERMINE THAT THE WORK AND B. BELOW GRADE DOMESTIC WATER PIPING SHALL BE ANY OF THE FOLLOWING: 3.4 ANGIN PP 2) GLASS-FlBER PIPE INSULATION,TYPE I: THICKNESS OF NOT LESS THAN TUE DIAMETER OF -MPG- MEDIUM PRESSURE NATURAL GAS � SAFETY REUEF VALVE EQUIPMENT WILL FIT AS PLANNED. 1. SOFT COPPER TUBE,TYPE K OR L CONFORMING TO ASTM B-88;COPPER PRESSURE THE PIPE. A PROVIDE PIPING HANGERS,SUPPORTS AND BUILDING ATTACHMENTS FROM ERSON.GRINNELL.B-UNE,O.Z., C. THE LOCATION OF PIPING,DUCTS,EQUIPMENT,ETC,SHALL BE CHECKED TO ENSURE CLEARANCE FROM FITTINGS;AND SOLDERED JOINTS. b. NPS 2 AND LARGER: INSULATION SHALL BE ANY OF THE FOLLOWING: SUPER-STRUT.GEDNEY,MICHIGM HANGER,BERGEN/CARPENTER,OR PATTERSON. -TUG- LOW PRESSURE NATURAL GAS VALVE IN VERTICAL OPENINGS,STRUCTURAL MEMBERS,CABINETS,LIGHTS,OUTLETS AND EQUIPMENT HAVING FIXED LOCATIONS. B. SUPPORT ALL DUCTWORK,PIPING,AND EQUIPMENT AS REQUIRED BY THE LOCAL CODES,MANUFACTURER'S THIS SNAIL BE ACCOMPLISHED PRIOR TO FABRICATION OF PIPE OR DUCTS. 2. WRAP BURIED METALLIC PIPE PER ASTM A 674 OR AWWA C105,HOPE,CROSS LAMINATED PE 1) GLASS-FIBER PIPE INSULATION,TYPE I: 2 INCH THICK. F FIRE SPRINKLER UNE FLOOR SINK D. IF,AT ANY TIME,MID IN MY CASE,CHANGES IN LOCATION OF PIPING,DUCTS,EQUIPMENT,ETC., FILM OF 0.004-INCH 0.10-MAP OR LLDPE,CROSS LAMINATED PE FILM OF 0.008-INCH 3. STORM DRANAGE PIPING: RECOMMENDATIONS,AND STANDARD INDUSTRY PRACTICE. ( ) C. INSTALL RANGERS FOR STEELL PIPING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND MINIMUM -CA- COMPRESSED AIR FLOOR DRAIN BECOMES NECESSARY WE TO EXISTING OBSTACLES OR INSTALLATION OF OTHER TRADES SHOWN ON ANY (0.20-AIM)MINIMUM THICKNESS. a. DRAIN BODIES AND HORIZONTAL APING. INSULATION SfWl BE ONE OF THE FOLLOWING: ROD DIAMETERS: -MA- MEDICAL AIR OF THE PROTECT DRAWINGS AND SUCH CONFLICT COULD HAVE BEEN AVOIDED BY PROPER COORDINATION 3. HOPE HIGH DENSITY POLYETHYLENE PLASTIC PIPE AND FITTING FOR WATER SERVICE ENTRY 1 BETWEEN TRADES OR PROPER PRE-PLANNING OF WORK,SUCH REWIRED CHANGES SHALL BE MADE BY ( ) ) GLASS-FIBER PIPE INSULATION,TYPE I: 1/2 INCH THICK. 1. NPS 1-1/4 MID SMALLER: 84 INCHES WITH 3/8-INCH ROD. �AV- MEDICAL VACUUM GRADE CLEMOM THE CONTRACTOR AT NO DM COST. THESE CHARGES ARE TO BE RECORDED ON THE RECORD PIPING. 2) 4'BATT INSULATION MAY BE USED FOR DRAIN BODIES. 2 NPS 1-1/2: 108 INCHES WITH 3/8-INCH ROD. /FLOOR CLEANOM DRAWINGS. a. PIPE CONFORMING TO ASTM D 2239,ASTM D 2737,AWWA C901,MINIMUM 160 PSI D. ACCEPTABLE MANUFACTURERS: ARMSTRONG,CERTMNIIEFDD,OWENS-CORNING,JOHNS MANVILLE,ARMACELL 3. NPS 2: 10 FEET WITH 3/8-INCH ROD. � BALANCE DEVICE , E. THIS CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL INCIDENTAL ELECTRICAL INTERCONNECTIONS,CONTROL PRESSURE PART 3 - 'b/a=WAIL CLEANOUT WIRING,ETC.,WHICH ARE NECESSARY FOR SYSTEM COMPLETION AND WHICH ARE NOT SPECIFICALLY SHOWN CLASS,SDR EQUAL TO 9. 4. NPS 2-1/2: 11 FEE WITH 1/2-INCH ROD. ��,HOSE BIBB OR OTHERWISE INDICATED ON THE ELECTRICAL DRAWINGS OR SPECIFIED IN DIVISION 26. 3.1 EXAMINATION5. NPS 3 AND NPS 3-1/2: 12 FEET WITH 1/2-INCH ROD. / --*--VENT THROUGH ROOF F. ALL ELECTRICAL WORK INCIDENTAL TO OR ACCOMPLISHED UNDER THIS DIVISION SHALL COMPLY WITH ALL b. FITTINGS CONFORMING TO ASTM D 2609,METAL INSERT FITTING AND 1W0 STAINLESS IN-LINE PUMP ,� REQUIREMENTS OF DIVISION 26. STEEL A. VERIFY'FINAL LOCATIONS FOR ROUGH-INS WITH FIELD MEASUREMENTS AND WITH THE REQUIREMENTS OF 6. NPS 4 AND NPS 5: 12 FEE WITH 5/8-INCH ROD. 8 PIPE DOWN G. PUNS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR IS RESPONSIBLE FOR REFERRING TO THE DESIGN CLAMPS;FOR OVER 1-1/2 INCH,SPECIAL,HEAVY DUN TIGHTENING CLAMPS. THE ACTUAL EQUIPMENT TO BE CONNECTED. 7. NPS 6: 12 FEET WITH 3/4-INCH ROD. -t'l PIPE BREAK DOCUMENTS FOR ALL OTHER DISCIPUNES FOR PRGIECT CONSTRUCTION AND OTHER DETAILS WHICH B. LOCATIONS OF EQUIPMENT AND DEVICES,AS SHOWN ON THE DRAWINGS,ARE APPROXIMATE UNLESS �0 PIPE UP C. ABOVE GRADE SANITARY WASTE AND VENT SHALL BE ANY OF THE FOLLOWING: DIMENSIONED;DO NOT SCALE DRAWINGS. EXACT LOCATIONS OF SUCH ITEMS SHALL BE DETERMINED BY 8. INSTALL SUPPORTS FOR VERTICAL SPELL PIPING EVERY 15 FEET. OVERFLOW DRAIN VONpE AFFECT THE MECHANICAL INSTALLATION. CONTRACTOR SHALL CONFER WITH ALL OTHER TRADES FOR FINISH D. INSTALL HANGERS FOR COPPER TUBING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND UNION g5 ADJACENT TO ITS WORK AND ARRANGE TO HAVE VISIBLE PORTIONS OF THIS WORK(SUCH AS ACCESS 1 HSFUAINELESS-STEEL COUSS CAST-IRON PO.IINGSP AND HUBLESSE AND S COUP NAG JOIAPNTSHEAVY-DITTY SHIELDED, TME PHYSICAL DIMENSIONSE ARCHIPECT'S OF EACATIVE HNDI MD/OR OF DETERMINED EQU PARENT TOEFR THE AVAILABLE S S.PACEAILS AND DRAWING AND MINIMUM ROD DIAMETERS: �p ROOF DRAINCAP �F�GGASTEp / DOORS,VALVES,SPRINKLER HEADS,ESCUTCHEONS,ETC.)MERGE WITH THE FINISH IN A MANNER L` Qi SATISFACTORY TO THE MCHIIECT. 2. SOLID WALL ABS PIPE PER ASTM D 2661,SCHEDULE 40,ABS SOCKET FITTINGS,AND PROMPTLY NOTIFY THE ARCHITECT PRIOR TO ROUGHING-IN IF CONFLICTS APPEAR. COORDINATION OF 1. NPS 3/4 AND SMALLER: 60 INCHES WITH 3/8-INCH ROD. V/ GAS PRESSURE REGULATOR [> }��� n A H. CONTRACTOR SHALL IDENDFY ALL SERVICEABLE TEEMS(VALVES,CLUNOUTS,COILS,ETC.)SO THAT THE SOLVENT-CEMENTED JOINTS. DIVISION 15 EDUIPMEM AND SYSTEMS TO THE AVAILABLE WIRING,EQUIPMENT,DUCTWORK,PIPING,ETC. 2 NPS 1 AND NPS 1-1/4: 72 INCHES WITH 3/8-INCH ROD. �y y Syr DOUBLE CHECK pQ SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE INSTALLATION SHALL BE CONCEALED WITHIN XX-X FIXTURE CAIlOM BACKFLOW PREVENIER 8BOZ CEILING SUBCONTRACTOR MAY KNOW WHERE TO INSTALL ACCESS-TYPE PANELS SHOULD A UET-UP TYPE 3. SOLID WAIL PVC PIPE PER ASTM E 2665,SCHEDULE 40 DRAIN,WASTE,AND VENT,PVC 3. NPS 1-1/2 AND NPS H 9I INCHES WITH ROD.INCH ROD. BUILDING CONSTRUCTION,OR EXPOSED IN MECHANICAL ROOMS,UNLESS OTHERWISE NOTED. e C REDUCED PRESSURE N� Z�CEILING NOT BE INSTALLED. THIS CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR HIS WORK UNLESS SOCKET FITTINGS,AND SOLVENT-CEMENTED JOINTS. 4. NPS 2-1/2: 108 INCHES WITH 1/2-INCH ROD. DEAL CALLOW SPECIFICALLY NOTED ON THE DRAWINGS. ARCHITECT SHALL APPROVE LOCATIONS OF ACCESS PANELS D. BELOW GRADE SANITARY WASTE AND VENT SHALL BE ANY OF THE FOLLOWING: 3INSTALLATION 5. NPS 3 TO NPS 5: 10 FEE WITH 1/2-INCH ROD. X.X XRP 84CKFLOW PREVENTER PRIOR TO INSTALLATION. A. UNLESS SPECIFICALLY PROVIDED FOR ELSEWHERE IN THESE DOCUMENTS,THIS CONTRACTOR SHALL EQUIPMENT CALLOUT Q`1. HUBLESS CAST-IRON SOIL PIPE AND FITTINGS PER CISPI 301;HEAVY-DUTY SHIELDED, 8. NPS 8: 10 FEE WITH 5/8-INCH ROD. FY AN I. CEILING HEIGHTS: ARCHITECTURAL DRAWINGS SHALL BE CHECKED FOR CEIUNG HEIGHTS,WALLS,AND INCLUDE IN HIS BID TINE COMPLETE EXCAVATION AND BACKFILL COST REQUIRED TO INSTALL HIS WORK / POINT OF CONNECTION CABINETS THAT ARE INTENDED TO CONCEAL WORK OF THIS SECTION. WHERE CONFLICTS OCCUR,THE STAINLESS STEEL COUPLINGS;AND HUBLESS-COUPUNG JOINTS. 7. INSTALL SUPPORTS FOR VERTICAL COPPER TUBING EVERY 10 FEE. 2. $QUO WAIL ABS PIPE PER ASTM D 2661,SCHEDULE 40,ABSSOCKET FITTINGS,AND AS SPECIFIED UNDER DIVISION 15(MECHANICAL)OF THIS SPECIFICATION. CONTRACTOR SHALL PROVIDE �� QUICK DISCONNECT 08/10/2023 ARCHITECT SHALL BE NOTIFIED PRIOR TO INSTALLATION OF THE WORK. LOCATION OF EXPOSED WORK ALL NECESSARY'SAW-CUTTING,EXCAVATION,SHORING AND BACKFlWNG REQUIRED FOR THE PROPER E. INSTALL HANGERS FOR CAST-IRON SOIL PIPING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND QQ /� SUCH AS PIPING,VALVES,SPEAKERS,SPRINKLER HEADS TAKE PRECEDENCE OVER CONCEALED WORK. SOLVENT-CEMENTED JOINTS. INSTALLATION OF HIS WORK,INSIDE BUILDING AND PREMISES,OR OUTSIDE AS MAY BE NECESSARY MINIMUM ROD DIAMETERS: ABBREVIATIONS R DESCRIPTIONS J. CONTRACTOR SHALL EXERCISE CARE TO MINIMIZE ANY DISTURBANCE TO ADJACENT AREAS OF THE BUILDING 3. SOLID WAIL PVC PIPE PER ASTM D 2665,SCHEDULE 40 DRAIN,WASTE,AND VENT,PVC DAMAGES RESULTING FROM IMPROPER SHORING OR FAILURE TO SHORE SHALL BE THE SOLE 1. NIPS 1-1/2 AND NPS 2: 60 INCHES WITH 3/8-INCH ROD. WHICH ARE TO REMAIN IN OPERATION. ISOLATE WORK AREAS BY TEMPORARY PARTITIONS,TARPS,ETC.,TO SOCKET FTTINGS,AND SOLVENT-CEMENTED JOINTS. RESPONSIBILITY OF THE CONTRACTOR. KEEP DUST MID DIRT IN THE CONSTRUCTION MCA. 2. NPS 3: 60 INCHES WITH 1/2-INCH ROD. E. STORM DRAINAGE PIPING SHALL BE ANY OF THE FOLLOWING: B. PROVIDE ALL VALVES,AND CONTROL DEVICES REQUIRED TO OOMPLErE BALANCING OF SYSTEMS AS K. PROVIDE ALL NECESSARY FLASHING.SEALING,ETC.,TO MAINTAIN THE WATERPROOF INTEGRITY C THE 3. NPS 4 AND NPS 5: 60 INCHES WITH 5/8-INCH ROD. AFF ABOVE CEILING KEG KITCHEN EQUIPMENT SUPPLIER 9 BUIWING AS REQUIRED BY THE INSTALLATION OR REMOVAL OF ITEMS AS REQUIRED BY THIS SCOPE OF 1. HUBLESS CAST-IRON SOIL PIPE AND FITTINGS PER CISPI 301;HEAVY-DUTY SHIELDED, DESCRIBED IN THESE DOCUMENTS OR AS NORMALLY ASSOCIATED WITH THE SYSTEMS TO BE INSTALLED4. AFF ABOVE FINISHED FLOOR LPG LIQUEFIED PETROLEUM GAS WHETHER SPECIFICALLY GAD.ED FOR ON THE DRAWINGS,DETAILS OR SPECIFICATIONS OR NOT. IT SHALL IN INSTALL SUPPORTS FOR VERTICAL CAST-IRON SOIL PIPING EVERY XI FEE. WORK. STAINLESSLSTEEL COUPLINGS,AND 2661,SCCOUPLING JOINTS. BE UNDERSTOOD,UNLESS SPECIFICALLY STATED OTHERWISE,THAT ALL SYSTEMS INSTALLED SHALL F. INSTALL HANGERS FOR ABS AND PVC PIPING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND AV ACID VENT LWCO LOW WATER CUTOFF L INSTALL ALL WORK OF THIS SCOPE TO BE READILY ACCESSIBLE FOR OPERATION,MAINTENANCE,NG 2. SOLID WAIL MABSEN PIPE PER ASTM D 2661,SCHEDULE 40,ABS SOCKET FFFlINGS,AND COMPLY WITH INDUSTRY RECOGNIZED STANDARDS AND FEATURES. MINIMUM ROD DIAMETERS: AW ACID WASTE MAX. MAXIMUM REPAIR. MINOR DEVIATIONS FROM THE DRAWINGS MAY BE MAIA TO ACCOMPLISH THIS,BUT CHARGES SOLVENT-CEMENTED JOINTS. 1. NPS 1-1/2 AND NPS 2: 48 INCHES WITH 3/8-INCH ROD. BF BELOW FINISHED FLOOR MIN. MINIMUM INVOLVING OTHER TRADES MAY NOT BE MADE WITHOUT PRIOR APPROVAL C. INSTALL WALL-PENETRATION FITTING AT EACH SERVICE PIPE PENETRATION THROUGH FOUNDATION WALL 3. SOLID WALL PVC PIPE PER ASIM D 2665,SCHEDULE 40 DRAIN,WASTE,AND VENT,PVC BG BELOW GRADE NO NATURAL GAS M. ALL PFNETRATDUS MADE THROUGH RAZED MSEMBLIES TO ACCOMMODATE WORK OF THIS SECTION,MUST MALE INSTALLATION WATERTIGHT. 2 NPS 3: 48 INCHES WITH 1/2-INCH ROD. SOCKET FITTINGS,AND SOLVENT-CEMENTED JOINTS. GA COMPRESSED AIR (N) NEW BE SEALED TO MAINTAIN THE RATING OF SUCH ASSEMBLY LL A U.L RECOGNIZED SEALING METHOD. D. COORDINATE MECHANICAL SYSTEMS,EQUIPMENT,AND TE INSTALLATIONS INSTALLATION WITH CAL BUILDING 3. NPS 4 AND 5: 48 INCHES WITH CH RANCH ROD. CD CONDENSATE DRAIN N.O. NORMALLY OPEN(VALVE) N. PROVIDE ALL CUTTING THE PATCHING REQUIRED FOR INSTALLATION OF THIS WORK. COORDINATE ALL F. FUEL GAS PIPING SHALL BE ANY OF THE FOLLOWING: COMPONENTS. SEQUENCE,COORDINATE,AND INTEGRATE INSfALLATONS OF MECHANICAL MATERIALS AND BLOCKING,SUPPORT,ETC.,NECESSARY'FOR THE INSTALLATION OF THIS WORK WITH THE GENERAL 1. ALL SIZES: STEEL PIPE PER ASTM A 53/A 53M;TYPE E OR S;GRADE B;BUCK. WALL EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. GIVE PARTICULAR ATTENTION TO URGE EQUIPMENT 4. NPS 6: 48 INCHES WITH 3/4-INCH ROD. C.I.N.H. CASE IRON NO HUB N.C. NORMALLY CLOSED(VALVE) CONTRACTOR. THICKNESS OF WROUGHT-STEEL PIPE SHALL COMPLY WITH ASME B36.10M. REQUIRING POSITIONING PRIOR TO CLOSING IN THE BUILDING.GIVE RIGHT-OF-WAY PRIORITY TO SYSTEMS 5. INSTALL SUPPORTS FOR VERTICAL ABS AND PVC PIPING EVERY 48 INCHES. CO CLEMOUT OH OVER HEAD a. MALLEABLE-IRON THREADED FRTINGS: ASME B16.3,CUSS 150,STANDARD PATTERN, REQUIRED TO BE INSTALLED AT A SPECIFIED SLOPE G. STEEL PIP:HANGER INSTALLATION: COMPLY WITH MSS SP-69 AND MSS SP-89. INSTALL RANGERS, OFF CAP FOR FUTURE POO POINT OF CONNECTION A ALL APPLICABLE CODE LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS WORK WITH THREADED ENDS ACCORDING TO ASME B1.20.1. E. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED,INSTALL SYSTEMS,MATERIALS,AND SUPPORTS,CLAMPS,AND ATTACHMENTS AS REQUIRED TO PROPERLY SUPPORT PIPING FROM BUILDING CKV CHECKVALVE (R) PIPE RISE ARE HEREBY INCORP)RATED INTO MD MADE A PART OF THESE SPECIFICATIONS. THEIR PROVISIONS EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM POSSIBLE STRUM CW COW WATER RIO ROUGH-IN ONLY b. STEEL WELDING FITTINGS: ASME 816.9,WROUGHT STEEL OR ASME B16.11,FORGED H. TRAPEZE PIPE HANGER INSTALLATION: COMPLY WITH MSS SP-69 AND MSS SP-89. ARRANGE FOR CX CONNECT TO EXISTING SHT. SHEET SHALL BE CARRIED OUT BY THE CONTRACTOR,WHO SHALL INFORM THE ARCHITECT IN WRITING PRIOR TO F. INSTALL SYSTEMS,MATERIALS,AND EQUIPMENT LEVEL AND PLUMB,PARALLEL AND PERPENDICULAR TO SUBMITTING A BID,OF ANY WORK OR MATERWS WHICH VIOLATE MY OF THE ENFORCED LAWS,CODES, STEEL OTHER BUILDING SYSTEMS AND COMPONENTS,WHERE INSTALLED EXPOSED IN FINISHED SPACES. GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING AND SUPPORT TOGETHER ON FIELD-FABRICATED (D) PIPE DROP SCAN SOFT COLD WATER OR REGULATIONS. IF THE CONTRACTOR PERFORMS ANY WORK CONTRARY TO SUCH LAWS,ORDINANCES, c. UNIONS: ASME B16.39,CLASS 150,MALLEABLE IRON WITH BRASS-TO-IRON SEAT, G. INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING,MAINTENANCE,AND REPAIR OR REPLACEMENT TRAPEZE PIPE HANGERS. ON PIPE DROP TO NEXT LEVEL SOC SHUT OFF COCK(GAS) RULES AND REGULATIONS,HE SHALL ASSUME FULL RESPONSIBILITY,AND SHALL BEAR ALL COSTS GROUND JOINT,AND THREADED ENDS ACCORDING TO ASME B1.20.1. OF EQUIPMENT COMPONENTS. M MUCH AS PRACTICAL,CONNECT EQUIPMENT FOR EASE OF I. INSTALL HANGERS AND SUPPORTS COMPLETE WITH NECESSARY INSERTS,BOLTS,RODS,NUTS,WASHERS, DTL DETAIL SON SHUT OFF VALVE ASSOCIATED WITH BRINGING WORK INTO COMPLIANCE d. JOINT COMPOUND AND TAPE: SUITABLE FOR NATURAL GAS. DISCONNECTING,WITH MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. EXTEND GREASE FITTINGS MD OTHER ACCESSORIES. (E) EXISTING TPL TRAP PRIMER LINE B. WHERE DRAWINGS OR SPECIFICATIONS CALL FOR MATERIAL OR CONSTRUCTION OF A BETTER QUALITY OR e. STEEL FLANGES AND FLANGED FITTINGS: ASME 816.5. TO M ACCESSIBLE LOCATION. J. INSTALL HANGERS AND SUPPORTS TO ALLOW CONTROLLED THERMAL AND SEISMIC MOVEMENT OF PIPING F FIRE SERVICE UG UNDERGROUND HIGHER CAPACITY THAN REQUIRED BY THE ABOVE-MENTIONED CODES AND STANDARDS,THE PROVISIONS 2. NIPS 1 AND SMALLER MAY BE CORRUGATED STAINLESS STEEL TUBING SYSTEMS. R DRAWINGS ARE NOT DETAILED TO THE DOW THAT ALL PIPING OFFSETS,BENDS,AND SPECIAL FITTINGS SYSTEMS,TO PERMIT FREEDOM OF MOVEMENT BETWEEN PIPE ANCHORS,AND TO FACIWATE ACTION OF FGQ FLOOR CLEANOUT UP PIPE RISE TO NEXT LEVEL OF THE DRAWINGS OR SPECIFICATIONS SHALL TARE PRECEDENCE OVER THE REQUIREMENTS OF THE CODES ME SHOWN MD EXACT WGTION INDICATED;HOWEVER,THEY ME TO BE PROVIDED WHETHER SHOWN EXPANSION JOINTS,IXPMSION LOOPS,EXPANSION BENDS,AND SIMILAR UNITS. FIND FOUNDATION DRAIN US UNDER SLAB AND STANDARDS. a. DESCRIPTION: COMPLY WITH AGA LC 1 AND INCLUDE THE FOLLOWING: OR NOT.REFER TO SCHEDULES FOR ACCESSORIES. K. LOAD DISTRIBUTION: INSTALL HANGERS AND SUPPORTS 50 PIPING LIVE AND DEAD TOMS AND STRESSES GOO GRADE CLEANOW WR UP THRU ROOF C. THE RESPECTIVE SUB-CONTRACTOR,AT HIS EXPENSE,SHALL OBTAIN ALL PERMITS AND FEES REQUIRED 1) TUBING: CORRUGATED STAINLESS STEEL WITH PLASTIC JACKET OR COATING. I. CORE DRILLING: PROVIDE ALL EQUIPMENT,LABOR AND MATERIAL FOR CORE DRIWNG HOLES WHERE FROM MOVEMENT WILL NOT BE TRANSMITTED TO CONNECTED EQUIPMENT. HIV HOT WATER V VENT FOR THIS SCOPE OF WORK ON THIS PROJECT. THE SUB-CONTRACTORS SHALL ALSO SCHEDULE ALL 2) FITTINGS: COPPER ALLOY WITH ENDS MADE TO FIT CORRUGATED TUBING. INCLUDE PIPING PENETRATES EXISTING CONCRETE WALLS OR FLOORS. DRILL HOLES 1'LARGER THAN O.D.OF L PIPING SUPPORTED BY THE ROOFTOP SHALL BE A MINIMUM OF 6'MOVE THE ROOF SURFACE AND HWC HOT WATER CIRCULATION VA VALVE REQUIRED INSPECTIONS AND OBTAIN CEITIFlCATES FOR HIS WORK,AT HIS EXPENSE. ENDS WITH THREADS ACCORDING TO ASME B1.20.1 IF CONNECTION TO THREADED PIPE. PROTECT ALL SURROUNDING AREAS FORM DAMAGE BY WATER OR DUST WHILE CORE DRILLING. URUZE MANUFACTURED PIPING SUPPORTS FOR THIS PURPOSE IDW INDIRECT WASTE VTR VENT THRU ROOF 1.4 SUBIVIFITALS AND SUBSTRMONS PIPE OR FITTINGS IS REQUIRED. WHERE PIPES PASS THROUGH SLEEVES OR CORE DRILLED HOLES,PROVIDE BACKER ROD AND FILL M. USE MATERIALS COMPATIBLE WITH ITEMS BEING SUPPORTED TO AVOID ELECTROLYTIC ACTION,AND I.E. INVERT ELEVATION W WASTE A SUBMITTAL MATERIALS SHALL BE COMPLETE IN EVERY RESPECT AND SHALL CLEARLY INDICATE EQUIPMENT 3) STRIKER PLATES: STEEL,DESIGNED TO PROTECT TUBING FROM PENETRATIONS. OUTER%-DEPTH OF THE ANNULAR SPACE WITH SEALER. CONFORM TO SMACNA,ANSI/ASME B31,NFPA MSS SP-58,69.89. IRR IRRIGATION WCO WALL CLEANOUT FUTURES,DIMENSIONS,WEIGHTS,PERFORMANCE CHARACTERISTICS,AND CAPACITIES. CAPACITY AND 4) MANIFOLDS: MALLEABLE IRON OR STEEL WITH PROTECTIVE COATING. INCLUDE J. PENETRATIONS ME PROHIBITED IN ANY STRUCURM MEMBERS(EXCEPT WHERE NOTED IN DRAWINGS) 3.5 PAINTING PERFORMANCE CALCULATIONS SHALL BE ADJUSTED T AT INDICATE ACTUAL EQUIPMENT PERFORMANCE AT THE THREADED CONNECTIONS ACCORDING TO ASME B1.20.1 FOR PIPE INLET AND WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. OBTAIN APPROVAL FOR OTHER FRAMED OPENINGS A. EXPOSED ABS AND PVC PIPING: PROTECT PLUMBING VENTS EXPOSED TO SUNUGHT WITH TWO COATS OF SHEET INDEX PROJECT ELEVATION. LITERATURE OR DRAWINGS THAT DESCRIBE MORE THAN ONE MODEL OR SIZE OF CORRUGATED TUBING OUTLETS. WHICH MAY BE REQUIRED IN ADDITION TO THOSE SHOWN ON DRAWINGS. PAY ALL COSTS FOR WATER-RASED LATEX PAINT. EQUIPMENT SHALL BE MARKED WITH ARROWS OR OTHERWISE CLEARLY INSCRIBED i0 IDENTIFY THE ACTUAL ADDITIONAL CURING OF HOLES M THE RESULT OF INCORRECT LOCATION OF SLEEVES OR FURNISHING EQUIPMENT THAT WILL BE FURNISHED. ALL OPTIONS AND SPECIAL PARTS OF FUTURES SHALL ALSO BE b. ACCEPTABLE MANUFACTURERS:OMEGAFLEX,INC.,TFEFLEX CORP.,TRU-FLEX METAL HOSE INCORRECT INFORMATION O TO THE REQUIREMENTS OF FRAMED OPENINGS. B. DAMAGE AND TOUCHUP: REPAIR MARRED AND DAMAGED FACTORY-PAINTED FINISHES WITH MATERIALS AND POLO PLUMBING COVER SHEET CLEAR IDENTIFIED. ALL SUBMITTED MATERIALS MUST BE CLEAR,COMPLETE,AND LEGIBLE ALL CORP.,WARD INDUSTRIES,INC. PROCEDURES TO MATCH ORIGINAL FACTORY FINISH. SUBMITTALS OF THIS SCOPE MUST BE SUBMITTED AT ONE TIME;MULTIPLE AND VARIED SUBMITTALS WILL G. INDIRECT WASTE PIPING SHAIl BE ANY OF THE FOLLOWING: K. FIRE-RATED ASSEMBLY PENETRATIONS: 3 P2.1 PLUMBING WASTE&VENT PLAN BE REJECTED. 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY PROTECTING ANY PENETRATION OF A FIRE P2.2 PLUMBING WATER&GAS PLAN B. SUBMITTALS FOR ALL EQUIPMENT SHAIl BE ROUTED THROUGH MD REVIEWED BY THE CONTRACTOR. THE 1. SQUID WAIL PVC PIPE PER ASTM D 2665,SCHEDULE 40 DRAIN,WASTE,AND VENT,PVC RATED ASSEMBLY. FIRE SEAL,CAULKING,AND APPURTENANCES SHALL BE UL LISTED FOR THE A. ARCHITECTURAL ACCESS DOORS OR PANELS: COORDINATE REQUIREMENTS FOR ACCESS PANELS AND P2.3 PLUMBING ROOF GAS PLAN CONTRACTOR SHALL CHECK ALL SUBMITTALS FOR ADEQUATE IDENTIFICATION,CORRECTNESS,AND SOCKET FITTINGS,AND SOLVENT-CEMENTED JOINTS. ASSEMBLY RATING IT IS APPLIED TO AND SHALL BE INSTALLED PER THE MANUFACTURERS WRITTEN DOORS WHERE MECHANICAL ITEMS REQUIRING ACCESS ARE CONCEALED BEHIND FlNISHED SURFACES. THIS P3.0 PLUMBING SCHEDULES COMPLIANCE WITH CONTRACT DRAWINGS AND SPECIFICATIONS AND APPLY A STAMP OF APPROVAL FOR 2. HARD COPPER TUBE CONFORMING TO ASTM B-88,TYPE M WATER TUBE,DRAWN AND INSTRUCTIONS. ALL SUCH MATERIALS SHALL MEET STATE,LOCAL,AND AUTHORITIES CODES AND CONTRACTOR SHALL PROVIDE ACCESS PANELS OR DOORS OF SUFFICIENT SIZE TO ALLOW ACCESS TO HIS P4.0 PLUMBING DETAILS SUBMITTALS THAT ARE REQUIRED TO BE REVIEW E BY THE ENGINEER,A DIGITAL COPY SHALL BE TEMPER;COPPER PRESSURE FITTINGS PER ASME B16.18;AND ALLOY SN95 SOLDER WITH STANDARDS. WORK THAT REQUIRES ACCESS FOR MAINTENANCE OR INSPECTION. FORWARDED FOR RENEW AFTER REVIEW AND APPROVAL BY THE CONTRACTOR. THESE SHALL BE WATER SOLUBLE FLUX. 2. REFER TO ARCHITECTURAL DRAWINGS FOR ALL FIRE RATED ASSEMBLY LOCATIONS AND RATINGS 3.7CLEANING. TESTING AND BALANCING RETURNED AND SHALL BE REVISED AND RESUBMITTED UNTIL ACCEPTED BY THE ENGINEER. PROVIDE H. VALVES AND PLUMBING SPECIALTIES: L. SEISMIC RESTRAINT: A CLEAN INFERIOR OF PIPING. REMOVE DIRT AND DEBRIS AS WORK PROGRESSES. PRODUCT DATA FOR EACH PIECE OF EQUIPMENT/COMPONENT LISTED BELOW: 1. ACCEPTABLE MANUFACTURERS: WATTS,APOLLO,RED&WHITE,NIBCO,MILWAUKEE, 1. THE CONTRACTOR SHALL PROVIDE PROPER MECHANICAL SEISMIC REgMNTS FOR ALL INSTALLED B. CLEAN AND DISINFECT POTABLE DOMESTIC USING PURGING AND DISINFECTING PROCEDURES PRESCRIBED 1. FLOOR AND ROOF DRAINS,FLOOR SINKS,CLFANOUTS. ARMSTRONG ITEMS INCLUDING,BUT NOT UNITED TO,DUCTS,PIPING,EQUIPMENT AND ACCESSORIES.THE BY AUTHORITIES HAVING JURISDICTION OR,IF METHODS ARE NOT PRESCRIBED,PROCEDURES DESCRIBED IN 2. ALL PLUMBING FIXTURES 2. GENERAL USE VALVES:AND ACCESSORIES. CONTRACTOR SHALL PROVIDE SEISMIC RESTRAINTS AS LISTED BY THE CODES USED BY THE MJ OR ETHER AWWA C651 OR AWWA C652 OR M DESCRIBED BELOW: 3, pQMpg, AS SHOWN ON THE DRAWINGS(WHICHEVER IS MORE STRINGENT). 1. FLUSH PIPING SYSTEM WITH CLEAR,POTABLE WATER UNTIL DIRTY WATER DOES NOT APPEAR AT r 4. WATER HEATERS. a. BALL VALVE(FULL PORT THRU 31 -WATTS FINS-1 SERIES ISYSTEMSI TI OUTLETS. GENERAL PLUMBING NOTES rl 5. VALVES AND PIPE ACCESSORIES. b. GATE VALVE(THRU 4'-WATTS WGV-1 SERIES A INSTALL SOIL AND WASTE DRAINAGE AND VENT PIPING AT THE FOLLOWING MINIMUM SLOPES,UNLESS 2. FILL SYSTEM OR PART THEREOF WMTH WATER/CHLORINE SOLUTION WITH AT LEAST 50 PPM OF 6. PIPE INSULATION AND LOCATIONS c. GAS(THRU 1'-WATTS G13V SERIES OTHERWISE INDICATED: CHLORINE. OR WITH VALVES AND ALLOW TO STAND FOR 24 HOURS. (RE:ALL PLUMBING SHEETS) W C. APPROVED MANUFACTURERS,WHICH MAY SUBMIT EQUAL PRODUCT TO THOSE SPECIFIED,ARE USTED IN d. GLOBE(THRU 21-WATTS GLV SERIES 1. BUIWING SANITARY DRAIN: 2 PERCENT DOWNWARD IN DIRECTION OF FLOW FOR PIPING NPS 4 MD 3. FLASH SYSTEM WITH CLEAN,POTABLE WATER UNTIL NO CHLORINE IS IN WATER COMING FROM SYSTEM 1. COORDINATE LOCATION OF VENTS THROUGH ROOF 70 MAINTAIN 10'CLEARANCE FROM OUTSIDE AIR INTAKES. W THE EQUIPMENT SCHEDULES. MY SUBMITTAL FOR CONSIDERATION M M EQUAL TO THAT SCHEDULED SMALLER;1 PERCENT DOWNWARD IN DIRECTION OF FLOW FOR PIPING NPS 5 AND LARGER. AFTER THE STANDING TIME. III MUST CONTAIN ALL INFORMATION REQUIRED TO EVALUATE THIS CLAIM. MANUFACTURERS NOT USTED AS e. CHECK(THRU 31-WATTS WCV-2 SERIES :y EQUAL MUST ALL IN WRITING FOR RENEW FIVE DAYS PRIOR TO BID CLOSING. CONTRACTOR IS f. STRAINER(THRU 21-WATTS S777SI SERIES 2. HORIZONTAL SANITARY DRAINAGE PIPING: 2 PERCENT DOWNWARD IN DIRECTION E FLOW. C. TEST DOMESTIC WATER PIPING AS FOLLOWS: 2. SITE UTILITIES: THE MECHANICAL THE IT DOCUMENTS INDICATE CONNECTION LOCATION OF VARIOUS BUILDING SERVICES, RESPONSIBLE TO ASSURE ANY SUBSTITUTED REM MEETS ALL PHYSICAL AND PERFORMANCE 3. VENT PIPING: 1 PERCENT DOWN TOWARD VERTICAL FIXTURE VENT OR TOWARD VENT STACK. 1. FILL DOMESTIC WATER PIPING. CHECK COMPONENTS TO DETERMINE THAT THEY ME NOT AIR BOUND CQUPOIRAIE WORK WITH THE SIZE UTLfTES CONTRACTOR TO ENSURE PROPER INVERT ELEVATION,PPE SLOPE REQUIREMENTS AS INTENDED IN THE DESIGN DOCUMENTS. 9. BALANCE(THRU 37-WATTS CSM-61-M1 SERIES B. INSTALL PIPING IN CONCEA ED LOCATIONS,UNLESS OTHERWISE INDICATED AND EXCEPT IN EQUIPMENT AND THAT PIPING IS FULL OF WATER. GRADIENT,PIPE SIZE AND SEPARATION WITHIN TRENCH WORK. NOTIFY ARCHITECT OR ENGINEER OF ANY *C. h. BUTTERFLY 3 AND URGER - ROOMS AND SERVICE AREAS. 2. LEAVE NEW,ALTERED,EXTENDED,OR REPLACED DOMESTIC WATER PIPING UNCOVERED AND DISCREPANCY BETWEEN DRAWINGS AND FIELD CONDITIONS /9�14 D. APPROVAL OF SUBMITTALS BY THE ENGINEER SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY ( ) FLI FOR DDMTIONS FROM DRAWINGS OR SPECIFICATIONS,NOR SHALL IT REUEVE HIM FROM RESPONSIBILM 3. WATER HAMMER ARRESTERS SIOUX CHIEF,PPP,SMITH): METAL BELLOWS OR COPPER TUBE C. INSTALL DOMESTIC WATER PIPING LEVEL WITH 0.25 PERCENT SLOPE DOWNWARD TOWARD DRAIN. UNCONCFMID UNTIL R HAS BEEN TESTED AND APPROVED. EXPOSE WORK THAT WAS COVERED OR W ( ) CONCEALED BEFORE IT WAS TESTED. 3. CONTRACTOR SNAIL IDENTIFY'ALL SERVICEABLE ITEMS(VALVES,CLFANOUIS,COILS,ETC.)SO THAT THE CEUNG FOR ERRORS IN SHOP DRAWINGS OR OTHER SUBMRTAL LITERATURE WITH PISTON PER ASSET 1010 OR PDI-WH 2O1. PROVIDE ACCESS PANELS AS REQUIRED. D. ESTABLISH ELEVATIONS OF BURIED PIPING OUTSIDE THE BUILDING TO ENSURE CONNECTION AT INVERT SUBCONTRACTOR MAY KNOW WHERE TO INSTALL ACCESS-TYPE PANELS SHOULD A UFT-UP TYPE CEILING NOT E. CONTRACTOR HAS SOLE RESPONSIBILITY TO COORDINATE ANY SUBSTIIUIIONS WITH ALL OTHER DISCIPLINES. I. DIELECTRIC FlTTNGS 3. CAP AND SUBJECT PIPING TO STATIC WATER PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE, O ELEVATION NOTED ON DRAWINGS. MAINTAIN NOT LESS THAN 48'OF COVER OVER WATER PIPING,36' BE INSTPLIID. THIS CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR HIS WORK UNLESS SPECIFICALLY EQUIPMENT OF GREATER POWER,DIMENSIONS,CAPACTIES,AND RATINGS MAY BE FURNISHED PROVIDED OVER WASTE PIPING. WITHOUT EXCEEDING PRESSURE RATING OF PIPING SYSTEM MATERIALS. ISOLATE TEST SOURCE AND NOTED ON THE DRAWINGS. ARCHITECT SHALL APPROVE LOCATIONS OF ACCESS PANELS PRIOR TO O .; 1. COMBINATION FITTING OF COPPER ALLOY AND FERROUS MATERIALS WITH THREADED, ALLOW TO STMD FOR FOUR HOURS. LEAKS AND LOSS IN TEST PRESSURE CONSUME DEFECTS SUCH PRDPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING MECHANICAL MD ELECTRICAL E. LAY BURIED BUILDING DRAINAGE AND STORM PIPING BEGINNING AT LOW POINT OF EACH SYSTEM. INSTALLATION. SOLDER-JOIN,PLAIN,OR WELD-NECK END CONNECTIONS THAT MATCH PIPING SYSTEM THAT MUST BE REPAIRED. SERVICES,CIRCUIT BREAKERS,CONDUIT,MOTORS,BASES,AND EQUIPMENT SPACES ARE INCREASED. NO INSTALL TRUE TO GRADES AND ALIGNMENT INDICATED,WITH UNBROKEN CONTINUITY OF INVERT. PLACE r Y �i ADDITIONAL COSTS WILL BE ACCEPTED FOR THESE INCREASES,IF W2GER EQUIPMENT IS PROVIDED. IF MATERIALS' 4. REPAIR LEAKS MO DEFECTS WRH NEW MATERIALS MD RETEST PIPING OR PoRIION THEREOF UNTIL U HUB ENDS OF PIPING UPSTREAM. ANTS,C REQUIRED GASKETS ACCORDING TO MANUFACTURER'S MAINTAIN 4. PROVIDE ALL NECESSARY'INSTALLATION SEALING,ETC.TO EMS AS THE WATERPROOF INTEGRITY OF THE BUIWING MINIMUM ENERGY RATINGS OR EFFICIENCIES IS THE EQUIPMENT ARE SPECIFIED,THE EQUIPMENT MUST 2. DIELECTRIC UNIONS: FACTORY-FABRICATED,UNION ASSEMBLY,FOR 250-PSIG MINIMUM INSTRUCTIONS FOR USE OF LUBRICANTS,CEMENTS, MP QED. INSTALLATION REQUIREMENTS, MAINTAIN SATISFACTORY D RESULTS ARE OBTAINED. AS REQUIRED BY THE INS1AllATION OR REMOVAL OF ITEMS AS REQUIRED BY THIS SCOPE OF WORK. MEET THE DESIGN REQUIREMENTS AND COMMISSIONING REQUIREMENTS. WORKING PRESSURE AT 180 DEG F. SCUM IN PIPING AND PULL PAST EACH JOINT AS COMPLETED. D. TEST SANITARY DRAINAGE AND VENT PIPING ACCORDING 10 PROCEDURES OF AUTHORITIES HAVING l HANDLING1.5 DEUIVIERY. STORAGE. AND 3. DIELECTRIC COUPLINGS: GALVMIZED-STEEL COUPLING WITH INERT AND NON-CORROSNE, F. LAY BURIED PIPING IN PIPING TRENCH ON BEDDING MATERIAL,HMNCHED,AND BACKFlLLED IN JURISDICTION OR,IN ABSENCE OF PUBLISHED PROCEDURES,AS FOLLOWS: 5. ALL PENETRATIONS MADE THROUGH RATED ASSEMBUES TO ACCOMMODATE WORK OF THIS SECTION MUST BE I--� ,. O A DELIVER PRODUCTS TO THE PROJECT PROPERLY IDENTIFIED WITH NAMES,MODEL NUMBERS,TYPES, THERMOPLASTIC LINING;THREADED ENDS;AND 300-PSIG MINIMUM WORKING PRESSURE AT ACCORDANCE WITH LOCAL PLUMBING CODES MD ASTM D2321 PROCEDURES.BURIED PIPING TO MEET 1. ROUGHING-IN PLUMBING TEST PROCEDURE: TEST DRAINAGE AND VENT PIPING,EXCEPT OUTSIDE SEALED TO MAINTAIN THE RATING OF SUCH ASSEMBLY BY A U.L RECOGNIZED SEMNG METHOD. GRADES,COMPLIANCE LABELS,AND OTHER INFORMATION NEEDED FOR IDENTIFICATION. 225 F. FOLLOWING PARAMETERS: LEADERS,ON COMPLETION OF ROUGHING-IN. CLOSE OPENINGS IN PIPING SYSTEM AND FILL WITH r--� WATER TO POINT OF OVERFLOW,BUT NOT LESS THAN 10-FOOT HEAD OF WATER. FROM 15 MINUTES 6. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF THIS WORK. COORDINATE ALL H B. ALL MECHANICAL EQUIPMENT AND MATERIAL HEIRS SHALL BE PROTECTED FROM WEATHER MD VANDMSM 1. INSTALL IN 24'MINIMUM WIDTH PIPING TRENCH OR AS REQUIRED BY LOCAL CODES OR ASTM D2321. BEFORE INSPECTION STARTS TO COMPLETION OF INSPECTION,WATER LEVEL MUST NOT DROP. BLOCKING,SUPPORT,ETC.NECESSARY FOR THE INSTALLATION OF THIS WORK WITH THE GENERAL CONTRACTOR. N PRIOR TO ACTUAL INSTALLATION. FM WHEELS,PUMPS AND OTHER ROTATING MACHINERY SHALL BE A. SOLDERED JOINTS: USE ASTM B 813,WATER-FLUSHABLE,LEAD-FREE FLUX;ASTM B 32, 2. PROVIDE 4'MINIMUM GRANULAR BEDDING MATERIAL(I.E.SAND OR EQUIVALENT). INSPECT JOINTS FOR LEAKS. M-7 "r.:' W� PERIODICALLY ROTATED DURING STORAGE. ANY FACTORY PAINTED EQUIPMENT SCRATCHED OR MARRED LEAD-FREE-ALLOY SOLDER;AND ASTM B 828 PROCEDURE,UNLESS OTHERWISE INDICATED. 3. PROVIDE GRANULAR MATERIAL FOR COMPACTED HAUNCH. 2. FINISHED PLUMBING TEST PROCEDURE AFTER PLUMBING FIXTURES HAVE BEEN SET AND TRAPS 7. THE RESPECTIVE SUB-CONTRACTOR,AT HIS EXPENSE,SHALL OBTAIN ALL PERMITS AND FEES REQUIRED FOR �-I y DURING SHIPMENT OR CONSTRUCTION SHALL BE RESTORED TO ORIGINAL'NEW'CONDITION. THIS FILLED WITH WATER,TEST CONNECTIONS AND PROVE THEY ARE GASTIGHT AND WATERTIGHT. PLUG THIS SCOPE OF WORK ON THIS PROJECT. THE SUB-CONTRACTORS SHALL ALSO SCHEDULE ALL REQUIRED W. INCLUDES COMPLETE REPAINTING OF THE EQUIPMENT IF NECESSARY TO PROVIDE EXACT PAINT MATCH. B. BRAZING FILLER METALS: AWS A5.8,BCUP SERIES,COPPER-PHOSPHORUS ALLOYS FOR 4. PROVIDE 12'MINIMUM GRANULAR MATERIAL FOR PIPING COVER,OR AS REQUIRED BY LOCAL CODES INSPECTIONS AND OBTAIN CERTIFICATES FOR HIS WORK,AT HIS EXPENSE. CLVO GENERAL-DUTY BRAZING,UNLESS OTHERWISE INDICATED;AND AWS A5.8,BAG1,SILVER ALLOY OR MEETING REQUIREMENTS OF ASTM D2321. VAR-STACK OPENINGS ON ROOF AND BUILDING DRAINS WHERE THEY LEAVE BUILDING. INTRODUCE C. CONTRACTOR IS RESPONSIBLE FOR RECEIVING AND OFFLOADING EQUIPMENT OF HIS SCOPE. IMMEDIATELY AIR INTO PIPING SYSTEM EQUAL TO PRESSURE OF 1-INCH WG. USE U-TUBE OR MANOMETER S = UPON RECEIPT,CONTRACTOR SHALL INSPECT ALL EQUIPMENT AND MATERIAL FOR SHIPPING DAMAGE AND FOR REFRIGERANT PIPING,UNLESS OTHERWISE INDICATED. 5. PROVIDE SUITABLE BACKFlLL MATERIAL ABOVE GRANULAR FILL TO GRADE CONSULT GEOTECHNICAL INSERTED IN TRAP OF WATER CWSET TO MEASURE TIHIS PRESSURE. AIR PRESSURE MUST REMAIN B. CONTRACTOR HAS SOLE RESPONSIBILITY TO COORDINATE ANY SUBST ITONS WRIT ALL OTHER DISCIPLINES. a O (\ REPLACE ANY DEFECTIVE ITEMS AT NO INCREASE TO CONTRACT MOUNT. C. EXTRUDED-TEE CONNECTIONS: FORM TEE IN COPPER TUBE ACCORDING TO ASTM F 2014. USE REPORT,LOCAL CODES,OR ASTM D2321 FOR APPROVED BACKFILL MATERIAL CONSTANT WITHOUT INTRODUCING ADDITIONAL AIRSU THROUGHOUT PERIOD IR INSPECTION. INSPECT EQUIPMENT OF GREATER POWER,DIMENSIONS,CAPACITIES,AND RATINGS MAY BE FURNISHED PROVIDED SUCH ^ rT 1.6 SEQUENCING AND SCHEDULING TOOL DESIGNED FOR COPPER TUBE;DRILL PILOT HOLE,FORM COLLAR FOR OUTLET,DIMPLE G. MALE CHARGES IN DIRECTION FOR SOIL WASTE,AND STORM DRAINAGE AND VENT PIPING USING PLUMBING FIXTURE CONNECTIONS FOR GAS AND WATER LEAKS. PROPOSED EQUIPMENT HAS BEEN SUBMITTED FOR REVIEW,IN WRITING AND CONNECTING MECHANICAL AND Fey FT* A COORDINATE PLUMBING EQUIPMENT INSTALLATION WITH OTHER BUIWING COMPONENTS PRIOR TO ORDERING TUBE TO FORM SEATING STOP,AND BRAZE BRANCH TUBE INTO COLLAR. APPROPRIATE BRANCHES,BENDS,AND LONG-SWEEP BENDS. SANITARY TEES AND SHORT-SWEEP 1/4 E. PERFORM TESTING AND BALANCING PROCEDURES ON EACH SYSTEM ACCORDING TO THE PROCEDURES ELECTRICAL SERVICES,CIRCUIT BREAKERS,CONDUIT,MOTORS,BASES,AND EQUIPMENT SPACES ARE ADJUSTED D. SOLVENT CEMENTS FOR JOINING PLASTIC PIPING: BENDS MAY BE USED ON VERTICAL STACKS IF CHANGE IN DIRECTION OF FLOW IS FROM HORIZONTAL TO APPROPRIATELY. NO ADDITIONAL COSTS WILL BE APPROVED FOR THESE INCREASES,IF LARGER EQUIPMENT IS OR FABRICATION OF ADJOINING WORK. CONTAINED IN NEBB'S*PROCEDURAL STANDARDS FOR TESTING,ADJUSTING,AND BALANCING OF PROPOSED. IF MINIMUM ENERGY RATINGS OR EFFICIENCIES OF THE EQUIPMENT ARE SPECIFIED,THE SCALE: VERTICAL USE LNG-TURN,DOUBLE Y-BRANCH AND 1/8-BEND FITTINGS IF 2 FIXTURES ARE INSTALLED EQUIPMENT MUST MEET THE DESIGN REQUIREMENTS AND COMMISSIONING REQUIREMENTS. CONTRACTOR IS B. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET SLEEVES IN 1. ABS PIPING: ASIM D 2235. FNVIRONMENTM SYSTEMS'. AS NOTED BACK 70 BACK OR SIDE Bf SIDE WITH COMMON DRAIN PIPE SITUIGHT LEES,ELBOWS,MD CROSSES POURED-IN-PLACE FOR CONCRETE AND OTHER STRUCTURAL BUILDING COMPONENTS U M THEY ME CONSTRUCTED. 2. CWC PIPING: ASTM F 493. MAY BE USED ON VENT UNES. DO NOT CHANGE DIRECTION OF FLOW MORE THAN 90 DEGREES. USE F. PREPARE TEST REPORTS WITH PERTINENT DESIGN DATA AND NUMBER IN SEQUENCE STARLING AT PUMP SOLELY RESPONSIBLE FOR SUBSRRITED EQUIPMENT MEETING THE INTENT OF THE ORIGINAL DESIGNED DATE: ARRANGE FOR CHAFES,SLOTS,AND OPENINGS IN BUILDING STRUCTURE DURING PROGRESS OF 3. PVC PIPING: ASTM D 2564. INCLUDE PRIMER ACCORDING TO ASTM F 656. PROPER SIZE OF STANDARD INCREASERS AND REDUCERS IF PIPES OF DIFFERENT SIZES ARE CONNECTED. TO END OF SYSTEM. CHECK THE SUM OF BRANCH-CIRCUIT FLOWS AGAINST APPROVED PUMP FLOW EQUIPMENT IN ALL ASPECTS. 08/10/2023 CONSTRUCTION TO ALLOW FOR MECHANICAL INSTALLATIONS. E. PVC TO ABS PIPING TRANSITION: ASTM D 3138. REDUCING SIZE OF DRAINAGE PIPING IN DIRECTION OF FLOW IS PROHIBITED. RATE. CORRECT VARIATIONS THAT EXCEED PLUS OR MINUS 5 PERCENT. G SEQUENCE,COORDINATE,AND INTEGRATE INSTALLATIONS OF MECHANICAL MATERIALS AND EQUIPMENT FOR 9. PROVIDE A COMMISSIONING PLAN DEVELOPED BY A REGISTERED DESIGN PROFESSIONAL OR APPROVED AGENCY' DRAWN BY., EFFICIENT FLOW OF THE WORK. COORDINATE INSTALLATION OF LARGE EQUIPMENT REQUIRING POSITIONING H. INSTALL D ON PLUMBING IN GRADE WHERE BUILDING STORM DRAINS IXR THE BUILDING. ClFAN0UT5 ME AS ERE REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. TSM PRIOR TO CLOSING IN THE BUILDING. SPECIFIED ON PLUMBING SCHEDULE A WHERE REQUIRED,CONTRACTOR SHALL FURNISH A COMBINATION STARTER SIZED IN ACCORDANCE WTH D. COORDINATE CONNECTION OF MECHANICAL SYSTEMS WITH EXTERIOR UNDERGROUND AND OVERHEAD I. INSTALL CAST-IRON SOIL PIPING ACCORDING TO CISPI'S'CAST IRON SOIL PIP:AND FITTINGS HANDBOOK; THE MOTOR RATING. STARTER SHALL BE SUPPUED WITH FUSES OR CIRCUIT BREAKERS,CONTROL CHECKED BY: UTIUTIES AND SERVICES. COMPLY WITH REQUIREMENTS OF GOVERNING REGULATIONS,FRANCHISED SERVICE CHAPTER N,INSTALLATION OF CAST IRON SOIL PIP:AND FITTINGS.' TRANSFORMER,OVERLOADS,ONE N.O.AND ONE N.C.AUXILIARY CONTACTS,AND AN HOA SWITCH IN THE CRA COMPANIES,AN CONTROLUNG AGENCIES. COORDINATE CONNECTION OF ELECTRICAL SERVCES. J. CONNECT SOIL AND WASTE PIPING TO EXTERIOR SANITARY SEWERAGE PIPING. USE TRANSITION FTTNG CABINET COVER. STARTER ENCLOSURE SHALL BE NEMA RATAN FOR ITS LOCATION, STARTER SHALL BE CITY APPROVED PLANS E. PROVIDE IDENTIFICATION OF ALL EQUIPMENT. COORDINATE INSTALLATION OF IDENTIFYING DEVICES AFTER TO JOIN DISSIMILAR PIPING MATERIALS. WIRED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. COMPLETING COVERING MD PAINTING WHERE DEVICES ARE APPLIED TO SURFACES. INSTALL IDENTIFYING K. DO NOT ENCLOSE,COVER,OR PUTPIPING INTO OPERATION UNTIL IT IS INSPECTED AND APPROVED BY B. CONTRACTOR SHALL PROVIDE A COMPLETE CONTROL SYSTEM TO OPERATE THE EQUIPMENT AS DESCRIBED Reviewed for Code Compliance DEVICES PRIOR TO INSTAWNG ACOUSTICAL CEILINGS AND SIMILAR CONCEALMENT. AUTHORITIES HAVING JURISDICTION. IN THESE DOCUMENTS. SYSTEM SHALL INCLUDE THERMOSTATS,LOW VOLTAGE WIRING,TRANSFORMERS, SHEET L. INSTALL WATER HARMER ARRESTERS IN WATER PIPING ACCORDING TO POI-WH 2O1. AND ASSOCIATED APPURTENANCES REQUIRED TO MEET THE INTENT OF THESE DOCUMENTS. PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS r 7� 0.0 Page 13 of 26 CONSTRUCTION NOTES: 1. ALL WORK ASSOCIATED WIM THE DRYERS AND WASHERS TO BE VERIFIED AS ACCEPTABLE PER THE DRYER AND WASHER MACHINE SUPPLIER,1HE c $ EQUIPMENT WRITTEN INSTALLATION INSTRUCTIONS AND THE GENERAL ED CONTRACTOR. Z I � GENERAL NOTES: �I w r 0 1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH Z p THE REQUIREMENTS OF ALL LOCAL PLUMBING CODES,REGULATIONS,AND I� m ORDINANCE. C7 - ® N 3 N 2. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF w_ 3 \ \ \ \ \ \ \ \ \ \ \ \ \ THE WORK.LOCATION OF UNDERGROUND SANITARY SEWER,STORM SEWER, WATER MAIN,GAS MAIN,ETC.IS APPROXIMATE AND THE BEST THAT COULD BE L) DETERMINED BY VISUAL OBSERVATION.CONTRACTOR SHALL VISIT THE SITE Q v -u -u 11 -u L L -u 1J -u 1J L L D L-1 PRIOR TO HIS BIDDING IT,AND SHALL INVESTIGATE ALL CONDITIONS THAT — AFFECT HIS WORK,VERIFY LOCATIONS,SIZES,DIMENSIONS AND INVERT ELEVATIONS OF ALL SEWER,GAS AND WATER PIPES AND MAKE CERTAIN THAT 3 ALL CONNECTIONS CAN BE MADE. i VIR 3. ALL SLOPE AND INVERT ELEVATIONS SHALL BE CHECKED BEFORE ANY PIPING 8 IS INSTALLED IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED.NOTIFY 3 ARCHITECT IF THERE ARE ANY PROBLEMS. O 4. IT SHALL BE NOTED THAT THE WORD"PROVIDE"MEANS FURNISH AND INSTALL IN CLEAN OPERATING CONDITION.THE WORD"PIPING'INCLUDES,PIPE, ED ---� FITRNGS,VALVES,CONTROLS AND EVERYTHING NECESSARY FOR COMPLETE V 2•f� SYSTEM.ALL MATERIALS SHALL BE NEW. i 5. DRAWINGS ARE DIAGRAMMATIC.DO NOT SCALE FOR THE EXACT LOCATION OF i FIXTURES,PIPING AND EQUIPMENT,ETC. ; 6. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID ALL EXCAVATION WITH THE PROGRESS OF CONSTRUCTION. U U i 7. ALL EXCAVATION AND BACKFlLL AS REQUIRED FOR PLUMBING WORK SHALL BE PART OF THIS CONTRACT. 8. PROVIDE ISOLATION VALVES ON ALL PLUMBING FIXTURES AND EQUIPMENT FOR �gBV04u' SERVICE. Qdc �p\S7Eo., i� 9. ALL DAMAGE,SAW CUTS Q PENETRATIONS RESULTING FROM PLUMBING WORK 8 F MUST BE PATCHED OR REPAIRED TO MATCH EXISTING AND/OR NEW WORK. OV 6�G G PATCHES AND REPAIRS TO WALLS AND FLOORS TO BE COMPLETED BY GENERAL CONTRACTOR. 10. THE CONTRACTOR SHALL BE COGNIZANT THAT THIS IS A REMODELING PROJECT FY ANTI V O3 AND AS SUCH,ALL FACETS OF THE CONSTRUCTION CAN NOT BE SHOWN.A OB/10/2023 VISIT TO SITE IS REQUIRED OF ALL BIDDERS PRIOR TO SUBMISSION OF BID. 2"0SS ALL WILL BE HELD TO HAVE FAMILIARIZED THEMSELVES WITH ALL DISCERNIBLE CONDITIONS AND NO EXTRA PAYMENT WILL BE ALLOWED FOR WORK REQUIRED BECAUSE OF THESE CONDITIONS,WHETHER SPECIFICALLY MENTIONED OR NOT. OO GCO_ 2 LINES OF OTHER SERVICES THAT ARE DAMAGED AS A RESULT OF THIS WORK -------------------------------------- - SHALL PROMPTLY BE REPAIRED AT NO EXPENSE TO THE OWNER TO COMPLETE 4"►SS O7 SATISFACTION OF THE OWNER. ------ ------------------ KEYED NOTES: 1. EXISTING CONCRETE FLOOR WILL NEED TO BE SAWCUT AND PATCHED BACK TO FF IF Fr r (r ( r r ( ( ( (r R 6 6 R R n 0 4 5 < BE BY THE GENERAL CONTRACTOR,COORDINATE LOCATION AND WORK. V V V V V V V V V V V V II II WH WH TRENCHING AND BACKRLL TO BE BY THE PLUMBING CONTRACTOR. 1 2 Oj 2. VERIFY AVAILABLE INVERT TO ALLOW INSTALLATION AND CONNECTION OF NEW 9 O O I WASTE TO SANITARY SEWER MAIN. COORDINATE WITH THE GENERAL 8 CONTRACTOR. 3. CONNECT VENT PIPE TO NEW VTR,REFER TO DETAIL ON SHEET P4.0. i (_______ - -I - 4. INSTALL WATER HEATER PAN AND ROUTE DRAIN TO FLOOR SINK. ROUTE T/P`------------------------------------------------------------------------------------------------------------------------------------------ --------------------------------------- ------4"® ------- RELIEF AND CONDENSATE DRAIN TO FLOOR SINK. SEE DETAIL ON SHEET P4.0. -------------------------------------- - --------------------- - O ABOVE GRADE ABS O 5. VENT WATER HEATER THROUGH ROOF PER MANUFACTURER'S CRITERIA. TROUGH DRAIN SYSTEM 6. COORDINATE THE WASTE LINE CONNECTION TO THE TROUGH DRAIN WITH THE BY OTHERS GENERAL CONTRACTOR. 7. SITE AND CIVIL WORK,INCLUDING EXCAVATION,WASTE LINE,AND ALL ASPHALT 1 PLUMBING WASTE&VENT PLAN O PATCH BACK BY OTHERS. SCALE.1/4"=1'-0" 8. WATER SOFTENER SIZED,PROVIDED,AND INSTALLED BY OTHERS. NORTH 9. TERMINATE DISCHARGE FROM REDUCED PRESSURE BACKFLOW PREVENTER AT FLOOR SINK WITH AIR GAP. SEE DETAIL ON SHEET P4.0. �7 ^.4 FBI z � o o w a � SCALE: AS N01M DATE: CITY APPROVED PLANS 08/10/2023 DRAWN BY.., Reviewed for Code Compliance TSM PLANS MUST BE ON JOB SITE CHECKED BY: CRA FOR ALL INSPECTIONS SHEET P2.1 Page 14 of 26 CONSTRUCTION NOTES: 1. ALL WORK ASSOCIATED WITH THE DRYERS AND WASHERS TO BE VERIFIED AS ACCEPTABLE PER THE DRYER AND WASHER MACHINE SUPPLIER,THE EQUIPMENT WRITTEN INSTALLATION INSTRUCTIONS AND THE GENERAL 1-1/4'ONG, CONTRACTOR. ED ED o (2PSI) 1-1/2"ONG, GENERAL NOTES: N _ 1-1/4'®NG, 1-1/4"ONG, (2PSI)FROMQ 2PSI 2PSI ROOF ABOVE 1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH w E THE REQUIREMENTS OF ALL LOCAL PLUMBING CODES,REGULATIONS,AND Z o ORDINANCE. 3/4'ONG,TYP.OF WC_1 2. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF z I m 3 TEN DROPS(LARGER DRYERS O , THE WORK.LOCATION OF UNDERGROUND SANITARY SEWER,STORM SEWER, n u n. n TYP' 0j - WATER MAIN,GAS MAIN,ETC.IS APPROXIMATE AND THE BEST THAT COULD BE W u DETERMINED BY VISUAL OBSERVATION.CONTRACTOR SHALL VISB THE SITE (]m PRIOR TO HIS BIDDING fI,AND SHALL INVESTIGATE ALL CONORONS THAT 0 3,AFFECT HIS WORK,VERIFY LOCATIONS,SIZES,DIMENSIONS AND INVERT 1/2"ONG,TYP.OF ELEVATIONS OF ALL SEWER,GAS AND WATER PIPES AND MAKE CERTAIN THAT -1/4'ONG, 1 1/4"ONG, THREE DROPS 2.0C / ALL CONNECTIONS CAN BE MADE. j3. ALL SLOPE AND INVERT ELEVATIONS SHALL BE CHECKED BEFORE ANY PIPING \ \ \ \ \ \ \ \ \ \ \ II\ II\ II 1 L-1 SS-1 IS ARCHITECT I IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED.NOTIFY O ARCHRECi F THERE ARE ANY PROBLEMS. v III III III III IIv III III III III II �� II �� II �� II -L _U JJ JJ JJ JJ -U JJ JJ JJ 4. IT SHALL BE NOTED THAT THE WORD"PROVIDE"MEANS FURNISH AND INSTALL IN CLEAN OPERATING CONDTIION.THE WORD"PIPING"INCLUDES,PIPE, --� FITTINGS,VALVES,CONTROLS AND EVERYTHING NECESSARY FOR COMPLETE i SYSTEM.ALL MATERIALS SHALL BE NEW. 3/4'0C(V 1 5. DRAWINGS ARE DIAGRAMMATIC.DO NOT SCALE FOR THE EXACT LOCATION OF 1/2'OFIW 1 FIXTURES,PIPING AND EQUIPMENT,ETC. i 6. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCES WITH THE PROGRESS OF CONSTRUCTION. i ---------- --------- 7. ALL EXCAVATION AND BACKFILL AS REQUIRED FOR PLUMBING WORK SHALL BE PART OF THIS CONTRACT. 8. PROVIDE ISOLATION VALVES ON ALL PLUMBING FIXTURES AND EQUIPMENT FOR SERVICE. \ONAL aF� ASTEoi 9. ALL DAMAGE,SAW CUTS k PENETRATIONS RESULTING FROM PLUMBING WORK 4 _2 � MUST BE PATCHED OR REPAIRED TO MATCH EXISTING AND/OR NEW WORK. p A PATCHES AND REPAIRS TO WALLS AND FLOORS TO BE COMPLETED BY 8BOZ 3/4"OCW GENERAL CONTRACTOR. lop C 1/2"OHW 10. THE CONTRACTOR SHALL BE COGNIZANT THAT THIS IS A REMODELING PROJECT 0� AND AS SUCH,ALL FACETS OF THE CONSTRUCTION CAN NOT BE SHOWN.A Y AN VISIT TO SITE IS REQUIRED OF ALL BIDDERS PRIOR TO SUBMISSION OF BID. OB/10/2023 ALL WILL BE HELD TO HAVE FAMILIARIZED THEMSELVES WITH ALL DISCERNIBLE CONDITIONS AND NO EXTRA PAYMENT WILL BE ALLOWED FOR WORK REQUIRED BECAUSE OF THESE CONDITIONS,WHETHER SPECIFICALLY MENTIONED OR NOT. LINES OF OTHER SERVICES THAT ARE DAMAGED AS A RESULT OF THIS WORK SHALL PROMPTLY BE REPAIRED AT NO EXPENSE TO THE OWNER TO COMPLETE SATISFACTION OF THE OWNER. i HS, KEYED NOTES: 3/4*0 i 3/4'OHW _____ 1. NEW OPENING THROUGH THE EXISTING ROOF. ROOF PATCH TO BE BY THE -------------------------------------- - ROOFING CONTRACTOR,COORDINATE WITH THE GENERAL CONTRACTOR. SEE P2.3 TONG, FOR CONTINUATION. (2PSI)FROM ------------------------------- ------- ROOF ABOVE 2. INSTALL NEW GAS CONNECTION AT EACH DRYER PER MANUFACTURER'S WRTIEN 199MBH 199MBH INSTRUCTIONS AND PER DETAIL ON SHEET P4.0. REGULATOR REGULATOR 3. INSTALL NEW PRESSURE REGULATOR PER DETAIL EX SHEET P4.0. PROVIDE VENT LIMITER OR VENT THE REGULATOR TO THE EXTERIOR. SIZE FOR Ir F Ir F Ir F IF IF IF F-, r \ � � � � � � � � � � � � � 3/FF 3 4'ONG, CONNECTED DRYERS. � � � � � � � � � � � � V V V V V V V V V V V V (2PSI (2�SQ�j 4. PROVIDE FULL SIZE ISOLATION AND BYPASS VALVES FOR THE WATER SOFTNER. 8 5. WATER SOFTENER SIZED,PROVIDED AND INSTALLED BY OTHERS. u _ 6 P� 4.O UNDERGROUND 6. SITE AND CIVIL WORK,INCLUDING EXCAVATION,WATER LINE,AND ALL ASPHALT PAT i PATCH BACK BY OTHERS. 2'OCW 10ya R O9 O6 7. NATURAL GAS CONNECTION TO WATER HEATERS. CONNECTION LOCATION SHOWN _______________ _ ___ _ _____ __ ___ _ �T_ .� _� FOR CLARTIY,CONNECT TO EQUIPMENT PER MANUFACTURER'S DRAWINGS. SEE "---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- V2'OM -- ---------- DETAIL ON SHEET P4.0. O O 12 B. PROVIDE EMREDUCED PRESSURE BACKFLOW PREVENTER IN ACCESSIBLE LOCATION 1-1/2'OCW 10 2"014W 9. PROVIDE MAIN BUILDING SHUTOFF IN ACCESSIBLE LOCATION IN THE MECHANICAL ROOM FOR INCOMING COLD WATER LINE. 10. CONNECT 1-1/2"COLD WATER AND HOT WATER TO WATER HEATER. 11. PROVIDE TMV-1 TYPICAL FOR ALL LAV/SINKS,REFER TO DETAIL ON SHEET P4.0.1 �PLUMBING WATER&GAS PLAN O 12. CONNECT HOT AND COLD WATER TO THE WASHING MACHINE BULKHEAD, a SCALE:1/4'=1'-0' COORDINATE WITH THE GENERAL CONTRACTOR,BULKHEAD PROVIDED AND NORTH INSTALLED BY OTHERS. `.J "O b C� 3 o w a � a �T* '02' H SCALE: AS NOTED CITY APPROVED PLANS DATE: 08/10/2023 Reviewed for Code Compliance DRAWN BY., TSM PLANS MUST BE ON JOB SITE CHECKED BY: CRA FOR ALL INSPECTIONS SHEET P2.2 Page 15 of 26 GENERAL NOTES: 1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF ALL LOCAL PLUMBING CODES,REGULATIONS,AND ORDINANCE. ED o S 2. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF Z � THE WORK.LOCATION OF UNDERGROUND SANITARY SEWER,STORM SEWER, y WATER MAIN,GAS MAIN,ETC.IS APPROXIMATE AND THE BEST THAT COULD BE DETERMINED BY VISUAL OBSERVATION.CONTRACTOR SHALL VISIT THE SITE I W E a PRIOR TO HIS BIDDING IT,AND SHALL INVESTIGATE ALL CONDITIONS THAT W c" AFFECT HIS WORK,VERIFY LOCATIONS,SIZES,DIMENSIONS AND INVERT Z Cp ELEVATIONS OF ALL SEWER,GAS AND WATER PIPES AND MAKE CERTAIN THAT a, 1 ALL CONNECTIONS CAN BE MADE. I E3 c 1-1/2"fNG Z m 3 N (2PSI) 3. ALL SLOPE AND INVERT ELEVATIONS SHALL BE CHECKED BEFORE ANY PIPING W IS INSTALLED IN ORDER THAT PROPER SLOPES WILL BE MAINTAINED.NOTIFY ARCHITECT IF THERE ARE ANY PROBLEMS. E3 m 1-1/2"fNG 0 v RTU (2PSI) 4. IT SHALL BE NOTED THAT THE WORD"PROVIDE"MEANS FURNISH AND INSTALL 7 IN CLEAN OPERATING CONDITION.THE WORD"PIPING*INCLUDES,PIPE, CONNECT NEW FITTINGS,VALVES,CONTROLS AND EVERYTHING NECESSARY FOR COMPLETE 3/4•fNG NATURAL GAS (E)1•fNG 5 SYSTEM.ALL MATERIALS SHALL BE NEW. (2PSI) PIPE TO EXISTING (E)NG TO BE REVISED 8. DRAWINGS ARE DIAGRAMMATIC.DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,PIPING AND EQUIPMENT,EFC. EXISTING EXISTING 6. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID ROOFTOP UNIT ROOFTOP UNIT INTERFERENCES WITH THE PROGRESS OF CONSTRUCTION. 2 7. ALL EXCAVATION AND BACKFILL AS REQUIRED FOR PLUMBING WORK SHALL BE PART OF THIS CONTRACT. 2"fNG 8. PROVIDE ISOLATION VALVES ON ALL PLUMBING FIXTURES AND EQUIPMENT FOR (2PSI) SERVICE. 9. ALL DAMAGE,SAW CUTS&PENETRATIONS RESULTING FROM PLUMBING WORK MUST BE PATCHED OR REPAIRED TO MATCH EXISTING AND/OR NEW WORK. PATCHES AND REPAIRS TO WAILS AND FLOORS TO BE COMPLETED BY 1 GENERAL CONTRACTOR. 1"fNG 10. THE CONTRACTOR SHALL BE COGNIZANT THAT THIS IS A REMODELING PROJECT TONAL AND AS SUCH,ALL FACETS OF THE CONSTRUCTION CAN NOT BE SHOWN.A VISIT TO SITE IS REQUIRED OF ALL BIDDERS PRIOR TO SUBMISSION OF BID. O� 1BT-c0 ALL WILL BE HELD TO HAVE FAMILIARIZED THEMSELVES WITH ALL DISCERNIBLE 4 A CONDITIONS AND NO EXTRA PAYMENT WILL BE ALLOWED FOR WORK REQUIRED 8602 BECAUSE OF THESE CONDITIONS,WHETHER SPECIFICALLY MENTIONED OR NOT. LINES OF OTHER SERVICES THAT ARE DAMAGED AS A RESULT OF THIS WORK SHALL PROMPTLY BE REPAIRED AT NO EXPENSE TO THE OWNER TO COMPLETE SATISFACTION OF THE OWNER. 2"fNG (2PSI) OB/10/2023 KEYED NOTES: T. 2 1. NEW OPENING THROUGH THE EXISTING ROOF. ROOF PATCH TO BE BY THE ROOFING CONTRACTOR,COORDINATE WITH THE GENERAL CONTRACTOR. SEE P2.2 FOR CONTINUATION. 2. EXISTING NATURAL GAS PIPING TO BE REMOVED BACK TO THE GAS METER AND REPLACED WITH NEW SIZING SHOWN. (E)3/4"fNG 3. COORDINATE NEW GAS METER(ASSUMING EXISTING METER TO BE UPSIZED). TO BE REVISED 5 SIZED FOR 3,150 MBH 0 2PSI WITH INTERMOUNTAIN GAS COMPANY. EXISTING 4. NEW 2"fNG FROM NEW GAS METER ROUTED EXPOSED UP THE EXTERIOR WALL ROOFTOP UNIT f' 5. RECONNECT TO NEW MAIN GAS PIPE. 2"fNG �ll (2PSI) ^�I FBI O �. O rx � 4 5 � APPROXIMATE EXISTING ❑ GAS METER LOCATIONS z 2 Lam". vi z o w a � Po (4 '02' H SCALE: AS NOTED 1 PLUMBING ROOF GAS PLAN O DATE: 08/10/2023 SCALE 1/8"= 1'-0• NORTH CITY APPROVED PLANS DRAWN BY. TSM Reviewed for Code Compliance CHECKED BY: CRA PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS SHEET P2.3 Page 16 of 26 WATER CALCULATIONS(Based on 2017 Idaho Plumbing Code,Table A 103.1) WASTE CALCULATIONS(Based on 2017 Idaho Plumbing Code) CITY of TWIN FALLS GAS CALCULATIONS TF Laundromat TI CODE FIXTURE UNITS PER FIXTURE(COLD WATER) TF Laundromat TI CODE FIXTURE UNITS PER FIXTURE WATER CALC #OF MIN. PRIVATE PUBLIC ASSEMBLY TOTAL WASTE CALC #OF MIN. PRIVATE PUBLIC ASSEMBLY TOTAL FIXTURES FIXTURE FIXTURE FIXTURES TRAP& FIXTURE SEWER CAPACITY WORKSHEET Z o s DISTANCE TO MOST REMOTE OUTLET(FEET) 280 FT BRANCH UNITS TRAP UNITS o ro PIPE ARM a' �+ is SIZE SIZE NEW EXISTING W a, EQUIVALENT LENGTH ADJUSTMENT 1.25 E FIXTURE FIXTURE FIXTURE TYPE I#OF UN ITS FIXTURE TYPE 1#OF UNITS W c EQUIVALENT LENGTH(FEET) 350 FT LAVATORIES 1 LAVATORIES ? clothes washer,domestic 2"standpipe private 0.0 2" 2.0 0.0 644 ch Clothes Washer private 0.0 1/2" 2.0 0.0 WATER CLOSETS-flush valve 0 WATER CLOSETS-flush valve E3 m 3 EQUIPMENT BRANCH PIPE SIZE INPUT M public 26.0 2" 3.0 78.0 BH WATER CLOSETS-flush tank 1 WATER CLOSETS-flush tank Z •- 3 public 26.0 2.0 52.0 assembly 0.0 3.0 0.0 �+ 3 URINAL 0 URINAL W RTU-1 3/4" 110.0 MBH drinking fountain or water cooler public 0.0 1/2" 0.5 0.0 e drinking fountain or watercooler private 0.01-114" 0.5 0.0 WATER SOFTENER 0 WATER SOFTENER V m public 1.0 0.5 0.5 public 1.01-1/4" 0.5 0.5 HANDSINK 2 HANDSINK 13 U (E)RTU-2 -- 110.0 MBH assembly 0.0 0.75 0.0 assembly 0.01-1/4" 1.0 0.0 DISHWASHER 0 DISHWASHER E RTU-3 -- 110.0 MBH lavatory private 0.0112" 1.0 0.0 BAR SINK 0 BAR SINK O lavatory private 1.0 1-1/4" 1.0 0.0 public 1.0 1.0 1.0 public 1.0 1-1/4" 1.0 1.0 CLOTHES WASHER 26 CLOTHES WASHER (E)RTU-4 -- 110.0 MBH assembly 0.0 1.0 0.0 assembly 0.01-1/4" 1.0 0.0 KITCHEN SINK 0 KITCHEN SINK Sinks:laundry private 0.0 1/2" 1.5 0.0 SHOWER 0 SHOWER 20 DRYERS@94 MBH/EA 3/4"/EA 1,880.0 MBH sink,laundry(with or without discharge from a clothes private 0.01-112" 2.01 0.0 DRINKING FOUNTAIN-ICE 1 DRINKING FOUNTAIN public 1.0 1.5 L5 public 1.0 1-1/2" 2.0 2.0 MOP/SVCE-SK/TR DR 1 MOP/SVCE-SK/TR DR 6 DRYERS @ 71.7 MBH/EA 3/4"/EA 430.2 MBH Sinks:service or mop basin private 0.0 112" 1.5 0.0 assembly 0.0 1-112" 2.0 0.0 HOSE BIBB 0 HOSE BIBB public 1.0 3.0 3.0 sink,seNce or mop basin,2"trap arm public 1.0 2" 3.0 3.0 LAUNDRYSINK-WASHER 0 LAUNDRY SINK WH-1 3/4" 199.9 MBH ,,eater closet,1.6 gpf gravity tank private 0.0112" 2.5 0.0 assembly 0.0 2" 3.0 0.0 FLOOR DRAIN/SINKS 0 IFLOOR DRAIN/SINKS WH-2 3/4" 199.9 MBH public 1.0 2.5 2.5 SWIMMI NG POOL 0 ISWIMMING POOL water closet,1.6 gpfgravity tank private 0.0 3" 3.0 0.0 HOTTUB/WHIRLPOOL 0 HOTTUB/WHIRLPOOL assembly 0.0 3.5 0.0 public 1.0 3" 4.0 4.0 TOTALCONNECTED LOAD 3,150.0 MBH 'Bathroom groups based on Table C 303.1(1) TOTAL OTHER 0 OTHER assembly 0.0 3" 6.0 0.0 FIXTURE 60.5 GAS PRESSURE 2PSI UNITS TOTAL GPM 55 FIXTURE MAIN PIPE SIZE LEAVING METER 2" INCO LINE SIZMINGE EXITING 2„ UNITS 88.5 Note:Pipe sizes based on longest length method,per 20181FGC,table ,- tONAL 402.4(5). WASTE SIZE STREET PRESSURE 60 PSI 4•• LOSS THROUGH METER 5 PSI pQOA A LOSS THROUGH BACKFLOW 10 PSI PRESSURE AT BUILDING 45 Psi m 86 L ix C PRESSURE AFTER ANY REQUIRED BOOSTING 45 PSI FIXNEFT 5 2 PSI GAS WATER HEATER SCHEDULE PIPE LENGTH 150 L.F. 08/10/2023 FITTING LOSS 15 % ELECTRICAL PIPE LENGTH WITH FITTING LOSS 173 EQ.FT. EQUIPMENT MANUFACTURER& TYPE CAPACITY RECOVERY GAS INPUT THERMAL OPTIONS NOTES LOSS THROUGH WATER SOFTENER 0 PSI NO. MODEL (GAL) (GAL/HOUR) (MBH) EFFICIENCY yr ADDITIONAL LOSS 0 PSI VOLT/PH/HZ F REQUIRED PRESSURE FOR FARTHEST FIXTURE 20 PSI _ (20 psi Flushvalve,8 psi Brevity) - PROVIDE WITH FACTORY INSTALLED HEATTRAPS OR PLUMBING ___----- REMAINING PRESSURE 23 PSI CONTRACTOR SHALL PROVIDE.PLUMBING CONTRACTOR SHALL PROVIDE PSI 1100 FT 1.1 25 AOSMITH DIRECTVENTGAS WH-1&WH-2 BTH-199A WATER HEATER 100 235 199,900 97% 120/1/60 AMTROLTHERM-X-TROLST-12 EXPANSION TANK,SEISMIC STRAP,DRAIN 1-7 PAN,AND ANY ADDITIONAL ACCESSORIES OR ANCILLARY COMPONENTS PLUMBING FIXTURE SCHEDULE REQUIRED FOR A COMPLETE AND PROPER INSTALLATION. ALTERNATE MANUFACTURERS:APPROVED EQUALS ONLY NOTES: EQUIPMENT DESCRIPTION MANUFACTURER SIZE FEATURES&ACCESSORIES PIPING CONN ECTIONS 1.PROVIDE ALL HAND WASHING SINKS WITH ASSE COMPLIANT TEMPERING VALVE,WATTS LFUSG-B OR EQUAL. NO. TRAP WASTE VENT C.W. H.W. 2.PROVIDE WITH 3YEAR LIMITED WARRANTY,BRASS DRAIN VALVE. 3.PROVIDE AND INSTALL SEISMIC RESTRAINTS PER I PC 502.4 AND CHAPTER 16 OF IBC. BARRIER FREE SINGLE ELECTRIC WATER COOLER,HIGH POLISHED STAINLESS STEEL 4 WATER HEATER TO BE EQUIPPED WITH FACTORY HEATTRAPS.INSULATE PIPING PER CODE. DRINKING FOUNTAIN WITH BUBBLER HEAD,PUSH BUTTON ACTIVATION,WASTE 5.SET WATER HEATERTO OPERATE AT 140 F. EWC-1 ELECTRIC WATER COOLER ELKAY EZ8S __ 1-1/4" 1-1/2" 1-1/2" 1/2" STRAINER,MATCHING BACK PANEL,ACCESS PANEL,VANDAL RESISTANT BOTTOM 6.RECOVERY CALCULATED AT 100 F TEMPERATURE RISE. (ADA) PLATES,AND COMPLETE MOUNTING SYSTEM.115/1/60,4.0 FLA,370 RATED TPROVIDE VENTING UP THROUGH THE ROOF FOR DIRECT VENTED IN LET/OUTLET PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.COORDINATELOCATION OF VENT INTAKE/OUTLET WITH OWNER. WATTS.DELIVERS 8.0 GAL CHILLED WATER PER HOUR.MOUNT PER ADA REQUIREMENT. r NOTE:WATER HEATER SIZING PROVIDED BY LAUNDRY EQUIPMENT SUPPLIER.VERIFY FINAL SIZE WITH THE LAUNDRY EQUIPMENT SUPPLIER PRIOR TO ODERING THE WATER HEATERS. FCO-1 FLOOR CLEANOUT(FINISHED FLOOR) JAYSERIES ROUND,MEDIUM DUTY FINISHED FLOOR CLEANOUT.PROVIDE WITH ROUND SER IES 4020S (SEE PLANS)R.SMITH LINE SIZE ADJUSTABLE NICKEL BRONZETOP,GASKETSEALAND TAPERED ABS PLUG.2" MINIMUM. ACID RESISTANT COATED CAST IRON,12"SQUARE,10"DEEP FLOOR SINK. FS-1 FLOOR SINK JAY R.SMITH 3440Y--C-P-12 12"x12"x10"DEEP 3" 3" 2" -- PROVIDE WITH A.R.COATED CAST IRON STRAINER,NO-HUB OUTLET,AND HALF GRATE COVER. GCO-1 GRADE CLEANOUT JAY RSMITH 4220S LINE SIZE(SEE PLANS) -- -- -- -- __ CAST IRON TAP,ABS PLUG WITH GASKETSEAL.SIZETO MATCH WASTE PIPING. VITREOUS CHINA,WALL MOUNT;0.5 GPM VANDAL RESISTANT AERATOR. PROVIDE WITH K-8999TRAP AND K-7131-A OFFSETGRID DRAIN ASSEMBLY FOR LAVATORY KOHLER K-2005 1- 1/4 WHEELCHAIR.PROVIDE WITH ANGLE STOP AND WATTS LFMMV THERMOSTATIC L-1 (WALL HUNG,ADA COMPLIANT) W/MOEN L4621 FAUCET 21"x18" 1-1/2" x 1-1/2" 1/T' 1/2" MIXING VALVE.SET MIXING VALVE TEMPERATURE PERTHE CURRENTADOPTED 1-1/2" VERSION OF THE ADA STANDARDS,PLUMBING CODE,AND LOCAL AHJ.PROVIDE ADA INSULATION KIT. 20 GAUGE STAINLESS STEEL;PUNCHED TO ACCOMMODATE FAUCET.1/2"x3/8" SINK EUKAY-CELEBRITY BCR15 WITH ANGLE STOP WITH OVAL HANDLE AND FLEXIBLE RISER:17 GAUGE TRAP.ELKAY LK- HS-1 (SINGLE COMPARTMENT, FAUCET,1 SELF RIM AMERTA5 GPM FAUCET 6409 15"x15"x6" 1-112" 2' 1-1/2" 1/2" 1/2" 58 DRAIN(REAR PUNCH);17GA.CONTINUOUS DRAIN ASSEMBLY.PROVIDE ER rT, FAUCET WITH WRIST BLADE HANDLES.PROVIDE WITH WITH WALL CLEANOUT Wj (WCO-1).PROVIDE WITH MIXING VALVE. MOLDED STONE;FLOOR MOUNTED,SQUARE,INTEGRAL DRAIN.STOPS IN SHANK. SS-1 SERVICFLOORMOUESINK- FIAT-SINK W/FIAT8 MSB_FAUCET 24"x24"x12 3" 3" 1-1/2" 1/2" 1/2" CAST IRON TRAP.832-AA HOSE AND WALL HOOK,889-CC STAINLESS STEEL MOP 2424 HANGER AND MSG-2424 STAINLESS STEEL SPLASH PANELS.PROVIDE WITH WALL W�•�•I CLEAN OUT(WCO-1). F•�•I BACKFLOW PREVENTOR REDUCED PROVIDE WITH 1/4"TURN BALL VALVE AND STRAINER,PROVIDE RRBP-1 PRESSURE WATTS LF009-QT-5 LINE SIZE -- -- -- LINE SIZE -- MANUFACTURER'S AIR GAP FITTING AS REQUIRED. THERMOSTATIC MIXING VAVES.PROVIDE WITH INTERGRAL CHECKS,BRASS AND STAINLESS STEEL INTERNAL COMPONENTS,DUAL STAIN LESS STEEL STRAINERS, TMV-1 THERMOSTATIC MIXING VALVE SYMMONS 7-225-CK --- -- -- -- 1/2" 1/2" PROVIDE WITH MIN.20 PSI,MAX 150 PSI.MOUNTAND SECURE IN ACCESSIBLE 3 LOCATION. KOHLER K-3999 VITREOUS CHINA;FLOOR MOUNTED.PROVIDE WITH VITREOUS CHINA TANK AND � WC-1 WATER CLOSET SEAT C 3" 2" 1/2"ELONGATED BOWL, TANK COVER,POLISHED CHROME TRIP LEVER,BOLT CAPS,CLOSET SWEEP,SEAT SUPPLY K-76 W SUPPLY -- -- (GRAVITYTANKTYPE,ADACOMPLIANT) 16.5"RIM FLANGE AND GASKET,WHITE OPEN FRONT SEAT WITHOUT COVER,AND OVAL � O r •3 HANDLE AND FLEXIBLE RISERS.MOUNT PER ADA;TRIP LEVER ON WIDE SIDE. a w O'o E� WCO-1 WALL CLEAN OUT JAY R.SMITH 4472 UNESIZE -- __ -- TAPERED BRONZE PLUG AND STAINLESS STEEL COVER.SIZE TO MATCH WASTE (SEE PLANS) LINE SIZE PIPING,2"MINIUM. SCALE: AS NOTED GENERALSCHEDULE NOTES EQUIVALENT MANUFACTURERS 1.FIXTURES INDICATED ASADA MUSTCOMPLYWITH ICC/ANSI A117.1.VERIFY EXACT NUMBERS,FIXTURE DESIGNATIONS,LOCATIONS, ENAMELED CAST IRON,VITREOUS CHINA,ACRYLIC:KOHLER,AMERICAN STANDARD,EUER,CRANE ZURN WARE, DATE: 08/10/2023 CLEARANCES,AND MOUNTING HEIGHTS WITH ARCHITECTURAL PLANS. BEST BATH,LASED,AQUAGLASS CITY APPROVED PLANS DRAWN BY., 2.ALL HW PIPING AND DRAIN LINES BENEATH ADA COMPLIANT LAVATORIES MUST BE INSULATED TO PREVENT BURNS.REF. STAINLESS STEEL SINKS:ELKAY,JUST,DAYTON,KOHLER TSN ARCHITECTURAL PLANS.INSULATE WITH MOLDED CLOSED CELLVINYL INSULATION-TRUEBRO OR EQUAL. SERVICE SINKS:FIAT,BRADLEY,ACORN,STERN&WILLIAMS,E.L.MUSTEE Reviewed for Code Compliance CHECKED BY: 3.PROVIDE TRAP PRIMERS FORALL FLOOR DRAINS(PPP INC.,OR EQUAL).PROVIDE ACCESS PANELS AS REQUIRED. FAUCETS:DELTA HDF,ELKAY,JUST,KOHLER,ZURN,AMERICAN STANDARD PLANS MUST BE ON JOB SITE CRA 4.ALLACCESS PANELS AND WALL BOXES SHALL BE RATED TO MATCH ASSEMBLY RATING. SHOWER VALVES,MIXING VALVES:POWERS,LEONARD,SYMMONS,MOEN TOILETSEATS:CHURCH,OSLONITE,BEMIS,SMITH FOR ALL INSPECTIONS ROOF DRAINS,FLOOR SINKS,FLOOR DRAINS AND TRAPS:WATTS,ZURN,WADE,JOSAM WATTS I I SHEET BACKFLOW PREVENTION DEVICES,PRESSURE REDUCING VALVES:WILKENS,FEBCO,APOLLO/CON BRA CO TRAP PRIMERS AND SHOCK ABSORBERS:PPP,SIOUX CHIEF,SMITH P3•O Page 17 of 26 S 7- J I ED Ir W W � 2 Z a 3 , , e.aso;a, Il Z- ®Q® a;a�a: Z 3 aea W=" 6 3 asoa�a $ aea L1 m 2 6 3 COMPONENTS: COMPONENTS: 1 1. CLIP CEILING 2 1. DROP-IN ANCHOR COMPONENTS: 2 ( 2.SPRING CLIP 1. EYE ROD 4 = FLANGE) CEILING PLATE 1 2.FLAT WASHER - 7'HANGER ENTS: 2.HEX NUT 3.HEX HEAD CAP (OPTIONAL) AMP � 3.WOOD SCREW 3.HANGER ROD SCREW SCREW 4 4.HANGER ROD 4 ADJUSTABLE 4.ADJUSTABLE 5 IN 5.ADJUSTABLE HANGER RING HANGER RING ROD HANGER RING 3 5.DROP-IN ANCHOR STABLE 6.HEX HEAD LAG ER RINGL BEAM 5 4 47.EXPANSION CASE AR JOIST 8.LOCK WASHER 9.HEX NUT STANDARD C-CLAMP PIPE HANGER CLIP PIPE HANGER CONCRETE PIPE HANGER FINISHED FLOOR FINISHED BRASS CLEANOUT PLUG 12°02°0-1/2°THICK - to 4F: ODjOC%RETE,BLOCK, 1ON12"z3-1/2"THICK GRADE HE COUNTER SUNK SMOOTH PAD TROWEL CON..PAD TROWEL _ $ EL(OPTIONAL) 2 �YONAL HEAD.(TYPICAL) SMOOTH AND EDGE. SMOOTH AND EDGE. 5 2 3 ,'AI 1STi (TYPICAL) hYPICAL) 1/8 BEND 6 L11Il L�11I L�11I _I III I_I III L1I II I�H 1 8 A=1111 T III P III a 602 -III=11I =III-1 WASTE LINE, FLOOR CLEANOUT 2 1 c III- I III I-1 I I III III III III III III III III III III III III III I III-11I-I I- LENGTH TO ___, COMPoNENrs: -' 1. POWDER-DRIVEN COMPONENTS: SEAR.(TYPICAL) _ STUD1. WALL BRACKETCOMPONENTS: 2.HEX NUT FOR WOOD FOR BRICKWASTE LINE, MAY EXTEND AS 1 1. HEX NUT 2 2.ROD COUPLINGOD 3.LOCK WASHER 2 5 2 08/10/2023 LENGTH TO SUIT. CHROME WALL WASTE OR VENT. 2.LOCK WASHER 4. � � 4.FIAT WASHER 3 3 (TYPICAL) COVER AND _ 3.HANGER ROD _ HANGER RING LE 5.TRANSITION RODg1/8 BEND SCREW� 4.ADJUSTABLE 6.RODCOUPLING 45'"WYE" 45'"WYE° PLUGGED TEE 3 HANGER RING 3 7.HANGER ROD11/8 BEND SANITARY 1/8 BEND SANITARI' W/CLEANOUT. ¢ 5.STEEL BEAM 8.ADJUSTABLE 1 1 FFITTING FITTING FINISHED FLOOROR BAR JOIST HANG R RING8FOR CONCRETEFOR STEELWASTE LINE 1/8 BEND DOUBLE GRADE CLEANOUT GRADE CLEANOUT WALL CLEANOUT BEAM PIPE HANGER STUD TYPE PIPE HANGER WALL BRACKET PIPE HANGER EYE ROD PIPE HANGER 2 CLEANOUT DETAILS 1 PIPE HANGER DETAIL SCALE:NTS SCALE:NTS (TYP.) 3°MINIMUM(FOR FROST CLOSURE) SHUT-OFF VALVE PVC INTAKE/EXHAUST 2°WIDE 24 GAUGE G.I.SEISMIC 18" MIN. IPS WATERTIGHT ROOF COLD WATER SUPPLY N ANCHOR. LOCATE WITHIN THE DSCHARGE SUPPLY FROM GAS FLASHING COLLAR;OR EQUAL UPPER AND LOWER ONE-THIRD OF PIPING TO FIXTURES SUPPLY SEAL ALL EDGES OF FLASHING THERMAL ITS VERTICAL DIMENSION,THE r`G COLLAR W/ROOF CAULK EXPANSION TANK LOWER STRAP LOCATED TO BALL VALVE 1 I I ROOF ki MAINTAIN A MINIMUM DISTANCE OF ( I ) _ GAS COCK I 1 I HOT WATER OURET - 4 INCHES ABOVE THE CONTROLS. E TO 1-1/2" TEMPERATURE& BFRAMING WITH MN.1/4z3OLT TO STRUCTURE� R LAG (TYPICAL) MANUAL SHUT-OFF VALVE WITH AN 1/8"N.P.T.PLUGGED TAPPING PRESSURE RELIEF VALVE L. SCREWS.(lYP) ACCESSIBLE FOR TEST GAGE WATER CONNECTION TO BE INSTALLED 12" FULL SIZE COPPER PIPE HEATER GAS SUPPLY PIPE INLET STRAINER W/ UPSTREAM OF THE GAS SUPPLY TO FLOOR DRAIN/SINK BLOW-DOWN VALVE GROUND JOINT CONNECTION TO THE APPLIANCE REDUCED PRESSURE TYPE UNION GAS COCK CITY APPROVED PLANS BACKFLOW PREVENTER, -" INCREASER FITTING AS m REQUIRED FOR FROST -UNION Reviewed for Code Compliance FIXED AIR GAP FITTING REQUIRED CLOSURE Ef WITH DRAIN TO FLOOR SINK ¢ 1°DRAIN PAN DRAIN TO DRIP LEG PLANS MUST BE ON JOB SITE INCOMING COLD WATER SIZE-AS PER DRAWING FLOOR DRAIN/SINK. 6"TRAP PROVIDE WHEN WATER FOR ALL INSPECTIONS FLEXIBLE STEEL HEATER IS NOT LOCATED CONNECTION TO (DRIP LEG) ON SUB ON GRADE. DRAIN VALVE /u EQUIPMENT/ 24°0 x 4°DEEP DRAIN PAN CONTROLS FLAT ROOF 6 REDUCED PRESSURE BACKFLOW PREVENTER 5 GAS CONNECTION DETAIL 4 PVC-VENT THROUGH ROOF 3 CLOSED COMBUSTION GAS W/H DETAIL SCALE:NTS SCALE:NTS SCALE:NTS SCALE:NTS FROM GAS SUPPLY O GAS PRESSURE REGULATOR MAXIROL 325L OR EQUAL NEW SHUT-OFF VALVE WITH AN �c FAUCETS`o �I EQUIP WITH APPROVED VENT LIMITING DEVICE WHEN INDOORS 1/8°N.P.T.PLUGGED TAPPING I W^ IF SIZING ALLOWS,OTHERWISE VENT TO THE OUTSIDE. INSTALL ACCESSIBLE FOR TEST GAGE WEATHER PROOF CAP WHEN OUTDOORS. SIZE REGULATOR PER CONNECTION TO BE INSTALLED INSULATE HOT WATER REQUIRED PRESSURE AND PER EACH UNIT OR SPECIFIC UPSTREAM OF THE GAS SUPPLY SUPPLY AND P-TRAP LAVATORY/SINK REGULATOR AS SHOWN ON THE GAS PIPING PLAN. INSTALL TO THE REGULATOR. PER ADA REQUIREMENT. l PER MANUFACTURER'S REQUIREMENTS. GROUND JOINT GAS COCK COCK HOT WATER SUPPLY FMM�-1 43 �) GAS TO FAUCET UNION (-I w (TYPICAL) TMV-1 COLD WATER SUPPLY THERMOSTATIC MIXING VALVE TO FAUCET WATTS MODEL No.LFUSG-B r (TEMPERATURE SET AT 105'F) a a ESCUTCHEON PLATE COLD WATER SUPPLY w FLEXIBLE STEEL SEDIMENT TRAP ON WALL(TYPICAL) SHUT-OFF VALVE SCALE: CONNECTION TO UNION EQUIPMENT HOT ATER AS NOTED NEW MANUAL SHUT-OFF VALVE WITH AN 1/8" SHUT-OFF VALVE DRAIN• DRAIN P-TRAP DATE: N.P.T.PLUGGED TAPPING ACCESSIBLE FOR 08/10/2023 TEST GAGE CONNECTION TO BE INSTALLED DRAWN BY., UPSTREAM OF THE GAS TSM TO THE APPLIANCE. SUPPLY CONNECTION THERMOSTATIC MIXING VALVE(7MV-1) CHECKED BY 8 GAS CONNECTION DETAIL 7 INSTALLATION UNDER LAVATORY DETAIL GRA SCALE:NTS SCALE:ITS SHEET P4.0 Page 18 of 26 ELECTRICAL LEGEND (LEGEND IS GENERAL IN NATURE.NOT ALL OF THE SYMBOLS SHOWN ARE USED IN THIS PROJECT.) MOUNTING HEIGHTS DETAIL ABBREVIATIONS & DESCRIPTIONS EWER LIGHTING(SEE LUMINAIRE SCHEDULE FOR EXACT REQUIREMENTS) CIRCUITINGSYMBOLS FIREALARM A AMPERES KW KILOWATT C7 0 AC ABOVE COUNTER;REFER TO ARCHITECTURAL ELEVATIONS KWH KILOWATT HOUR m DUPLEX AFCI OUTLET. +18"AFF LINO. ® FOR REQUIRED HEIGHT. M MAGNETIC CONTACTOR COIL Z o SINGLE FACE EXIT SIGN.CEILING MOUNTED. CONDUIT STUBBED,CAPPED,AND 4 PULLSTATION.+48'AFT. AFF ABOVE FINISHED FLOOR MB MAIN BREAKER O: y DUPLEX AFCI OUTLET. ABOVE COUNTER. MARKED WITH PULL CORD. AFG ABOVE FINISHED GRADE MCC MOTOR CONTROL CENTER W DOUBLE FACE EXIT SIGN.CEIUNG MOUNTED. W E SIMPLEX OUTLET.+18°AFF LINO. CONDUIT UP. �F] FIRE ALARM HORN.+80"AFF LINO. AF AMPERE FRAME MLO MAIN LUGS ONLY AFCI ARC FAULT CIRCUIT INTERRUPT MS MOTOR STARTER Z o DUPLEX OUTLET.+18"AFF UNO. SINGLE FACE EXIT SIGN.WALL MOUNTED. CONDUIT DOWN. �..L{15 FIRE ALARM STROBE.+80"AFF TO BOTTOM OF AHF ACTIVE HARMONIC FILTER MFFS MANUAL TRANSFER SWITCH DUPLEX OUTLET.MOUNTED ABOVE COUNTER UNO. HOMERUN.PANEL AND CIRCUIT AS l DEVICE,UNO.STROBE INTENSITY INDICATED. AHJ AUTHORITY HAVING JURISDICTION MH MANHOLE I E)c Y: g DOUBLE FACE EXIT SIGN.WALL MOUNTED. INDICATED. AT AMP TRIP MW MICROWAVE m 3 DUPLEX OUTLET.+18"AFF LINO WITH GROUND lB/15 FIRE ALARM HORN/STROBE.+80"AFF TO BOTTOM ATS AUTOMATIC TRANSFER SWITCH N NEUTRAL W FAULT INTERRUPTION PROTECTION. SINGLE FACE COMBO EXIT SIGN/EMERGENCY CIRCUIT CONCEALED IN CEILING OR y� OF DEVICE,UNO.STROBE INTENSITY INDICATED. AWG AMERICAN WIRE GAUGE NC NORMALLY CLOSED DUPLEX OUTLET.MOUNTED ABOVE COUNTER UNO LUMINAIRE.WALL MOUNTED. WALL 3/4"-2#12,1#12G UNO. BW BLANKET WARMER NCL NON CRITICAL LOAD (]m WITH GROUND FAULT INTERRUPTION PROTECTION. C CONDUIT NEC NATIONAL ELECTRICAL CODE SWITCHED DUPLEX OUTLET.+18"AFF UNO. y ARROW INDICATES DIRECTION TO BE SHOWN ON --- CIRCUIT CONCEALED IN FLOOR OR FIRE ALARM BELL+80"AFF UNO. CB CIRCUIT BREAKER NIC NOT IN CONTRACT 0 v SIGN. UNDERGROUND.3/4"-2#12,1#12G � CC CRASH CART NO NORMALLY OPEN a CHARGING OUTLETS. INTEGRATED AFF UNO. m LIGHT FIXTURE. UNO. L`[ JF DUAL FIRE ALARM HORN.+80"AFF UNO. wk CKT CRITICAL L LOAD OL NOTOVE TO SCALE DUPLEX ISOLATED GROUND OUTLET.+18"AFF UNO. GROUNDING -015 FIRE ALARM STROBE.CEILING MOUNTED. "i-l"'i-1 CM CEILING MOUNTED OS OCCUPANCY SENSOR LIGHT FIXTURE. CONDUCTOR tr\ STROBE INTENSITY INDICATED. CO CONDUIT ONLY,PROVIDE PULL-LINE OFCI OWNER FURNISHED CONTRACTOR INSTALLED DUPLEX ISOLATED GROUND OUTLET.MOUNTED SIZE D MECHANICAL DUCT-MOUNTED DEVICE P PHOTO LIGHT FIXT ABOVE COUNTER LINO. X"-XXURE. ,XXG 15 FIRE ALARM HORN STROBE.CEIUNG MOUNTED. DC DIRECT CURRENT PC PHOTOCELL DUPLEX 20A OUTLET.+18"AFF LINO. � F STROBE INTENSITY INDICATED. DET DETAIL PVC POLYVINYL CHLORIDE RACEWAY SIZE� CONDUCTOR SIZE E EMERGENCY/CRITICAL CARE RCPT RECEPTACLE DUPLEX 20A OUTLET.MOUNTED ABOVE COUNTER UNO. ® EMERGENCY LIGHT FIXTURE. FIRE ALARM CHIME/STROBE.+80"AFF TO BOTTOM F CONDUCTOR QUANTITY C OF DEVICE,UNO.STROBE INTENSITY INDICATED. PANEL ®IO EF EXISTING (R) RELOCATED EXHAUST FAN REPLACED SINGLE 20A OUTLET.+18"AFF UNO. o SUSPENDED LIGHT FIXTURE. }�F. FIRE ALARM CHIME/STROBE.CEILING MOUNTED. 90" EL EMERGENCY LIGHT REF REF REFRIGERATOR FOURPLIX OUTLET.+18°AFF LINO. J-i-t' STROBE INTENSITY INDICATED. N S/I[] EWC ELECTRIC WATER COOLER SER REDUCED VOLTAGE SOFT START � WALL MOUNTED FIXTURE. ONE LINE 78` FWH ELECTRIC WATER HEATER SER SERVICE ENTRANCE RATED FOURPLEX OUTLET.MOUNTED ABOVE COUNTER UNO. SD SMOKE DETECTOR.CEIUNG MOUNTED LINO. F FUSE SPST SINGLE POLE SINGLE THROW Q WALL SCONCE FIXTURE. HD HEAT DETECTOR.CEILING MOUNTED LINO. FACP FIRE ALARM CONTROL PANEL TC TIME CLOCK LXtANDH G/G FULL VOLTAGE NON-REVERSING TDB TIME DELAY RELAY FOURPLEX ISOLATED GROUND OUTLET.+18"AFF UNO. WALL PACK FIXTURE. 46"Pip BRANCH PANEL. Sp ADDRESSABLE SMOKE DETECTOR.CEILING 56o GFI GROUND TSB TERMINAL JUNCTION BOX FOURPLIX ISOLATED GROUND OUTLET.MOUNTED 4 MOUNTED LINO. GFl GROUND FAULT INTERRUPTION 7SP TWISTED SHIELDED PAIR ABOVE COUNTER UNO. I®0# 14 GFP GROUND FAULT PROTECTION TFB TELEPHONE TERMINAL BOARD UNDERCABINET MOUNTED FIXTURE. ADDRESSABLE HEAT DETECTOR.CEIUNG FOURPLEX CONVENIENCE OUTLET,+187AFF UNO. HD MOUNTED UNO. H HEAT TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER (1)RECEPTACLE IS TO BE CONTROLLED BY A LOCAL I vw• TRACKLIGHT. 18" HH HHID IGH INTENSITY UH UNIT TYPICAL AL OCCUPANCY SENSOR.THE CONTROLLED RECEPTACLE SD HVAC DUCT SMOKE DEFECTOR. FINISH FLOOR HOA HAND TOFF AUTTODISCHARGE UNO UNLESSEXNOTED OTHERWISE F�TERc'S\ NS SHALL BE GRAY IN COLOR.THE OTHER RECEPTACLE O PENDANT LIGHT FIXTURE. A CIRCUIT BREAKER.SIZE AND TYPE AS HP HOUSE PHONE UPS UNINFERRUPTIBLE POWER SUPPLY SHALL BE UNCONTROLLED(UNSWITCHED)AND WHITE O SPECIFIED, EOL END OF LINE RESISTOR. c m IN COLOR. WAC HEATING,VENTILATING,k AIR CONDITIONING V VOLT :0 ROUND DECORATIVE LIGHT FIXTURE.SURFACE I IONIZATION VA VOLT AMPERE A G CIRCUIT BREAKER.FRAME SIZE A Q FLOW SWITCH. SPECIAL PURPOSE OUTLET.VERIFY SIZE AND TYPE MOUNT 30AF (� ID IN-DUCT VARIABLE FREQUENCY DRIVE o WITH EQUIPMENT SUPPLIER. �30AT AND TRIP PLUG/RATING(AT),3 POLE, Q TAMPER SWITCH. IC INTERRUPTING CAPACITY WG WG PROVIDE PROTECTIVE WIRE GUARD O RECESSED UGHT FIXTURE. I UNO. IG ISOLATED GROUND WP WEATHER PROOF/NEMA 3R `9T F F ® CONNECTION POINT TO EQUIPMENT SPECIFIED, ® PRESSURE SWITCH. INT INTERCOM XFMR TRANSFORMER 641V A FURNISHED AND INSTALLED UNDER OTHER SECTIONS. RECESSED WALL WASH LIGHT FIXTURE. 15A FUSE.SIZE AND TYPE AS SPECIFIED, J/JB JUNCTION BOX OB/09/2023 ELECTRICAL CONTRACTOR FINAL SUPPLY RACEWAY, PROVIDE FUSE FOR EACH POLE,3 EQUIPMENT UNDER THIS SECTION,LINO. PN POST INDICATOR VALVE. �+CONDUCTORS AND MAKE FINAL CONNECTION TO PORCELAIN LAMP HOLDER. POLE,UNO. DH ELECTROMAGNETIC DOOR HOLDER. SHEET INDEX DUPLEX OUTLET.FLUSH,FLOOR MOUNTED. WALL MOUNTED PORCELAIN LAMP HOLDER. l 30A INTERRUPTER SWITCH.SIZE AS DM FIRE/SMOKE DAMPER. E0.0 ELECTRICAL COVER SHEET E4.0 ELECTRICAL DETAILS ILT ® INDICATED,3 POLE,UNO. LED INDICATOR LIGHT. EO.1 ELECTRICAL SPECIFICATIONS F DUPLEX SWITCHED OUTLET.FLUSH,FLOOR MOUNTED. .-0 POLE UGHT 1 HEAD ROUND WITH POLE. F� EO.2 ENERGY COMPLIANCE FORMS ® OF LED INDICATOR LIGHT WITH TEST SWITCH. E2.1L UGHTING PLAN DUPLEX ISOLATED GROUND OUTLET.FLUSH,FLOOR 0-0 POLE LIGHT 2 HEAD ROUND WITH POLE. 1 T E2.1P POWER PLAN ® MOUNTED. / FUSED SWITCH.SWITCH SIZE(AS)Q E2.2 ELECTRICAL ROOF PLAN FOURPLEX OUTLET.FLUSH,FLOOR MOUNTED. ►❑ POLE LIGHT 1 HEAD SQUARE WITH POLE. FUSE SIZE(AF)AS INDICATED,3 POLE, E3.0 ELECTRICAL SCHEDULES 30AF UNO. f SPECIAL PURPOSE OUTLET.FLUSH,FLOOR MOUNTED. 0 POLE LIGHT 2 HEAD SQUARE WITH POLE. GENERAL ELECTRICAL NOTES WIREMOLD OUTLET. 0 BOLLARD LIGHT. (RE:ALL ELECTRICAL SHEETS) DRAW OUT CIRCUIT BREAKER FRAME M MOTOR CONNECTION.RE:MECHANCIAL EQUIPMENT (AF)SIZE AND TRIP PLUG RATING(AT), 1. ALL ELECTRICAL EQUIPMENT AND SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 18. FIELD VERIFY EXISTING CIRCUITING AND MAKE ADJUSTMENTS AS NECESSARY TO THE CIRCUFNNG f�Qf SCHEDULE 3 POLE,UNO. NATIONAL ELECTRICAL CODE,INTERNATIONAL FIRE CODE,AND ALL OTHER STATE AND LOCAL SHOWN ON THE PLANS,AS REQUIRED BY FIELD CONDITIONS. POWERPOLE-DUAL CHANNEL. ® DECORATIVE POST-TOP LIGHT. CODES. CONTRACTOR SHALL IMMEDIATELY NOTIFY ENGINEER IN WRITING IF PORTIONS OF THE DESIGN SET OR FIELD CONDITIONS DO NOT MEET REQUIRED CODES. 19. COORDINATE NEMA CONNECTION TYPE REQUIREMENTS WITH MANUFACTURER PRIOR TO ROUGH IN PAD MOUNT TRANSFORMER. '-Q SPOT/FLOOD LIGHT. INDIVIDUAL BREAKER FRAME(AF)SIZE ON EQUIPMENT. AND TRIP PLUG RATING(AT),NEMA 1 2. FIRE ALARM SYSTEM IS DESIGN BUILD BY ELECTRICAL CONTRACTOR AND SHALL BE INSTALLED IN EMERGENCY EGRESS LIGHT.WALL MOUNTED. UNO,3 POLE UNO. ACCORDANCE WITH NFPA 72 AND ALL OTHER STATE AND LOCAL CODES.PROVIDE AND INSTALL 20. PROVIDE AND INSTALL TAMPER RESISTANT RECEPTACLES IN LAUNDROMAT AREA UNLESS NOTED ON COMMUNICATIONS1�d CONDUIT AND CONDUCTORS FOR ALL FIRE ALARM DEVICES REQUIRED BY LOCAL AUTHORITY PLANS. TAMPER RESISTANT RECEPTACLES SHALL BE INSTALLED AS PER CURRENT NEC 0/P D<d0 EMERGENCY EGRESS LIGHT.CEIUNG MOUNTED. HAVING JURISDICTION,INCLUDING BUT NOT LIMITED TO HVAC SHUTDOWN,FIRE ALARM CONTROL REQUIREMENTS. Y TELEPHONE/DATA OUTLET,+18"AFF LINO, OM METER. PANEL,INITIATING AND ANNUNCIATING CIRCUITS.FIELD INSPECTION IS REQUIRED TO VERIFY THIS FOUR-SQUARE DEEP TYPE BOX WITH SINGLE GANG PP20 POWER PACK INFORMATION PRIOR TO BID. MUDRING. PROVIDE 1"CONDUIT TO ABOVE O AMMETER. 3. EMERGENCY UGHTING SYMBOLS ARE SHADED ON THE UGHTING PLANS.EMERGENCY SOURCE ACCESSIBLE CEIUNG UNO. PROVIDE AND INSTALL SHALL BE BATTERY BACKED BALLAST WITH MINIMUM 1400 LUMEN OUTPUT FOR A 90 MINUTE QUANTITY OF DATA(D)AND PHONE CABLES(P) PERIOD,UNLESS NOTED OTHERWISE.PROVIDE UNSWITCHED CONDUCTORS FOR CHARGING CIRCUIT INDICATED TO TERMINATE IN PATCH PANEL AND TEST. SWITCHES O VOLTMETER. AS REQUIRED. QK DATA OUTLET,+1 LINO,FOUR-SQUARE DEEP a 4. DESIGN OF ELECTRICAL REQUIREMENTS,FOR MECHANICAL EQUIPMENT,IS BASED ON MECHANICAL TYPE BOX WITH SINGLE GLELE KIRK KEY LOCK. GANG MUDRING. PROVIDE S/ SWITCH.TYPE INDICATED.+46"AFT,UNO. EQUIPMENT SPECIFIED.MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL 1"CONDUIT TO ABOVE ACCESSIBLE CEIUNG UNO. 2 DOUBLELE POLE GFP GROUND FAULT PROTECTION.3 3-WAY CONTRACTOR IF EQUIPMENT PURCHASED IS DIFFERENT FROM THAT SPECIFIED STILL MEETS PROVIDE AND INSTALL QUANTITY OF DATA(D) 4 4-WAY SPD SURGE PROTECTION DEVICE. DESIGN INTENT,INCLUDING BUT NOT LIMITED TO OVERCURRENT PROTECTION,LOCAL INDICATED TO TERMINATE IN PATCH PANEL AND D DIMMER DISCONNECTING MEANS,WIRE SIZING AND DESIGN COSTS. TEST. HP HORSEPOWER RATED ED ARC FLASH MITIGATION. $ DATA OUTLET,FOUR-SQUARE DEEP TYPE BOX WITH K KEYED 5. SCALE IS FOR 24°x36"SHEETS. WHEN PRINTED 11"z17°DRAWINGS ARE NOT TO SCALE. SINGLE GANG MUDRING.LOCATED ABOVE COUNTER LV LOW VOLTAGE FTI VARIABLE FREQUENCY DRIVE.UNO. M MOMENTARY CONTACT 6. ALL EMERGENCY EXIT LIGHTING IS TO BE POWERED VIA NON-SWITCHED LEG OF LIGHTING MM MANUAL MOTOR STARTER TVSS TRANSIENT VOLTAGE SURGE SUPRESION. CIRCUIT. TELEPHONE OUTLET.FLUSH,FLOOR MOUNTED. OS OCCUPANCY SENSOR P PILOT LIGHT F-__1 SHUNT TRIP COIL. 7. REFER TO SHEET E3.0 FOR LUMINAIRE SCHEDULE. 0 TELEPHONE/DATA OUTLET.FLUSH,FLOOR MOUNTED. T TIMER rT, p❑ DATA OUTLET.FLUSH,FLOOR MOUNTED. TO THERMAL OVERLOAD KWH KILOWATT HOUR METER. 8. FIELD VERIFY EXISTING CIRCUITING AND MAKE ADJUSTMENTS AS NECESSARY TO THE CIRCUITING F+i V VOLUME CONTROL SHOWN ON THE PLANS,AS REQUIRED BY FIELD CONDITIONS. W �A TELEVISION OUTLET,SINGLE-GANG BOX WITH MUDRING. VS VACANCY SENSOR KILOVAR DEMAND METER.T a SUPERSCRIPT INDICATES LIGHTS TO BE 9. CONTRACTOR SHALL COORDINATE ELECTRICAL SYSTEMS INSTALLATION TO AVOID INTERFERENCE �y Y +18"AFF UNO. WITH DUCTWORK/PIPING AND OTHER TRADES. CONTRACTOR SHALL COORDINATE PLACEMENT OF SWITCHED TOGETHER TEST BLOCK. LI1 ® TELEVISION OUTLET,SINGLE-GANG BOX WITH MUDRING. FIXTURES WITH ARCHITECTURAL REFLECTED CEIUNG PLAN. LOCATION OF FIXTURES SHALL CEILING MOUNTED. �S MULTI-LEVEL SWITCHING,TO MEET LIGHT GOVERN WHEN CONFLICTS WITH SUPPLY/EXHAUST DIFFUSERS OCCUR. REDUCTION LEVELS PER ENERGY CODE AS OVERHEAD SERVICE DROP. SHOWN. PROVIDE ADDITIONAL OR STEP- 10. COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN(RCP)FOR CEILING TYPES. MISCELLANEOUS DIMMING BALLASTS WHERE REQUIRED.O GENERATOR SET.MAIN BREAKER SIZE j JUNCTION BOX. I� INDICATED. 11. ALL FIXTURES WITHIN A GIVEN ROOM/AREA ARE THE SAME TYPE AS THE SINGLE FIXTURE CALLED O ® OCCUPANCY SENSOR.CEILING MOUNTED. OUF WITHIN THAT ROOM/AREA,UNLESS OTHERWISE NOTED. O JUNCTION BOX,WALL MOUNTED. TRANSFER SWITCH. U (� 4 PHOTOCELL WALL MOUNTED. 12. LINEWORK SHOWN FOR CLARITY OF SWITCHING ONLY. PROVIDE QUANTITY OF CONDUCTORS AS YX INDICATED.THERMOSTAT +56"AFF UNO.UNIT CONTROLLED O PHOTOCELL CEILING MOUNTED. REQUIRED FOR CONTROL. --11 GUTTER. 1 ^� QX HUMIDISTAT.+56"AFF UNO.UNIT CONTROLLED 13. CONTRACTOR SHALL PROVIDE#10 AWG CONDUCTORS FOR ALL CIRCUITS OF 100'OR MORE . C� INDICATED. ® OCCUPANCY SENSOR/PHOTOCELL.CEIUNG METER AND BASE. UNLESS SHOWN LARGER. r Y p SURFACE MOUNTED PANELBOARD/ENCLOSURE.SEE MOUNTED. �•/ NEl1TRAL NEUTRAL 14. EXISTING TENANT SPACE ELECTRICAL DEMOLITION WORK TO BE DONE BY OTHERS. DEMOLITION SCHEDULE FOR TYPE. n SINGLE BUTTON,WALL MOUNTED PUSHBUTTON. OF EXISTING ELECTRICAL DEVICES ARE NOT SHOWN UNLESS OTHERWISE NOTED. FLUSH MOUNTED PANELBOARD/ENCLOSURE.SEE MOUNT AT SWITCH HEIGHT UNO. 1-N� SCHEDULE FOR TYPE. o0o TRANSFORMER 15. WIRE SIZE SHALL BE SIZED BASED ON OVERCURRENT PROTECTION DEVICE UNLESS OTHERWISE 0 THREE BUTTON,WALL MOUNTED PUSHBURON. AM MECHANICAL EQUIPMENT SYMBOL(RE:MECHANICAL MOUNT AT SWITCH HEIGHT UNO. 1 NOTED. CITY APPROVED PLANS , W a, DRAWINGS FOR EXACT LOCATION OF UNITS). ® MOTOR STARTER/CONTACTOR. STARTER AND OVERLOAD NEMA SIZE� 16. REFER TO SHEET E4.0 FOR ONE LINE DIAGRAM. S"y yam, AS INDICATED. Reviewed for Code Compliance INDICATES FIXTURE TYPE. REFER TO LUMINARE ® COMBINATION STARTER AND DISCONNECT. 17. SEE CONTRACTOR TO ARCHITECTURAL PLANS FOR DEMOLITION. CONTRACTOR WILL WORK WITH THE GENERAL w M SCHEDULE. � CONTRACTOR TO REMOVE ALL OUTLETS AND MAKE THE CIRCUITS SAFE. REMOVE ALL EXISTING W w � � 1 GROUND LIGHT FIXTURES AND UTILIZE EXISTING CIRCUITS FOR NEW UGHTING LAYOUT AND SWITCHING. PLANS MUST BE ON JOB SITE © TRANSFORMER X NON-FUSED DISCONNECT SWITCH.SIZE AS - ALL DEMOLITION WORK INDICATED BY ARCHITECT THAT REQUIRES ELECTRICAL SUPPORT SHALL BE SCALE: INDICATED,NEMA 1 LINO,3 POLE LINO. PART OF THE CONTRACT. FOR ALL INSPECTIONS AS NOTED EPX FUSED DISCONNECT SWITCH.SIZE AS INDICATED, DATE: NEMA 1 UNO,3 POLE UNO. 08/09/2023 DRAWN BY: TSM CHECKED BY, CB SHEET E0.0 Page 19 of 26 ELECTRICAL SPECIFICATIONS ED o s PART 1 - GENERAL F. CONVENIENCE RECEPTACLES SHALL BE,FLUSH WALL TYPE,COORDINATE FINISH WITH ARCHITECT. Z'� 0. INSTALL WIRING AT OUTLETS WITH AT LEAST 12 INCHES OF SLACK CONDUCTOR AT EACH OUTLET. y 1.1 SCOPE OF WORK 2.5 WIRE CONNECTORS 7 I o P. CONNECT OUTLET AND COMPONENT CONNECTIONS TO WIRING SYSTEMS AND TO GROUND. TIGHTEN ELECTRICAL W WE a c FURNISH AND INSTALL ALL MATERIALS AND E AND PROVIDE ALL LABOR REQUIRED AND NECESSARY TO A. FOR WIRE SIZES AN AWG AND SMALLER:INSULATED PRESSURE TYPE(WITH LIVE SPRING)RATED 105'C,600V,FOR Z O COMPLETE THE WORK SHOWN ON THE DRAWINGSINGS AND M CONNECTORS AND TERMINALS,ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF Ila!ND ALL OTHER WORK AND MISCELLANEOUS TEEMS,NOT SPECIFICALLY BUILDING WIRING AND 1000V IN FIXTURES,SCOTCHLOK OR IDEAL. MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED,USE THOSE SPECIFIED IN ILL 486A. MENTIONED,BUT REASONABLY INFERRED FOR A COMPLETE INSTALLATION,INCLUDING ALL ACCESSORIES AND c a APPURTENANCES REQUIRED FOR TESTING THE SYSTEM.IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS THAT B. FOR WIRE SIZES#6 AWG AND LARGER:T&B OR EQUIVALENT COMPRESSION TYPE WITH 3M#33+OR PLYMOUTH 3.5 IDENTIFICATION E3 N 3 N ALL SYSTEMS BE COMPLETE AND READY FOR OPERATION.THIS PROJECT INCLUDES ELECTRICAL SERVICE,GENERAL "SLIPKNOT GREY"TAPE INSULATION. W= 3 m POWER,LIGHTING,AND COMMUNICATIONS SYSTEM RACEWAY.FIRE ALARM SYSTEM IS TO BE DESIGN/BUILD BY ELECTRICAL A. PROVIDE ENGRAVED 3 LAYER LAMINATE PLASTIC NAMEPLATES FOR PANELBOARDS,DISCONNECT SWITCHES AND ALL CONTRACTOR.COMMUNICATIONS SYSTEM CABLING AND HEAD-END EQUIPMENT IS BY OWNER. 2.6 PANELBOARD SIMILAR DEVICES. L1`m 1.2 CODE COMPLIANCE / 13 U B. COLOR-CODE THEY 120-VOLT SYSTEM SECONDARY SERVICE,FEEDER,AND BRANCH-CIRCUIT CONDUCTORS PANELBOARDS SHALL BE AS MANUFACTURED BY SQUARE D,EATON,ABB OR SIEMENS. PANELBOARDS AS INDICATED ON THROUGHOUT THE SECONDARY ELECTRICAL SYSTEM AS FOLLOWS: ALL WORK AND MATERIALS SHALL COMPLY WITH LATEST RULES,CODES AND REGULATIONS,INCLUDING,BUT NOT LIMITED SCHEDULES,WITH THE FOLLOWING FEATURES:HARD-DRAWN COPPER BUS(98 PERCENT CONDUCTIVITY), MECHANICAL-TYPE MAIN AND NEUTRAL LUGS,NEUTRAL BUS RATED 100 PERCENT OF PHASE BUS,GROUND BUS 1. PHASE A BLACK TO OSHA,THE NATIONAL ELECTRICAL CODE,INTERNATIONAL BUILDING AND FIRE CODES,NFPA,AND OTHER APPLICABLE BONDED TO ENCLOSURE,BOLT-ON MOLDED-CASE THERMAL-MAGNETIC BREAKERS. OVERCURRENT DEVICES OVER 1200 2. PHASE B:RED STATE AND LOCAL LAWS AND REGULATIONS.CODE COMPLIANCE IS MANDATORY.NOTHING IN THESE DRAWINGS AND AMPS SHALL INCLUDE ARC FLASH MITIGATION. 3. PHASE C:BLUE SPECIFICATIONS PERMITS WORK NOT CONFORMING TO THESE CODES.WHERE WORK IS SHOWN TO EXCEED MINIMUM EXISTING PANELS TO MATCH MANUFACTURER TO BE COMPATIBLE WITH SERIES RATING OF AVAILABLE FAULT CURRENT. 4. NEUTRAL:WHITE CODE REQUIREMENTS,COMPLY WITH DRAWINGS AND SPECIFICATIONS. OTHERWISE SHALL BE FULLY RATED. 5. GROUND:GREEN 1.3 LICENSE. FEES AND PERMITS 2.8 RACEWAYS 3.6 STARTUP SERVICES ARRANGE FOR REQUIRED INSPECTIONS AND PAY ALL LICENSE,PERMIT AND INSPECTION FEES. A. OUTDOORS: CONTRACTOR SHALL ALLOT A MINIMUM OF 2 HOURS FOR STARTUP SERVICES. START AND OPERATE ALL SYSTEMS AS REQUIRED BY THE OWNER. INSTRUCT OWNER'S REPRESENTATIVE ON THE PROPER OPERATION AND MAINTENANCE OF 1.4 CONDITIONS AT SITE EXPOSED:RIGID STEEL OR INTERMEDIATE METAL CONDUIT THE SYSTEMS AND EQUIPMENT. CONCEALED:RIGID STEEL OR INTERMEDIATE METAL CONDUIT VISIT TO SITE IS REQUIRED of ALL BIDDERS PRIOR TO SUBMISSION OF BID.ALL WILL BE HELD TO HAVE FAMILIARIZED UNDERGROUND:RIGID NON-METALLIC CONDUIT 3.7 OPERATING AND MAINTENANCE INSTRUCTIONS (O+M MANUAL) THEMSELVES WITH ALL DISCERNIBLE CONDITIONS AND NO EXTRA PAYMENT WILL BE ALLOWED FOR WORK REQUIRED TO VIBRATING EQUIPMENT:LIQUID-TIGHT FLEXIBLE METAL CONDUIT BECAUSE OF THESE CONDITIONS,WHETHER SPECIFICALLY MENTIONED OR NOT.LINES OF OTHER SERVICES THAT ARE PREPARE THREE 3 COPIES FOR ALL EQUIPMENT. DAMAGED AS A RESULT OF THIS WORK SHALL PROMPTLY BE REPAIRED AT NO EXPENSE TO THE OWNER TO COMPLETE B. INDOORS: () SATISFACTION OF THE OWNER. EXPOSED:ELECTRICAL METALLIC TUBING,RIGID STEEL CONDUIT,PVC-COATED RIGID STEEL CONDUIT 3.8 RECORD AS-BUILTS 1.5 SAFELY CONCEALED:ELECTRIC METALLIC TUBING,METAL CLAD DAMP OR WEr LOCATIONS:RIGID STEEL CONDUIT PROVIDE(1)CLEAN,LEGIBLE COPY OF DRAWINGS TO ENGINEER INDICATING ALL DEVIATIONS FROM INITIAL DESIGN AL �'<�°'r' �y THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE,INCLUDING TO VIBRATING EQUIPMENT:FLEXIBLE METAL CONDUIT (AS-BUILT CONDITIONS). NS SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF THE WORK. PART 3 - EXECUTION END OF SECTION i Fp 1.6 GUARANTEE 9 3.1 - GENERAL a GUARANTEE THE INSTALLATION FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR F �O y F AFTER DATE OF CERTIFICATE OF FINAL PAYMENT AND PROMPTLY REMEDY ANY DEFECTS DEVELOPING DURING THIS A. ELECTRIC SYSTEM LAYOUTS INDICATED ON THE DRAWINGS ARE GENERALLY DIAGRAMMATIC,BUT SHALL BE FOLLOWED REMODEL:If construction will move or alter the existing Fire 9rHgN GpQ.P� PERIOD,WITHOUT CHARGE. AS CLOSELY AS ACTUAL CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT. A Alarm System,it may need to be evaluated by the Idaho State 0e/09/2023 1.7 SUBSTITUTIONS B. CONSULT ALL OTHER DRAWINGS.VERIFY SCALES AND REPORT ANY DIMENSIONAL DISCREPANCIES OR OTHER Fire Marshal's(ID SFM)office to ensure code compliance and CONFLICTS TO ARCHITECT BEFORE SUBMITTING BID. power calculations. WHEREVER POSSIBLE,MORE THAN ONE MANUFACTURER HAS BEEN LISTED FOR VARIOUS ITEMS OF EQUIPMENT,ANY ONE OF WHICH WILL BE ACCEPTABLE.BASE THE BID ON USE OF MATERIALS SPECIFIED.IF,AFTER AWARD OF THE CONTRACT, C. ALL HOME RUNS ARE INDICATED AS STARTING FROM THE DEVICE NEAREST THE PANEL AND CONTNUING IN THE 111 A SUBSTITUTE IS PROPOSED,THE REQUEST FOR PERMISSION TO SUBSTITUTE SHALL BE ACCOMPANIED WITH A GENERAL DIRECTION OF THAT PANEL CONTINUE SUCH CIRCUITS TO THE PANEL AS THOUGH THE ROUTES WERE F STATEMENT OF THE AMOUNTIf significant changes need to be made,plans shall be submitted OF MONEY TO BE RETURNED TO THE CONTRACT IF THE SUBSTITUTION IS PERMITTED.THE COMPLETELY INDICATED. If the ID SFM for acceptance. ENGINEER IS THE SOLE JUDGE OF ACCEPTABILITY OF PROPOSED SUBSTITUTIONS,IF A SUBSTITUTE ITEM IS PERMITTED, to AND ANY REDESIGN EFFORT IS THEREBY NECESSITATED,THE REQUIRED REDESIGN SHALL BE AT THE CONTRACTOR'S D. AVOID CUTTING AND BORING HOLES THROUGH STRUCTURE OR STRUCTURAL MEMBERS WHEREVER POSSIBLE.OBTAIN EXPENSE PRIOR APPROVAL OF ARCHITECT AND CONFORM TO ALL STRUCTURAL REQUIREMENTS WHEN CUTTING OR BORING THE Idaho State Fire Marshal STRUCTURE IS NECESSARY AND PERMITTED. 1.8 SHOP DRAWINGS AND MATERIALS LISTS 3.2 - ELECTRICAL GROUNDING sfm.planreview@doi.idaho.gov SUBMIT TO THE ENGINEER SEVEN(7)COPIES OF COMPLETE SHOP DRAWINGS AND MATERIALS LISTS FOR REVIEW WITHIN New work/changes shall not be covered up prior to fire inspection. THIRTY 30 DAYS AFTER AWARD OF CONTRACT,ALL PROPOSED DEVIATIONS FROM SPECIFICATIONS MUST BE CLEARLY GROUND ALL ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC.IN ADDITION PROVIDE A SEPARATE GROUND WIRE FOR ( ) Fire Inspection Line:208-735-7338 LISTED UNDER A PROMINENT HEADING ENTITLED'DEVIATIONS". ALL FEEDERS AND BRANCH CIRCUITS. 1.9 WORKMANSHIP 3.3 - ELECTRICAL EQUIPMENT INSTALLATION ONLY QUALITY WORKMANSHIP WILL BE ACCEPTED.HAPHAZARD OR POOR INSTALLATION PRACTICE WILL BE CAUSE FOR A. HEAD ROOM MAINTENANCE:IF MOUNTING HEIGHTS OR OTHER LOCATION CRITERIA ARE NOT INDICATED,ARRANGE AND Fire Alarm Control Panel(FRCP)Access: REJECTION OF WORK. INSTALL COMPONENTS AND EQUIPMENT TO PROVIDE THE MAXIMUM POSSIBLE HEADROOM. 1.10 COORDINATION B. MATERIALS AND COMPONENTS: INSTALL LEVEL,PLUMB,AND PARALLEL AND PERPENDICULAR TO OTHER BUILDING Access doors and/or pathways leading to the SYSTEMS AND COMPONENTS,UNLESS OTHERWISE INDICATED. FACP shall be labeled with an approved sign. COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT AND TO PROVIDE CORRECT ROUGH-IN AND CONNECTION C. EQUIPMENT: INSTALL TO FACILITATE SERVICE,MAINTENANCE,AND REPAIR OR REPLACEMENT OF COMPONENTS. FOR EQUIPMENT FURNISHED UNDER OTHER TRADES THAT REQUIRE ELECTRICAL CONNECTIONS.VERIFY EQUIPMENT CONNECT FOR EASE OF DISCONNECTING,WITH MINIMUM INTERFERENCE WITH OTHER INSTALLATIONS. The lettering shall have a minimum height of DIMENSIONS AND REQUIREMENTS WITH PROVISIONS SPECIFIED UNDER THIS SECTION.CHECK ACTUAL JOB CONDITIONS 9 g BEFORE FABRICATING WORK.REPORT NECESSARY CHANGES IN TIME TO PREVENT NEEDLESS WORK. D. RIGHT OF WAY: COORDINATE INSTALLATION OF ELECTRICAL DEVICES WITH OTHER TRADES. 2 Inches with a minimum stroke of 3/8 Inch. 1.11 CUTTING AND PATCHING 3.4 - RACEWAY AND CABLE INSTALLATION Red sign with white letters."FACP" ALL CUTTING AND PATCHING REQUIRED FOR WORK OF THIS DIVISION IS INCLUDED HEREIN.COORDINATION WITH GENERAL A. ABOVE GRADE:RIGID STEEL OR IMC IN WET LOCATIONS,WHERE SUBJECT TO MECHANICAL DAMAGE AND IN CONTRACTOR AND OTHER TRADES IS IMPERATIVE. CONCRETE OR BLOCK WALLS,EMT IN OTHER LOCATIONS WHERE PERMITTED BY CODE.METAL CLAD WHERE ALLOWED 1.12 SITE CLEANUP BY LOCAL AUTHORITY HAVING JURISDICTION. B. CONCEAL RACEWAYS AND CABLES WITHIN FINISHED WALLS,CEILINGS,AND FLOORS,UNLESS OTHERWISE INDICATED. A. AFTER ALL OTHER WORK HAS BEEN ACCOMPLISHED,CLEAN ALL EXPOSED CONDUIT,FIXTURES,EQUIPMENT AND SUPPORTS. TOUCH UP PAINT ON ANY EQUIPMENT SCRAPED,SCRATCHED OR DAMAGED DURING CONSTRUCTION. C. INSTALL RACEWAYS AND CABLES AT LEAST SIX(6)INCHES AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES. LOCATE HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPING. B. LEAVE ALL AREAS INVOLVING ELECTRICAL WORK IN A CONDITION SATISFACTORY TO THE OWNER. REMOVE ALL CRATES,CARDBOARD,PACKING MATERIAL,WASTE MATERIAL,AND OTHER DEBRIS LEFT OVER FROM CONSTRUCTION. D. USE TEMPORARY RACEWAY CAPS TO PREVENT FOREIGN MATTER FROM ENTERING. PART 2 - PRODUCTS E. MAKE CONDUIT BENDS AND OFFSETS SO INSIDE DIAMEFER IS NOT REDUCED. KEEP LEGS OF BENDS IN THE SAME O PLANE AND STRAIGHT LEGS OFFSETS PARALLEL,UNLESS OTHERWISE INDICATED. I--1 2.1 MATERIAL APPROVAL F. USE RACEWAY FITTINGS AND CABLE FITTINGS COMPATIBLE WITH RACEWAYS AND CABLES AND SUITABLE FOR THIS ALL MATERIALS MUST BE NEW AND BEAR U.L.LABEL MATERIALS THAT ARE NOT COVERED BY ILL TESTING STANDARDS APPLICATION AND LOCATION. SHALL BE TESTED AND APPROVED BY AN INDEPENDENT TESTING LABORATORY OF A GOVERNMENTAL AGENCY APPROVED G. INSTALL RACEWAYS EMBEDDED IN SLABS IN MIDDLE THIRD OF SLAB THICKNESS WHERE PRACTICAL,AND LEAVE AT BY THE AUTHORITY HAVING JURISDICTION. LEAST 1-INCH OF CONCRETE COVER. I--I 2.2 WIRES AND CABLES 1. SECURE RACEWAYS TO REINFORCING RODS TO PREVENT SAGGING OR SHIFTING DURING CONCRETE PLACEMENT. rU A. CONDUCTORS FOR 600V SYSTEMS AND BELOW SHALL BE STRANDED COPPER,#12 AWG MINIMUM. 2. SPACE RACEWAYS LATERALLY TO PREVENT VOIDS IN CONCRETE. W B. INSULATION SHALL BE THWN FOR WET LOCATIONS AND THHN FOR DRY LOCATIONS. 3. INSTALL CONDUIT LARGER THAN 1-INCH TRADE SIZE PARALLEL TO OR AT RIGHT ANGLES TO MAIN 2.3 OUTLET BOXES. JUNCTION AND PULL BOXES REINFORCEMENT. WHERE CONDUIT IS AT RIGHT ANGLES TO REINFORCEMENT,PLACE CONDUIT CLOSE TO SLAB SUPPORT. l A. OUTLET BOXES:HOT-DIPPED,GALVANIZED OR SHERADIZED.SIZE AS REQUIRED WITH 4"SQUARE MINIMUM,FOR 4. TRANSITION FROM NONMETALLIC TUBING TO RIGID STEEL CONDUIT,OR IMC BEFORE RISING ABOVE FLOOR. FLUSH MOUNTED DEVICES AND LIGHTING FIXTURES. r Y p H. MAKE EXPOSED BENDS TOR BANKED RUNS FROM SAME CENTERLINE IN ORDER THAT BENDS ARE PARALLEL. USE \./ y B. JUNCTION AND PULL BOXES:HOT DIPPED,GALVANIZED OR SHERADIZIED,SIZED ACCORDING TO CODE.LARGER FACTORY ELBOWS ONLY WHERE ELBOWS CAN BE INSTALLED PARALLEL;OTHERWISE,PROVIDE FIELD BENDS FORcC JUNCTION AND PULL BOXES SHALL BE FABRICATED FROM SHEET STEEL,SIZED ACCORDING TO CODE,WITH EXPOSED PARALLEL RACEWAYS. SCREW-ON COVERS,FINISHED GRAY BAKED ENAMEL. ~ I. INSTALL PULL WIRES IN EMPTY RACEWAYS. USE NO.14 AWG ZINC-COATED STEEL OR MONOFILAMENT PLASTIC LINE 2.4 WIRING DEVICES WITH NOT LESS THAN 200-LB TENSILE STRENGTH. LEAVE AT LEAST 12-INCHES OF SLACK AT EACH END OF PULL U O w WIRE. rT, A. ALL WIRING DEVICES OF ANY ONE GENERAL TYPE SHALL BE OF THE SAME MANUFACTURER AND SHALL MATCH W J. INSTALL TELEPHONE AND SIGNAL SYSTEM RACEWAYS,2-INCH TRADE SIZE AND SMALLER,IN MAXIMUM LENGTHS OF � a � 0 THROUGHOUT. 150 FEET(45 M)AND WITH A MAXIMUM OF TWO 90-DEGREE BENDS OR EQUIVALENT. SEPARATE LENGTHS WITH rT�l rT Mo0 3 W w B. WIRING DEVICES SHALL BE AS MANUFACTURED BY HUBBELL,GE,LEVITON,P&S,OR BRYANT.NO SUBSTITUTIONS. PULL OR JUNCTION BOXES WHERE NECESSARY TO COMPLY WITH THESE REQUIREMENTS,IN ADDITION TO REQUIREMENTS ABOVE. C. COVER PLATES SHALL BE AS MANUFACTURED BY ARROW HART,SIERRA,LIBATION OR MULLBURRY.COORDINATE SCALE: FINISH WITH ARCHITECT. K. CONNECT MOTORS AND EQUIPMENT SUBJECT TO VIBRATION,NOISE TRANSMISSION,OR MOVEMENT WITH A MAXIMUM AS NOTED OF 72-INCH FLEXIBLE CONDUIT. INSTALL LRMC IN WET OR DAMP LOCATIONS. INSTALL A SEPARATE GROUND DATE: D. WHERE INDICATED,PROVIDE GENERAL-DUTY,DUPLEX RECEPTACLES,GROUND-FAULT CIRCUIT INTERRUPTERS: CONDUCTOR ACROSS FLEXIBLE CONNECTIONS. 08/09/2023 GROUNDING TYPE UL-RATED CLASS A,GROUP 1,20 AMPERES RATING,120 VOLTS,60Hz:WITH SOLID-STATE L SEr FLOOR BOXES LEVEL AND TRIM AFTER INSTALLATION TO FIT FLUSH TO FINISHED FLOOR SURFACE. DRAWN BY: GROUND-FAULT SENSING AND SIGNALING:WITH 5 MILLIAMPERES GROUND-FAULT TRIP LEVEL:WHITE FINISH. CITY APPROVED PLANS TSM E. SWITCHES SHALL BE FLUSH WALL TYPE,COORDINATE FINISH WITH ARCHITECT. M. CONDUCTORS:TYPE THHN/THWN INSULATED CONDUCTORS IN RACEWAY. CHECKED BY: N. INSTALL SPLICES AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR Reviewed for Code Compliance CB BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN UNSPLICED CONDUCTORS. PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS SHEET E0.1 Page 20 of 26 ED COMcheck Software Version 4.1.5.5 COMcheck Software Version 4.1.5.5 Section o g # Rough-In Electrical Inspection Complies? Comments/Assumptions Z'� Interior Lighting Compliance Certificate Inspection Checklist 6r Req.ID C405.2.2. required have light- Co:reduction W D d 2 reduction controls ,[ mplies have a manual ODoes Not W E =e [EL2271 control that allows the occupant to Energy Code:2018 IECC ONotObservable'; W .E retluce the connectetl lighting loatl inONot Applicable Requirements:0.0%were addressed directly in the COMcheck software a reasonably uniform Illumination pp ice e Z OT Project Information Text in the"Comments/Assumptions"column is provided by the user in the COMcheck Requirements screen.For each :pattern>=50 percent. en requirement,the user certifies that a code requirement will be met and how that is documented,or that an exception C4052.1,lOccupancy sensors installed in IDComplies Energy Cotle: 2018 IECC q q p C405.2.1. classrooms/lecture/training rooms, �ODoes Not I Z .D. 3 N is being claimed.Where compliance is itemized in a separate table,a reference to that table is provided. Project Title: Laundromat 1 ConferenCe/meeting/multipurpose m 3 m Project Type: Alteration [EL18]1 rooms,copy/print rooms, ',[Not Observable; W Section lounges/breakrooms,enclosed offices,[Not Applicable V # Plan Review Compiles? Comments/Assumptions ;open plan office areas,restrooms, S Re .ID ;storage rooms,locker rooms, Q L) Construction Site: Owner/Agent: Designer/Contractor: C103.2 Plans,specifications,and/or ',[Complies warehouse storage areas,and other Twin Falls,ID 83301 [PR411 calculations provide all information ';[]Does Not ;:spaces<=300 sqft that are enclosed with which compliance can be ',ONot Observable by floor-to-ceiling height partitions. Allowed Interior Lighting Power determined for the interior llghtinq Reference section language A B C D and antl electrical systems and equipment'; :C405.2.1.2 for control function in document where exceptions to [Not Applicable warehouses and section C405.2.1.3 Area Category Floor Area Allowed Allowed Watts the standard are claimed.Information for open plan office spaces. (tt2) Watts/ft2 (B X C) provided should include interior fighting power calculations,wattage f: C405.2.1.',Occupancy sensors control function in',[Complies 1-Laundromat Retail 4311 1.06 4570 ge o 2 warehouses:In warehouses,the ❑goes Not (Retail) bulbs and ballasts,transformers and [EL19]1 lighting in aisleways and open areas is Total Allowed Watts= 4570 control devices. controlled with occupant sensors that [Not Observable', Additional Comments/Assumptions: :automatically reduce lighting power ',[Not Applicable; Proposed Interior Lighting Power by 5o%or more when the areas are p B C D E unoccupied.The occupant sensors Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) control lighting in each isle Fixture Fixtures WaH. independently antl tlo not control lighting beyond the aisleway being Laundromat f Retail 4311 sO.ft.l controlled by the sensor. LED 1:CIE:LED CAN:Other: 1 1 22 22 C405.2.1.',Occupant sensor control function in ',[Complies LED 2:TI:LED 2x4:Other: 1 19 45 859 3 open plan office areas:Occupant ',[Does Not LED 3:TIE:LEDX4 (EMERGENCY):Other: 1 2 45 90 [EL2011 sorcontrolsi n open office spaces ',[Not Observable; >=300 sq.ft.have controls 1) 'E]Not Applicable ble LED 4:T2:LED 2x4:Other: 1 4 34 138 configured so that general lighting can pp LED 5:T2E:LED 2x4(EMERGENCY):Other: 1 1 34 34 :be controlled separately in control LED 6:WB1:WALL BRACKET:Other. 1 1 17 17 :zones with floor areas<=600 sq.ft. LED 7:WB2:WALL BRACKET:Other. 1 2 35 70 within the space,2)automatically turn: ';off general lighting in all control zones LED 8:WB2E:WALL BRACKET(EMERGENCY):Other: 1 1 35 35 within 20 minutes after all occupants $\ AL Total Proposed Walls= 1268 ',have left the space,3)are configured tcF'$ NS so that generel lighting power in each Interior Lighting ',control zone is reduced by>=80%of a PASSES '.the f p 'full zone general lighting power r1 Interior Lighting Compliance Statement :within 20 minutes of all occupants t7 leaving that control zone,and 4)are O Compliance Statement:The proposed interior lighting alteration project represented in this document is consistent with the configured such that any daylight building plans,specifications,and other calculations submitted with this permit application.The proposed interior lighting responsive control will activate space systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.5 and to comply with any ;general lighting or control zone applicable mandatory requirements listed in the Inspection Checklist. ',general lighting only when occupancy qN A C� Tracey S.McAuley %4.drav 7nr,A2e�.av 07-26-2023 for me:ame area:detected. Name-Title Signatur Date C405.2.2, Each area not served by occupancy ;[Complies OB/09/2023 C405.2.2. sensors(per C405.2.1)have time '[Does Not 1, switch controls and functions detailed',[Not Observable; C405.2.2. in sections C405.2.2.1 and C405.2.2.2.''[Not Applicable ty 2 f— [EL211� G 1 High Impact(Tier 1) I It Medium Impact(Tier 2) 1 3 1 Low Impact(Tier 3) 11 High Impact(Tier 1) Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Laundromat Report date:07/26/23 Project Title: Laundromat Report date:07/26/23 Project Title: Laundromat Report date:07/26/23 Data filename:\\DCE\Projects\2023\23B0001-Lau ndromat\Caks\Electrical\Energy Calcs\Laundromatcck Page 1Of 6 Data filename:\\DCE\Projects\2023\23B0001-Laundromat\Calcs\Electrical\Energy Calcs\Laundromai Page 2of 6 Data filename:\\DCE\Projects\2023\23B0001-Laundromat\Calcs\Electrical\Energy CalcAl-sundromatcck Page 3of 6 Section Section # Rough-In Electrical Inspection Complies? Comments/Assumptions # Final Inspection Complies? Comments/Assumptions &Re.ID &Re .ID C405.2.3, Daylight zones provided with [Complies C303.3, Furnished O&M instructions for ',[Complies C405.2.3. individual controls that control the ODoes Not C408.2.5. systems and equipment to the ';[Does Not 1, lights independent of general area []Not Observable 2 building owner or designated ;[Not Observable C405.2.3. llghtinq.See code section C405.2.3 [FI1713 representative. 2 Daylight-responsive controls for ONot Applicable ;[Not Applicable [EL23]' applicable spaces,C405.2.3.1 Daylight responsive control function and ; C405.4.1 Interior installed lamp and fixture ',[Complies ;See the Interior Lighting fixNre xnedule for values. section C405.2.3.2 Sidelit zone. [FI18]1 lighting power is consistent with what';[Does Not C405.2.4 Se to lighting control devices for OCom lies is shown on the approved lighting pare g gcon p ;[Not Observable, [EL26]1 specific uses installed per approved [Does Not plans,demonstrating proposed watts [Not Applicable lighting plans. [Not Observable less than or equal to allowed PV watts. [Not Applicable C408.1.1 Building operations and maintenance ',[Complies ; C405.2.4 ;Additional interior lighting power [Complies [FI57]1 documents will be provided to the ';[Does Net [EL27]1 ',allowed for special functions per the [Does Not wner.Documents will cover ;ONot Observable :approved lighting plans and is manufacturers'information, '[Not Applicable; automatically controlled and ',[Not Observable; specifications,programming pp ice separated from general lighting. '[Not Applicable procedures and means of illustrating to owner how building,equipment and C405.3 Exit signs do not exceed 5 watts per [Complies systems are intended to be installed, [EL6]1 face. [Does Not ma intained,and operated. [Not Observable; C408.2.5. Furnished as-built drawings for ;[Complies ;ONot Applicable 1 electric power systems within 90 days';[Does Not C405.6 Low-volta d t distribution '.00om lies [FI1613 of system acceptance. O ge ry-ype p ;[Not Observable, [EL26]' electric transformers meet the [Does Not ;ONot Applicable rr ible C4 efficiency requirements of [Not Observable C408.3 Lighting systems have been tested to ',[Complies F'�) Table C405.6. [Not Applicable [FI33]1 ensure proper calibration,adjustment,';[Does Not W C405.7 Electric motors meet the minimum [Complies programming,and operation. :[]Not Observable [EL27]1 :efficiency requirements of Tables ODoes Not ;[Not Applicable `./ C405.7(1)through C405.7(4). [Not Observable Efficiency verified through certification', Additional Comments/Assumptions: �..1 under an approved certification ONot Applicable program orthe equipment efficiency ratings shall be provided by motor manufacturer (where certification ~ O programs do not exist). I�1 C405.8.2, Escalators and moving walks comply [Complies C405.8.2.'with ASME A17.1/CSA B44 and have [Does Not 1 suit r lc Controls confgured to [EL28]1 'retluce speed to the minimum [Not Observable', permitted speed in accordance with ONot Applicable O r ASME A17.1/C5A B44 or applicable local code when not conveying passengers. U C405.9 'Total voltage drop across the [Complies [EL29]' Combination of feeders and branch .[Does Not Iy' ✓ cults<=5%. ',ONot Observable; ;ONot Applicable \/ _ Additional Comments/Assumptions: o w Z C) a, ' W (� O'C F SCALE: AS NOTED DATE: 08/09/2023 CITY APPROVED PLANS DRAWN BY: rSM 1 High Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3) 11 High Impact(Tier 1) WMedlum Impact(Tier 2) 3 Low Impact(Tier 3) Reviewed for Code Compliance CHECKED BY. Project Title: Laundromat Report date:07/26/23 Project Title: Laundromat Report date:07/26/23 Project Title: Laundromat Report date:07/26/23 CB Data filename:\\DCE\Projects\2023\23B0001-Lau ndromat\CaI<s\Electrical\Energy Calcs\Laundromatcck Page 4of 6 Data filename:\\DCE\Projects\2023\2380001-Laundromat\Calcs\Electrical\Energy Calcs\Laundromai Page 5of 6 Data filename:\\DCE\Projects\2023\23B0001-Laundromat\CaICS\Electrical\Energy Calcs\Laundromatcck Page 6of 6 PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS SHEET E0.2 Page 21 of 26 EXISTING TENANT SPACE KEY NOTES: ni 1. PROVIDE AND INSTALL WALL MOUNTED OCCUPANCY SENSOR-SENSOR SWITCH/WSD-PDT OR EQUIVALENT. ED o 8'AF.F. 8'A.F.F. B2E 8'A.F.F. 7 !RESTRO CO NTER _ M T1 DRYER TUNNEL W W62 M 2. PROVIDE AND INSTALL CEILING MOUNTED,SMALL MOTION,OCCUPANCY Z 5 n �,- -.. SENSOR-SENSOR SWITCH#CM-PDT-9-R OR EQUIVALENT. TIE INTO u - ASSOCIATED ZONE POWER PACK. W E g S a �) 1 CIE 3. PROVIDE AND INSTALL POWER PACK-SENSOR SWITCH#PP20 OR Z O(b O APPROVED EQUIVALENT. 4 OFFICE 1 7 4. PROVIDE LOW VOLTAGE WALL SWITCH-SENSOR SWITCH sPOD SERIES OR Z m 3 APPROVED EQUIVALENT. TIE INTO ASSOCIATED ZONE POWER PACK. I m i _ II II II _ WB1 - FIRE RISER 5. PROVIDE AND INSTALL CEILING MOUNTED,LARGE MOTION,LOW VOLTAGE V A A �� �� OCCUPANCY SENSOR WITH PHOTOCELL-SENSOR SWITCH 0 v 11 _ll _u _u JJ 11 _ll _u _ll T T #CM-PDT-10-R-P OR APPROVED EQUIVALENT. TIE INTO ASSOCIATED ZONE FolPOWER PACK. i --,i 6. PROVIDE AND INSTALL CEILING MOUNTED,LARGE MOTION,LOW VOLTAGE � OCCUPANCY SENSOR-SENSOR SWITCH ACM-PDT-10-R OR EQUIVALENT. EXIT TIE INTO ASSOCIATED ZONE POWER PACK. (a) (a) b b (b) (b) b i 7. PROVIDE AND INSTALL CONDUIT AND CONDUCTORS AS REQUIRED TO p u RECONNECT NEW LIGHT FIXTURES AND WALL SWITCHES TO EXISTING LIGHTING 6 O4 (b CIRCUIT IN THE AREA. i T1 I i i - LAUNDROMAT (a) u � 3 7 PP20 9� AL 5 � NS �y �O O® O I IZ I T2E y? Fm E (a) PP20 (a) (NL)X-XX b b (b) (NL)X-XX (b) 9 p 3 7 STORAGE T TIE THAN A G�'P 08/09/2023 Fol i i 1y11� (b)PP20�) ------ ---- ---------- ------- i O a a b b b (b) FF FF F Tim �� �� F � A A A A A A T' R' Fr T' R' T' T' R' 0 II � II \ II \ I $\ II \ ECHANICAL i i T------- ______ __________ __________ a _r_______ __________ ____________________ _________ O EXISTING TENANT SPACE O 1 LIGHTING PLAN O SCALE:1/4•=1'-0" NORTH C� z a 3 w '021 � SCALE: AS NOTED DATE: 08/09/2023 CITY APPROVED PLANS DRAWN BY: TSM Reviewed for Code Compliance CHECKED BY: PLANS MUST BE ON JOB SITE CB FOR ALL INSPECTIONS SHEET E2.1 L Page 22 of 26 EXISTING TENANT SPACE E-10 E-10 (E)� E E o -12 2 1] COUNTER E-12 6 TYP GFl DRYER TUNNEL 6 T7 GFl --� O PANEL'D1' iRESTRO PANEL M 'H' Z o Od' y 4 PANEL'E' W E R E-12 _ .n�n rn n �n o w _..� W i i i i i i i i i i i i i i Z [2/1 00 00 00 00 0� o0 00 00 00 0 00 00 00 E-11 1 4 E-12 OFFICE EF y GFl2 E-12 [2/1) H-g I Z y 3 m 3 `ry E-11 LLI -1 T U_2 E-12 I I �1\ II\ II\ II 42"/GFl - -, TTB' FIRE RISER (] 3 � II III III III III III III III III II �� II �� II �� J _u ��_u �--u �--u 1__u '—JJ '--u ��_u ��_u �U �.0 �.0 CT CAN& METER O i i M ICE-14 � i � (E) i i i (E) E 3 J (E) i i i LAUNDROMAT PDP1 �-J E-14 U (D(E-10 E-11 AL �y S lJ' [2/1] O O 9 RTU-3 T 3 v E-14 O O STORAGE (E)TRANSFORMER yV, F F 64N A G�'P 08/09/2023 F0_1 i i i WLy E-11 ` F GFl -------------------------------------- ---------------- - O O i i WE-14 PANEL 11' MECHANICAL ��� ��� ��� ��� ��� ��� ��� ��� T�� T�� T�� ��� n- Ire T- T- n- re n- n- T- n- Ire n- T- T i 7i i N i7 7i i i i i i i 1 2 Sw Sw Sw Sw Sw Sw Sw Sw 00 E-8----------�---a E-11 - ___________ - - - ___ - - - _____ _________ GA GFI GFI GFI L_____________________IYF_ ________ ______________________________________________________________ ____________ _________________________________________ SY6 ____ ________ ---------------J O EXISTING TENANT SPACE O 1 POWER PLAN O SCALE:1/4"= 1'-0" NORTH GENERAL NOTES: 1. NUMBER ADJACENT TO HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICES SHALL BE CIRCUITED. 2. THERE IS LIMITED INFORMATION ON THE ELECTRICAL CONNECTIONS IN THE BULKHEAD. ELECTRICAL CONTRACTOR TO COORDINATE AND COMPLETE THE FINAL ELECTRICAL CONNECTION FOR ALL WASHERS AND DRYERS. KEY NOTES: 1. COORDINATE WITH MILLWORK PROVIDER PRIOR TO ROUGH-IN. 2. INSTALL DEVICES FOR TV AT 72"OR AS DIRECTED BY OWNER. 3. PROVIDE AND INSTALL 3/4"CONDUIT WITH PULL CORD FROM T-STAT TO UNIT INDICATED. WIRING BY MECHANICAL. 4. PROVIDE AND INSTALL COMBO DUPLEX-USB RECEPTACLE-HUBBELL #USB20X2W OR EQUIVALENT. COORDINATE COLOR WITH ARCHITECT. 5. PROVIDE AND INSTALL EXTERIOR JUNCTION BOX FOR SIGN. COORDINATE " MOUNTING LOCATION WITH ARCHITECT AND OWNER PRIOR TO ROUGH IN. COORDINATE SIGN REQUIREMENTS WITH OWNER PRIOR TO ROUGH IN. SIGN ELECTRICAL REQUIREMENTS UNKNOWN AT TIME OF DESIGN. PROVIDE AND INSTALL 3/4"CONDUIT WITH PULL CORD BACK TO PANEL. 6. PROVIDE AND INSTALL 3/4"CONDUIT WITH 2#12 AND 1#12 GROUND TO PANEL INDICATED. Ctl 7. COORDINATE WITH WASHER AND DRYER MANUFACTURER FOR NEMA CONFIGURATION CONNECTION REQUIREMENTS PRIOR TO ROUGH IN. FBI 8. PROVIDE DUPLEX ABOVE WINDOW PER CURRENT NEC REQUIREMENTS. F•�I ,N MOUNTING HEIGHT WILL BE BELOW TILE CEILING AND ABOVE WINDOW SEAL. W F7-I h N 9. EXHAUST FAN TO BE CONTROLLED BY RESTROOM LIGHT SWITCH. SEE LIGHTING Y5 O LTy PLAN ON SHEET E2.1L. O r SCALE: AS NOTED DATE: 08/09/2023 CITY APPROVED PLANS DRAWN BY: TSM Reviewed for Code Compliance CHECKED BY: CB PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS SHEET E2.1 P Page 23 of 26 KEYED NOTES: 1. SEE ONE LINE DIAGRAM FOR CONDUIT AND CONDUCTORS ON SHEEP E4.0. c Z I W z Z Il Z 3 L1 O� D1-41 PDP1-4 3R/60/3 0 RiU 1 EXISTING ROOFTOP EXISTING ROOFTOP UNIT#2 TO REMAIN UNIT#3 TO REMAIN AL aO��yg� NS 9 9 O THgN A 08/09/2023 G F+� w � � b U W EXISTING ROOFTOP UNIT TO REMAIN Fil 3 7� W ow a � W wO'CH 1 ELECTRICAL ROOF PLAN SCALE:As NOTED SCALE:1/4'=1'-0" DATE: 08/09/2023 NORTH CITY APPROVED PLANS DRAWN BY.' Reviewed for Code Compliance TSM CHECKED BY: PLANS MUST BE ON JOB SITE CB FOR ALL INSPECTIONS SHEET E2.2 Page 24 of 26 PANELBOARD SCHEDULE PANELBOARD SCHEDULE EMSTINGPANEL:E PANEL:Li VOLTAGE 20W120V PHASE 1 WIFE AMPBRERATING:100A I SC RATING:NA MAIN:MAINLUGONLY VOLTAGE-20WI20V PHASE 1 WIRE AMPBRERATING:225A SC RATING:22,000 IMAIN:MAINLUGONLY ENTRY:NA MOUNTING:FLUSH I ENTITY: MOUNTING:FLUSH ED LOADS: Amps VA LOGOTYPES: 1=LIGHTNG REMARKS: LOADS: Amps VA LOAD TYPES: 1=LIGHHNG REMARKS: Z' RH45EA: I6 1920 2=RECEPTACLES IXIGTING PANE-FOR REFERENCEONLY RHASEA: 77 9268 2=RECEPTACLES - m PHASE B'. 12 1440 3=MSC TOWER FROM EXISTING PANELH PHASES: ]] 922E 3=MSC 6,44 I PHASE C'. 20 2340 4=MOTOR PHASE C: 68 8170 4=MOTOR W E B TOTAL 5700 5=KITCHEN TOTAL: 28664 S=KITCHEN W _ (VA) LOAD SERVED NOTE TVPE FOL6 NO PHASE NO POLES TYPE NOTE LOADSBRVED (VA) (VA) LOADSBRVED NOTE TV FE FOL6 NO PHASE NO TOLES TYPE NOTE LOAD SERVED (VA) Z LTS-LIGHTS E 1 20 1 1 A 2 20 1 1 E LTS-LIGHTS 650 WASHER 4 20 2 1 A 2 20 2 4 WAGHE 448 LTS-LIGHTS E 1 20 1 3 B 4 20 1 1 E LTS-LIGHTS 650 --- 4 -- -- 3 B 4 -- -- 4 448 REG-FLOOR E 2 20 1 5 C 6 20 1 1 E LTS-LIGHTS 650 WASHER 4 20 2 5 C 6 20 2 4 WASHER 448 Z m 3 m REG-FLOOR E 2 20 1 7 A 8 20 1 2 WD RED-WATER HEATER CONTROLS 1200 650 --- 4 -- -- 7 A 8 -- -- 4 --- 448 W REG-FLOOR E 2 20 1 9 B 10 20 1 2 N REEG-LAUNDROMAT 1080 650 WASHER 4 20 2 9 B 10 20 2 4 WASHER 448 W 1260 REC-STORAGE N 2 20 1 11 C 12 20 1 2 N REC-DFFlDE,COUNTER 1080 650 --- 4 -- -- 11 C 12 -- -- 4 -- 448 (] m u 180 REQDRINONGFOUNTAIN WD 2 20 I 13 A 14 20 1 2 N REC-FRONT WINDDWSISIGN 540 SH 448 0 U t SPACE 15 B 16 20 1 2 N TELE'HONETERMINAL BOARD 360 650 --- 4 -- -- 15 B 16 -- -- 4 --- 448 u SPACE 17 C 18 SPA 650 WASHER 4 20 2 17 C 18 20 2 4 WAGE 448 SPACE 19 A 20 SPAC 650 --- 4 -- 19 A 20 -- -- 4 --- 448 SPACE 21 B 22 BPA 650 WASHER 4 20 2 21 B 22 20 2 4 WASHER 448 650 -- 4 -I- 23 C 24 - - 4 -- 448 650 WASHER 4 20 2 25 A 26 20 2 4 WASHER 448 650 -- 4 - -_1 27 B 28 - - 4 LOADING BY TYPE CONNECTED NEC CODE DEMANDFACTOR DEN AND NOTE: 650 WASHER 4 20 2 29 C 30 20 2 4 WASHER 448 LIGHTING OVA 210.19 125% OVA E-DENOTES EXISTING BREAKER TO REMAIN 650 -- 4 - - 31 A 32 - - 4 -- 448 RECEPTACLES 5700 VA 220-44 1OkVA @ 100%,ESE@ 50% 5700 VA N-DENOTES NEW BREAKER REQUIRED. 650 WASHER 4 20 2 33 B 34 20 2 4 WASHER 406 MISC OVA 2 00.60 100% OVA R-DENOTESTO RBJSEEXISTING BREAKER. 650 --- 4 -- -- 35 C 36 -- -- 4 --- 406 MOTOR LARGESTMOT: OVA 200.50 100%+LARGESTx 25% OVA D-DEDICATED BREAKER. 650 WASHER 4 20 2 37 A 38 20 2 4 WASHER 406 KITCHEN #OF KR.UNITS: OVA 220.5E OVA 406 WASHER 4 20 1 41 C 42 20 2 4 WASHER 406 TOTAL 16A 16A 4. 4 1 43 A 44 4 406 406 WASHER 4 20 1 45 B 46 20 2 4 WASH 406 406 --- 4 -- 1 47 C 48 -- -- 4 PANELBOARD SCHEDULE 406 WASHER 4 20 1 49 A 50 20 2 4 WASHER 406 EXISTINGPANEL:H 406 --- 4 -- 1 51 B 52 -- -- 4 --- 406 VOLTAGE 20SM2OV I PHASE 1 WIRE AMPERERATING:200A SC RATING: MAIN:MAINLUGONLY ENTRY: MOUNTING:FLUSH OR SURFACE LOADS: Amps VA LOADTYPES: 1=LIGHTING REMARKS: LOADING BY TYPE CONNECTED NEC CODE DEMANDFACTOR DEMAND NOTE: RHASEA. O 0 2=RECEPTACLES D(SRNG PANEL FOR REFERENCE ONLY PHASE B: O 0 3=MISC LIGH TING OVA 210-19 125% OVA PHASE C 0 O 4=MOTOR RECEPTACLES OVA 220-44 10kVA9?100%,ELSE@50% OVA AL TOTAL: 0 5=KITCHEN MSC. OVA 220-60 100% OVA SS1 CKTLOAD MOTOR LARGEST MOT'. 26664 VA 220-50 100%+LARGESTx 25% #WA (VA) LOAD SETRV ED NOTE TYPE PDL6 NO PHASE NO PjPE NOTE LOAD SERVED (VA) KITCHEN #OF KIT.UNITS. OVA 220-56 OVA y F10 TTB,FIREALARM E 3 20 1 1 A 2 3 E NORTHEAST-ROOFTOP UNIT9 LTS B ROOF CFI E 3 20 ��71 B 4 E _- TOTAL 74A #WAROOM HEATER E 3 20 C 6 E o3 A 8 4 E SOUTH WEST-ROOFTOP UNI SPACE E B 10 - E -- PANELBOARD SCHEDULESPACE E C 12 E - PANE-:D1 THEN A G�•P SPACE E 13 A 14 10 E PANEL'S VOLTAGE 208/120V PHASE3 WIRE4 AMPBRERATING:200A SC RATING:22,000 MAIN:MAIN LUG ONLY SPACE E 15 B 16 - E -- ENTRY: MOUNTINGSURFACE 08/09/2023 SPACE E 17 C 18 - 4 E -- LOADS: Amps VA LOAD TYPES: I=LIGHE E 19 A 20 44 E NORTHWEST-ROOFTOP UNI RIASEA'. 1O8 12720 2=RECEPTACLES SPACE E 21 B 22 - 4 E -- 'SEE10612203=MISC SPACE E 23 C 24 - 4 E -- PHASEC: 101 12080 4=MOTOR y� SPACE E 25 A 26 SPAC TOTAL' 37520 5=KITCHEN F SPACE E 27 B 28 SPAC GS (VA) LOADSERVED NOTE TYPE POLES NO PHASE NO POLES TYPE NOTE LOADSERVED (VA) 1680 DRYER 1 4 20 1 1 A 2 20 1 4 1 DRY B2 1080 LOAOINGBYTYPE CONNECTED NEC CODE DEMANDFACTOR DEMAND NOTES: 1680 DRYER 1 4 20 1 3 B 4 20 1 4 1 DRYER 1080 LIGHTING OVA 210.19 125% OVA E-DENOTES EXISTING BREAKER TO REMAIN. 1680 DRYER 1 4 20 1 5 C 6 20 1 4 1 DRYER 1080 RECEPTACLES OVA 220-44 1OkVA @ 100%,ELSE@ 50% OVA N-DENOTES NEW BREAKER REQUIRED. 1680 DRYER 1 4 20 1 7 A 8 20 1 4 1 DRY 1080 1680 DRYER 1 4 20 1 9 B 10 20 1 4 1 DRYER 1080 MISC OVA 220.60 100% OVA R-DENOTES TO REUSE EXISTING BREAKER. 1680 DRY ETR 1 4 20 1 11 C 12 20 1 4 1 DRYER 1080 MOTOR LARGESTMDT.: OVA 220-50 100%+LARGESTx 25% OVA D-DEDICATEBREAKER 1680 DRYER 1 4 20 1 13 A 14 20 1 4 1 DRYER 1080 KITCHEN #OF KIT UNITS: OVA 2 00.56 OVA 1680 DRYER 1 4 20 1 15 B 16 20 1 4 1 DRY 1080 TOTAL OA OA 1680 DRYER 1 4 20 1 17 C 18 20 1 4 1 DRYER 1080 1680 IDRYER 1 4 20 I 1 19 1 A 1 20 20 1 4 1 1 1 DRYER 1080 1680 DRYER 1 4 20 1 21 B 22 20 1 4 1 DRYER 1080 EXISTING PANEL SCHEDULE 1680 DRYER 1 4 20 ' 23 ° 24 20 1 4 DRYER '666 1680 DRYER 1 4 20 1 25 A 28 20 1 SPAR SCALE:NTS 1680 DRYER 1 4 20 I 27 B 28 20 1 SPAR 500 SIGN-EXTERIOR 3 20 1 29 C 30 20 1 SPAR SPARE 20 1 31 A 32 20 1 SPAR SPARE 20 1 33 B 34 20 1 SPAR 360 TELEPHONE TERMINAL BOARD 1 2 20 1 35 C 36 20 1 SPAR SPARE 20 1 37 A 38 20 1 SPAR SPARE 20 1 39 B 40 20 1 SPAR LOADING BY TYPE CONNECTED NEC CODE DEMANDFACTOR DEMAND NOTES: LIGHTING OVA 210-19 125% OVA 1.DEDICATED CIRCUIT. RECEPTACLES 540 VA 220-44 1OkVA @ 100%,ELSE@ 50% 540 VA MEG 500 VA 220-60 100% 500 VA MOTOR LA RGEST MOT.: 16807 36480 VA 220-50 100%+LA RGEST x 25% 38900 VA KITCHEN #OF KF.UNITS. O VA 220-56 O VA TOTAL IN A 105 A PANEL SCHEDULES SCALE:NTS LUMINAIRE SCHEDULE LUM INAIRE MANUFACTURER CATALOG NUM BBR LAMPS INPUT WATTS VOLTAGE MOUNTING COMMENTS Cn CIE LFHONIA LDW-40/20-L06AR-LSS-TRW-MVOLT-GZ10-E10WCP LED 22.5 120 SURFACE W T1 LRFgNW CPX-2X4-A LO8-80CRFSWW7-Al2-WOLT LED 452 120 RECESSED l T1E LFHONA CPX-2X4-ALO8-800RFSWVV7-AI2-MVOLT-E10WLCP LED 45.2 120 RECESSED T2 LUFIONA CPX-2X4-AL08-BOCRFSWWI-AI2-MVOLT LED 34.4 120 RECESSED T2E LRFIONW CPX-2X4-AL08-BOCRFSWYN-AI2-MVOLT-E10WLCP LED 34.4 120 RECESSED WEN LHONA BLWF2-20L-A UPWOLT-EZ I-LP840 LED 17 120 ABOVEMIRROR CDORDINATE MOUNTING HI WITH A RCHITB,T _ W32 LRFIONW BLWT9-40L-ADRMVOLT-FZI-LF840 LED 35 120 WALL MOUNTED BUILT IN OCCUPANCY SENSOR W WB2E LFMONA BLWF'4-40L-ADIR MVOLTEZ1-LP840-EL14L LED 35 120 WALL MOUNTED BUILT IN OCCUPANCY SENSOR X1 LITHONA LQM-S-W-3G1=77-E--N LED 062 120 CHI w NOTES: r , o 1.CONTRACTOR SHALL FTROVIDEAND COORDINATEALL FORURE MOUNTING ACCESSORIES. (/v'� �..� 2.PROVIDE EMERGENCY BATTERY PACK WHEN SHOWN ON PLANS. 3.VERIFY ALL CATALOG NUMBERS WITH SUPPLIER PRIOR TO SUBMITTING A BID. l �^ 4.DESIGNS ON FIRST NAMED MANUFACTURER ALTERNATE MANUFACTURERS AREACCEPTABLE SUBJECT TO COMPLINNCEWTH THES�IFl EN ED REQUIREMENTS MODEL NUMBER,TYPE AND OR CATALOG NUMBER t� ^� LUMINAIRE SCHEDULE U SCALE:NTS N y 7� U W ow a � -� O r ' W fT* 1021 H SCALE: AS NOTED DATE: CITY APPROVED PLANS DRAWN BY:o BY., 023 Reviewed for Code Compliance TSM CHECKED BY: PLANS MUST BE ON JOB SITE CD FOR ALL INSPECTIONS SHEET E3.0 Page 25 of 26 S ED 'METER PACK' 208/120V,3P,4W,800A BUS O 22KAIC W U Q W Z m c 2"TELECOMM CONDUIT TO MAIN TELEPHONE TERMINAL M M M I Z m 3 N BOARD IN EXISTING FIRE W m 3 m RISER SPACE GROUND PER Ii � KEY NOTES: ® _ _ v NEC 250 1. EXISTING METER AND DISCONNECTS TO BE REMOVED. EXISTING CONDUCTORS SPECIFICATION GRADE N N G [�N:E QUAD RECEPTACLE TO REMOVED BACK TO EXISTING TRANSFORMER. SEE MODIFIED ONE LINE :] BY UTILITY 4 6 DIAGRAM THIS SHEET. TRANE UTILITY N W SFORMER _ TENANT SPACE 2. NEW SERVICE ENTRANCE RATED DISTRIBUTION PANEL'PDP1'LOCATED ON o 0 TELEPHONE TERMINAL _ EXTERIOR OF BUILDING. N n o VENDOR m < TO FIRE ALARM BOARD TTB',4'z8'x3/4", _ _ _ (E) (E)PANEL 3. EXTEND EXISTING CONDUIT AND CONDUCTORS AS REQUIRED FROM EXISTING EQUIPMENT FIRE RETARDANT PLYWOOD GROUND METAL CONCRETE E PANEL'H'LOCATED IN FIRE RISER ROOM TO NEW DISTRIBUTION PANEL'PORT o ROD DISCHARGE ELECTRODE 208V/120 LOCATED ON EXTERIOR OF BUILDING. n�^ TELECOMM PROVIDER----_ 3/4"C PIPING 3/4"C 3/4"C 3P MUD z 200A 4. EXTEND EXISTING CONDUIT AND CONDUCTORS AS REQUIRED FROM EXISTING z 3 3/OG 3/OG 3/OG EXISTING PANEL IN EXISTING TENANT SPACE TO NEW METER LOCATED ON EXTERIOR OF w^o w o TELECOMM METER PROVIDER (2)3"C,EACH WITH BUILDING. PROTECTOR 4#350KCMIL,I#2G (E)PANEL PANEL PANEL 5. NEW METER PACK AND CT BY IDAHO POWER COMPANY. CT CAN AND BASE BY O 'H' 11' 'D1' ELECTRICAL CONTRACTOR. M =(E) CD PROVIDE 4"x10"CU 208V/120 208V/12C 208V/120 GROUND BUS BAR 3P 3P 3P 6. COORDINATE WITH IDAHO POWER FOR DOWNTIME WITH WHOLESOME BEAUTY 200A MLO 225A MLO 225A MLO SCHOOL TENANT PRIOR TO IDAHO POWER SHUTDOWN.TO BUILDING STEEL� RTU-1 PROVIDE CU GROUND TO TELECOMM GROUND BUS 3 2-1/2"C 2-1/2"C 3/4"C,3#8,1/8G AL 4#4/0,1(j4G 4/4/0,1�4G O (E)UTILITY oF�ss\ NS y FINISH FLOOR _ /F 244 225 22S TRANSFORMER i m SIZE CONDUIT AN 3P 3P SPACE 3P (E) 9 v GROUNDING CONDUCTOR PER SCHEDULE N1 N23 �4 N5 F\0 05 DISTRUBUTION PANEL-PDP1 THgIV A GOQ'P GROUND PER _ SERVICE ENTRANCE RATED 08/09/2023 NEC 250 - 208V/120,600A,3P,4W 35KAIC 3 TELEPHONE TERMINAL BOARD DETAIL 2 MODIFIED ONE LINE DIAGRAM 1 EXISTING ONE LINE DIAGRAM DEMO SCALSCALE:INTS SCALE:NTS (E)TTB (E) PANEL'E' PANEL'H' FIRE RISER (E)DISCONNECT DEMO KEY NOTES: (E)DISCONNECT O 1. EXISTING METER AND DISCONNECTS TO BE REMOVED. EXISTING CONDUCTORS 1 TO REMOVED BACK TO EXISTING TRANSFORMER. SEE EXISTING ONE LINE DIAGRAM DEMO THIS SHEET. (E)METER (E) (E) (E) �ll ^ C� 1--1 ORAGL (E)TRANSFORMER U 4 � 3 CITY APPROVED PLANS Reviewed for Code Compliance W ow PLANS MUST BE ON JOB SITE a a' FOR ALL INSPECTIONS W w °O F" SCALE: AS NOTED - BUILDING LOAD SUMMARY DATE: 08/09/2023 EXISTING TENANT SPACE PANELS DRAWN BY: ADDITION LOADS kVA AMPS TSM PANEL'E' 6 16 CHECKED BY: PANEL'H' NO ADDITONAL LOAD NO ADDITONAL LOAD CB DISTRUBUT10N PANEL-PDP1 PANELL1 27 74 4 POWER DEMO PLAN PANEL D1 36 05 ROOF TOP UNIT#1 11 30 SHEET SCALE:1/4"= 1'-0" 0 TOTAL: 82 225 208/120V E4.0 NORTH Page 26 of 26