HomeMy WebLinkAboutSpecial Inspection Reports for Robert Weed Dust Collector MATERIALS PAGE#1 2
PRINT DATETE 8/23/2013
M:\Reports\Twin Falls\2013
TESTING GT Reports\T130095n-Dust Collection Frame,
cc
Robert Weed Plywood,Twin Falls Facility,
N S P DTI O N 3351 Eldridge Avenue,Twin Falls,
CP ID\rpt001.docx
❑Environmental Services ❑Geotechnical Engineering ❑Construction Materials Testing ❑Special Inspections
Michael Arrington Phone: 208-733-5675
Starr Corporation, Inc. Fax:
2995 East 3600 North Other: EMAIL ONLY
Twin Falls, ID 83301
Project: Dust Collection Frame, Robert Weed
Plywood, Twin Falls Facility,3351
Eldridge Avenue, Twin Falls, ID
Permit#:
Project Manager: Nathan DeWitt
Inspector: Curtis Buatte
Inspection Date: August 22, 2013
INSPECTION REPORT
On the above date, our representative performed work on the referenced project as reported below.
MTI inspector arrived on site to perform a visual inspection of recommended weld modifications to the hopper
frame per the engineer's direction dated 8-5-2013. Item #1 on frame 1: perimeter angle at top of frame be
welded along full bearing surface approximate 36"; as modified: a 3/8" x 8" x 4" plate welded to center of
perimeter angles and hopper. Item #2 on frame 1: install 3/8" x 4" high reinforcing plate full length of gutter
perimeter angle and welded all around with 3/16" wrap around fillet weld; as modified: reinforcing plate
installed as required but welded with 3/16" intermittent welds 3" on 6" not completely wrapped. The inspector
takes no exception to quality of welds.
If there are questions concerning this report(rpt001),please contact the project manager at(208) 733-5323.
Respectfully submitted,
MATERIALS TESTING& INSPECTION,INC.
c ,4
Reviewed by:George DuPont
Project Manager
2283 Wright Avenue•Twin Falls, ID 83301 •(208)733-5323•Fax(208)733-0564
www.mti-id.com•mti(a)mti-id.com Revised February 2011
MATERIALS PAGE#2 2
PRINT DATE
8/23I2013
M:\Reports\Twin Falls\2013
TESTING GT Re ports\T1 30095n-Dust Collection Frame,
cc
Robert Weed Plywood,Twin Falls Facility,
INSPECTION 3351 Eldridge Avenue,Twin Falls,
ID\rpt001.docx
❑ Environmental Services ❑Geotechnical Engineering ❑Construction Materials Testing ❑Special Inspections
I 3
_. 00
df w
im, v
v
M
C7 ice` b hid rN
N
Cj\ fi
J i u
i
Q � th
to � m
i '1t
r o�
� Yt
C1
2283 Wright Avenue•Twin Falls, ID 83301 •(208)733-5323• Fax(208)733-0564