HomeMy WebLinkAbout22-1855 3351 Eldridge Ave-City Approved Plans OF I OF TIN vM'IS �IN YFAUfj City of Twin Falls �0 �� General Inspection Notes �0 0 SE'RV►NG SE RVtNG �/ NOTE: This is not a complete list and is not inclusive of all construction methods, materials or practices. These checklists are intended to serve as a guide for the items that cause the most issues during inspections and promote consistency in the application of the codes & standard practices. Compliance with all the provisions of applicable codes shall be required. O The information in the checklists is not, or was it ever intended to be, all inclusive. It does not include all code or individual plan requirements. It is intended to reflect local policies, procedures & practices within the City of Twin Falls. These checklists do not waive any specific code requirements not listed or allow for the decrease in the requirements of an engineered design. It also does not add requirements where the minimum of the code has been met. Z This page and all approved plans, associated documents, revisions & changes to the plans must be maintained on site and available for review at all times. FIRE BUILDING FINAL INSPECTION INFORMATION O Fire Alarm Inspection: Footing/Foundation Inspection: COMMERCIAL OCCUPANCY • * Fire alarm plans must be approved by the State Fire Marshal's office or if applicable the Twin Falls * All re-bar must be tied in place at time of inspection. Fire Marshal prior to installation and inspection. * All hold down anchors installed properly. Final inspections are required by multiple City Departments/Inspectors prior to getting your * Fire alarm system must be wired to call out from a land line, or with a cell dialer. (Voice over IP is not Certificate of Occupancy. allowed). Shear Inspection: U * Fire alarm system must be live and capable of calling the Twin Falls Dispatch Center on the day of * All hold downs must be installed per approved plans and manufacturers installation guide. Make sure to have the approved set of plans and inspection card on site for all inspections. testing. * Fasteners should not be overdriven and shiners should be removed and/or replaced. a) * Install the correct type of fastener at the correct spacing. If you have Special Inspections: Once the required special inspections have been completed a final Fire Sprinkler Inspection: report needs to be submitted to the building department certifying corrections of any discrepancies * Fire sprinkler plans must be approved by the State Fire Marshal's office prior to installation and Framing Inspection: noted in the special inspection reports.This final report can be submitted any time before requesting inspection. Underground fire sprinkler line must be inspected by the Twin Falls Fire Department prior * Accessibility standards are in compliance. (ICC A117.1-2009) occupancy. to be covered. * Required load paths to footing for all load points are installed. * Pipe or hose used for flushing the underground sprinkler line must be secure, incapable of * Stair rise and treads must meet code requirements. * Required Site Work inspections may be requested and completed as the work is done or as required movement, and is deemed safe by the inspector. *Min rise 4", Max rise 7", Max tread 11" by the specific department by contact the following: * Rough to cover inspection and hydro testing must be completed before covering or tenting the *Min nosing is 3/4", Max nosing is 1 1/4" and cannot differ in length by more than 3/8" above ground fire sprinkler system. * Provide required up-lift protection for all trusses. - Planning&Zoning (parking and landscaping) Planner-208-735-7270 or Office-208-735-7267 Kitchen Hood Inspections: Final Inspection: - Engineering (Retention, curb, gutter, sidewalk, drive approaches) * Fire suppression system must be installed and ready for trip test (trip link, balloons, etc.) prior to * Landings to meet minimum code requirements. (Doors 1010.1.6, Ramps 1012.6, Stairs 1011.6) Lab inspection line 208-735-3446 inspection. * Accessibility Standards are in compliance.(ICC A117.1-2009) -Street Department (road cuts) * Kitchen hood must be wired to initiate the fire alarm upon activation of the fire suppression system. * Egress door sign-age is posted and correct verbiage is used. Office- 208-736-2226 (The only exception to this is if the building does not require a fire alarm to be installed) * "DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED" * All electrical outlets, lighting, and appliances under the kitchen hood must shut down upon *Correct hardware has been installed on all doors. * When you are ready for any Fire Department inspections please call (extinguishers, activation of the fire suppression system. *Panic hardware is installed where required. fire/alarm/sprinkler systems): * Main gas valve must be installed and must shut down upon activation of the fire suppression *Accessible hardware is installed where required. Fire Marshall -208-735-7232 system. * Handrails shall be installed where required. * Exhaust fan must be capable of running continuously upon activation of the fire suppression * Stairways shall have handrails on each side. * When you are ready for a building final inspection on the structure: system. * All racking and shelving to be in place. Make sure you have the final inspections on the plumbing, electrical, and mechanical work. * Make up air must be capable of running continuously upon activation of the fire suppression system. * All Exit signs are field verified. (must be visible—nothing can block the line of sight) Call the building inspection line 208-735-7333 * Maximum Occupancy signs posted where required. All departments will be notified by this office to go do their final inspection. Final Inspection: * Special Inspection reports and balance reports need to be received by our office. * Address must be posted as outlined on the approved set of plans or previously approved by the If there is an elevator in the building please contact the Division of Building Safety at the following link Twin Falls Fire Marshal. PLANNING &ZONING for any permits/inspections: http://dbs.idaho.gov/programs/industrial/fagEL.html I ENGINEERING Landscaping: Once ALL the departments have signed the Certificate of Occupancy the Building Official will sign and * Our code allows for us to issue a TCO with landscaping incomplete; however, we cannot extend the then it will be ready to be picked-up or emailed. In order to streamline and eliminate confusion in regards to the engineering department commercial TCO beyond the current planting season.This means that we will work with the applicant on a V J permit inspections,the following will need to be inspected prior to signing the Certificate of definitive date of their choosing, but not typically beyond 2-3 months. If you need a Temporary Certificate of Occupancy there is a $1,000 refundable deposit required. All Occupancy. All inspections will be completed using the City of Twin Falls approved (stamped) plans. departments are required to sign and give a list of outstanding issues. Once the temporary is all signed Trash Enclosures: &the list made you will need to come in and sign stating you know what those issue are, that you will Storm Water Facility Inspections: (3 phases) * Trash enclosures should be finished before a final inspection is requested,this includes the front have them completed by the specified time, and will call for inspection as those items are completed. * Inspection of excavation, including dimensions and geotextile fabric. All adjoining trenches leading gate on the enclosure. Per our code, we cannot issue a TCO if this item is not completed. It is up to each department to determine if you meet their qualification for temporary occupancy. to storm water facilities also need to be excavated and inspected. * Inspection of storm drain pipes (per plans) need to be in place (not covered)for visual inspection. Note: If a building was originally done as a shell, the shell building permit is required to be finaled The drain rock must meet ISPWC section 801 Drain Rock requirements. All pipe connections to storm prior the tenant improvement permits can be finaled. In addition, if Temporary Occupancy is needed water facilities must be completed. there will be $1,000 refundable deposit for each permit. * Inspection of completed storm water facilities with the above referenced drain rock and geotextile fabric showing proper cover and overlap. • Site Inspections: * Verify that the parking lot layout (design) &striping matches the plans * Verify that the parking lot surface is an approved "hard" surface * Verify that there is ADA compliant access from the Right-of-Way(ROW)to the building envelope Right-Of-Way Inspections: * Verify driveway approach widths & locations according to plans CITY APPROVED PLANS * Verify ADA compliance of Curb/Gutter, Sidewalks, and Sidewalk/Driveway combinations O * Verify ROW connections to other Agencies/Entities meet's ADA tolerances Reviewed for Code Compliance Flood Plain Inspections: PLANS MUST BE ON JOB SITE * Verify flood plain location and compare plans to the site * Verify the commercial buildings are one foot above base flood elevation >% When ready for inspection please call the Engineering inspection line at (208) 735-3446 for same day FOR ALL INSPECTIONS 4�J• inspections call before 7:30 am. Having these inspections approved when the work has been completed will ensure the Certificate of Occupancy is issued in a timely manner. U 2015 IBC Section 105.4 Validity of Permit: The issuance or granting of a permit shall not be a permit for, or approval of, any violation of any of the provisions of this code or of any other ordinances of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the building official from requiring the correction of errors in the construction documents and other data. The building official is authorized to prevent occupancy or use of a structure where in violation of this code or of any other ordinance of this jurisdiction. Page 1 of 97 LICENSED ARCHITECT AN OFFICE REMODEL FOR: °�T08 ROBERT WEED PLYWOOD sr 6/i6/2022 222 6/ PLAN 3351 ELDRIDGE AVE. TWIN FALLS, IDAHO 83301 Based on20 8NALYSIS Editionofl.B.0 Architect of Record Laughlin Ricks Architecture,L.L.C. SHEET INDEX Engineer: Sheet Number Sheet Name GENERAL NOTES: 1. ALL WORK SHALL MEET CURRENT STATE,LOCAL CODES,ORDINANCES,&2018 IBC AO-0 TITLE SHEET Job Address: 3351 ELDRIDGE AVE.TWIN FALLS,ID.83301 2. ALL MECHANICAL,ELECTRICAL,&PLUMBING WORK SHALL MEET ALL CURRENT APPLICABLE AO-1 CODE ANALYSIS STATE&LOCAL CODES. Legal Description: AO-2 CODE REQUIREMENTS 3. ALL UTILITIES SHALL BE PROPERLY IDENTIFIED&LOCATED BEFORE WORK BEGINS ON AO-3 CODE REQUIREMENTS PROJECT. Occupancy Classification: B,F-1 Occupant Load Per Area: A1-0 SITE PLAN 4. CONTRACTOR SHALL VERIFY ALL CONDITIONS&DIMENSIONS AT THE JOB SITE&NOTIFY OFFICE,PLYWOOD MANUFACTURING B=27 A2-0 DEMOLITION PLAN THE ARCHITECT OF ANY DIMENSIONAL ERRORS,OMISSIONS,OR DISCREPANCIES BEFORE Occupancy Use: CO BEGINING OR FABRICATING ANY WORK. A2-1 OVERALL MAIN LEVEL FLOOR PLAN F-1=93 A2-2 ENLARGED MAIN LEVEL FLOOR PLAN 5. DO NOT SCALE DRAWINGS. A2-3 ENLARGED 2ND LEVEL FLOOR PLAN 6. ALL DOOR HANDLES SHALL BE LEVER TYPE,ALL DOOR HARDWARE SHALL BE A.D.A Allowable Stories Per Code: Provided: (IBC Table 504.4) Total: 120 A5-0 SECTIONS COMPLIANT AS PER CURRENT ANSI117.1 48.550OVERALL 7. AT MAIN ENTRANCE DOOR SHALL HAVE SINGLE ACTION LOCKING DEVICE W OR SIGNED Floor Area: Basement: 1st. 1,950 SF NEW Exits Required: Basement: 1st: 2 A7-O CEILING PLANS 'THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." A7-1 CEILING DETAILS 2nd Floor: 1,700 BE 3rd: Total: 2"d: 3rd: 411. A9-0 SCHEDULES S-001 GENERAL STRUCTURAL NOTES Total Required Exits Per Occupant Load: 2 (IBC Table 1006.3.2) S-002 INSPECTIONS 9T-6" S-101 FOUNDATION PLAN Actual furthest travel distance to exit: (IBC Table 1017.2&1006.2.1) S-102 SECOND FLOOR FRAMING PLAN Penetrations?Show Approved Listed Products on Plans: S-103 SECOND FLOOR CEILING FRAMING S-501 DETAILS Type of Construction: V6 Allowable Building Height: so' S-502 DETAILS SEE IBC Seismic Design Category: vC Allowable Area Calc's: O S-510 STAIR DETAILS LL SECTION 507.5 n B-3s,000 sF F- 34,000 SF z 0 S-602 SCHEDULES Automatic Sprinkler System: Yes: No: (IBC Table 506.2) Z O Maximum Floor Area Allowed: UNLIMITED Exit Signs: Yes: E No: Lu 0j Special Inspections Required? Yes: No: x Emergency Lights: Yes: E No: > J o Firewalls Required? Yes: No: x Fire Extinguishers Shown: Yes: E No: 0 Of (Specify Type&Rating) (IFC Section 906) 0 LL d W z � Occupancy Separation Use? Yes: No: x Fire Hydrant Locations Shown: Yes:_No: x �j LU W Areas of Refuge Required? Yes: No: x Vestibule Required: Yes: No: x Z w 2 (IBC Section 1009.2,3,4) Q o U) x Z W a W Area Separation Required? Yes: No: Classified Areas? Yes: No: x W m 9 J (Show on plans&Show Areas) Q 0 M Fire Resistance Ratings of BLDG Elements: 0 (IBC Table 601) (Specify Rating) Minimum Roof Class: Q (IBC Table 1505.1) Exterior Wall Openings: x (IBC 705.8) Fire Doors: X (IBC Table 716.1.2) Fire Alarm System: x (IBC 907.2) Fire Flow and Duration: Corridor Width: X (IBC Table 1020.2) Rated Structural Frame: Yes: No: x Rated Corridors: Yes: No: x (Roof Supports Only) (IBC Section 1020.1) Rated Bearing Walls-Exterior: Yes: No: X Rated Bearing Walls-Interior: Yes:_No: X 0 ABBREVIATIONS Rated Nonbearing Walls-Exterior: Yes: No: X Rated Bearing Walls-Interior: Yes: No: X pp (>30'Fire Separation) (Roof Supports Only) r •� o AC ACOUSTICAL CEILING DIA DIAMETER GYP BD GYPSUM BOARD PL PLATE,PLASTIC LAMINATE T THREAD Rated Nonbearing Walls-Exterior: Yes:_ No:__x_ Rated Nonbearing Walls-Interior: Yes: o ADJ ADJUSTABLE-ADJACENT DIM DIMENSION HB HOSE BIB P-LAM PLASTIC LAMINATE TBB TILE BACKER BOARD (10'-30'Fire Separation) No: x C AFF ABOVE FINISH FLOOR DF DRINKING FOUNTAIN HC HANDICAPPED PLWD PLYWOOD T&G TONGUE AND GROOVE W AL ALUMINUM DP DEEP HDR HEADER PNL PANEL TO TO OF Rated Floor Construction: Yes: No: x Rated Roof Construction: Yes: No: x ALT ALTERNATE DR DOOR HIMHOLLOW METAL PORC.TILE PORCELAIN TILE TOW TOP OF WALL , ANOD ANODIZED DS DOWNSPOUT HORIZ HORIZONTAL PR PAIR TPD TOILET PAPER DISPENSER Ir� s- B^ AP ACOUSTICAL WALL PANEL DWG DRAWING HT HEIGHT PSF POUNDS PER SQUARE FOOT TSCD TOILET SEAT COVER DISPENSER Lighting Layout and COM Check? Yes:_ No: X * N APPROX APPROXIMATE E EAST HVAC HEATING/VENTILATING/ PSI POUNDS PER SQUARE INCH TT TIRE TREAD V V ARCH ARCHITECT(-URAL) (E) EXISTING AIR CONDITIONING PT PAINT,PRESSURE TREATED TYP TYPICAL Comments rlN w AW ACOUSTICAL WALL EA EACH ILO IN LIEU OF PTO PAPER TOWEL DISPENSER UNO UNLESS NOTED OTHERWISE AWE ACOUSTICAL WALL FABRIC EJ EXPANSION JOINT INSUL INSULATION QT QUARTZ TILE U/S UNDERSIDE BLDG BUILDING EL EMERGENCY LIGHTING INT INTERIOR R RISER,RADIUS VB VAPOR BARRIER 4 a BM BEAM ELEC ECLECTRIC(-AL) JNT JOINT RB RESILIENT BASE VCT VINYL COMPOSITION TILE Boo BOTTOM OF DECK EP ENAMEL PAINT KID KNOCK DOWN RD ROOF DRAIN VERT VERTICAL BOT BOTTOM EQ EQUAL LAV LAVATORY RO ROUGH OPENING VGF VINYL GYM FLOORING BTWN BETWEEN EW EACH WAY MCFP MULTI-COLORED FINISH RR RESTROOM VIE VINYL INDUSTRIAL FLOORING CB CATCH BASIN EXG EXISTING PAINT SYSTEM RSF RUBBER SHEET FLOORING VR VAPOR RETARDER CBT CABINET EXP EXPANSION MDo MEDIUM DENSITY S SOUTH VT VINYL TILE CG CORNERGUARD EXT EXTERIOR OVERLAY PLYWOOD SC SOLID CORE VWF VINYL WALL FABRIC r-! cJ CONTROLJOINT FA FIREALARM MECH MECHANIC(-AL) SCU STRUCTURAL CLAY UNIT W WEST nPLAN ANALYSIS CL CENTERLINE FD FLOOR DRAIN MFR MANUFACTURE(-R) SD SOAP DISPENSER W/C WATER CLOSET U 1/4"=1'-O" `y CLG CEILING FE FIRE EXTINGUISHER MIN MINIMUM SDSV STATIC DISIPATIVE SHEET VINYL WD WOOD CUR CLEAR(-ANCE) FEC FIRE EXTINGUISHER CABINET MISC MISCELLANEOUS SF SPECIALTY FINISH W/o WASHER&DRYER CMT CERAMIC MOSAIC TILE FF FACTORY FINISH,FINISH FLOOR MRGB MOISTURE RESISTANT SFGL SAFETY GLASS Woo WINDOW CMU CONCRETE MASONRY UNIT FIN FINISH(-ED) GYPSUM BOARD SHTG SHEATHING WE WALL FABRIC cc CLEAN OUT FLR FLOOR(-ING) MTL METAL SIM SIMILAR WFV WOOD FACE VENEER COL COLUMN END FOUNDATION N NORTH SL SLOPE WG WIRE GUARD CONC CONCRETE FOC FACE OF CONCRETE (N) NEW SND SANITARY NAPKIN DISPENSER WGL WIRED GLASS CONT CONTINUOUS,CONTINUE FRP FIBERGLASS REINFORCED NA,N/A NOTAPPLICABLE SP SPACE(-S) WM WIRE MESH CORR CORRIDOR PLASTIC PANEL NIC NOT IN CONTRACT SPEC SPECIFICATION W/O WITHOUT CP CARPET FRVR FLAME RESISTANT VAPOR BARRIER NDU SANITARYNAPKIN so SQUARE WOC WALK-OFF CARPET CITY APPROVED PLANS CS CONCRETE SLAB,SEALED FT FOOT,FEET DISPOSAL UNIT S/S STAINLESS STEEL WP WATERPROOFING CT CERAMICTILE FTG FOOTING NOM NOMINAL ST STAIN WPS WALL PROTECTION SYSTEM CTJ CONTROLJOINT FWC FABRIC WALL COVERING NTS NOT TO SCALE STL STEEL WR WATER RESISTANT DATE: 6/i6/2022 CTR COUNTER(-TOP) GA GAUGE OC ON CENTER STIR STRUCTURE(-AL) WRGB WATER RESISTANT GYPSUM Reviewed for Code Compliance DBL DOUBLE GALV GALVANIZED OD OUTSIDE DIAMETER STRG STORAGE WALLBOARD RCR/LJS RCR DET DETAIL GH GARMENT HOOK OPP OPPOSITE SV SHEET VINYL FLOORING WWF WELDED WIRE FABRIC PLANS MUST BE ON JOB SITE GMM GLASS MESH MORTAR BOARD PCMU PRE-FACED CMU W/ WITH FOR ALL INSPECTIONS AO-0 Page 2 of 97 LICENSED ARCHITECT —as TABLE 504.4 TABLE 506.2 ALLOWABLE NUMBER TA STORIES ABOVE GRADE PLANE ALLOWABLE AREA FACTOR(A,=NS,S,S13R,OR SM.AS APPLICABLE)IN SQUARE FEET sraTE ioa(o TYPE OF CONSTRUCTION TYPE OF CONSTRUCTION 6/16/2022 OCCUPANCY OCCUPANCY TYPE I TYPto- 71��4o PE III TYPE IV TYPE V TABLE N FEET CLASSIFICATION TYPE I TYPE II TYPE III TYPE IV TYPE V CLASSIFICATION SEE FOOTNOTES ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE SEE FOOTNOTES A B A B A B HT A B A B A B HT A B TYPE OF CONSTRUCTION Ns UL UL m 19,00o a6,0o0 IS.- %M OCCUPANCY TYPE TYPE II "TYP Ns uL n 5 a s 3 5 3 2 B St 1W.000 CLASSIFICATION SEE FOOTNOTES B UL UL o0]6,6w 1a4,o0o 12.000 ,6 A B tA � B UL UL 1 Sao W STOW 1ofi,000 Ko00 27,0. UL 16055 NS UL 11 4 2 a 2 4 2 1 F-i S1� 100.000 A,B,E,F,M,S,U a0S UL UL W 00 36,000 100,500 42,000 25,500 TABLE 504.3 n TABLE 504.4 rl TABLE 506.2 1/4 -1-0 TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING(HOURS) TYPE OF CONSTRUCTION BUILDING ELEMENT TYPE I TYPE II TYPE III TYPE IV JEA B A B A B HT PRIMARY STRUCTURAL FRAMe(SEE SECTION zoz) TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE-Ao BEARING WALLS EXTERIOR INTERIOR FIRE SEPARATION OCCUPANCE OCCUPANCE GROUP DISTANCE=X(FEET) TYPE OF CONSTRUCTION OCCUPANCE GROUP He GROUP F-1,M,S-1' A,B,E,F-2,I,R,S-2,UN O NON BEARING WALLS AND PARTITIONS LL EXTERIOR SEE TABLEem X<5 All 3 2 1 1--- 0 TABLE 508.4 O NO REQUIRED SEPARATION OF OCCUPANCIES(HOURS) RING WALLS AND PARTITIONS 5<X<10 IA 3 2 1 Z TBRoR ° Others 2 1 1 W N OCCUPANCY A,E I-1a1 I3,I-4 1-2 R F-2,S-2B,U M S 1' H-1kS H-2 H-3,H-4 H-5 IA,IB 2 1 1 w } FLOOR C'NITRU"'IAND S NS S NS S NS S NS S NS S NS S N3 NS S NS S NS SECONDARY ME ERS(SEE SECTION ere) 1 10<X130 1113,VB 1 J o Others 1 1 1 O a- U) B,F 1.M.s-1 - - - -- -- - - - -- - N ry z ry RaIF carvsrnucnoN o AssOIIATeo v Q LL SECONDARY MEMBERS(SEE SECTION 2.) X>3O All O O O LLJ Q y TABLE 508.4 TABLE 601 Z w Z 1/4"=1'-0" 1/4"=1'-0" TABLE 602 Q o Q LU W m 9 0 w Q 0� - TABLE 1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE- FUNCTION OF SPACE OCCUPANT LOAD FACTOR- SECTION 507 OCCUPANCY WITHOUT SPRINKLER WITH SPRINKLER UNLIMITED AREA BUILDINGS BUSINESS AREAS 150 GROSS SYSTEM(faet) SYSTEM(feet) CONCENTRATED BUSINESS USE AREAS q B,F-1,M,R.s1 507.5 TWO-STORY BUILDINGS.THE AREA OF A GROUP B,F,M OR S BUILDING NOT MORE THAN TWO STORIES ABOVE GRADE PLANE SHALL NOT BE LIMITED -1 NOT 1E 1 TEo zsro WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER $„( WAREHOUSES 500 GROSS SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 AND IS SURROUNDED AND ADJOINED BY PUBLIC WAYS OR YARDS NOT LESS THAN 60 FEET IN WIDTH. n TABLE 1004.5 SECTION 507 n TABLE 1017.2 U 1l4"=1'-0" J 1/4"=1'-0" U 1/4"=1'-0" M U A cd �o �Q'+w U �1-- U 'T �I N U I'' C� CITY APPROVED PLANS Reviewed for Code Compliance DATE: 6/i6/2022 PLANS MUST BE ON JOB SITE oCRLJS RCR FOR ALL INSPECTIONS AO-1 Page 3 of 97 LICENSED ARCHITECT -as 42� D, n/�//A, NON ABSORBENT WATER CLOSET(W/C) TOILET PARTITIONS R HEIGHT OF LAVATORIES HEIGHT OF MIRRORS STADTE ioaio NON ABSORBENT SURFACE TO 4'-0" SEAT HEIGHT U 6/16/2022 SURFACE T04'-O" J ABOVE FINISH FLOOR WALL 60" ABOVE FINISH FLOOR 3 yr'MIN ¢ 18 20 3 MIN 3 5 0" 7 42". 39"-41 - `O 24" CLEAR w < ��` ¢ -� AMBULATORY STALL 4om 15" 2-0„1�-0,� 12"MAX J r- HEIGHT OF URINALS �¢ GRAB MIN MIN GRAB O PILASTER ANSI A117.1-2003,605.2 <� - BAR BAR g RIM HT. J IM HT. uu T.O.SEAT HT. _ T.O.SEAT RIM LL 60"MIN J LL - - n„ Z M - - f RIM T. O Z g CLE7 I L�6 EAR N y 16"-18" 24"MIN Or TOILET PARTITIONS ACCESSIBLE / � STANDARD URINAL SCREENS ACCESSIBLE STANDARD ACCESSIBLE STANDARD 18"X30" 20"X60" WATER CLOSET(W/C) CLEAR 48'MAX NDU WHERE WATER CLOSET(W/C) PROVIDE ONE GARMENT URINAL URINAL LAVATORY LAVATORY MIRROR FULL MIRROR INDICATED HOOK AT EACH TOILET UNO PARTITION DOOR PROVIDE ADA PADS,PER SPECS IN FORWARD REACH DISPENSERS 1.PROTECTION UNDER SINKS 606.6 EXPOSED PIPES AND SURFACES.WATER SUPPLY AND DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT.THERE O NOTE:AT RESTROOMS/TOILET ROOMS THE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. TOWEL,SOAP,AND SANITARY NAPKIN ¢ DISPENSERS ARE TO BE INSTALLED SO AS 2.FLUSH CONTROLS - x ¢ _ .-a"e e a NOT TO EXCEED 40"AFF TO ANY OPERATING 604.E FLUSH CONTROLS.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.HAND w e Z Z CONTROLS,RECEPTACLE,OR DISPENSER. OPERATED FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER CLOSET. °? 3 p _� F v g EXCEPTION:IN AMBULATORY ACCESSIBLE COMPARTMENTS COMPLYING WITH SECTION 604.9,FLUSH m CONTROLS SHALL BE PERMITTED TO BE LOCATED ON EITHER SIDE OF THE WATER CLOSET. O LL ACCESSIBLE SOAP TOILET NAPKIN TOILET GARMENT MOP)P FIRE EXTINGUISHER SANITARY BABY CHANGING 3.TOILET PAPER DISPENSER. PAPER TOWEL DISPENSERS PAPER DISPOSAL SEAT COVER HOOK HOOK)K CABINET NAPKIN STATION 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL COMPLY WITH SECTION 309.4 AND SHALL BE 7 DISPENSER (SD) DISPENSER UNIT DISPENSER (GH) (MH)H) (FEC) DISPENSER INCHES(180 mm)MINIMUM AND 9 INCHES(230 mm)MAXIMUM IN FRONT OF THE WATER CLOSET (PTD) AS INDICATED (TPD) (NDU) (TSCD) MOUNT ON BACKSIDE PROVIDE ONE @@ LOCATION DIRECTED MEASURED TO THE CENTERLINE OF THE DISPENSER.THE OUTLET OF THE DISPENSER SHALL BE 15 AS INDICATED (OFCI) @ ALL WIC PROVIDE ONE PROVIDE ONE ABOVE EA. OF ALL RESTROOM DOORS ALL CUSTODIAL4L BY OWNER INCHES(380 mm)MINIMUM AND 48 INCHES(1220 mm)MAXIMUM ABOVE THE FLOOR,AND SHALL NOT (OFCI) LOCATIONS @ ALL ADA RESTROOM WATER CLOSET &PARTITIONS,U.N.O. SPACES=S BE LOCATED BEHIND THE GRAB BARS.DISPENCERS SHALL NOT BE OF A TYPE THAT CONTROL (OFCI) STALLS,WOMEN DELIVERY,OR DO NOT ALLOW CONTINUOUS PAPER FLOW. GENERAL-FIXTURE MOUNTING n HEIGHTS L 1/4"=1'-0" O LL H 0 RADIUS AT ALL CORNERS Z O REE D Lu c O o PA K NG GREEN TEXT&BORDER G LLJ �- ro Z > J e LLCu BLUE SQUARE,WHITE SYMBOL U ' G JAI 0' C) LLW F = WHITE BACKGROUND Lw COUNTER SINKCOUNTER SINKw Z w p — HOLES FOR SCREW HOLES FOR SCREW r-O w 3j w V HEAD(TYP) HEAD(TYP) N z W-X I U a ALUMINUM SIGN W/TAMPER z ¢ LLI 8" 8" w o_w N w g a RESITANT SIGN BOARD Q O O O O r O vi MOUNTING FASTENERS o RADUSED RADUSED ¢w w U z z o` LL z-y, 2"GALV.STEEL POST Z w w co o w �o CORNERS o CORNERS Q¢w C�Q O O Q W 5.-0.. AFF LU ��` 5'-0" AFF / z 0¢w / 0e o O= �O EN OMEN / g w<O zOm wwz �LL� MIN 314"RAISED RAISED MIN 314"RAISED RAISED \ 30 70 LETTERS BRAILLE LETTERS BRAILLE \ co SURFACE MOUNTED PANEL SURFACE MOUNTED PANEL \ SIGN TYPE A SIGN TYPE B "I - n GENERAL-SIGNS GENERAL-SIGN MOUNTING HEIGHT r1 ACCESSIBLE ENTRANCE n ACCESSIBLE PARKING SIGNS 1 1/2"=1'-0" 1/4"=1'-0" 1/4"=1'-0" 1"=1'-0" U U p.l M 1-0 U A > � � V » v � U 'T' 8"MIN P 3-I R MAX MAX '-q Cd UNOBSTRUCTED FORWARD REACH UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH FORWARD REACH (A) I I 1 20 TO 25 10T024 =-O CITY APPROVED PLANS MAX _� DATE: 6/i6/2022 OBSTRUCTED HIGH FORWARD REACH (B) OBSTRUCTED HIGH SIDE REACH OBSTRUCTED HIGH SIDE REACH Reviewed for Code Compliance RCR/LJS RCR (A) (B) FLOOR 1- 1"MIN - cn�k"e PLANS MUST BE ON JOB SITE n OPERABLE PARTS&REACH RANGES n LAVATORY CLEARANCE /� U 3/8"=1'-0" U FOR ALL INSPECTIONS AO-2 Page 4 of 97 LICENSED ARCHITECT -as 2TO(68 DES THE MANDATORY z 2 6 mm)FLOOR TO UNDER- c? SIDE1'-0" 32"MIN MOUREOUIREMENTS WHEN sWE IC.. I MOUNTED IN THIS MANNER. 6/16/2022 v MIN 35" A.D.A.ACCESSORY c=::= APRON C== I x_x O 35" 1'-6' 32"MIN FLOOR LINE FRONT APPROACH FRONT APPROACH -5"MAX FOR FORWARD APPROACH PULL SIDE,CLEARANCE PUSH SIDE,CLEARANCE 3\"MAX FOR PARALLEL APPROACH 2 DRINKING FOUNTAIN DETAIL L 1/4„_�,_0„ I I I I _ T-0' 32"MIN - 1 3'-6" 32"MIN 1 MIN 35" MIN 35" I 4"BACK ANDSZDE SOLID TF SURFACE BACKSPLASH T-3 15/16" HINGE APPROACH HINGE APPROACH APRON PULL SIDE,CLEARANCE PULL SIDE,CLEARANCE n F- -r 71 WRAP PIPES WITH INSULATI WOOD ACCESS PANEL,PT, l MATERIAO L O 1 12"X12",VERIFY z L.L z 12"` 35" 22" L J _ O MIN MIN 32" MIN 1 24" 35" Z e MIN MIN 32" ui O H W > ro Z 'IF BOTH CLOSER AND TILE BASE > -1LLI LATCH ARE PROVIDED Q `54"MIN IF E Q LL LLI 48"MIN IF BOTH CLOSER IS FRONT VIEW CLOSER AND LATCH PROVIDED Lw ? PROVIDED u d HINGE APPROACH Z w LLI PUSH SIDE,CLEARANCE LATCH APPROACH s" Q 6f PULL SIDE,CLEARANCE 4"BACK AND w m o 0 SIDE SPLASH O Q SOLID SURFACE Q M V COUNTERTOP 5'-0"MIN 5'-0"MIN I \ APRON E 24 35" // —— \ r INSULATE PIPES AT MIN MIN 32" z ALL ACCESSIBLE / \ CUT SKIRT TOP TO MATCH / b BOWL PROFILE WITH I TOILETS i \ 9 z CLEARANCE TO REMOVE SKIRT `48"MIN IF \ I — — WOOD DEMOUNTABLE CLOSER IS \ / z SKIRT WITH FIXED SIDES PROVIDED \ / \ / N 81/i6"MIN 911/16" 6"MAX U 3'-0"MIN 1'-0"MIN 1'-0"MIN L�.Q LATCH APPROACH TILE BASE PER O0 PUSH SIDE,CLEARANCE ELEVATIONS V CIRCULAR T-SHAPED A TURNING SPACE TURNING SPACE SECTION VIEW (j n DOOR CLEARANCE REQUIREMENTS TYP ADA VANITY 'u N �I N C� CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RCR/LJS RCR PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS AO-3 Page 5 of 97 �`-` LICENSED r ARCHITECT I ` �� PIL905]OS I 6/16/2022 ` PROPERTYLINE i 19 wi RAILROAD EASEMENT al �� I I i EXISTING DUMPSTERS IRRIGATION EASEMENT I I Q I O1< LL Z O 17 E)PARKING SPOTS W O PLUS 1 E)ADA SPOT i W I > J a 10 E)PARKING SPOTS O a j I p LL I W I i H �: � Z Z w Q Z W a 3 W Co 9 W I EXISTING BUILDING I I I I I I I I I U I AREA OF WORK I M I U I (E)FIRE HYDRANT I \$:Lq W �M I 0 -- -- -- -- --------•--------------•----- -- -- -- — ELDRIDGE AVENUE — -- -- -- -- ---------"-----------•--•--.--.PROPERTY LINE A� -__-.--.-----.-----_----__--_--_--_--_----- w? I� 1 SIS1"-30'-O" NORTH CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RCR/LJS RCR PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Al-0 Page 6 of 97 LICENSED ARCHITECT -as STATE IC.. 6n6/2022 DASHED LINES INDICATE ITEMS TO BE DEMO'D A O z ai LLI z w II " �' If`" �`.`:: • ,:I Imo :.`: Q � o � Z w O w m H I•I"::.: _ -. . . is .: Imo,:.'_ :_-" ..:II,..: "..".-... ::...,' `•: : ..,. .._ ..".. .;::': J M !� O �M REMOVE 3)EXISTING WINDOWS, 2 ON 2ND LEVEL,1 ON LOWER LEVEL; V * N A PATCH AND REPAIR AS ROD wy'I O DEMOLITION FLOOR PLAN C� CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RcwL�s RCR D,� cn�ke PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Page 7 of 97 LICENSED ARCHITECT -as 1. ANY LOCATION WHERE WOOD IS TOUCHING CONCRETE,MASONRY,CMU,OR STEEL SHALL BE PRESSURE TREATED. 2. ALL WOOD SHALL BE DOUGLAS FIR#2 OR BETTER. 3. ALL NEW INTERIOR WALLS SHALL BE M W/5/8"GYP BD EA.SIDE U.N.O. 4. ALL NEW INTERIOR WALLS SHALL HAVE SOUND BATT INSULATION srnTE iC.. A B C D E F G H J l K ) 6/16/2022 GENERALNOTES I I I I I I I I I I 234'-0" 26'-0" 26'-0" 26'-0" 1, 26'-0" 26'-0" 26'-0" 26'-0" 26'-0" 1, 26'-0" IEXIT EXIT 1 Z Q J � d O �- - � - - - - - - - - - - - - - - � z O OJ W O LL. PRODUCTION M W AREA W > J ° W —TO-81 O d J 48,550 SF 0 LL Z LLI Z Q Q ED z W � � Lu m W Q 0 MO INSULATE"BLUE"WALLS W/R-21 BATT INSULATION ALL INTERIOR WALLS SHALL HAVE SOUND BATT INSULATION A2-2 Q� 3.1 ~- U Lw N Lw IIII up I 3.2 - I '~ \Q wM I _ I � � >o 4 EXIT T EXIT A •^ U p Px —-—-— — A.1 — ---—--- A VOID c� See C/0#1 1 OVERALL NEW FLOOR PLAN CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RCR/LJS RCR PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS A2-1 Page 8 of 97 LICENSED sm; rtable fire extinguishers to meet the ARCHITECT PR-9 as ments of 2015 IFC 906.1 /NFPA 10. 5 lbs.portable fire extinguisher withum rating of 2A-10B.el distance from an extinguishert exceed 75 feet.The extinguisher sraTE ;C..mounted in a conspicuous location 6/16/2022 ucted and unobscured from view (E)ELECTRICAL SERVICE Exit Signs: A Emergency power shall be provided for exit signs as required in Section 4'-0' EYE WASH SINK 1013.6.3.The system shall be capable CLEAR UTILITY SINK of powering the required load for a duration of not less than 90 minutes. ALL INTERIOR WALLS SHALL HAVE SOUND BATT INSULATION w ii> m a OPEN TO ABOVE- - 102 w a LOBBY 3, _ _ — �— \ 1008.3.3 Rooms and spaces:In the event of power supply m 101 _N _ _ — — m- — 32 42"HIGH PARTITION failure,an emergency electrical system shall automatically illuminate all the followingareas: 1.Electrical equipment rooms. \ 2.Fire command centers. 6 3.Fire pump rooms. z D \ 4.Generator rooms. 5.Public restrooms with an area greater than 300 square feet a 2•-6,. 3' 0" �\ PASS THRU WINDOW i,\ (SLIDING GLASS)W/ MARBLE SHELF AT � 2'-10^AFF. OFFICE -------- OFFICE \ Z Q 3'x X FIXED WINDOW; 1O2 103 \ J m i ALIGN TOP OF WINDOW 11'-4" 63/4" 4'-0" 6314" 7 14'-8718" 63/4" \ Il W/TOP OF DOOR LL 0 SEE DETAIL 3/AO-3 -- Q O WOMEN'S ;� 0 LL RESTROOM -' 1os W O J W 6'-0" 104 2A 1 OBC FE / W �- W 3 � ICE / A5-0 \ / > LL7 105 J o J \ FLOOR DRAIN ,/ 0 11 Z _ PROVIDE FLOOR SINK FOR ICE MACHINE _____ __ a QW z Q / _____ __ 2 LJ_i 3'-6" 1'-6' / I— > LL1 / Z a O DRINKING FOUNTAIN / QED / Z LLJ e a -— m ----- --�� 42"HIGH PARTITION I- O Z MOP SINK - / Q R'i LLI v / STORAGE 16s / BREAKROOM -- 107 106 3'-6" 1'-6" SEE DETAIL 3/AO-3, \ - FLOOR DRAIN / E)WALL TO REMAIN 9 °, s-2\ MEWS / r-s" 3'-0^ RESTROOM / 6-0 O 63/4" 28'-3718' V STEP 105 - 8'-0" 6'-8" 6'-8. UP r o � Tn 00 k 109 U Cd �o I I 16'-5 112" 11'-5 3/4" 22'- 1 5/8" 17'-87/8" �.�. PROVIDE 3)NEW 4'X4'FIXED WINDOWS ALIGN TOP OF WINDOWS WITH TOP OF DOORS V « N A A.1 B.1 B.2 •,� _� w ax U p a rl ENLARGED NEW FLOOR PLAN 1/4"=1'-0" VOID See C/O#1 CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RCR/LJS RCR PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS AZ-L Page 9 of 97 LICENSED ARCHITECT -as A I� 6/16/2022 2x4@161'O.C.W/R-15 INSULATION&5/8"GYP BD EA SIDE 4" +1-6'-4318" 5'-103/4" 19'-93/8" 2 x 4 PARTITION WALL 2 x 6 PARTITION WALL 3.1 e T WALL WINDOW; W/R`-2211NSULATION&58HGYP PBD WINDOW;ALIGN EA SIDE W/DOOR BELOW ALIGN TOP OF - WINDOW W/TOP OFFICE OF DOOR � F 201 2 N, w A5-0 a J 2 x 6 PARTITION WALL Z 201 2 x 4 PARTITION WALL J (Y s BREAKROOM O p OFFICE LL 202 ON F203 ❑ p z O LL SEE DETAIL 31AO-3 O LLI p> J 2 x 4 @ 16"O.C.W/R-15 :2 > LLI 4314" 4'-0" 43/4" 15'-07/8" INSULATION&5/8"GYP BD EA SIDE 1 LLI } As-o J o LLI p � � J c� ❑ LL ❑ 3 EXIT F H G LWLI 2 (lJ AS-0 b 25'-6" �j ❑ 5._2. — — — — — — — — — — — — — — — — — — — — — Z W W CLEAR zos CORRIDOR ' I D Q o RESTROOM 205 2A 10BC FE W m 9 J 2 x 4@ 16"O.C.WITH 5/8" I w 2O4 GYP BD EA SIDE&SOUND ~ O Z BATT INSULATION. I Q c"'i W 3- 2"' PARTITION WALLS SHALL EXTEND 6"MIN ABOVE FINISHED CEILING,TYP AT 2ND FLOOR / HVAC CHASE 3.3 zo 208 — LOUNGE 208 OFF,CE OFFICE M U 207 206 I M i 3'-515/16" 4'-0" 3'-515/16" 5'-63/4" 4'-0" H o 3/4" 11'-10 3/8" I S-0 -11 31IT' I ,O PROVIDE 4)NEW 4'X 4-FIXED Q a WINDOWS;ALIGN WINDOWS IN Q LOUNGE W/WINDOWS IN BREAKRM A A.1 BELOW B. VOID See C/0#1 n ENLARGED 2ND LEVEL FLOOR PLAN 1/4" CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance LJs arc PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS A2-3 Page 10 of 97 LICENSED ARCHITECT -as 6/16/2022 1 112"DIAM RAILING AT T-0"H 42"HIGH PARTITION W/WOOD TOP CAP BLOCKING AT LEDGE LOCATION v 10'-634ELFLOOR 2 X6 LEDGER 42"HIGH PARTITION 11 7/8"EVIL. W/WOOD TOP CAP JOIST HANGER 1 1/2"DIAM RAILING AT 3'-0"H (4)1 3/4"X 14 EVE 2 X 8 LEDGER 7"RISE MAX 2 11R@+-T'EA=6'-5" 11"MIN.RUN 19 R @+-6.75"EA=10'-6 3/4" 11 7/8"LV LVL 10 T @ 11"EA=10'-0" 3/4"-1 1/4"NOSING< 18 T @ 11"EA=15'-7"+LANDING 12"TREAD DEPTH HANDRAIL 34"-38" 4)1 3/4"X 14 LVLIII BUILDING Level 1_ PRESSURE TREATED 2 X 6 0 1/2'.0 EPDXY AB L3X3X3/16"X0'-5" PRESSURE TREATED 2 X 4 Level 1 n EMBED 2 1/2",TYP WITH(2)1/2"0 PRESSURE TREATED 2 X 6 V 1/2"0 EPDXY AB L3X3X3/16'XO'-5" EACH STRINGER A307 BOLTS PRESSURE TREATED 2 X 4 EMBED 2 1/2",TYP WITH 0 EACH STRINGER A3076OLTSTS n SECTION 1 0 1 1/4"=1'-0" 2 SECTION 2 LL Q 1'-0" LLI J 0 a.� 0 LL Z LLI U7 Z Q 00 z w aF- w m 9U w Q MU) ED. EO VOID -F------L See C/O#1 4 STAIR EXTENSIONS 2"MAX.FROM 3/4"=1'-0° LEADING EDGE V RECCOMENDE \ �1 O - VISUAL CONTRASTING STRIPE '^I P W 12 X 72(SEE STRUCTURAL DRAWINGS) $"I ��IIIIIIIII 2ND LEVEL FLOORcd C/� F 10'-63%4" 504.6 VISUAL CONTRAST. V * N THE LEADING 1 TO 2 INCHES OF EVERY U Fcj�{.Tx.11 TREAD AND LANDING,MEASURED \\\\ �Z HORIZONTALLY FROM THE LEADING EDGE OF THE NOSING,SHALL CONSIST OF A SOLID SOLOR HAVING VISUAL 1"MIN. CONTRAST OF DARK-ON-LIGHT OR 2"MAX LIGHT-ON-DARK FROM THE REMAINDER OF THE TREAD.THE CONTRASTING J l - MARKING SHALL BE DURABLE AND 1 1/4"-2" _ SHALL EXTEND FROM ONE SIDE OF a)TREAD MARKING EACH TREAD TO THE OTHER SIDE OF EACH TREAD. E)CONCRETE FLOOR (� OLevel l +34^TO38" 112"MAX CITY APPROVED PLANS ORECCOMENDED Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS b)ALTERNATE LOCATION RCR/LJS RCR D,� cnxk"e 3 Section 4 5 HANRAIL TO BUILDING DETAIL 6 STAIR CONTRAST 1/4"=11_01. 3„=1D'_0" 3/4"=1,_0,� A5-� Page 11 of 97 ACENSED ARCHITECT PIt-905]OS 3.1 — OPEN TO ABOVER. STATE ia WS 6/16/2022 S' b AF .,. OFF ICE 2 2' 4 ACT System 8'-6"A.F.F. OFFICE F2 103 2'x4'A TSyst m 8'- "A.F.F. 2'x4'A TSystem VWY MEWS \ a'-6 A.F.F. RE TROOM EL 04 i BREAKROO M EMERGENCY LIGHT 107 A 3.3 STORAGE F2E O 0 1 O 'x 4'ACT Syste 0 5'-6"A.F.F. Z a' nBF F 3.1 w >- a/s > J o \ O D_ J EL Q LL In 2'z 4' CT System 2 LLI Z Q ESTROOM 2 x 4'ACT SYs[e 201 2'x 4'ACT S m z > > ll A.F.F. 9'-0"A.F.F..F. z 1-- < U J Q QL 0 LU W Z W m 9 J O LLI 4 Q MU A.1 B.1 B.2 OFFICE ENLARGED MAIN LEVEL CEILING PLAN 203 1'_0" 0"A.F.F. REAKROOI 3.2 - aA Lighting Fixture Schedule 00 ILABELI DESCRIPTION MOUNTING VOLTAGE WATTAGE1 MANUFACTURER NOTES 'x4.ACTSysteii 9'-O"A.F.F. F1 1X4 SURFACE COLUMETRIC SURFACE 120 35 LITHONIA 1 Q w 0Oo LED,STEPPED-DIMMING .E F2 2X4 LED TROFFER LAY-IN 120 40.4 METALUX 1 dWg 3 0 F2E 2X4 LED TROFFER(EM) LAY-IN 120 40.4 METALUX 1 RE$CRQOIVf., EL LO N p 1. DESIGN IS BASED ON FIRST NAMED MANUFACTURER.ALTERNATE MANUFACTURERES ARE ACCEPTABLE,SUBJECT TO ��., Z COMPLIANCE WITH SPECIFIED REQUIREMENTS,MODEL NUMBER,TYPE,AND OR CATALOG NUMBER. F 3.3 2'x 4'AC r System '-q cd 9'-0"A.RF. EL J `V OFFICE 207 ----- ---- 206— — 2' 4'ACT System 9'-O'A.F.F. CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RCR/LJS RCR PLANS MUST BE ON JOB SITE PROVIDE TJI FRAMING ABOVE 206 FOR ALL INSPECTIONS MEFZZANINE.ICE MECHANICAL A.1 B.1 B.2 A7-0 2 E NLA RGED 2ND LEVEL CEILING PLAN N =VE Page 12 of 97 LICENSED ARCHITECT -as VERTICALWIRES /7 q 12 GA.@ 4'-0'O.C. COMPRESSION STRUT, FIRST LINE OF FULL HEIGHT,(TYP) BRACING 6'-0"OR LESS FROM sraTE Dallo I WALL BOUNDARY 6/16/2022 45 M ,�� CEILING SUSPENSION 45 M SYSTEM WALL SPLAY WIRE 12 GA.@ 12'-0' O.C.IN EACH PLAN OF EACH 45 MAX. RUNNER x. 45 M "M �E 00 SPLAYWIRE o�Q55�J� MA/vRGNN `� l PR NOTE: COMPRESSION 1.HANGERS SHALL BE SADDLE-TIED BRACE AROUND MAIN RUNNERS. NOTE: 2.LOWER ENDS OF FLAT HANGERS AREAS SMALLER THAN 144 SQ.FT.AND WITH SHALL BE BOLTED WITH 3/8"BOLTS WALLS ON FOUR SIDES EXTENDING TO THE TO RUNNER CHANNELS. STRUCTURE NEED NOT BE BRACED.NOTE: 3.SPLAY WIRES MUST BE AT 90 BOUNDARY WALLS MUST BE BRACED TOP AND DEGREE ANGLES TO EACH ADJACENT BOTTOM INDEPENDENT OF CEILING TO QUALIFY WIRE. CEILING DETAILS -0. COMPRESSION STRUT AT INTERSECTION MUST BE PLACED @ 12'-0'O.C. SCREW (MAX)EACH WAY&WITHIN ATTACHMENT g 6'-0"OF PERIMETER WALLS TO STUDS (4)-12 GA.SPLAY WIRES CROSS TEE 0 0 2"EDGE TRIM O B Q MAIN RUNNER ® 4 F O 2• (; SCHEDULED W O ACOUSTICAL LAY-IN •"4 CEILING PANEL CEILING Lu �j SLIP CLIP .C W } � Da > J ACOUSTICAL SEALANT "•y O D_ j U) J SCHEDULED WALL "m LL STRUT SIZE MAXIMUM LENGTH SCHEDULED ,"4P W 3/4"DIAMETER CONDUIT EMT 8'-6" SUSPENSION 1"DIAMETER CONDUIT(EMT) 10'-0" SYSTEM W SINGLE 21/2"x20 GA.METAL 1T-6" z w STUD(Imin=0.18 h4) Q o Z BACK TO BACK 2 1/2"x20 15'-0" W m o f GA.METAL STUDS SCREWED w TOGETHER @ 24"O.C. � O � W Q ly- MU 2 CEILING GRID DETAILS 3"=1'-0" U N r--1 aA P p.l M U A U * � �I N C� CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RCFJLJS RCR PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS A7-1 Page 13 of 97 LICENSED ARCHITECT -as STATE IDPH� Room Finish Schedule 6/16/2022 Materials Finishes Ceiling Number Name Base Finish Floor Finish North East South West North East South West Material Ceiling Finish Remarks 101 LOBBY RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT 102 OFFICE RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT GYP BD PAINT 103 OFFICE RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT GYP BD PAINT 104 WOMEN'S RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD EPDXY PAINT EPDXY PAINT EPDXY PAINT EPDXY PAINT GYP BD PAINT RESTROOM 105 MEN'S RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD EPDXY PAINT EPDXY PAINT EPDXY PAINT EPDXY PAINT GYP BD PAINT RESTROOM 106 STORAGE RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT GYP BD PAINT 107 BREAKROOM RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT GYP BD PAINT 108 PRODUCTION RUBBER CONCRETE GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT GYP BD PAINT AREA 201 OFFICE 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT PAINT BASE 202 BREAKROOM 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT PAINT BASE 203 OFFICE 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT PAINT BASE 204 RESTROOM 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD EPDXY PAINT EPDXY PAINT EPDXY PAINT EPDXY PAINT 2 X 4 ACT PAINT BASE 205 CORRIDOR 206 OFFICE 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT PAINT BASE 207 OFFICE 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT PAINT BASE 208 LOUNGE 1 x 4 WOOD LVP GYP BD GYP BD GYP BD GYP BD PAINT PAINT PAINT PAINT 2 X 4 ACT PAINT BASE O LL Door Schedule DIMENSIONS DOOR FRAME W O Thickn Door > M DOOR ROOM EL Level Width Height ess Material Finish Accessories Door Latch Material Finish Glass Comments Uj 101 LOBBY Levels T-0" 13/4" EXISTING EXISTING DOOR TO REMAIN > J 102 PRODUCTION Levels 3'-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT O AREA 0� Q LL 103 LOBBY Levels T-0" 7'-0" 1314" WOOD PAINT CLASSROOM WOOD PAINT ac L1J z 104 PRODUCTION Levels 3'-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT G LLI U) AREA LLI 105 WOMEN'S Levels 3'-0" 7'-0" 13/4" WOOD PAINT PRIVACY WOOD PAINT > J RESTROOM Z 106 STORAGE Levels 3'-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT Q o Q 107 MEN'S Levels 3'-0" 7--0" 13/4" WOOD PAINT PRIVACY WOOD PAINT Z LU ER LLI RESTROOM 108 BREAKROOM Levels 6'-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT O U 109 PRODUCTION Levels T-0" 7'-0" 13/4" HIM PAINT WEATHERSTRIPPING,THRESHOLD, LOCKSET HM PAINT Q M AREA CLOSER,CONTINUOUS HINGES, PANIC HARDWARE 201 BREAKROOM 2ND LEVEL FLOOR 3'-0" 7'-0" 1314" WOOD PAINT CLASSROOM WOOD PAINT 202 CORRIDOR 2ND LEVEL FLOOR 3'-0" 7'-0" 1314" WOOD PAINT CLASSROOM WOOD PAINT 203 CORRIDOR 2ND LEVEL FLOOR 3'-0" 7'-0" 1314" WOOD PAINT CLASSROOM WOOD PAINT 204 LOUNGE 2ND LEVEL FLOOR 3'-0" 7'-0" 1314" WOOD PAINT CLASSROOM WOOD PAINT 205 LOUNGE 2ND LEVEL FLOOR T-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT 206 RESTROOM 2ND LEVEL FLOOR 3'-0" 7'-0" 13/4" WOOD PAINT PRIVACY WOOD PAINT 207 CORRIDOR 2ND LEVEL FLOOR 3'-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT 208 CORRIDOR 2ND LEVEL FLOOR 3'-0" 7'-0" 13/4" WOOD PAINT CLASSROOM WOOD PAINT U U r--1 aA P p.l M U A U * � 'T' �I N U I'' C� CITY APPROVED PLANS DATE: 6/i6/2022 Reviewed for Code Compliance RcwLls RCR PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Page 14 of 97 1 2 3 4 15 ABRIVIATIONS 2 GENERAL NOTES 5 CONCRETE NOTES n DESIGN CRITERIA LAUGHLIN RICKS L ROBERT WEED PLYWOOD INTERIOR OFFICE FRAMING AB ANCHORBOLT(S) O.C. ON CENTER 1. TYPICAL DETAILS AND SECTIONS SHALL APPLY WHERE SPECIFIC DETAILS ARE NOT SHOWN. 1. MATERIALS,UNLESS NOTED OTHERWISE: 1. BUILDING CODE IBC2018 3351 ELDRIDGE AVE. ABV ABOVE O.F. OUTSIDE FACE 2. THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS AND DIMENSIONS.IF ACTUAL CONDITIONS DIFFER FROM THOSE A. NORMAL WEIGHT AGGREGATES ASTMC33 2. SEISMIC TWIN FALLS,ID83301 ALT ALTERNATE OPNG OPENING SHOWN INTHE CONTRACT DRAWINGS,THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER BEFORE B. REINFORCING STEEL ASTM A615 GRADE 60(FY=60 KSI) a. Occupancy II APPROX APPROXIMATE USE GRADE 40 FY=40 KSI b. Seismic Design Category B OPP OPPOSITE PROCEEDING WITH THE FABRICATION OR CONSTRUCTION OF ANVEFFEREDELEMENTS. ( )FOR FIELD BENT DOWELS WITH NOESIS ENGINEERING ARCH ARCHITECT(URAL) SPACINGS INDICATED REDUCED BY 1/3. c. Soil Site Class D 3. THE CONTRACTORMODIFHALL ICATIONS. S.ANY RITTEN B THECONTR CONTRACTR BEFORE OR RECEIVINGDING WRITTEN CHANGES, C. DEFORMED BAR ANCHORS IDEA) ASTMA496 d. Mapped Spectral ResponseAccel 5,=0.194 SERVICES,P.C. PCF POUNDS PER CUBIC FOOT SUBSTITUTIONS OR MODIFICATIONS.ANY WORK DONE BY THE CONTRACTOR BEFORE RECEIVING WRITTEN APPROVAL e. Site Coefficients F,=1.6 BLDG BUILDING D. HEADED STUD ANCHORS(HSA) ASTM A108 PL PLATE IN CASLL E OF ACOATTHE FLICT BETWEESKOFTHE 7RACTOR. f. Design Spectral Response Ac<el SDs=0.207 BLW BELOW E. ANCHOR RODS ASTM F3554 GRADE 36 WITH ASTM A563 HEAVY HEX PLF POUNDS PER LINEAL FOOT 4. IN CASE OFACONFLICi BETWEEN THE CONTRACT DRAWINGS AND THE SPECIFICATIONS,FOLLOW THE MOST STRINGENT g. Response Modification Factor R=6.5 411111111111111111, BM BEAM NUTS WITH HARDENED WASHERS PNL PANEL REQUIREMENT OR DIRECTIONS PROVIDED BY THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER. h. System Overstrength Factor Oo=3.0 BOG BOTTOM F. ADMIXTURES: - / PSF POUNDS PER SQUARE FOOT Deflection F - D ERG BEARING Q 5. THE CONTRACTOR SHALL COORDINATE WITH ALL TRADES ANY ITEMS THAT ARE TO BE INTEGRATED IN THE STRUCTURAL I. AIR-ENTRAINING ADMIXTURES COMPLY WITH ASTM C260(WHEN USED). I. Amplification actor Ca-4 p PSI POUNDS PER SQUARE INCH SYSTEM SUCH AS OPENINGS,PENETRATIONS,MECHANICAL,ELECTRICAL EQUIPMENT,ETC.SIZES AND LOCATIONS OF j. Seismic Response Coefficient C,=Sos%/R=0.032 I BTWN BETWEEN T CALCIUM CHLORIDES HALL NOTBEADDEH SHALL THE BE USED FOR ALLIX. l PT POINT MECHANICAL AND OTHER EQUIPMENT THAT DIFFERS FROM THOSE SHOWN ON THE CONTRACT DRAWINGS SHALL BE G. TYPE I/II CEMENT COMPLYING WITH ASTM C1508HALL BE USED FOR ALL CONCRETE. k. W Dead Load of Structure C.1. CONST/CONTROL JOINT REPORTED TO THE ENGINEER. H. THE WATER/CEMENT RATIOS SHALL MEETTHE REQUIREMENTS OF ACI 318. I. Base Shear V=COW-0.032W CMU CONCRETE MASONRY UNIT REINF REINFORCING 6. THE CONTRACTOR SHALL PROVIDE ADEQUATE SHORING AND BRACING AS REQUIRED FOR HIS METHOD OF ERECTION. I. PROVIDE AIR ENTRAINING AS RECOMMENDED BY ACI 318. 3. FLOOR LOAD 1712 CABALLERO DR. COL COLUMN REDID REQUIRED SHORING AND BRACING SHALL REMAIN IN PLACE UNTIL FINAL CONNECTIONS FOR THE PERMANENT MEMBERS ARE J. NO ALUMINUM CONDUIT OR PRODUCT CONTAINING ALUMINUM OR ANY OTHER MATERIAL INJURIOUS TO a. Live Load 80 psf CONIC CONCRETE R.D. ROOF DRAIN COMPLETED.THE BUILDING SHALL NOT BE CONSIDERED STABLE UNTIL ALL CONNECTIONS ARE COMPLETED. CONCRETE SHALL BE EMBEDDED IN CONCRETE. b. Dead Load 15 psf AMMON,IDAHO 83406 CONST CONSTRUCTION RS ROUGH SAWN LUMBER WALLS SHALL NOT BE CONSIDERED SELF-SUPPORTING AND SHALL BE BRACED UNTIL TH E FLOOR/ROOF SYSTEM 15 2. COMPRESSIVE STRENGTHS OF CONCRETE AT 28 DAYS SHALL BE AS FOLLOWS: (208)9322720 CTR CENTER RTU ROOFTOP UNITS COMPLETED. A. FOOTINGS 3,000 P51 W W W.NOESIS.US B. INTERIOR SLABS ON GRADE 4,000 PSI DB DECK BEARING SCW SEISMIC CRITICAL WELD WOOD NOTES C. WALLS 3,000 PSI IRANVN BY DEL DOUBLE SHT SHEET D. ALL SITE CONCRETE 4,000 P51 DET DETAIL SI SPECIAL INSPECTION 3. ONLY ONE GRADE OR TYPE OF CONCRETE SHALL BE POURED ON THE SITE AT ANY GIVEN TIME. DBv CIA DIAMETER SIM SIMILAR 1. MATERIALS: 4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN,DETAILING,CARE,PLACEMENT AND REMOVAL OF ALL DIM DIMENSION A. FRAMING LUMBER SHALL BE#1-2 DOUGLAS FIR-LARCH OR BETTER UNLESS NOTED OTHERWISE. FORMWORK AND SHORING. BD By DN DOWN SMU SUSPENDED MECHANICAL UNITS A. SUPPORTING FORMS AND SHORING SHALL NOT BE REMOVED UNTIL STRUCTURAL MEMBERS HAVE SOG SLAB-ON-GRADE B. WOOD SHEATHING SHALL BE INTERIOR GRADE WITH GLUE,SPAN INDEX RATIO,UNLESS NOTED OTHERWISE, DWG DRAWING SO, SQUARE 24/0 WALLS ACQUIRED SUFFICIENT STRENGTH TO SAFELY SUPPORT THEIR OWN WEIGHT AND ANY CONSTRUCTION LOAD TO DWL DOWEL 48/24 ROOF WHICH THEY MAY BE SUBJECTED.IN NO CASE,HOWEVER,SHALL FORMS AND SHORING BE REMOVED IN LESS STAG STAGGERED THAN 24 HOURS AFTER CONCRETE PLACEMENT. STD STANDARD C. NAILS:STANDARD COMMON WITH THE FOLLOWING PROPERTIES: EA EACH 5. CAST-IN-PLACE CONCRETE: CLEAR THE FOLLOWING CONCRETE COVER: E.F. EACH FACE STL STEEL NAIL SIZE SHANK DIAMETER MIN.PENETRATION INTO SUPPORT MEMBER CAST-IN-PLACE CONCRETE: CLEAR COVER STIR STRUCTURAL 6D 0.113" 1.25" E.J. EXPANSION JOINT A. CAST AGAINSTAND PERMANENTLY EXPOSED TO EARTH 3" ELEC ELECTRICAL STS SELF TAPPING SCREWS 8D 0.131" 1.50" B. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER: ELEV ELEVATION 10D 0.148" 1.63" #6 THRU#18 BARS 2" O EQUIP EQUIPMENT T&B TOP AND BOTTOM 12D 0.148" 1.63" #5 AND SMALLER BARS 1-1/2" L1..1 EQ EQUAL TEMP TEMPERATURE 16D 0.162" 1.75" C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: L_ LLI E.W. EACH WAY THDS THREADS FASTENERS OTHER THAN COMMON NAILS ARE NOT PERMITTED WITHOUT PRIOR WRITTEN APPROVAL FROM SLABS,WALLS,JOISTS;#11 BARS AND SMALLER 3/4" Q EXST EXISTING T.O. TOP OF THE ENGINEER. BEAMS,COLUMNS:PRIMARY REINF.,TIES,STIRRUPS,SPIRALS 1-1/2" (n z (E) EXISTING TOC TOP OF CONCRETE D. BOLTS SHALL BE ASTM A36 OR EQUAL WITH ASTM A563 HEAVY HEX NUTS AND HARDENED WASHERS,GRADE 6. CONSTRUCTION JOINTS AND CONTROLJOINTS: EXP EXPANSION TOD TOP OF DECK A,UNLESS NOTED OTHERWISE. A. PROVIDE A FORMED AND BEVELED 2 X 4 X CONTINUOUS KEYWAY IN ALL HORIZONTAL AND VERTICAL Q EXT EXTERIOR CONSTRUCTION JOINTS,UNLESS NOTED OTHERWISE.IN ADDITION,ALL JOINTS SHALL BE INTENTIONALLY Y C TOF TOP OF FOOTING E. ALL LAMINATED VENEER LUMBER(LVL)SHALL BE 1.9E OR BETTER. O 2. ALL WOOD IN CONTACT WITH CONCRETE,MASONRY OR SOIL SHALL BE PRESSURE TREATED OR BE REDWOOD. ROUGHENED TO A FULL AMPLITUDE OF APPROXIMATELY 1/4-INCH. C z Q TOW TOP OF STEEL FC-x CONTINUOUS FOOTING MARK 3. GENERAL FRAMING AND CARPENTRY SHALL BE CONNECTED AS PER NAILING SCHEDULE" SHEET S-601 B. CONTROL JOINTS SHALL REINSTALLED IN SLABS ON GRADE SO THE LENGTH 70 WIDTH RATIO OF THE SLAB IS = ` TOW TOP OF WALL 5 F.D. FLOOR DRAIN TYP TYPICAL UNLESS NOTED OTHERWISE. NO MORE THAN 1.25:1.CONTROL101NTS SHALL BE COMPLETED WITHIN 12 HOURS OF CONCRETE � FDN FOUNDATION .PLACEMENT CONTROL JOINTS MAY BE INSTALLED BY: 4. ALL FRAMING ANCHORS,POST CAPS,HOLD DOWNS,COLUMN BASES,ETC.SHALL BE PROVIDED BY WIMPSON STRONG- l/1 FS-x SQUARE FOOTING MARK I. SAW CUT DEPTH OF I/4 THE THICKNESS OF THE SLAB J LINO UNLESS NOTED OTHERWISE TIE OR APPROVED EQUAL. } F7 FOOT 5. BUILT-UP BEAMS OF 2X-MEMBER 12 IN.OR LESS IN DEPTH SHALL BE SPIKED TOGETHER WITH NOT LESS THAN I6-D II. CONSTRUCOLED TION IONNTS OR CON ROLJOIOF 1/4 TS IN SLABS ON GRADE ATF THE A SPACING Q Y Z FTS FOOTING SPIKES AT TWELVE-INCH(12 IN.)CENTERS, IF THE DEPTH OF BEAM IS MORE THAN TWELVE INCHES C. THESINSTAL BTHIC THICKNESS NOR CONTROL101 RUN EINFOR ED SLAB AND TIMES THE SLAB HIC 3NESS IN > Y 0 Z FTS-x THICKEN SLAB MARK VERT VERTICAL THE SLAB THICKNESS IN ANY DIRECTION FOR UNREINFORCED SLABS AND 75 TIMES THE SLAB THICKNESS IN IN.),THE MEMBERS SHALL BE CONNECTED TOGETHER WITH 1/2"0 BOLTS @ 241N.O.C.STAGGERED.BOLTS SHALL BE Q W Q ANY DIRECTION FOR REINFORCED SLABS,UNLESS NOTED OTHERWISE.CONSTRUCTION JOINTS SHALL NOT EXCEED GA GAUGE W/ WITH PLACED 1/4 THE DEPTH OF THE MEMBER FROM THE TOP AND BOTTOM OF THE MEMBER. ADISTANCE OF 125'-0"O.C.IN ANY DIRECTION. Z GALV GALVANIZED WD WOOD 6. ALL WALLS SHALL HAVE A MINIMUM OF TWO TOP PLATES.SPLICES IN TOP PLATES SHALL BE STAGGERED A 7. CONSTRUCTION z J GLB GLULAM BEAM MINIMUM OF FOUR FEET FROM THE NEAREST SPLICE IN ADJOINING TOP PLATE. A. USE CHAIRS OR OTHER SUPPORT DEVICES RECOMMENDED BY THE CRSI TO SUPPORTAND TIE REINFORCEMENT LL GSN GENERAL STRUCTURAL NOTES BARS AND WWF PRIOR TO PLACING CONCRETE.WWF SHALL BE CONTINUOUSLY SUPPORTED AT 36"D.C. _ LU MAXIMUM.REINFORCING STEEL FOR SLABS ON GRADE SHALL BE ADEQUATELY SUPPORTED ON PRECAST W C)HB HORIZONTAL BRIDGING CONCRETE UNITS.LIFTING THE REINFORCING OFF THE GRADE DURING PLACEMENT OF CONCRETE IS NOT LU M HORIZ HORIZONTAL PERMITTED. 0 LL oo STEEL NOTES HSA HEADED STUD ANCHOR n B. CONCRETE TO BE MECHANICALLY CONSOLIDATED DURING PLACEMENT PERACI STANDARDS. Q O 04 HT HEIGHT C. CONTRACTOR SHALL COORDINATE PLACEMENT OF ALL OPENINGS,CURBS,DOWELS,SLEEVES,CONDUITS, BOLTS, INSERTS AND OTHER EMBEDDED ITEMS PRIOR TO CONCRETE PLACEMENT. IBC INTERNATIONAL BUILDING CODE D. ALL EMBEDS AND DOWELS SHALL BE SECURELY TIED TO FORMWORK OR TO ADJACENT REINFORCING PRIOR I.F. INSIDE FACE 1. MATERIAL: TOTHE PLACEMENT OF CONCRETE. IN. INCH A. WIDE FLANGES SECTION ASTM A992(50 KSI) E. NO PIPES,DUCTS,SLEEVES,ETC.SHALL BE PLACED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY INT INTERIOR B. OTHER SHAPES&PLATES ASTM A36 DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER.PENETRATIONS THROUGH WALLS WHEN C. PIPE COLUMNS ASTM A53,TYPES E OR S,GRADE B. APPROVED SHALL BE BUILT INTO THE WALL PRIOR TO CONCRETE PLACEMENT.PENETRATIONS WILL NOT BE JT JOINT D. STEEL TUBES ASTM A500 GRADE B(46KSI) ALLOWED IN FOOTINGS OR GRADE BEAMS UNLESS DETAILED.PIPING SHALL BE ROUTED AROUND THESE JST JOIST E. DEFORMED BAR ANCHORS IDEA) ASTMA496 ELEMENTS AND FOOTINGS STEPPED TO AVOID PIPING. F. HEADED STUD ANCHORS(HSA) ASTM A108 F. REINFORCING BARS SHALL NOT BE WELDED.DO NOT SUBSTITUTE REINFORCING BARS FOR DBAS OR HSAS. k KIP(S)=1000 POUNDS G. BOLTED CONNECTIONS: ASTM A325 8. DETAILING: KLF KIPS PER LINEAL FOOT 2. FABRICATION AND CONSTRUCTION SHALL COMPLY WITH THE LATEST EDITION OF THE FOLLOWING A. LAP LENGTHS SHALL BE AS FOLLOWS: KSF KIPS PER SQUARE FOOT CODES AND STANDARDS: I. 30 BAR DIAMETERS FOR#3 AND 44 BARS B a. AMERICAN INSTITUTE OF STEEL CONSTRUCTION(AISC),"SPECIFICATION FOR THE DESIGN, II. 40 BAR DIAMETERS FOR#5 THROUGH#8 BARS B LBS POUNDS III. DO NOT SPLICE STIRRUPS AND TIES. FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,"WITH LF LINEAL FOOT "COMMENTARY". IV. DO NOT SPLICE VERTICAL BARS IN RETAINING WALLS UNLESS SPECIFICALLY SHOWN. LVL LAMINATED VENEER LUMBER b. AISC"CODE OF STANDARD PRACTICE"EXCLUDING THE FOLLOWING:SECTION 3.4,SECTION B. AT JOINTS PROVIDE REINFORCING DOWELS TO MATCH THE MEMBER REINFORCING,UNLESS NOTED OTHERWISE. 1 4.4,SECTION 4.4., MAS MASONRY C. AT ALL DISCONTINUOUS CONTROL OR CONSTRUCTION SLOB ON GRADE JOINTS,PROVIDE 2-114%481NCHE5. MAX MAXIMUM c. AISC"SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" D. PROVIDE CORNER BARS AT INTERSECTING WALL CORNERS USING THE SAME BAR SIZE AND SPACING AS THE MECH MECHANICAL d. AMERICAN WELDING SOCIETY(AWS),STRUCTURAL WELDING CODE(SPECIFIC ITEMS DO HORIZONTAL WALL REINFORCING. MFR MANUFACTURER NOTAPPLV WHEN THEY CONFLICT WITH THE AISC REQUIREMENTS). E. ALL VERTICAL REINFORCING SHALL BE DOWELED TO FOOTINGS,OR TO THE STRUCTURE BELOW WITH THE SAME MIN MINIMUM e. AISC"SEISMIC PROVISION FOR STRUCTURAL STEEL BUILDINGS" SIZE AND SPACING AS THE VERTICAL REINFORCING FOR THE ELEMENT ABOVE.DOWELS EXTENDING INTO MISC MISCELLANEOUS 3. WELDING FOOTINGS SHALL TERMINATE WITH A 90 DEGREE STANDARD HOOK AND SHALL EXTEND TO WITHIN 4"OF THE a. ALL WELDING AND CUTTING SHALL BE PERFORMED BYAWS CERTIFIED WELDERS. BOTTOM OF THE FOOTING.FOOTING DOWELS(#8 BARS AND SMALLER)WITH HOOKS NEED NOT EXTEND MORE NIC NOT IN CONTRACT b. USE E-70 XX OR AS NOTED OTHERWISE. THAN 20"INTO FOOTINGS. NTS NOTTOSCALE c. ALL INTERSECTING STEEL SHAPES WHICH ARE NOT BOLTED SHALL BE CONNECTED BY A F. HORIZONTAL WALL REINFORCING SHALLTERMINATE AT ENDS OF WALLS AND OPENINGS INTO THE FAR END ORIGINAL FILLET WELD ALL AROUND,UNLESS NOTED OTHERWISE.WHERE FILLET WELD SIZES ARE OF THE JAMB COLUMN WITH A 90-DEGREE STANDARD HOOK PLUS A 6 BAR DIAMETER EXTENSION. NT1`ER EDex/BicBoxi.wn ooc DER.NE NOT SHOWN THEY SHALL BE I/16"LESS THAN THE THINNEST OF THE CON NECTED PARTS HORIZONTAL WALL REINFORCING SHALL BE CONTINUOUS THROUGH CONSTRUCTION AND CONTROL JOINTS. oB NUMBER FD UMENn. FOR THICKNESSES 1/4"AND LARGER.FILLET WELDS ON PLATES LESS THAN 1/4"SHALL BE OF THE SAM E SIZE AS TH E THINNEST OF THE CONNECTED PART. ESS(� Ell. DO NOT WELD ANCHOR BOLTS,INCLUDING"TACK"WELDS. 4. BOLTED CONNECTIONS: a. USE ASTM A325N BOLTS FOR STEEL TO STEEL CONNECTIONS,AS NOTED HEREIN OR AS 1 6 6 7 6 NOTED ON THE DRAWINGS.A325N BOLTS SHALL BE USED IN CONNECTIONS FOR SIMPLE 6/08/202 SPAN FRAMING AND BEAM(OR GIRDER)TO BEARING PLATE CONNECTIONS.TIGHTEN BOLTS TO A G TIGHT or b. USE HARDENED U CONDITION.WAS E H RS BENEA THE TURNED ELEMENT OF ALL BOLTS OR NUTS.USE O9/�K HARDENED BEVELED WASHERS,TO COMPENSATE FOR THE LACK OF PARALLELISM,WHERE THE OUTER FACE OF THE BOLTED PARTS HAS ASLOPE GREATER THAN ONE IN TWENTY CITY APPROVED PLANS WITH RESPECT TO THE PLANE NORMAL TO THE BOLT AXIS.AT OVERSIZED HOLES LEE*1 reHARDENED WASHERS OR PLATES SHALL CONFORM WITH ASTMF-436 AND SHALL David K.B _ACOMPLETELY COVER THE SLOTAFTER INSTALLATION. RevleWedfo1 Code Complia ce os.oB,a.zcs,nsvv A c. WHEREASTEELTO STEEL BEAM CONNECTION IS NOTSHOWN,PROVIDE A STANDARD AISC FRAMED CONNECTION FOR ONE HALF THE TOTAL UNIFORM LOAD CAPACITY OF THE BEAM PLANS MUST BE ON JOB SITE FOR THE SPAN AND STEEL SPECIFIED. GENERAL STRUCTURAL D. BOLTS,NUTS AND WASHERS SHALL NOT BE REUSED. NOTES 5. PROVIDE FULL-DEPTH WEB-STIFFENER PLATES AT EACH SIDE OF ALL BEAMS AT ALL BEARING FOR ALL INSPECTIONS POINTS.STIFFENER PLATES SHALL BE THE THICKNESS CALLED OUT BELOW UNLESS NOTED OTHERWISE AND SHALL BE WELDED BOTH SIDES WITH FILLET WELDS ALL AROUND: FLANGEWIDTH STIFFENER THICKNESS WELD SIZE LESS THAN 81/4" 1/4" 3/16" 81/4"TO 12 1/4 3/8" 1/4" No. Description Date C 12 1/4"TO 16%" 1/2" 5/16" "-001 16%"TO 20 K" 5/8" 3/8" 1 2 3 4 5 Page 15 of 97 1 2 3 14 5 SPECIAL INSPECTION SCHEDULE WELDING STRUCTURAL STEEL SPECIAL INSPECTION SCHEDULE ESTABLISHED PER 2018 IBC SECTION 110 AND CHAPTER 17 ESTABLISHED PER 2018 IBC SECTION 1705.2.1,STANDARDS PER AISC STEEL CONSTRUCTION MANUAL 15TH ED. LAUGHLI N RICKS ITEM CONTINUOUS° PERIODIC° REFERENCE COMMENTS ROBERT WEED PLYWOOD FABRICATOR SPECIAL INSPECTOR 1.1 SPECIAL INSPECTION IS NOT REQUIRED WHERE THE WORK IS DONE ON THE PREMISES OFA FABRICATOR REGISTEREDAND INSPECTION TASKS PRIORTOWELDING(AISCTABLENS.4-1) QUALITY CONTROL QUALITY ASSURANCE NOTES INTERIOR OFFICE FRAMING APPROVED TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION,PROVIDED THE FABRICATOR COMPLIES WITH IBC 3351 ELDRIDGE AVE. PRE-FAB CONSTRUCTION(IBC1704.2.5) REFERENCE NOTES 1704.2.5.1. WELDER QUALIFICATION RECORDS AND CONTINUITY RECORDS P O 1. (0)OBSERVE(PERIODIC)-OBSERVE THESE ITEMS ON A RANDOM BASIS.OPERATIONS NEED NOT BE DELAYED TWIN FALLS,ID83301 1.1&1.2 1.2 INSPECTION FOR PREFABRICATED CONSTRUCTION SHALL BE THE SAME AS IF THE MATERIAL USED IN THE CONSTRUCTION PENDING THESE TOOK PLACE ON SITE.SPECIAL INSPECTION WILL NOT BE REQUIRED DURING PREFABRICATION IF THE APPROVED AGENCY WELDING PROCEDURE SPECIFICATIONS(WPSs)AVAILABLE P P INSPECTIONS. NOESIS ENGINEERING CERTIFIES THE CONSTRUCTION AND FURNISHES EVIDENCE OF COMPLIANCE.(SEE NOTE 2). MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE p p 2. (P)PERFORM(CONTINUOUS)-PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER. SERVICES,P.C. SEE IBC TABLE 1705.3 FOR FULL TABLE 2.1 SPECIAL INSPECTION IS NOT REQUIRED FOR CONC.ISOLATED SPREAD FOOTINGS,CONTINUOUS FOOTINGS,NON-STRUCTURAL 3. QUALITY CONTROL(QC)SHALL BE PROVIDED BY THE FABRICATOR AND ERECTOR. CONCRETE CONSTRUCTION(IBC 1705.3) MATERIAL IDENTIFICATION(TYPE/GRADE) O O REF NOTE 2.1 SLABS,FOUNDATION W ALLS,PATIOS,DRIVEWAYS,AND SIDEWALKS PROVIDED THE REQUIREMENTS OF IBC 1705.3 ARE MET. 4. QUALITY ASSURANCE(QA)SHALL BE PROVIDED BY OTHERS WHEN REQUIRED BY THE AUTHORITY HAVING REINFORCING STEEL PLACEMENT 0 2.2 PERIODIC SPECIAL INSPECTION IS ALLOWED FOR VERIFICATION OF THE WELDABILITY OF REINFORCING STEEL RESISTING WELDER IDENTIFICATION SYSTEM' O O JURISDICTION(AHJ),APPLICABLE BUILDING CODE(ABC),PURCHASER,OWNER,OR ENGINEER OF RECORD(EOR). a FLEXURAL AND AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT FRAMES,BOUNDARY ELEMENTS OF SPECIAL NONDESTRUCTIVE TESTING(NOT)SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE FOR QUALITY WELDING OF REINFORCING STEEL O 0 REFERENCE NOTE 2.2 REINFORCED CONCRETE SHEAR WALLS,AND SHEAR REINFORCEMENT.PERIODIC SPECIAL INSPECTION IS ALLOWED FOR FIT-UP OF GROOVE WELDS(INCLUDING JOINT GEOMETRY) ASSURANCE,EXCEPTAS PERMITTED IN ACCORDANCE WITH SECTION N7. D WELDING OF OTHER ASTM A 706 REINFORCING STEEL NOT INCLUDED IN THE CONTINUOUS SPECIAL INSPECTION REQUIREMENTS *JOINT PREPATATION 5. QC AND QA INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE WITH AISC 360-10 CHAPTER N4. /r\\\`� D INSPECT ANCHORS CAST IN CONCRETE O 6. NONDESTRUCTIVE TESTING PERSONNEL SHALL BE QUALIFIED IN ACCORDANCE WITH AISC 360-30 CHAPTER N4.3. 1\ NOTED ABOVE. *DIMENSIONS(ALIGNMENT,ROOT OPENING,ROOT FACE,BEVEL) O O Q ANCHORS POST-INSTALLED IN O O 2.3 PERFORM AIR,SLUMP AND TEMPERATURE.TESTS WHEN CONCRETE SAMPLES ARE CAST. 7. NONDESTRUCTIVE TESTING OF WELDED JOINTS SHALL COMPLY WITH AISC 360-30 CHAPTER NSa AND b. / HARDENED CONCRETE MEMBERS REFERENCE NOTE 2.5 2 4 PERIODIC SPECIAL INSPECTION IS REQUIRED FOR VERIFICATION OF IN-SITU CONCRETE STRENGTH FOR POST-TENSIONED 'CLEANLINESS(CONDITION OF STEEL SURFACES) 8. OBSERVATION OF WELDING OPERATIONS AND VISUAL INSPECTION OF IN-PROCESS AND COMPLETED WELDS (EPDXY/EXPANSIONANCH OR CONCRETE PRIOR TO TENSIONING TENDONS OR REMOVING SHORING OR FORMS. *TACKING(TACK WELD QUALITY AND LOCATION) SHALL BE THE PRIMARY ITHT THE CO CONFIRM NSTRUCTIONCOON DO THAT TTH MATERIALS, RUCTUPROCED LRESAND WORKMANSHIP ARE IN/ 1712 CABALLERO DR. PLACEMENT) 2.S EPDXY AND EXPANSION ANCHORS INTO MASONRY OR CONCRETE MAY BE USED ONLY WHEN APPROVED BV ARCHITECT.AND/OR AMMON,IDAHO 83406 ENGINEER USING AN APPROVED PRODUCT W ITH CURRENT PUBLISHED ICC RESEARCH REPORT NUMBERS.COORDINATE *BACKING TYPE AND FIT(IF APPLICABLE) D1.IM STRUCTURAL WELDING CODE-STEEL FOR STATICALLY LOADED STRUCTURES SHALL APPLY. 208 932-2720 VERIFYING REQUIRED DESIGN MIX 0 CONTINUOUS/PERIODIC SPECIAL INSPECTION REQUIREMENTS WITH ICC REPORT. 9. THERMALLY CUT SURFACES OF ACCESS HOLES SHALL BE TESTED BY QA USING MT OR PT,WHEN THE FLANGE CONCRETE PLACEMENT/SAMPLING O REFERENCE NOTE 2.3 FIT-UP OF CIP GROOVE WELDS OF HSST-,Y-AND K-JOINS WITHOUT BACKING THICKNESS EXCEEDS 2 IN.(50mm)FOR ROLLED SHAPES,OR WHEN THE WEB THICKNESS EXCEEDS 2 IN.(50mm) VYl'W.NOESIS.US (INCLUDING JOINT GEOMETRY) FOR BUILT-UP SHAPES.ANY CRACK SHALL BE DEEMED UNACCEPTABLE REGARDLESS OF SIZE OR LOCATION. CURING TEMPERATURE/TECHIQUES O JOINT PREPATATION 10. WHEN REQUIRED BY APPENDIX 3,TABLE A-3.1,W ELIDED JOINTS REQUIRING WELD SOUNDNESSTO BE By All ` P O ESTABLISHED BY INSPECT PRESTRESSED CONCRETE 0 *DIMENSIONS ALIGNMENT,ROOT OPENING,ROOT FACE,BEVEL BD By ( ) RADIOGRAPH OR ULTRASONIC INSPECTION SHALL BE TESTED BY QA AS PRESCRIBED.REDUCTION IN THE RATE ERECTION OF PRECAST CONCRETE 0 *CLEANLINESS(CONDITION OF STEEL SURFACES) OF UT IS PROHIBITED. BD By CHICK VERIFICATION OF IN-SITU STRENGTH 0 REFERENCE NOTE 2.4 11. REDUCTION OF RATE OF ULTRASONIC TESTING-THE RATE OF UT IS ONLY PERMITTED TO BE REDUCED IF P. 'TACKING(TACK WELD QUALITY AND LOCATION) APPROVED BY THE FOR AND THE AHJ PER AISC 360-10 CHAPTER Nye. FORMWORK FOR SHAPE,LOCATION 0 12. FOR STRUCTURES IN RISK CATEGORY 11,WHERE THE INITIAL RATE FOR UT IS 30%,THE NOT RATE FOR AN AND DIMENSIONS *BACKING TYPE AND FIT(IF APPLICABLE) INDIVIDUAL W ELDER OR WELDING OPERATOR SHALL BE INCREASED TO 300%SHOULD THE REJECT RATE,THE WOOD IIBC 1705.5) 3.1 WOOD STRUCTURAL PANEL SHEATHING SHALL BE INSPECTED TO ASCERTAIN THAT GRADE AND THICKNESS ARE IN COMPLIANCE CONFIGURTATION AND FINISH OF ACCESS HOLES O O NUMBER OF WELDS CONTAINING UNACCEPTABLE DEFECTS DIVIDED BY THE NUMBER OF WELDS COMPLETED, WITHAPPROVED BUILDING PLANS.NOMINAL SIZE OF FRAMING MEMBERS AT ADJOINING PANEL EDGES,THE NAIL OR STAPLE FIT-UP OF FILLET WELDS EXCEEDS 5%OFTHE WELDS TESTED FOR THE WELDER OR WELDING OPERATOR.A SAMPLING OF AT LEAST 20 HIGH LOAD DIAPHRAGMS(ROOF/FLOOR) O REFERENCE NOTE 3.1 COMPLETED WELDS FOR A JOB SHALL BE MADE PRIOR TO IMPLEMENTING SUCH AN INCREASE.WHEN THE REJECT DIAMETER SHALL LENGTH,THE NUMBER OFVERIFIED FOR R LINES, SPACING BETWEENDBUILDING FASTENERS PLANS. LINEANDAT EDGE -DIMENSIONS(ALIGNMENT,GAPS AT ROOT) O O SITE-BUILT ASSEMBLIES O MARGINS SHALL ALSO BE INSPECTED AND VERIFIED FOR COMPLIANCE WITH APPROVED BUILDING PLANS. RATE FOR THE WELDER OR WELDING OPERATOR,AFTER A SAMPLING OF AT LEAST 40 COMPLETED WELDS,HAS 3.2 SPECIAL INSPECTION IS NOT REQUIRED FOR WOOD SHEAR WALLS,WOOD DIAPHRAGMS,INCLUDING NAILING,&BOLTING,AND 'CLEANLINESS(CONDITION OF STEEL SURFACES) FALLEN TO 5%OR LESS,THE I.H O SHEAR WALL&DIAPHRAGM NAILING 0 REFERENCE NOTE 3.2 RATE OF UT SHALL BE RETURNED TO 10%.FOR EVALUATING THE REJECT RATE OF CONTINUOUS W ELDS OVER 3 _ OTHER FASTENING TO OTHER COMPONENTS HERE THE SPACING OF THE SHEATHING FASTENERS IS GREATER THAN 4"o.c' *TACKING(TACK WELD QUALITY AND LOCATION) FT(1M)IN LENGTH WHERE THE EFFECTIVE THROAT IS I IN.(25mm)OR LESS,EACH 121N.(300mm)INCREMENT OR DRAG STRUTS 0 CHECK WELDING EQUIPMENT O O FRACTION THEREOF SHALL BE CONSIDERED AS ONE W ELD.FOR EVALUATING THE REJECT RATE ON CONTINUOUS I BRACES&SHEAR PANELS 0 WELDS OVER 3 FT(1M)IN LENGTH WHERE THE EFFECTIVE THROAT IS GREATER THAN 1 IN.(25mm),EACH 61N. Q HOLDOWNS 0 'THE FABRICATOR OR ERECTOR,AS APPLICABLE,SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A (150mm)OF LENGTH OR FRACTION THEREOF SHALL BE CONSIDERED ON WELD. V) Z GLUING OPERATIONS O JOINTORMEMBER CAN BE IDENTIFIED.STAMPS,IF USED,SHALL BE THE LOW-STRESS TYPE. 13. ALL NDT PERFORMED SHALL BE DOCUMENTED.FOR SHOP FABRICATION,THE NDT REPORT SHALL IDENTIFY THE TESTED Q FABRICATOR SPECIAL INSPECTOR Y INSPECTION TASKS DURING WELDING(AISC TABLE N5.4-21 WELD BY PIECE MARK AND LOCATION IN THE PIECE.FOR FIELD C SOILS IIBC 1705.61 REFERENCE NOTE 4.1 41 SPECIAL INSPECTION OF SOILS SHALL REFERENCE THE APPROVED SOILS REPORT TO DETERMINE COMPLIANCE. QUALITY CONTROL QUALITY ASSURANCE Z O C WORK,THE NDT REPORT SHALL IDENTIFY THE TESTED WELD BY LOCATION IN THE STRUCTURE,PIECE MARK,AND VERIFY ADEQUATE MATERIALS BELOW O REFERENCE NOTE 4.1 4.2WHERESOILSREPORT IS NOT PROVIDED SPECIAL INSPECTIONS ARE REQUIRED TO VERIFY THAT THE IN-PLACE DRY DENSITY OF USE OF QUALIFIED WELDERS 0 O LOCATION IN THE PIECE.WHEN A WELD IS REJECTED ON THE BASIS OF NDT,THE NDT RECORD SHALL INDICATE _ FOOTINGS THE COMPACTED FILL IS NOT LESS THAN 90 PERCENT OF THE MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE CONTENT THE LOCATION OF THE DEFECT AND THE BASIS OF REJECTION I­_DETERMINED IN ACCORDANCE WITH ASTM D 1557. CONTROLAND HANDLING OF WELDING CONSUMABLES 14. DEMAND CRITICAL WELDS SHALL MEETTHE PROVISION FOUND IN AISC 341-10 AND WELDING METHODS, EXCAVATIONS EXTEND TO PROPER 0 REFERENCE NOTE 4.2 'PACKING 0 O PROCEDURES AND QUALITY CONTROL SHALL COMPLY WITH AWS DI.I AND THE FOLLOWING: } DEPTH AND REACH PROPER MATERIAL A. ARC STRIKES,GOUGES AND OTHER IMPERFECTIONS WITHIN OR ADJACENTTO THE JOINT,SHALL BE Q (n *EXPOSURE CONTROL REPAIRED OR REMOVED. > Y Q Z CLASSIFY&TEST CONTROLLED FILL 0 REFERENCE NOTE 4.2 NO WELDING OVER CRACKED TACK WELDS O 0 B. PREHEAT AND INTER-PASS REQUIREMENTS AS OUTLINED IN SECTION 3.5. -.1U LLJ MATERIALS C. UNREPAIRED CRACKS,GOUGES,AND NOTCHES WILL NOT BE PERMITTED IN THE JOINT AREA. Q w Q ENVIROMENTAL CONDITIONS D. USE ELECTRODES WITH CHAFFY V-NOTCH ABSORBED > PERFORM MATERIALS,DENSITIES,AND REFERENCE NOTE 4.1 'WIND SPEED WITHIN LIMITS O O ENERGY EQUALTO OR GREATER THAN 20 FT-LBS AT 20 DEGREES FAHRENHEIT UNDER AWS AS Z LIFT THICKNESSES DURING PLACEMENT 0 CLASSIFICATION TEST METHODS,AND 40 FT-LBS AT 70 DEGREES FAHRENHEIT USING TEST PROCEDURES J AND COMPACTION OF CONTROLLED FILL. *PRECIPITATION AND TEMPERATURE PRESCRIBED IN APPENDIX X OF AISC 358.ACCEPTABLE ELECTRODES INCLUDE E70TG-K2,E71 T-1. _ of W PROPERLY PREPARED SITE AND SUB- 0 REFERENCE NOTE 4.1 WPS FOLLOWED !ll LIJ C) GRADE PRIOR TO FILL. *SETTINGS ON WELDING EQUIPMENT V� m L.L cM GENERAL STEEL SPECIAL INSPECTION NOTES: Q 0 LL oo GENERAL SPECIAL INSPECTION NOTES: 'TRAVEL SPEED 1. QUALITY ASSURANCE(QA)INSPECTION OF FABRICATED ITEMS SHALL BE MADE AT THE FABRICATOR'S PLANT.THE J w 0 N 1. THE ITEMS MARKED WITH A"O"IN THE SPECIAL INSPECTION SCHEDULE SHALL BE INSPECTED IN ACCORDANCE W ITH IBC CHAPTER 17 BY A CERTIFIED SPECIAL INSPECTOR FROM AN ESTABLISHED TESTING AGENCY.FOR 'SELECTED WELDING MATERIALS 0 0 DUAL ITYASSURANCE INSPECTOR(QAI)SHALL SCHEDULE THIS WORK TO MINIMIZE INTERRUPTION TO THE WORK MATERIAL SAMPLING AND TESTING REQUIREMENTS,REFER TO THE MATERIAL SAMPLING AND TESTING SECTION,THE PROJECT SPECIFICATIONS,AND THE SPECIFIC GENERAL NOTES SECTIONS.THE TESTING AGENCY SHALL SEND 'SHIELDING GAS TYPE/FLOW ATE OF THE FABRICATOR. COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO THE ARCHITECT,ENGINEER,CONTRACTOR,AND BUILDING OFFICIAL.ANY ITEMS WHICH FAIL TO COMPLY WITH THE APPROVED CONSTRUCTION 2. QA INSPECTION OF THE ERECTED STEEL SYSTEM SHALL BE MADE AT THE PROJECT SITE.THE QAI SHALL SCHEDULE DOCUMENTS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION.IF DISCREPANCIES ARE NOT CORRECTED,THEY SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL, APREHEATAPPUED THIS WORKTO MINIMIZE INTERRUPTION TOTHE WORK OFTHE ERECTOR. ARCHITECT,AND ENGINEER PRIOR TO COMPLETION OFTHAT PHASE OFW ORK.SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLVTOALL BIDDER DESIGNED COMPONENTS. *INTERPASS TEMPERATURE MAINTAINED(MIN./MAX) 3. WHERE ATASK IS NOTEDTO BE PERFORMED BY BOTH QC AND CIA,IT IS PERMITTEDTO COORDINATETHE 2. ANY CONSTRUCTION OR MATERIALTHAT HAS FAILED INSPECTION SHALL BE SUBJECTTO REMOVALAND REPLACEMENT. INSPECTION FUNCTION BETWEEN THE QCI AND QAI SOTHATTHE INSPECTION FUNCTIONSARE PERFORMED BY 3. CONTINUOUS SPECIAL INSPECTION MEANSTHE FULL-TIME OBSERVATION OFWORK REQUIRING SPECIAL INSPECTION BYAN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREAWHERE THE WORK IS BEING 'PROPER POSITION(F,V,H2OH) ONLY ONE PARTY.WHERE QA RELIES UPON INSPECTION FUNCTIONS PERFORMED BY QC,THE APPROVAL OF THE PERFORMED.PERIODIC SPECIAL INSPECTION MEANS THE PART-TIME OR INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA W HERE THE WELDING TECHIQUES ENGINEER OF RECORD AND THE AUTHORITY HAVING JURISDICTION IS REQUIRED. WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION OF THE WORK.(IBC SECTION 1702) 4. THE FABRICATOR'S QCI SHALL INSPECT THE FABRICATED STEELTO VERIFY COMPLIANCE WITH THE DETAILS 'INTERPASS AND FINAL CLEANING SHOWN ON THE SHOP DRAWINGS,SUCH AS PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION.THE O O ERECTOR'S QCI SHALL INSPECT THE ERECTED STEEL FRAME TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN *EACH PASS WITHIN PROFILE LIMITATIONS ON THE ERECTION DRAWINGS,SUCH AS BRACES,STIFFENERS,MEMBER BOLTING STRUCTURAL STEEL SPECIAL INSPECTION SCHEDULE *EACH PASS MEETS QUALITY REQUIREMENTS LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION. B ESTABLISHED PER 2018 IBC SECTION 1705.2.1,STANDARDS PER AISC STEEL CONSTRUCTION MANUAL 15TH ED. PLACEMENT AND INSTALLATION OF STEEL HEADED STUDS ANCHORS P P 5. THE QAI SHALL BE ON THE PREMISES FOR INSPECTION DURING THE PLACEMENT OF ANCHOR RODS AND OTHER B EMBEDMENTS SUPPORTING STRUCTURAL STEEL FOR COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS.AS A INSPECTION TASKS AFTER WELDING AISC NSA-3) FABRICATOR SPECIAL INSPECTOR MINIMUM,THE DIAMETER,GRADE,TYPE AND LENGTH OF THE ANCHOR ROD OR EMBEDDED ITEM,AND THE FABRICATOR QUALISPECIALINSSURAN QUALITY CONTROL QUALITY ASSURANCE EXTENT OR DEPTH OF EMBEDMENT INTO THE CONCRETE,SHALL BE VERIFIED INSPECTION TASKS PRIOR TO BOLTING(AISC TABLE N5.6-11 QUALITY CONTROL QUALITY ASSURANCE NOTES: WELDS CLEANED O O PRIOR TO PLACEMENT OF THE CONCRETE. 6. THE QAI SHALL INSPECT THE FABRICATED STEEL OR ERECTED STEEL FAME,AS APPROPRIATE,TO VERIFY MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS 0 P 1. (0)OBSERVE(PERIODIC)-OBSERVE THESE ITEMS ON A RANDOM SIZE,LENGTH AND LOCATION OF WELDS P P COMPLIANCE WITH THE DETAILS SHOWN ON THE CONSTRUCTION DOCUMENTS,SUCH AS BRACES,STIFFENERS, FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS 0 0 BASIS.OPERATIONS NEED NOT BE DELAYED PENDING THESE WELDS MEET VISUAL ACCEPTANCE CRITERIA MEMBER LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION. INSPECTIONS. 7. QUALITY ASSURANCE(QA)INSPECTIONS,EXCEPT NONDESTRUCTIVE TESTING(NDT),MAY BE WAIVED WHEN THE CORRECT FASTENERS SELECTED FOR THE JOINT DETAIL(GRADE,TYPE,BOLT 2. (P)PERFORM(CONTINUOUS)-PERFORM THESE TASKS FOR EACH *CRACK PROHIBITION WORK IS PERFORMED IN A FABRICATING SHOP OR BY AN ERECTOR APPROVED BY THE AUTHORITY HAVING LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE) O 0 WELDED JOINT OR MEMBER. 'WELD/BASE-METAL FUSION JURISDICTION(AHJ)TO PERFORM THE WORK WITHOUT CIA.NOT OF WELDS COMPLETED IN AN APPROVED 3. QUALITY CONTROL(QC)SHALL BE PROVIDED BY THE FABRICATOR FABRICATOR'S SHOP MAY BE PERFORMED BY THAT FABRICATOR WHEN APPROVED BY CORRECT BOLTING PROCEDURES SELECTED FOR JOINT DETAIL 0 0 AND ERECTOR. 'CRATER CROSS SECTION P P THE AHJ.WHEN THE FABRICATOR PERFORMSTHE NOT,THE QA AGENCY SHALL REVIEW THE FABRICATOR'S NOT A 4. QUALITY ASSURANCE(QA)SHALL BE PROVIDED BY OTHERS WHEN •WELD PROFILES REPORTS. ocur°ErvrHi DBRTHE CONNECTING ELEMENTS,INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION OB IUMBER FOLDER/B7O ORIGINAL o Exn AND HOLE PREPARATION,IF SPECIFIED,MEET APPLICABLE REQUIREMENTS O 0 REQUIRED BVTHDING CODE BC),HAV PURCHASER, JURISDICTION 8. AT COMPLETION FABRICATION,THE FABRICATOR PERFORMED THE FABRICATOR RARE(COMPLIANCE APPLICABLE BUILDING CODE(ABC),PURCHASER,OW TER,OR •WELD SIZE TO THE AHJ STATING THAT THE MATERIALS SUPPLIED AND WORK PERFORMED BY THE FABRICATOR ARE IN ENGINEER OF RECORD(EOR).NONDESTRUCTIVE TESTING(NDT) 'UNDERCUT ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS.AT COMPLETION OF ERECTION,THE APPROVED ERECTOR 10NA(E,I' PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE FOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE AHJ STATING THAT THE N OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED P 0 QUALITY ASSURANCE,EXCEPT AS PERMITTED IN ACCORDANCE 'POROSITY MATERIALS SUPPLIED AND WORK PERFORMED BY THE ERECTOR ARE IN ACCORDANCE WITH THE CONSTRUCTION WITH SECTION N7. DOCUMENTS. ARC STRIKES P P PROPER STORAGE PROVIDED FOR BOLTS,NUTS,WASHERS AND OTHER FASTENER S. FOR SNUG-TIGHT JOINTS,PRE-INSTALLATION VERIFICATION TESTING 9. IDENTIFICATION AND REJECTION OF MATERIAL OR WORKMANSHIP THAT IS NOT IN CONFORMANCE WITH THE 1 6 6 7 6 COMPONENTS 0 0 ASSPECIFIED INTABLE N5.6-1AND MONITORINGOFTHE K-AREA' P P CONSTRUCTION DOCUMENTS,SHALL BE PERMITTED AT ANYTIME DURING THE PROGRESS OF THE WORK. 6/08/202 INSTALLATION PROCEDURES AS SPECIFIED IN TABLE N5.6-2 ARE NOT P p HOWEVER,THIS PROVISION SHALL NOT RELIEVE THE OWNER OR THE INSPECTOR OF THE OBLIGATION FOR FABRICATOR SPECIAL INSPECTOR BACKING REMOVED AND WELD TABS REMOVED(IF REQUIRED) INSPECTION TASKS DURING BOLTING(AISC TABLE N5.6-21 QUALITY CONTROL QUALITY ASSURANCE INSTALLATION PATEN RSINSNUG-TBE PRESENT DURING THE REPAIR ACTIVITIES P P SHALL BE BROUGHTTO THE IMMEDIATE ATTENTTIMELY,IN-SEQUENCE INSPECTIONS. ION OFHE FABNG RICATOR ORL AND RE ERECTOR,AS APPLICABLE.KMANSHIP9L/O �BQy� INSTALLATION OF FASTENERS IN SNUG-TIGHT JOINTS. K. 6. FOR PRETENSIONED JOINTS AND SLIP-CRITICAL JOINTS,WHEN THE DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER P p 111. NONCONFORMING MATERIAL OR WORKMANSHIP SHALL BE BROUGHT INTO CONFORMANCE,OR MADE SUITABLE FASTENER ASSEMBLIES PLACED IN ALL HOLES AND WASHER AND NUTS ARE INSTALLER IS USING THE TURN-OF-NUT METHOD WITH FOR ITS INTENDED PURPOSE AS DETERMINED BY THE ENGINEER OF RECORD. POSITIONED AS REQUIRED O 0 MATCHMARKING TECHNIQUES,THE DIRECT-TENSION-INDICATOR NO PROHIBITED WELDS HAVE BEEN ADDED WITHOUTTHE APPROVAL O O 11. CONCURRENT WITH THE SUBMITTAL OF SUCH REPORTS TO THE AHJ,FOR OR OWNER,THE QA AGENCY SHALL METHOD,OR THE TWIST-OFF-TYPE TENSION CONTROL BOLT OF THE FOR SUBMIT TO THE FABRICATOR AND ERECTOR: JOINT BROUGHTTO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING METHOD,MONITORING OF BOLT PRETENSIONING PROCEDURES A. NONCONFORMANCE REPORTS A A OPERATION O 0 SHALL BE AS SPECIFIED IN TABLE N5.6-2.THE QCI AND QAI NEED 'WHEN WELDING OF DOUBLER PLATES,CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, B. REPORTS OF REPAIR,REPLACEMENT OR ACCEPTANCE OF NONCONFORMING ITEMS FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING O 0 NOT BE PRESENT DURING THE INSTALLATION OF FASTENERS WHEN VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 31N.(75mm)OF THE WELD) THESE METHODS ARE USED BY THE INSTALLER. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION, 7. FOR PRETENSIONED JOINTS AND SLIP-CRITICAL JOINTS,WHEN THE INSPECTIONS PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE INSTALLER IS USING THE CALIBRATED WRENCH METHOD OR THE EDGES O 0 TURN-OF-NUT METHOD WITHOUT MATCHMARKING,MONITORING CITY APPROVED PLANS OF BOLT PRETENSIONING PROCEDURES SHALL BE AS SPECIFIED IN TABLE N5.6-2.THE QCI AND QAI SHALL BE ENGAGED IN THEIR INSPECTION TASKS AFTER BOLTING(AISC TABLE N5.6-31 FABRICATOR SPECIAL INSPECTOR ASSIGNED INSPECTION DUTIES DURING INSTALLATION OF QUALITY CONTROL QUALITY ASSURANCE FASTENERS WHEN THESE METHODS ARE USED BY THE INSTALLER. Reviewed for Coda Compliance No. Description Date _002 c DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P P 8. OBSERVATION OF BOLTING OPERATIONS SHALL BE THE PRIMARY LMETHOD USED TO CONFIRM THAT THE MATERIALS,PROCEDURES PLANS MUST BE ON JOB SITE J AND WORKMANSHIP INCORPORATED IN CONSTRUCTION ARE IN CONFORMANCE WITH THE CONSTRUCTION DOC FOR ALL INSPECTIONS 1 2 3 4 5 Page 16 of 97 1 2 3 4 5 MARKS AND SYMBOLS LEGEND LAUGHLIN RICKS 7 1 Ij ROBERT WEED PLYWOOD INTERIOR OFFICE FRAMING SECTION MARK 3351 ELDRIDGE AVE. SHEET NUMBER TWIN FALLS,ID 83301 NOESIS ENGINEERING SERVICES,P.C. �//11� INDICATES FOOTING,SEE PLAN AND D (2)2A ABV O SCH.ON S-501 • `� D I I (1)2A ABV _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ / 3.1 — — — — — — — — — — — — — — — — — — — — — — — — — — 1712 CABALLERO DR. AMMON,IDAHO 83406 (208)932-2720 FOUNDATION PLAN NOTES WWWNOESIS.US 2 All A ABV BY (2)2w AB-01. VERIFY ALL FLOOR OPEINGS FOR MECHANICAL oeY SHAFTS,STAIRS,ETC.WITH ARCHITECTURAL eo ev AND MECHANICAL DRAWINGS. 2. SEE ARCHITECTURAL DRAWINGS FOR COLUMN IL "gol PM WALLS AND OPENING DIMENSIONS. 3. FIELD VERIFY ALL DIMENSIONS. \ 26 ABV, 2l ABV 4. ARCHITECT TO VERIFY REQUIRED BEAM P#x6 ABv L CLEARANCE 5. COORDINATE LOCATION OF DEPRESSED SLABS, SLOPED SLABS,AND FLOOR DRAINS ARCHITECTURAL AND MECHANICAL DRAWINGS. 6. SEE ARCHITECTURAL AND CIVIL DRAWINGS FOR ILL] E%TERIOR CONCRETE WORK AT DOORS, SIDEWALKS,ETC. LL w zxs Aev� e�zm Aev 7. SEE ARCHITECTURAL DRAWINGS FOR CONTROL Q JOINT LOCATION. V) Z 8. ALL SPOT FOOTINGS SHALL BE CENTERED Hssaxaxva ABv UNDER COLUMNS(UNO). Y 0 C Z O C —_L_------- THICKEN SLAB 3.2 —_—_—_—_— _—_—_—_—_—_—_—_—_ L —_—_—_—_ _ _ _ _—_—_—_—_—_—_—_—_—_—_—_—_—_—_ Q } I F53.75 J w HSSOX4X1/4 ABV Q w Q THICKEN SLAB z LL (B)2A ABVp Cl--(3)2x6 ABV of J ~ w O wv mLLm LJ Q O _p SON IN THESE FOUR LOCATIONS THE EXISTING SLAB SHALL BE SAW CUT AND (])?xb ABV A THICKEN SPOT FOOTING/SLAB INSTALLED.THE REMAINING BEARING WALLS AND MINOR COLUMNS SHOWN ON SHEET 5-101 SHALL BEAR ON 3.3 --_—_—_—_—_—_—_—_— _—_—_—_ _—_—_—_—_—_— —THE EXISTING 6"SIAB ON GRADE-_—_—_—_—_—_—_—_—_—_—_—_—_ _ I I I I I i I B B I ' FS1.3x6 FS1.3x6 HICKENS AB HSSI4—1 a ABV THICKEN SLAB HSE—X-ABV EKAL IVI 4 EPDXY CROSSWISE FOOTING o6 NUMBER Fo LOER/i IGINAL—ME— orpT E E .R/7B ORIGINAL OM REBAR INTO EXISTING WALL W/4"EMBED DEPTH AND SIMPSON SETXP ORSIMLIAR NJA) / Ty TYP �o s-o1 s-o1 16676 6/08/202 17 9" 8'-3" 3'-2 3/4" 22'- 1/4" 09�Q or BQy��Q 26'-0" 26,-0" A b B C CITY APPROVED PLANS A Reviewed for Code Compliance A PLANS MUST BE ON JOB SITE FOUNDATION PLAN FOR ALL INSPECTIONS 1 FOUNDATION PLAN No. Description Date S-101 1 2 3 4 5 Page 17 of 97 1 2 3 4 5 qLAUGHLIN RICKS MARKS AND SYMBOLS LEGEND ROBERT WEED PLYWOOD INTERIOR OFFICE FRAMING 3351 E AVE. TWIN FALLS,GD 3301 SECTION MARK SHEET NUMBER NOESIS ENGINEERING SERVICES,P.C. INDICATES WOOD SHEATHING.SEE GSN AND SCHEDULE ON SHEET S-602 D (E)2x6 �x6 BEARING WALL I i INDICATES SHEAR WALL TYPE,SEE 5-602 ./ J, D (1)1 3/4 x 11 7/8 LVL FRAMING PLAN NOTES ` 3.1 _—_—_—_—_----- (rPA—_—_ _—_—_ _—_—_—_— —_—_—_—_—_—_—_— _—_—_—_—_—_—_—_—_—_ 1712 CABALLERO DR. Sim 1. VERIFY ALL FLOOR OPEINGS FOR MECHANICAL AMMON,IDAHO 83406 2 5-510 SHAFTS,STAIRS,ETC.WITH ARCHITECTURAL (208)932-2720 J AND MECHANICAL DRAWINGS. W W W.NOESIS.US 2. 2. SEE ARCHITECTURAL DRAWINGS FOR COLUMN 212s 2x12 DF#2 er izz - - - - - - t WALLSAND OPENING DIMENSIONS. 3. FIELD VERIFY ALL DIMENSIONS. oev 4. ARCHITECT TO VERIFY REQUIRED BEAM CLEARANCECHIC1 eo ev 5. SEE 6/S-602 FOR TOP PLATE SPLICE AND x6 BEARING WALL 1/S-520 AT PIPES. (7)2.s 6. ALL DOOR AND WINDOW OPENING NOT CALLED OUT SHALL BE WH-1 HEADER 7. WALL INTERIOR WALLS SHALL BE SHEAR WALL 2ifi� 2. TYPE SW-1(GYPSUM BOARD)PER SCHEDULE 2x12 DF#2 1 2.61 BEARING WALL ON 5-602. 2x6 BEARING WALL O 2x6 BEARING WALLiLu __ __ LL.I Q 2s -- — - -—-—-—- —-—1 V) z (1)1 314x14 LVL Hss4x4xv4 LOADING ASSUMPTIONS Y 0 c z OO c 2z6 BEARING WALL FLOOR DEAD LOAD 15 PSF 3.2 —_ FLOOR LIVE LOAD 80 PSF -------- — J /^ _HSS4—x4-- V vl D_ (1)1 3/4 x 11 7/8 LVL Y 0 Z U Lu g a wQ (312 z > LL J LL1 2x6 BEARING WALL 2x6 BEARING WALL— 7I = U m LL M 2x6 BEARING WALL0 LL a0 Q w0N I I (2)1 314 x 11 718 LVL 9 TYP 3.3 - - - - - - - - - - - ¢x 5-501 � 3 Sim 3 5-510 x I I 3 I I B B I I I I 2z6 BEARIN WALL — — HSS4x4xt14 HSS4-1/4 2x6 BEARING WALL ILE�- - - - - - - - nrieo on�ry n I. 2x6 BEARING WAL ,NG=,N roLcex5,IC H01IORIGINAL oacuSIRIIR IIRIII os OI ME- 16'-S5/8" 11'-53/416'-SS/8" 11'-53/4" I�11'-53/4�11'_13/4�53/4�11'-13/4" FLOOR TYPE KEY: FSSON 11 11 7/8"TJI 360 OR SIMLIAR @ 16"O.C.BEAR ON WALL OR SIMPSON ITS2.37/11.88 HANGER WITH WEB gp STIFFENERS AT HANGER LOCATIONS 1 6 6 7 6 1 SECOND FLOOR FRAMING PLAN o 9/08/202 1i4"=1'-0" q� OF K. BQy CITY APPROVED PLANS Reviewed for Code Compliance A PLANS MUST BE ON JOB SITE A FOR ALL INSPECTIONS SECOND FLOOR FRAMING PLAN No. 1 Description Dale S-102 1 2 3 4 5 Page 18 of 97 1 2 3 4 5 MARKS AND SYMBOLS LEGEND LAUGHLIN RICKS ROBERT WEED PLYWOOD INTERIOR OFFICE FRAMING SECTION MARK 3351 ELDRIDGE AVE. SHEET NUMBER TWIN FALLS,ID 83301 NOESIS ENGINEERING INDICATES WOOD SHEATHING.SEE SERVICES P.C. I GSN AND SCHEDULE ON SHEET 5-602 0 i i i SW-x INDICATES SHEAR WALL TYPE,SEE S-602 D /1\ 2x4 @ 16"O.C.WALL 2x4 @ 16"O.C.WALL _ _—_—_—_—_—__ 1712 CABALLERO DR. AMMON,IDAHO 83406 (208)932-2720 W W W.NOESIS.US _ I 2x4 @ 16"0.1.WALL BY 2x8 DF#2 BRACING FRAMING PLAN NOTES IINIII CHIC11111 1. VERIFY ALL FLOOR OP El NGS FOR MECHANICAL 2x4 @ 16"O.C.WAL SHAFTS,STAIRS,ETC.WITH ARCHITECTURAL - 2z4 @ 16"O.C.WALL AND MECHANICAL DRAWINGS. 2. SEE ARCHITECTURAL DRAWINGS FOR COLUMN WALLS AND OPENING DIMENSIONS. 3. FIELD VERIFY ALL DIMENSIONS. 2x8 DF#2 BRACING 2x8 DF#2 BRACING 4. ARCHITECT TO VERIFY REQUIRED BEAM CLEARANCE O 5. SEE 615-602 FOR TOP PLATE SPLICE AND _ 1/S-520 AT PIPES. w 6. ALL DOOR AND WINDOW OPENING NOT Lu ene Gric-2z47 CALLED OUT SHALL BE WH-1 HEADER LOADING ASSUMPTIONS N Z 2x8 DF#2 BRACING 2x8 DF#2 BRACING I Y C — Z 0O C 2x4 @ 16"O.C.WALL— FLOOR DEAD LOAD 15 PSF 2x4 @ 16"O.C.WALL 2x4 @ 16"O.C.WALL MECH PLATFORM LIVE LOAD 80 PSF —_—_—_—_—_ _—_—_—_—_—_— _ _ _ _ _ _ _—_—_— Lrl J ED a U) u 3: Y O Z U Iz IW J " Lu a U Q w Q h U 2z4 @ 16"O.C.WALL 00 � � u� 2x8 DF#2 BRACING Z LL 2 y w wU I. LL E0 N 2x8 DF#2 BRACING Q O ILLo w0N 6'-9" 6'-6" 6'-0" 6'-0" 3'-3 1/4" Cf I I W I _—_—_—_—_—_—_—_—_—_- 2x4 @ 16"O.C.WALL I I 2x4 @ 16"O.C.WALL N C1 —2x4 @ 16"O.C.WALL Z z U B B J - C7 LL I I I I I I I I I ,xE 2x4@16"O.C.WALL OB NUMBER FOioewio ORIGINAL—ME— OEB GREYAREAMECHANICALMERANINE WITH EQUIPMENHT LOADS(TWO 300 LBF), FLOOR TYPE KEY: �5510�1 E I OTHER AREAS(NON-GREY)SHALL HAVE NO }' N � STORAGE OR EQUIPMENT 11 117/8"TA 110 OR SIMLIAR @ 16"O.C.BEAR ON WALL HANGING CEILING GRID NOTE:SEE ARCH CATOON FOR CEILING GRID AND DETAIL 16676 REQUIREMENTS.CEILING GRIDE SHALL BE CONNECTED TO THE EXISTING STEEL 6/08/202 BUILDING STRUCTURE PER ARCH DRAWINGSAND MANUFACTURE REQUIREMENTS or /a K. eoy CITY APPROVED PLANS A A SECOND CEILING FRAMING PLAN Reviewed for Code Compliance PLANS MUST BE ON JOB SITE SECOND FLOOR CEILING FRAMING FOR ALL INSPECTIONS No. Description Dale S-103 1 2 3 4 5 Page 19 of 97 1 2 3 4 5 PIPE,SEE MECH.PROVIDE SLEEVESAROUNDALLPIPES LAUGHLIN RICKS PASSING THROUGH WALL AND ROBERT WEED PLYWOOD FOOTINGS %u 1/2"CLEAR INTERIOR OFFICE FRAMING o z 3351 ELDRIDGE AVE. Z Powp CONCRETE FOOTING SCHEDULE TWIN FALLS,ID 83301 REINFORCING CROSSWISE REINFORCING LENGTHWISE <4 - DIAGRAM MARK WIDTH LENGTH DEPTH NOESIS ENGINEERING No. SIZE LENGTH SPACING No. SIZE LENGTH SPACING m d FS1.3x6 14" 6'-0" 10" 6 N6 1'-6" EQ 3 N5 5'-6" EQ SERVICES,P.C. FS3.75 3-9" 3'-9" 1.. 5 N4 3'3" EQ 5 N4 3'-3" EQ 1 N SHALL APPLY FORCE 2'-0"MININOCENTI RUNLESS OTHERWI E \\� BACK-FILLED TRENCH NOTED 1l D CONCRETE FOOTING,SEE _ PLAN AND SCH ,,,_—III-III-III r, „L» � T �f\ / D a 12"MIN 12"MIN ADDITIONAL REINF TO �\\`��i = � — �— <,'-'.-• —�—III—� MATCH CONT FTG REINF REINFORCING REINFORCING —�III— ` =IIIIIIIII III III III III�II—III PIPE PASSES BELOW FOOTING CROSSWISE LENGTHWISE 1712 CABALLERO DR. PIPE,SEE MECH.PROVIDE III III—III III _ AMMO8)IDAHO 06 SLEEVES AROUND ALL PIPES ��}I PIPE,SEE CIVIL III III—III PASSING THROUGH WALL AND 1/2"CLEAR 24 BAR IDEPTH (208I 9322720 FOOTINGS DIAMETERS ,� WWW.NOESIS.US i ° x Ar °° ° d eNc \ �\otN oar BOTTOM OF TRENCH -II SHALL BE ABOVE THIS n ° EDer E IN -1I„III III— ? IL CONCRETE FOOTING, CONCRETE FOOTING NOTES: 51 -III ADDITIONAL REINF TO 1. COMPRESSIVE STRENGTHS OF CONCRETE AT 28 DAYS SHALL BE 3,000 PSI SEE PLAN AND SCHED — III III= III —III 2 MATCH CONT FTG REINF 2. PLACE ALL FOOTING REINFORCING IN THE BOTTOM OF THE FOOTING WITH 3"CLEAR CONCRETE COVER(UNO). CONCRETE FOOTING,SEE 12"MIN 12"MIN 3. TOP REINFORCI RIG,WHERE OCCURS,SHALL BE PLACED IN THE TOP OF THE FOOTING WITH 2"MINIMUM CONCRETE COVER. PLAN AND SCH INTERRUPT CONT FTG REINF 4. IF FOOTINGS ARE EARTH-FORMED,FOOTINGS SHALL BE 6"LONGER AND WIDER THAN SCHEDULED. PIPE PASSES THROUGH FOOTING FOR PASSAGE OF PIPE 5. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS. rl CONDITION AT PIPE PARALLEL TO CONCRETE FOOTING n CONDITION AT PIPE PERP.TO CONC.FTG. CONC.FOOTING SCHEDULE 0 W W W BEAM CONNECTION SCHEDULE N Z SHEAR PLATE INFORMATION BOLTS W/STANDARD BEAM WASHER OVER Y PL,DIMENSIONS SLOTS z O C 5 1/2" SLO T- LEV LEH WELD COMMENTS 23/4„ SLOTTED HOLES NO. SIZE "A" = O W8,W10 PL.1/4"x4" 11/2" 2" 2 3/4"0 3/16" (n STEEL COLUMN,SEE PLAN _ o STEEL COLUMN,SEE PLAN J Z. d W12 IN14 PL.5/16"x4" 11/2" 2" 3 3/4"0 1/4" Q (n D_ 0 v W16 PL.5/16"x4" 11/2" 2" 4 3/4"0 1/4" > Y O z C.: W18 PL.5/16"x4" 11/2" 2" 5 3/4"0 1/4" J U_ W ALL COLUMNS ADJACENT TO OR EMBEDDED IN WOOD STUD WALLS IoI ALL COLUMNS ADJACENT TO OR EMBEDDED IN WOOD STUD WALLS x 4" 2" Q W Q SHALL HAVE(1)1/2"0 x 31/2"THREADED STREEL ROD SHOP-WELDED 0 2X6 WALL = SHALL HAVE(1)1/2"0 x 3 1/2"THREADED STREEL ROD SHOP-WELDED W21 PL 5/16" 11/2" 6 3/4"0 1/4" Z 1/4 T T TO THE FACE OF THE COLUMN AT 24"O.C.AND EXTENDING EACH 1/4 T 1 TO THE FACE OF THE COLUMN AT 24"O.C.AND EXTENDING EACH W24 PL.3/8"x4" 11/2" 2" 7 7/8"0 1/4" z J A A WAV INTO THE ADJACENT STUD WALLS.ATTACH ADJACENTWOOD SECTION A-A A A WAY INTO THE ADJACENT STUD WALLS,ATTACH ADJACENT WOOD W27 PL.3/8"x4" 11/2" 2" 7 7/8"0 1/4" J EDGE OF BUILDING,WHERE OCCURS WALL STUDS TO STEEL COLUMN WITH STANDARD NUT&WASHER. WALL STUDS TO STEEL COLUMN WITH STANDARD NUT&WASHER. "W30 PL.1/2"x4" 13/4" 2 8 1"0 5/16" 1: Of LI W L C)EXISTING 6"CONCRETE SLAB ON GRADE W33 PL.1/2"x 4" 13/4" 2" 9 '..0 5/16 m W M W36 PL.1/2"x41/2"1 2" 21/4" 10 1-1/8"0 5/16" Q Q LL.oo 3/4"0 X 12"EXPANSION 1/2"STEEL BASE PLATE ON 11/2"NON- 3/4"0 X 12"EXPANSION 1/2"STEEL BASE PLATE ON 11/2"NOW J O N BOLTS,SEE SECTION IoI SHRINK GROUT(MAX GROUTTHICKNESS) BOLTS,SEE SECTION IoI SHRINK GROUT(MAX GROUT THICKNESS) EPDXY CROSSWISE FOOTING REBAR INTO EXISTING WALL W/4"EMBED DEPTH AND FACE OF HSS COLUMN SIMPSON SET-XP OR SIMLIAR 11/2" 1/2" LEH IITiI I I I I—I NOTAND BASE T SILLPLATE TO BE AND FLOORNCRMEMBERSE(GOUCOLU T STEEL NEDED).COLUMN w EXISTING CONC. - = ',; AND BASE PLATE TO BEAR ON CONCRETE(GROUT AS NEEDED). FOUNDATION WALL NEW FOOTING,SEE PLAN AND SCHEDULE NEWFOOTING,SEE PLAN AND SCHEDULE SHEAR PL.SEE SCHEDULE - 3/4"MINUS CRUSHED AGGREGTE BASE(4"MIN.) SHORT-SLOTTED HOLES IN m B COMPACTED TO 95%MODIFIED PROCTOR SHEAR PLATE W/WASHER ® B PER THE STRUCTURAL NOTES w NATURAL GRADE OR STRUCTURAL FILL COMPARED TO 95%MODIFIED PROCTOR W BEAM-SEE PLAN EXISTING FOOTING SEESCHED. 4 NEW SPOT FOOTINGS AND HSS COLUMN CONECTION BEAM CONNECTION SCHEDULE 1/4"CAP PLATE oe nuwaEx EOLoex/S7o ORIGINAL COCUNE—UNDER Ixe �S5ONA1 E r A=1/2"MINIMUM N SHEATHING PER SCHEDULE I I B=11/2" 1 6 6 7 6 s/o8/202 or C=GAGE OF CONNECTED MEMBER L J D=COLUMN WIDTH+1"BEAM O9/� OR GIRDER WIDTH+1"OR BOLT GAGE+3"WHICHEVER IS GREATER CITY APPROVED PLANS 1/4 Reviewed for Code Compliance A A PLANS MUST BE ON JOB SITE BEAM,SEE PLAN JOIST PER PLAN FOR ALL INSPECTIONS DETAILS ITS2.37/11.88 HANGER,WITH WEB STIFFENERS SIMPSON BA3.56/11.88 BEAM PER PLAN W/2X(WIDTH)NAILER W/1/2"dia.BOLTS @ 24"O/C(ALT.SIDES) NOTE:ALL STEEL COLUMNS SHALL HAVE A COLUMN CAP PLATE,U.N.O. No. Description Dale BEAM AND JOIST Ca)STEEL BEAM 10 TYPICAL COLUMN CAP PLATE S-501 1 2 3 4 5 Page 20 of 97 1 2 3 4 5 LAUGHLIN RICKS STEEL BUILDING PURUNS ROBERT WEED PLYWOOD INTERIOR OFFICE FRAMING 3351 ELDRIDGE AVE. TWIN FALLS,ID 83301 PERIMETER WALL,SEE PLAN, STEEL BUILDING PURLINS I NOESIS ENGINEERING 2X8 DF#2 OR BETTER CONTINUOUS FROM SECOND FLOOR LEVEL TO EXISTING SIMPSON SFC4.25 0R SIMILAR CONNECTOR W/ a SERVICES,P.C. BRACING,SEE PLAN BOTTOM PLATE #10 FASTNERS PER MANUFACTURER SIMPSON DTC CLIP @ BUILING PURLIN - � PURLIN SPACING ` SIMPSON A34 BLOCKING @ 48"O.C. NON-BEARING WALL D FINISH S.A.D. /rt \� D STUD nkI I SIMPSON A34 SIMPSON DTC CUP @ 48"O.C. 2X BLOCKING 1712 CABALLERO DR. I I I NON-BEARING WALL AMMON,IDAHO 83406 WALL,SEE PLAN — (208)932-2720 FINISH S.A.D. WWW.NOESIS.US FINISH S.A.D. V/ I I DOUBLE JOIST o By 1 0eY CEILING 2X8 BRACING 2 DOUBLE JOIST UNDER A NONLOADBEARING WALL 3 NON-BEARING WALL TOP CONN.TO STEEL BLG TOP PLATE SPLICE FLOOR BOUNDARY NAILING FLOOR BOUNDARY NAILING O HOLE SIZE STRAPS WALL ABOVE,WHERE� WALL ABOVE,WHERE LESS THAN OR EQUAL TO OCCURS,SEE PLAN OCCURS,SEE PLAN LL.I 1/3 STUD WIDTH NONE REQUIRED L_ (If GREATER THAN I/3 AND LESS ST2122 WITH 16d FLOOR SHEATHING, FLOOR SHEATHING, LJ_ THAN OR EQUAL TO 2/3 STUD WI DTH NAILS EACH END SEE PLAN SEE PLAN N Z ~�WALL ABV PER PLAN&SCH GREATER THAN ST2215 WITH(6)16d C STUD WIDTH NAILS EACH END CONTINUOUS RIM CONTINUOUS RIM Y BOARD BOARD Z O C SHEARWALL PIPE AND STRAP SIMPSON STRAP EDGE NAILING SHEARWALL EDGE NAILING VERIFY SIZE AND LOCATION WITH ARCH, EACH SIDE _J MECH,AND ELECTRICAL DRAWINGS } � DOUBLE TOP PLATE WOOD JOIST,SEE PLAN Q DOUBLE TOP PLATE DOUBLE TOP PLATE 77WO OD JOIST,SEE PLAN > Y 0 Z SIMPSON HANGER J U_ LL ONE SD NAIL EACH SIDE INTO TOP Q / ui Q PLATE AT ANGLE AT ELAST 1 1/2" > FLOOR JOISTWITH IN WALL WOOD COL SEE PLAN A O$DMOIST BLOCK FROM END OF TJI JOIST Z > LL HANGER,SEE PLAN N TYP WALL STUDS ONES D NAIL EACH SIDE INTO TOP = LL LU PLATE AT ANGLE AT ELAST 11/2" // LL.I U WALL SH EATHI NG, FROMENDOFTJIJOIST WALLSHEATHING, V WOOD BEAM a] LL M SEE PLAN SEE PLAN SIMPSON'A34'AT 24"O.C. SEE PLAN O ILL CSEE FOR(2)13/4"BEAMS USE(1)LPC4Z POST CAP. Q w O N FOR(1)13/4"BEAMS USE(3)16D TOE NAILS WOOD STUD WALL, WOOD STUD WALL, SEE PLAN SEE PLAN 5 BEAM TO COLUMN CONNECTION 8 TOP PLATE SPLICE AT PIPE 7 WOOD FLOOR BEARING PARRALLEL TO EXT.WOOD STUD WALL 8 WOOD FLOOR BEARING PREP.TO EXT.WOOD STUD WALL B B JOB NUMBER FOLDER/7o ORIGINAL—ME— OBR.xe �55(aNA( N i 16676 6/08/202 or BQy��e CITY APPROVED PLANS Reviewed for Code Compliance A A PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS DETAILS No. Description Date S-502 1 2 3 4 5 Page 21 of 97 1 2 3 4 5 SIMPSON LSSR410Z SLOPE HANGER ON CENTERS STRINGERS LAUGHLI N RICKS LANDING JOIST,WHERE OCCURS,5EE PLAN AND STAIR DETAILS ROBERT WEED PLYWOOD 14"LVL 2.0E OR BETTER STRINGER,1 ON EACH SIDE INTERIOR OFFICE FRAMING ALONG WALLS AND 2IN THE CENTER, 3351 ELDRIDGE AVE. SEE PLAN AND STAIR TWIN FALLS,ID 83301 DETAILS NOESIS ENGINEERING SERVICES,P.C. STRINGER AT WOOD STUD WALL, CONNECT TO STUDS WITH(2)16D NAILS D DOUBLE PLATE OPENING UNDER STAIRS,WHERE / OCCUR,SEE ARCH PLANS 1712 CABALLERO DR. AMMON,IDAHO 83406 (208)932-2720 W W W.NOESIS.US All STUD H O Lu L L Lu V) Z Y 0 C z O C GENERAL WOOD FRAMED STAIR _ � J Q U) D C) o � a 11� LU>> Q TREND STYLE/FINISH BY ARCH z > IY LL O (� LU = w U STUD WALL PER PLAN @ 16"O.C. 11 7/8"T1L PER PLAN O L1_C SIMPSON LSSJHAN �)RGER SON 2X8 LEDGER WI 1.75"X14"LVL 1.9e OR BETTER NAILS @ 16"O.CDS) SIMPSON L11R430Z HANGER 1.75"X14"STRINGER VERSA-LAM 2.0E OR BETTER Aj LANDING JOIST:2X8 DF#2 @ STUD WALL SEE PLANS,SHALL BE BALLON FRAMED AT STAIR PARTITION STUD WALL SEE PLANS,SHALL BE BALLON FRAMED AT STAIR PARTITION WITH SIMPSON LU28 H LOCATIONS,CONTINOUS STUD FROM EXISTING SLAB TO TOP OF RAILING'S LOCATIONS,CONTINOU5 STUD FROM EXISTING SLAB TO TOP OF RAILING'S 2X32 DF#2 PARTITION PARTITION BLOCKING AT LEDGE LOCATION BLOCKING AT LEDGE LOCATIONDOUBLE TOPB //�A 2X6 LEDGER WITH(3)16D 2X12 LEDGER WITH(3)16D B WOOD STUD - NAILS @ 16"O.C.(INTO STUDS) NAILS @ 16"O.C.(INTO STUDS) SIMPSON IT52.37/11.88 HANGER STUD WALL PER PLAN @ 16"O.C. TREND STYLE/FINISH BY ARCH 2X8 LEDGER WITH(3)16D NAILS @ 16"O.C.(INTO STUDS) 1.75"X34"STRINGER VERSA-LAM 2.0E OR BETTER 1.75"X14"STRINGER VERSA-LAM 2.0E OR BETTER LANDING JOIST:2X8 DF#2 @ 16 C."O. O CERT A WITH SIMPSON LU28 HANGERS FLOOR1015T,SEE PLAN csEro.. DER INE O A oB NUMBER FDLDEv7�B DNBNAL—ME- 2X12 OF#2 OR 117/8"LVL 1.9e OR BETTER BLOCKING AT ALL BEARING LOCATIONS DOUBLE TOP PLATE 117/8"LVL 1.9e OR BETTER WOOD STUD WALL,SEE PLAN (ESS�� DOUBLE TOP PLATE Q� WOOD STUD WALL SECTION A-A SIMPSON LSSR1.81Z HANGER WOOD STUD WALL 16676 SIMPSON LSSR1.81Z HANGER 6/08/202 - '' 09p9 OF K. Bay - JI III III III��III III III-III= "'=11I III III III III III III III L3X3X3/16 X 5'WITH(2)1/2"�A307 BOLTS INTO EACH L3X3X3/16X5"WITH(2)1/2"0 A307 BOLTS INTO EACH J C1111�I ICI III (I STRINGER,CONNECT TO EXISTING 6"CONCRETE SLAB WITH CITY APPROVED PLANS STRINGER,CONNECT TO EXISTING 6'CONCRETE SLAB WITH II—I11= — (1)1/2"0 EPDXY ANCHOR BOLT EMBED 21/2"MIN (1)1/2"0 EPDXY ANCHOR BOLT EMBED 21 MIN Reviewe/2" 2 DETAILS FOR WEST STAIRS 3 DETAILS FOR EAST STAIRS or Code Compliance A 3i4"=1'-0" PLANS MUST BE ON JOB SITE STAIR DETAILS FOR ALL INSPECTIONS No. I Description Date S-510 1 2 3 4 5 Page 22 of 97 1 2 3 4 5 MINIMUM NAILING SCHEDULE LAUGHLIN RICKS SHEATHING SCHEDULE AT ROOF AND FLOOR HEADER BEARING SCHEDULE FOR 2x STUD WALL CONNECTION NAILING ROBERT WEED PLYWOOD LOCATION WOOD SHEATHING NAIL EDGE NAIL FIELD BOUNDARY EDGE COMMENTS MAXIMUM IAMB INTERIOR OFFICE FRAMING SOLE PLATETOJOISTOR BLOCKING,FACE NAIL 16d AT 16"O.C. THICKNESS SIZE CONT EDGE OTHER EDGE NAIL NAIL BLOCK MARK HEADER HEADERSPAN BEARINGSTUDS KINGSTUDS COMMENTS 3351 ELDRIDGE AVE. BRIDGING TO JOIST,TOENAIL EACH END (2)8d WH-1 (2)ZX10 DF42 OR BETTER ---- (1)2X DFN2 (1)ZX DFN2 TWIN FALLS,ID 83301 BLOCKING BETWEEN101STOR RAFTERS TO TOP PLATE,TOE NAIL (3)8d FLOOR 23/32"OSB(48/24) 1 10d 61N 61N 121N 61N NO RIM JOIST TO TOP PLATE,TOE NAIL 8d AT 6"O.C. NOESIS ENGINEERING COLLAR TIE TO RAFTER,FACE NAIL (3)1Od SHEATHING NOTES: SERVICES,P.C. JACK RAFTERTO HIP,TOE NAIL (3)lOd 1. MINIMUM NAIL PENETRATION INTO FTAMING:8d-1 1/2",10d-15/8". FACE NAIL (2)16d 2. USE COMMON NAILS(8d DIAMETER=0.131",10d DIAMETER=0.148". ROOF RAFTER TO 2x RIDGE BEAM,TOE NAIL (2)16d 3. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS. FACE NAIL (2)16d JOIST TO BAND JOIST,FACE NAIL (3)16d NOTE:MEMBER SIZES SHOWN ARE MINIMUM DEPTHSANO WIDTHS D LEDGER STRIP,TO FACE NAIL (3)16d 2x WALL STUDS,TYP ,1 D DOUBLE STUDS, END NAIL 16d AT CENTER EDGESTS SHEATHING.STAGGER 8"GAP AT END JOINTS KING STUD(S) DOUBLE STOP PLATES, FA 16d AT 24"O.C. PLYWOOD O BLOCKS JOINTS AND ALTERNATE ix CONTPLATE / DOUBLED TOP PLATES,FACE NAIL 16d AT 16"O.C. AND BLOCKS GRAIN DIRECTIONS LEDGER TOP PLATES,LAPS&INTERSECTION,FACE NAIL (2)16d 1712 CABALLERO DR. CONTINUOUS HEADER,TWO PIECES l6d AT 16"O.C.ALONG EACH EDGE z AMMON,IDAHO 83406 CEILING JOISTS TO PLATE,TOE NAIL (3)8d (208)932-2720 CONTINUOUS HEADER TO STUD,TOENAIL (4)8d o CEILING JOISTS,LAPS OVER PARTITIONS,FACE NAIL (3)16d �+ 16d NAILS @ 1.5" W W W.NOESIS.US CEILING JOISTS TO PARALLEL RAFTERS,FACE NAIL (3)16d ¢ O.C.(MIN.4)EACH RAFTER TO PLATE,TOENAIL (3)8d 4 WALL(WHERE END OF HEADER ByAll 1"BRACE TO EACH STUD&PLATE,FACE NAIL (2)8d OCCURS),SEE BUILT-UP CORNER STUDS 16d AT 24"O.C. PLAN D By BUILT-UP GIRDER&BEAMS 20d AT 32"O.C.AT TOP,BOTTOM, D. AND STAGGERED.(2)20d AT ENDS BD By AND AT EACH SPLICE. EDGE NAIL CONTINUOUSIL 6A-2N­M PLYWOOD&PARTICLEBOARD: EDGE(WHEN BLOCKING SUBFLOOR,ROOF&WALL SHEATHING(TO FRAMING)` IS REQUIRED) 1/2"AND LESS 8d 19/32"-3/4" 8d OR 10d EDGE NAIL,OTHER TRIM STUD(S) 7/8"-1" 8d EDGE 11/8"-11/4' 8dOR10d WOOD HEADER SCHEDULE COMBINATION SUBFLOOR-UNDERLAYMENT(TO FRAMING)` FIELD NAILING O 3/4"AND LESS 6d7/8 L1..1 11/8"-11/4" Sd OR 10d-1" 8d EDGE BLOCKING WHERE BOUNDARY NAIL LL _ 1/ REQ'D,LAY FLAT(UNO) Lu Ln z 2 SHEATHING SCHEDULE AT FLOOR 'NAILS SPACED AT 6"O.C.AT EDGES,12"O.C.AT INTERMEDIATE SUPPORTS(EXCEPT WHERE SPANS ARE 48"OR Y C MORE,THEN SPACE AT 6"O.C.AT SUPPORTS).FOR NAILING OF DIAPHRAGMS AND SHEAR WALLS,REFER TO DOUBLE 2x IN 6"STUD WALL z O C SHEARWALL SCHEDULE. O MINIMUM NAILING NOTES: In J 1. NAILING SCHEDULE IS PER TABLE 2304.10.1 OF THE I.B.C.2015 OR SHOWN ABOVE,WHICHEVER IS } U) D_ GREATER Q> 2. NAILING REQUIREMENTS SHOWN HERE DO NOT REPLACE HARDWARE SHOWN ON THE PLANS OR 16d NAILSAT I2"O.C. > Y 0 z DETAILS. EA SIDE J U Lu 3. ALLNAILSUSED ARECOMMONNAILS. 16d NAILSATI2'O.C. Q 11� ui Q 4. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS. DOUBLE2x TRIPLE 2x EA SIDE-STAGGERED >: n MINIMUM NAILING SCHEDULE WOOD SHEATHING SHEARWALL SCHEDULE z I__ LL WALL FRAMING WALLSHEATHING 12" 12" cr LU MARK TOP BOTTOM FASTENER FASTENER COMMENTS V Lu U STUDS PLATE PLATE BOTTOM PLATE ANCHORS THICKNESS TYPE SIZE EDGESCREW FIELDSCREW u m LL.M LL CD O SW-1 2x6 AT 16"O.C. (2)2X6 2x6 1/2"0 SIMPSON STRONG BOLT 2 1/2„ SCREW NO 8"O.C. 12"D.C. SHALLAPPLY u a Q O N WEDGE ANCHOR WITH 3"MIN.EMBED TO ALL GYPSUM DEPTH.SPACE AT 6'O.C.AND WITHIN INTERIOR 242 OJ THRU-BOLT AT IB"FROM END OF WALLS BOARD WALLS 24"O.C.-STAGGERED n QUADRUPLE 2x 5 WOOD BUILT-UP BEAM DETAILS WOOD SHEATHING SHEARWALL NOTES: 1. INSTALL SIMPSON STRONG BOLT 2 WEDGE ANCHOR PER MANUFACTURER INSTRUCTIONS 2. WHERE CALLED FOR ON SCHEDULE,USE COMMON NAILS.GALVANIZED NAILS SHALL BE HOT-DIPPED OR TUMBLED. 3. WH ERE STUDS ARE CUT FOR PLACEMENT OF ANCHOR BOLTS OR OTHER ELEMENTS,AN ADJACENT STUD SHALL BE ADDED. 4. SEE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS. B 5. ALL WOOD SHEAR WALLS GREATER THAN I6'TALL SHALL HAVE BLOCKING AT LOFT O.C.OR LESS,AND NAILED AT EDGE NAIL SPACING AT BLOCKING B 4'-O"MINIMUM LAP SPLICE BOTTOM PL 4 WOOD WALL SHEARWALL SCHEDULE OVERSTUD TOP PLATE SPLICE (2)16d AT 4"O.C. DER,NE ((24)16d MIN EA OB NUMBER Foioewzo ORIGINAL—ME— SIDE OF EA SPLICE) �55(aNA( N i 16676 6/08/202 O TYPICAL WALL STUDS 9/� B�y��� CITY APPROVED PLANS Reviewed for Code Compliance A PLANS MUST BE ON JOB SITE A FOR ALL INSPECTIONS SCHEDULES SOP PLATE SPLICEPLATE SPLICE \_J No. Description Dale S-602 1 2 3 4 5 Page 23 of 97 HVAC SPECIFICATIONS MECHANICAL LEGEND PART 1 - GENERAL 1.5 DELIVERY. STORAGE. AND HANDLING 2.5 ACCESS DOORS AND PANELS 3.6 TESTING AND BALANCING EQUIPMENT ® SUPPLY DIFFUSER 1.1 GENERAL INTENT A. DELIVER PRODUCTS TO THE PROJECT PROPERLY IDENTIFIED WITH NAMES,MODEL NUMBERS, A. DUCT MOUNTED ACCESS DOORS:DOUBLE WALL,DUCT MOUNTING,AND RECTANGULAR;FABRICATED OF A. PERFORM TESTING AND BALANCING PROCEDURES PER RECOGNIZED STANDARDS.AIR BALANCE rrrrrr A THE INTENTION OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND TYPES,GRADES,COMPLIANCE LABELS,AND OTHER INFORMATION NEEDED FOR IDENTIFICATION. GALVANIZED SHEET METAL WITH INSULATION FILL AND THICKNESS AS INDICATED FOR DUCT PRESSURE DOES NOT NEED TO BE BY AN INDEPENDENT CERTIFIED CONTRACTOR.THE HVAC CONTRACTOR JJJJJJ FLEXIBLE DUCTWORK RETURN GRILLE EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING, B. ALL MECHANICAL EQUIPMENT AND MATERIAL ITEMS SHALL BE PROTECTED FROM WEATHER AND C . MAY PERFORM THE BALANCE. INSTALLATION AND TESTING,COMPLETE AND READY FOR SAFE OPERATION OF THE SYSTEMS DESCRIBED VANDAIJSM PRIOR TO ACTUAL INSTALLATION.FAN WHEELS,PUMPS AND OTHER ROTATING 1. FRAME:GALVANIZED SHEET STEEL,WITH BEND-OVER TABS AND FOAM GASKETS. B. PREPARE TEST REPORT AND SUBMIT TO THE CRY PER CITY REQUIREMENTS.SUBMIT COPY TO L12"M" LINED RECTANGULAR DUCTWORK HEREIN. 2. PROVIDE NUMBER OF HINGES AND LOCKS AS FOLLOWS: THE ENGINEER. EXHAUST GRILLE B. SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS MADE A MACHINERY SHALL BE PERIODICALLY ROTATED DURING STORAGE.ANY FACTORY PAINTED EQUIPMENT SCRATCHED OR MARRED DURING SHIPMENT OR CONSTRUCTION SHALL BE a. LESS THAN 12 INCHES SQUARE:SECURE WITH TWO SASH LOCKS. C. ADJUST EXHAUST FANS TO SCHEDULE. OF SPECIFIED AIR FLOWS.SET OSA DAMPER TO CFM AS THOROUGH EXAMINATION OF THE SITE,AND ALL EXISTING CONDITIONS AND LIMITATIONS WHICH AFFECT -------- DEMO THIS WORK.LATER CLAIMS SHALL NOT BE MADE FOR LABOR,EQUIPMENT OR MATERIALS REQUIRED RESTORED TO ORIGINAL,"NEW"CONDITION.THIS INCLUDES COMPLETE REPAINTING OF THE b. UP TO 18 INCHES SQUARE:TWO HINGES AND TWO SASH LOCKS. SHOWN IN THE EQUIPMENT SCHEDULE. ROUND DUCIIYORK BREAK BECAUSE OF DIFFICULTIES ENCOUNTERED,WHICH COULD RAVE BEEN FORESEEN DURING SUCH AN EQUIPMENT IF NECESSARY TO PROVIDE EXACT PAINT MATCH. c. UP TO 24 BY 48 INCHES:THREE HINGES AND TWO COMPRESSION LATCHES. 3.7 CONTROLS AND ELECTRICAL COMPONENTS QD DEHUMIDISTAT EXAMINATION, C. CONTRACTOR IS RESPONSIBLE FOR RECEIVING AND OFFLOADING EQUIPMENT OF HIS SCOPE. 2.6 EQUIPMENT CURBS AND SUPPORT C. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT,GENERAL CHARACTER,AND LOCATION OF THE IMMEDIATELY UPON RECEIPT,CONTRACTOR SHALL INSPECT ALL EQUIPMENT AND MATERIAL FOR A. CONTRACTOR SHALL PROVIDE A COMPLETE CONTROL SYSTEM TO OPERATE 1O EQUIPMENT AS WORK TO BE PERFORMED.WHERE MINOR ADJUSTMENTS OF THE WORK ARE NECESSARY FOR PURPOSES A ROOF MOUNTED EQUIPMENT:PROVIDE FACTORY CURB TO MATCH EQUIPMENT PROVIDED.CURB TO DESCRIBED IN THESE DOCUMENTS.SYSTEM SHALL INCLUDE THERMOSTATS,LOW VOLTAGE WIRING, OT THERMOSTAT DUCTWORK BREAK OF FABRICATION OR INSTALLATION OF ITEMS,THE CONTRACTOR SHALL MAKE SUCH ADJUSTMENTS WITH SHIPPING DAMAGE AND REPLACE ANY DEFECTIVE ITEMS AT NO INCREASE TO CONTRACT MATCH ROOF SLOPE,TYPE,AND INSULATION DEPTHS FOR PROPER EQUIPMENT MOUNTING(ACCOUNT TRANSFORMERS,AND ASSOCIATED APPURTENANCES REQUIRED TO MEET THE INTENT OF THESE AMOUNT. FOR APPLICABLE ACCESSORIES SUCH AS ECONOMIZERS AND ERVS DOCUMENTS. TEMPERATURE SENSOR NO ADDED COMPENSATION.WHERE SUCH ADJUSTMENTS THE AFFECT FUNCTIONAL OR AESTHETIC DESIGN OF ) THE WORK,THEY SHALL FIRST BE SUBMITTED TO THEE ARCHITECT FOR REVIEW AND APPROVAL 1.6 SEQUENCING AND SCHEDULING PART 3 - EXECUTION X v Z3 DucnvoRK RISE D. SITE UTILITIES:THE MECHANICAL DOCUMENTS INDICATE CONNECTION LOCATION OF VARIOUS BUILDING A. COORDINATE MECHANICAL EQUIPMENT INSTALLATION WITH OTHER BUILDING COMPONENTS PRIOR 3.1 EXAMINATION SMOKE DETECTOR SERVICES.COORDINATE WORK WITH THE SITE UTIUTIES CONTRACTOR TO ENSURE PROPER INVERT TO ORDERING OR FABRICATION OF ADJOINING WORK. GENERAL HVAC NOTES DUCTWORK DROP ELEVATION,PIPE SLOPE GRADIENT,PIPE SIZE AND SEPARATION WITHIN TRENCH WORK.NOTIFY A VERIFY FINAL LOCATIONS FOR ROUGH-INS WITH FIELD MEASUREMENTS AND WITH THE REQUIREMENTS ARCHITECT OR ENGINEER OF ANY DISCREPANCY BETWEEN DRAWINGS AND FIELD CONDITIONS. B. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES AND SET SLEEVES IN OF THE ACTUAL EQUIPMENT TO BE CONNECTED. (RE:ALL MECHANICAL SHEETS) CO2 SENSOR E. COMPLY WITH ALL LOCAL AND STATE CODES REGARDING SEISMIC SUPPORT AND ISOLATION.NOT ALL POURED-IN-PLACE CONCRETE AND OTHER STRUCTURAL COMPONENTS AS THEY ARE B. LOCATIONS OF EQUIPMENT AND DEVICES,AS SHOWN ON THE DRAWINGS,ARE APPROXIMATE UNLESS SPIN-IN SUPPLY(WITH VOLUME SEISMIC REQUIREMENTS ARE SHOWN ON THESE DRAWINGS.CONTRACTOR SHALL MEET THE CONSTRUCTED.ARRANGE FOR CHASES,SLOTS,AND OPENINGS IN BUILDING STRUCTURE DIMENSIONED;DO NOT SCALE DRAWINGS.EXACT LOCATIONS OF SUCH ITEMS SHALL BE DETERMINED BY G1 THE INTENTION OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND M MOTORIZED DAMPER rww REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION FOR SEISMIC SUPPORT/ISOLATION OF HIS DURING PROGRESS OF CONSTRUCTION TO ALLOW FOR MECHANICAL INSTALLATIONS. THE ARCHITECT'S REPRESENTATIVE AND/OR DETERMINED FROM SPECIAL DETAILS AND DRAWINGS. EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING, - DAMPER) WORK. C. SEQUENCE,COORDINATE,AND INTEGRATE INSTALLATIONS OF MECHANICAL MATERIALS AND VERIFY THE PHYSICAL DIMENSIONS OF EACH ITEM OF MECHANICAL EQUIPMENT TO FIT THE AVAILABLE INSTALLATION AND TESTING,COMPLETE AND READY FOR SAFE OPERATION OF THE SYSTEMS 1.2 GENERAL COORDINATION EQUIPMENT FOR EFFICIENT FLOW OF THE WORK.COORDINATE INSTALLATION OF LARGE SPACE AND PROMPTLY NOTIFY THE ARCHITECT PRIOR TO ROUGHING-IN IF CONFLICTS APPEAR. DESCRIBED HEREIN. Bo- BAROMETRIC DAMPER SPIN-IN RETURN/EXHAUST A THE CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF A SATISFACTORY,COMPLETE,AND FULLY EQUIPMENT REQUIRING POSITIONING PRIOR TO CLOSING IN THE BUILDING. COORDINATION OF DIVISION 15 EQUIPMENT AND SYSTEMS TO THE AVAILABLE WIRING,EQUIPMENT, (WITH VOLUME DAMPER) OPERATIONAL PIECE OF WORK IN ACCORDANCE WITH TRUE INTENT OF THE DRAWINGS AND D. COORDINATE CONNECTION OF MECHANICAL SYSTEMS WITH EXTERIOR UNDERGROUND AND DUCTWORK,PIPING,ETC.SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.THE INSTALLATION G2 THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR T-STATS AND ALL LOW VOLTAGE WIRING. MANUAL VOLUME DAMPER �� 45'SQUARE DUCT TAKE-OFF CONTROL CONDUIT IS BY ELECTRICAL CONTRACTOR. SPECIFICATIONS. OVERHEAD IRILRIES AND SERVICES.COMPLY WITH REQUIREMENTS OF GOVERNING SHALL BE CONCEALED WITHIN BUILDING CONSTRUCTION,OR EXPOSED IN MECHANICAL ROOMS,UNLESS s��� FROM SQUARE DUCT B. CONTRACTOR SWILL CONSULT ALL DRAWINGS FOR THE PROJECT TO DETERMINE THAT THE WORK AND REGULATIONS,FRANCHISED SERVICE COMPANIES,AND CONTROLLING AGENCIES.COORDINATE OTHERWISE NOTED. G3 ALL OUTSIDE AR DUCTS TO BE EXTERNALLY INSULATED. FSD -{ COMBINATION SMOKE/FIRE DAMPER EQUIPMENT WILL FIT AS PUNNED. CONNECTION OF ELECTRICAL SERVICES. 3.2 GENERAL INSTALLATION 45'ROUND DUCT TAKE-OFF M C. THE LOCATION OF PIPING,DUCTS,EQUIPMENT,ETC.,SHALL TS CHECKED TO ENSURE CLEARANCE FROM E. PROVIDE IDENTIFICATION OF ALL EQUIPMENT.COORDINATE INSTALLATION OF IDENTIFYING A PROVIDE ALL VALVES,DAMPERS AND CONTROL DEVICES REQUIRED TO COMPLETE BALANCING OF G4 ALL SUPPLY DUCTS AND RETURN DUCTS TO BE INSULATED AND INTERNALLY TINED AS SHOWN ON sA� FROM SQUARE DUCT w OPENINGS,STRUCTURAL MEMBERS,CABINETS,LIGHTS,OUTLETS AND EQUIPMENT HAVING FIXED }-{ FIRE DAMPER LOCATIONS. THIS SHALL BE ACCOMPLISHED PRIOR TO FABRICATION OF PIPE OR DUCTS. DEVICES AFTER COMPLETING COVERING AND PANTING WHERE DEVICES ARE APPLIED TO SYSTEMS AS DESCRIBED IN THESE DOCUMENTS OR AS NORMALLY ASSOCIATED WITH THE SYSTEMS TO DRAWINGS AND SPECIFICATIONS. 45'ROUND DUCT TAKE-OFF D. IF,AT ANY TIME,AND IN ANY CASE,CHANGES IN LOCATION OF PIPING,DUCTS,EQUIPMENT,ETC., SURFACES.INSTALL IDENTIFYING DEVICES PRIOR TO INSTALLING ACOUSTICAL CEILINGS AND BE INSTALLED WHETHER SPECIFICALLY CALLED FOR ON THE DRAWINGS,DETAILS OR SPECIFICATIONS OR s��w' FROM ROUND DUCT BECOMES NECESSARY DUE TO EXISTING OBSTACLES OR INSTALLATION OF OTHER TRADES SHOWN ON SIMILAR CONCEALMENT. NOT.IT SHALL BE UNDERSTOOD,UNLESS SPECIFICALLY STATED OTHERWISE,THAT ALL SYSTEMS G5 DUCTWORK LAYOUT IS PARTIALLY DIAGRAMMATIC.OFFSETS AND ADJUSTMENTS MAY BE REQUIRED TO ® EQUIPMENT CALLOUT ANY OF THE PROJECT DRAWINGS AND SUCH CONFLICT COULD RAVE BEEN AVOIDED BY PROPER INSTALLED SHALL COMPLY WITH INDUSTRY RECOGNIZED STANDARDS AND FEATURES. COORDINATE WITH UGHTS,DUCTS,PLUMBING,FIRE SPRINKLERS AND STRUCTURE. 1.7 PROJECT CLOSE-OUT TURNING VANE COORDINATION BETWEEN TRADES OR PROPER PRE-PUNNING OF WORK SUCH REQUIRED CHANGES B. COORDINATE MECHANICAL SYSTEMS EQUIPMENT PAID MATERIALS INSTALLATION WITH OTHER BUILDING SHALL BE MADE BY THE CONTRACTOR AT NO EXTRA COST. THESE CHANGES ARE TO BE RECORDED ON A CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE TO REPLACE OR REPAIR ANY DEFECTS IN COMPONENTS.SEQUENCE,COORDINATE,AND INTEGRATE INSTALLATIONS OF MECHANICAL MATERIALS AND G6 COORDINATE T-STAY LOCATIONS WITH OWNER. ® DETAIL CALLOUT f THE RECORD DRAWINGS. WORKMANSHIP OR EQUIPMENT,WHICH DEVELOP WITHIN ONE YEAR FROM ACCEPTANCE BY THE OWNER. EQUIPMENT FOR EFFICIENT FLOW OF THE WORK.GIVE PARTICULAR ATTENTION TO LARGE EQUIPMENT MITERED CORNER E. THIS CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL INCIDENTAL ELECTRICAL INTERCONNECTIONS, CONTRACTOR MUST ASSUME RESPONSIBILITY FOR ALL EXPENSES INCURRED TO REPAIR OR REPLACE REQUIRING POSITIONING PRIOR TO CLOSING IN THE BUILDING.GIVE RIGHT-OF-WAY PRIORITY TO G7 CONTRACTOR SHALL IDENTIFY ALL SERVICEABLE ITEMS(VALVES,DAMPERS,COILS,ETC.)SO THAT THE CONTROL WIRING,ETC.,WHICH ARE NECESSARY FOR SYSTEM COMPLETION AND WHICH ARE NOT HIS WORK AS WELL AS WORK OF OTHER TRADES THAT MAY BE AFFECTED BY THIS REPLACEMENT. SYSTEMS REQUIRED TO BE INSTALLED AT A SPECIFIED SLOPE. CEIUNG SUBCONTRACTOR MAY KNOW WHERE TO INSTALL ACCESS-TYPE PANELS SHOULD A UFT-UP (T� TEMPERATURE GAUGE _ SPECIFICALLY SHOWN OR OTHERWISE INDICATED ON THE ELECTRICAL DRAWINGS OR SPECIFIED IN B. CONTRACTOR SHALL MAINTAIN A REDLINED SET OF CONSTRUCTION DRAWINGS SHOWING DEVIATIONS C. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED,INSTALL SYSTEMS,MATERIALS,PAID TYPE CEILING NOT BE INSTALLED.THIS CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR HIS WORK - DMSION 26. BETWEEN THE DRAWINGS AND INSTALLED CONDITIONS.THESE SHALL BE TURNED OVER TO THE OWNER EQUIPMENT NT PROVIDE THE MAXIMUM HEADROOM POSSIBLE UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.ARCHITECT SHALL APPROVE LOCATIONS OF ACCESS / )T RADIUS ELBOW \ANAL F. ALL ELECTRICAL WORK INCIDENTAL TO OR ACCOMPLISHED UNDER THIS DIVISION SHALL COMPLY WITH AT ACCEPTANCE OF THE WORK. PANELS PRIOR TO INSTALLATION. POINT OF CONNECTION STEp D. INSTALL SYSTEMS,MATERIALS,AND EQUIPMENT LEVEL AND PLUMB,PARALLEL AND PERPENDICULAR TO 'O ALL REQUIREMENTS OF DIVISION 26. C. PROVIDE THREE 3 COMPLETE SETS OF OPERATION AND MAINTENANCE MANUALS.THESE ARE TO G. PLANS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR IS RESPONSIBLE FOR REFERRING TO THE DESIGN () OTHER BUILDING SYSTEMS AND COMPONENTS,WHERE INSTALLED EXPOSED IN FINISHED SPACES. G8 ALL PENETRATIONS MADE THROUGH RATED ASSEMBLIES TO ACCOMMODATE WORK OF THIS SECTION, DOCUMENTS FOR ALL OTHER DISCIPUNES FOR PROJECT CONSTRUCTION AND OTHER DETAILS WHICH INCLUDE ALL EQUIPMENT CUT-SHEETS,MANUFACTURERS RECOMMENDED MAINTENANCE PROCEDURES, INTAKE OR EXHAUST MANUFACTURERS WARRANTEE INFORMATION,AND CONTRACTORS WARRANTEE LETTER AND CONTACT E. INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING,MAINTENANCE,AND REPAIR OR MUST BE SEALED TO MAINTAIN THE RATING OF SUCH ASSEMBLY BY A U.L.RECOGNIZED SEALING 6 2 INFORMATION. REPLACEMEIIT OF EQUIPMENT COMPONENTS.AS MUCH AS PRACTICAL,CONNECT EQUIPMENT FOR EASE METHOD. AFFECT THE MECHANICAL INSTALLATION.AND A CONTRACTOR SHALL CONFER WITH F T OTHER TRADES FOR DIRECTION OF AIRFLOW N O FINISH ADJACENT A ITS WORK AND ARRANGE TO HAVE VISIBLE PORTIONS IT THIS WORK(SUCH AS OF DISCONNECTING,WITH MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS.EXTEND GREASE I• Z ACCESS DOORS,VALVES,SPRINKLER HEADS,ESCUTCHEONS,ETC.)MERGE WITH THE FINISH IN A D. PROVIDE THREE(3)REVIEWED BALANCE REPORTS OF WATER AND AIR SYSTEMS AS APPLICABLE. FITTINGS TO AN ACCESSIBLE LOCATION. G9 CONTRACTOR HAS SOLE RESPONSIBILITY TO COORDINATE ANY SUBSTITUTIONS WITH ALL OTHER MANNER SATISFACTORY TO THE ARCHITECT. E. CONTRACTOR SHALL INSTRUCT THE OWNER ON THE OPERATION AND MAINTENANCE OF ALL SYSTEMS F. DRAWINGS ARE NOT DETAILED TO THE EXTENT THAT ALL DUCTWORK AND PIPING OFFSETS,BENDS,AND DISCIPUNES.EQUIPMENT OF GREATER POWER,DIMENSIONS,CAPACITIES,AND RATINGS MAY BE FY AYVQ H. CONTRACTOR SHALL IDENTIFY ALL SERVICEABLE ITEMS(VALVES,DAMPERS,COILS,ETC.)SO THAT TINE PROVIDED UNDER THIS CONTRACT. SPECIAL FITTINGS ARE SHOWN AND EXACT LOCATION INDICATED;HOWEVER,THEY ARE TO BE PROVIDED FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT HAS BEEN SUBMITTED FOR RENEW,IN WRITING CEILING SUBCONTRACTOR MAY KNOW WHERE TO INSTALL ACCESS-TYPE PANELS SHOULD A UFT-UP PART 2 - PRODUCTS WHETHER SHOWN OR NOT.REFER TO SCHEDULES FOR ACCESSORIES. AND CONNECTING MECHANICAL AND ELECTRICAL SERVICES,CIRCUIT BREAKERS,CONDUIT,MOTORS, 07 19/2022 TYPE CEILING NOT BE INSTALLED.THIS CONTRACTOR SHALL PROVIDE ACCESS PANELS FOR HIS WORK G. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY PROTECTING ANY PENETRATION OF A FIRE BASES,AND EQUIPMENT SPACES ARE ADJUSTED APPROPRIATELY.NO ADDITIONAL COSTS WILL BE ABBREVIATIONS & DESCRIPTIONS UNLESS SPECIFICALLY NOTED ON THE DRAWINGS.ARCHITECT SHALL APPROVE LOCATIONS OF ACCESS 2.1 GENERAL RATED ASSEMBLY. FIRE SEAL,CAULKING,AND APPURTENANCES SHALL BE UL LISTED FOR THE APPROVED FOR THESE INCREASES,IF LARGER EQUIPMENT IS PROPOSED.IF MINIMUM ENERGY PANELS PRIOR TO INSTALLATION. A DUCT DIMENSIONS SHOWN ON PUNS ARE NET FREE AREA ASSEMBLY RATING IT IS APPLIED TO AND SHALL BE INSTALLED PER THE MANUFACTURERS WRITTEN RATINGS OR EFFICIENCIES OF THE EQUIPMENT ARE SPECIFIED,THE EQUIPMENT MUST MEET THE AC AR CONDITIONING HVAC HEATING,VENTILATING,AIR CONDITIONING CONTRACTOR IS SOLELY RESPONSIBLE I. CEILING HEIGHTS:ARCHITECTURAL DRAWINGS SHALL BE CHECKED FOR CEILING HEIGHTS,WALLS,AND B. ROUND ELBOWS MUST HAVE A CENTERLINE RADIUS OF NO LESS THAN 1.5 TIMES THE DIAMETER OF INSTRUCTIONS.ALL SUCH MATERIALS SHALL MEET STATE,LOCAL.,AND AUTHORITIES CODES PAID DESIGN REQUIREMENTS AND COMMISSIONING REQUIREMENTS. A'F ABOVE FINISHED FLOOR FOR SUBSTITUTED EQUIPMENT MEETING THE INTENT OF THE ORIGINAL DESIGNED EQUIPMENT IN ALL K KITCHEN EQUIPMENT SUPPLIER CABINETS THAT ARE INTENDED TO CONCEAL WORK OF THIS SECTION.WHERE CONFLICTS OCCUR,THE THE ELBOW.SQUARE ELBOWS SHALL HAVE TURNING VANES UNLESS SHOWN AS RADIUSED ELBOWS. STANDARDS. AHU AIR HANDLING UNIT KW KILOWATT ASPECTS' BTU BRITISH THERMAL UNITS `` ARCHITECT SHALL BE NOTIFIED PRIOR TO INSTALLATION OF THE WORK.LOCATION OF EXPOSED WORN C. ALL DUCTWORK EXPOSED TO VIEW SHALL BE ROUND SPIRAL H. PENETRATIONS ARE PROHIBITED IN ANY STRUCTURAL MEMBERS(EXCEPT WHERE NOTED IN DRAWINGS) KWH KILOWATT HOUR O SUCH AS LIGHTS,DIFFUSERS,SPEAKERS,SPRINKLER HEADS TAKE PRECEDENCE OVER CONCEALED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT.OBTAIN APPROVAL FOR OTHER FRAMED OPENINGS BTUH BTU'S PER HOUR L ACOUSTICAL DUCT LINER WORK. 2.2DUCTWORK MATERIALS CA COMBUSTION AIR LAT LEAVING AR TEMPERATURE WHICH MAY BE REQUIRED IN ADDITION TO THOSE SHOWN ON DRAWINGS.PAY ALL COSTS FOR J. CONTRACTOR SHALL EXERCISE CARE TO MINIMIZE ANY DISTURBANCE TO ADJACENT AREAS OF THE A COMPLY WITH SMACNA'S'HVAC DUCT CONSTRUCTION STANDARDS--METAL AND FLEXIBLE"FOR ADDITIONAL CUTTING OF HOLES AS THE RESULT OF INCORRECT LOCATION OF SLEEVES OR FURNISHING CC COOLING COIL MAX MAXIMUM BUILDING WHICH ARE TO REMAIN IN OPERATION.ISOLATE WORK AREAS BY TEMPORARY PARTITIONS, ACCEPTABLE MATERIALS,MATERIAL THICKNESS,AND DUCT CONSTRUCTION METHODS,UNLESS INCORRECT INFORMATION AS TO THE REQUIREMENTS OF FRAMED OPENINGS. CFF CAP FOR FUTURE TARPS,ETC.,TO KEEP DUST AND DIRT IN THE CONSTRUCTION AREA OTHERWISE INDICATED.SHEET METAL MATERIALS SHALL BE FREE OF PITTING,SEAM MARKS,ROLLER I. FIRE-RATED ASSEMBLY PENETRATIONS: CFM CUBIC FEET PER MINUTE MCA MINIMUM CIRCUIT AMPS K. PROVIDE ALL NECESSARY FLASHING,SEAJNG,ETC.,TO MAINTAIN THE WATERPROOF INTEGRITY OF THE MARKS,STAINS,DISCOLORATIONS,AND OTHER IMPERFECTIONS.UNLESS STATED OTHERWISE,ALL 1 THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY PROTECTING ANY PENETRATION OF A CHI CHILLED WATER RETURN MOCP MAXIMUM OVERCURRENT PROTECTION BUILDING AS REQUIRED BY THE INSTALLATION OR REMOVAL OF ITEMS AS REQUIRED B .Y THIS SCOPE OF DUCTWORK TO BE 26 GAUGE MINIMUM. CHWS CHILLED WATER SUPPLY MIN MINIMUM WORK. FIRE RATED ASSEMBLY. FIRE SEAL,CAULKING,AND APPURTENANCES SHALL BE UL LISTED FOR L INSTALL ALL WORK OF THIS SCOPE TO BE READILY ACCESSIBLE FOR OPERATION,MAINTENANCE,AND B. GALVANIZED SHEET STEEL LOCK-FORMING QUALTY;COMPLYING WITH ASTM A 653/A 653M AND THE ASSEMBLY RATING IT IS APPUED TO AND SHALL BE INSTALLED PER THE MANUFACTURERS CLG CEILING NC NOISE CRITERIA REPAIR.MINOR DEVIATIONS FROM THE DRAWINGS MAY BE MADE TO ACCOMPLISH THIS,BUT CHANGES HAVING G90(Z275)COATING DESIGNATION;DUCTS SHALL HAVE MILL-PHOSPHATIZED FINISH FOR WRITTEN INSTRUCTIONS.ALL SUCH MATERAS SWILL MEET STATE,LOCAL,AND AUTHORITIES CODES CW COLD WATER NFPA NATIONAL FIRE PROTECTION ASSOCIATION INVOLVING OTHER TRADES MAY NOT BE MADE WITHOUT PRIOR APPROVAL SURFACES EXPOSED TO VIEW. AND STANDARDS. DEG DEGREE NTS NOT TO SCALE M. ALL PENETRATIONS MADE THROUGH RATED ASSEMBLIES TO ACCOMMODATE WORK OF THIS SECTION, C. CARBON-STEEL SHEETS:ASTM A 3661 366M,COLD-ROLLED SHEETS;COMMERCIAL QUALTY;WITH 2. REFER TO ARCHITECTURAL DRAWINGS FOR ALL FIRE RATED ASSEMBLY LOCATIONS AND RATINGS. DIA DIAMETER OSA OUTSIDE AR MUST BE SEALED TO MAINTAIN THE RATING OF SUCH ASSEMBLY BY A U.L.RECOGNIZED SEALING OILED,MATTE FINISH FOR EXPOSED DUCTS. J. SEISMIC RESTRAINT: DB DRY BULB TEMPERATURE PD PRESSURE DROP METHOD. D. STAINLESS STEEL ASTM A 480/A 480M,TYPE 316 OR 304,AND HAVING A NO.2D FINISH FOR 1. THE CONTRACTOR SHALL PROVIDE PROPER MECHANICAL SEISMIC RESTRAINTS FOR ALL INSTALLED EA EXHAUST AIR PH PHASE N. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF THIS WORK.COORDINATE ALL CONCEALED DUCTS AND SUITABLE FINISH FOR EXPOSED DUCTS. ITEMS INCLUDING,BUT NOT LIMITED TO,DUCTS,PIPING,EQUIPMENT AND ACCESSORIES.THE EAT ENTERING AIR TEMPERATURE PRV PRESSURE REDUCING VALVE BLOCKING,SUPPORT,ETC.,NECESSARY FOR THE INSTALLATION OF THIS WORK WITH THE GENERA CONTRACTOR SHALL PROVIDE SEISMIC RESTRAINTS AS LISTED BY THE CODES USED BY THE AHJ EER ENERGY EFFICIENCY RATIO RA RETURN AIR 2A. INSULATION AND LINER OR AS SHOWN ON THE DRAWINGS(WHICHEVER IS MORE STRINGENT). ESP EXTERNAL STATIC PRESSURE CONTRACTOR. RPM REVOLUTIONS PER MINUTE 1.3 CODES. STANDARDS. PERMITS. AND FEES A GENERAL: 3.3 DUCT INSTALLATION EWT ENTERING WATER TEMPERATURE RTU ROOFTOP UNIT A AL APPLCABLL CODE LAWS AND REGULATIONS GOVERNING OR RELATING TO ANY PORTION OF THIS 1. FIRE-HAZARD CLASSIFICATION:MAXIMUM FUME-SPREAD INDEX OF 25 AND SMOKE-DEVELOPED FCO FLOOR CLEANOUT SA SUPPLY AR WORK ARE HEREBY INCORPORATED INTO AND MADE A PART OF THESE SPECIFICATIONS.THEIR INDEX OF 50 WHEN TESTED ACCORDING TO ASTM E 84. A. CONSTRUCT AND INSTAL DUCTS ACCORDING TO SMACNAS°HVAC DUCT CONSTRUCTION SEER SEASONAL ENERGY EFFICIENCY RATIO ID FIRE DAMPER SFD/FSD COMBINATION SMOKE/FIRE DAMPER PROVISIONS SHALL BE CARRIED OUT BY THE CONTRACTOR,WHO SHALL INFORM THE ARCHITECT IN 2. INSULATION SCHEDULE: STANDARDS--METAL AND FLEXIBLE." FlA FULL LOAD MAPS WRITING PRIOR TO SUBMITTING A BID,OF ANY WORK OR MATERIALS WHICH VIOLATE ANY OF THE a. INSIDE THE BUILDING THERMAL INSULATION ENVELOPE-ALL INSTALLED VALUES TO BE R-6 B. INSTALL DUCTS WITH FEWEST POSSIBLE JOINTS.INSTALL FABRICATED FITTINGS FOR CHANGES IN IT SP STATIC PRESSURE ENFORCED LAWS,CODES,OR REGULATIONS.IF THE CONTRACTOR PERFORMS ANY WORK CONTRARY TO MINIMUM. DIRECTIONS,SIZE,AND SHAPE AND FOR CONNECTIONS. FLR FLOOR SYM SYMBOL SUCH LAWS,ORDINANCES,RULES AND REGULATIONS,HE SHALL ASSUME FULL RESPONSIBILITY,AND FPM FEET PER MINUTE 1) INSULATE ALL RECTANGULAR DUCT WITH 1/2°DUCT LINER MINIMUM UNLESS NOTED C. COORDINATE LAYOUT WITH SUSPENDED CEILING,FIRE-AND SMOKE-CONTROL DAMPERS,LIGHTING FT FEET TA TRANSFER AIR SHALL BEAR ALL COSTS ASSOCIATED WITH BRINGING WORK INTO COMPLIANCE. OTHERWISE ON THE MECHANICAL SHEETS. LAYOUTS,AND SIMILAR FINISHED WORK. T&P TEMPERATURE AND PRESSURE B. WHERE DRAWINGS OR SPECIFICATIONS CALL FOR MATERIAL OR CONSTRUCTION OF A BETTER QUALITY OR 2) INSULATE ALL ROUND SUPPLY DUCT AND OUTSIDE AIR DUCT WITH 1-1/2"FOIL FACED D. SEAL ALL JOINTS WITH UNITED DUCT SEALANT.APPLY SEALANT TO MALE END CONNECTORS BEFORE GA GAUGE TYP TYPICAL HIGHER CAPACITY THAN REQUIRED BY THE ABOVE-MENTIONED CODES AND STANDARDS,THE PROVISIONS GCO GRADE CLEANOUT TEMP TEMPERATURE OF THE DRAWINGS OR SPECIFICATIONS SHALL TAKE PRECEDENCE OVER THE REQUIREMENTS OF THE DUCT WRAP EXCEPT EXPOSED SPIRAL TO BE UN-INSULATED. ROUND RETURN DUCT INSERTION,AND AFTERWARD TO COVER ENTIRE JOINT AND SHEET METAL SCREWS. GPM GALLONS PER MINUTE UMC UNIFORM MECHANICAL CODE CODES AND STANDARDS. DOES NOT NEED TO BE INSULATED. E. NON-FIRE-RATED PARTITION PENETRATIONS:WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS AND HC HEATING COIL UPC UNIFORM PLUMBING CODE C. THE RESPECTIVE SUB-CONTRACTOR,AT HIS EXPENSE,SHALL OBTAIN ALL PERMITS AND FEES REQUIRED b. OUTSIDE THE BUILDING THERMAL INSULATION ENVELOPE,BUT INSIDE THE ATTIC SPACE EXTERIOR WALLS AND ARE EXPOSED TO VIEW,CONCEAL SPACES BETWEEN CONSTRUCTION OPENINGS HP HORSEPOWER VTR VENT THROUGH ROOF FOR THIS SCOPE OF WORK ON THIS PROJECT.THE SUB-CONTRACTORS SHALL ALSO SCHEDULE ALL 1) INSULATE ALL SUPPLY AND RETURN DUCTS TO R-6 MINIMUM. REFERENCE NOTE ON AND DUCTS OR DUCT INSULATION WITH SHEET METAL FLANGES OF SAME METAL THICKNESS AS DUCTS. IECC INTERNATIONAL ENERGY V VOLTS REQUIRED INSPECTIONS AND OBTAIN CERTIFICATES FOR HIS WORK,AT HIS EXPENSE. SHEET M2.1 FOR ADDITIONAL INFORMATION. OVERLAP OPENINGS ON 4 SIDES BY AT LEAST 1-1/2 INCHES. CONSERVATION CODE D. THE FOLLOWING SPECIFIC STANDARDS SHALL BE CONSIDERED AS MINIMUM REQUIREMENTS FOR WORK OF 3. ALL DUCTWORK TO BE INSULATED AT A MINIMUM TO MEET 2018 IECC SUPERCEDING THE ABOVE F. FIRE-RATED PARTITION PENETRATIONS:WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS AND WB WET BULB THIS SECTION: SCHEDULE IF CALLED OUT AS LESS THAN CODE. EXTERIOR WALLS,INSTALL APPROPRIATELY RATED FIRE DAMPERS,SLEEVES,AND FlRESTOPPING W/ WITH 1. DUCTWORK:ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED PER THE PUBLISHED STANDARDS B. DUCT INSULATION:MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN.COMPLY WITH SLAB' OF THE AMERICAN SOCIETY OF HEATING,REFRIGERATION,AND AIR CONDITIONING ENGINEERS ASTM C 553,TYPE II AND ASTM C 1290,TYPE III WITH FACTORY-APPLIED FSK JACKET. G. PAINT INTERIORS OF METAL DUCTS,THAT DO NOT HAVE DUCT LINER,FOR 24 INCHES UPSTREAM OF SHEET INDEX (AS HRAE)AND THE SHEET METAL AND AIR CONDITIONING NATIONAL ASSOCIATION(SMACNA),AND C. FIBROUS-GLSS LINER:COMPLY WITH NFPA 9QA OR NFPA 908 AND WITH NAIMA AH124. REGISTERS AND GRILLES.APPLY ONE COAT OF FLAT,BLACK,LATEX FINISH COAT OVER A COMPATIBLE MEET THE REQUIREMENTS OF NFPA 90 AND NFPA 91. 1. MATERIALS:ASTM C 1071;SURFACES EXPOSED TO AIRSTREAM SHALL BE COATED TO PREVENT GALVANIZED-STEEL PRIMER. H. PROVIDE BALANCING DAMPERS AT POINTS ON SUPPLY,RETURN,AND EXHAUST SYSTEMS WHERE MOO HVAC COVER SHEET 2. FILTERS:ALL FILTER MEDIA SHALL BE UL CLASS 2. EROSION OF GLASS FIBERS. BRANCHES LEAD FROM LARGER DUCTS AS REQUIRED FOR AIR BALANCING.INSTALL AT A MINIMUM OF MOA HVAC ENERGY COMPLIANCE FORMS 3. FIRE DAMPERS:ALL FIRE DAMPERS SHALL BE LISTED AND INSTALLED PER UL FOR THE ASSEMBLY a. THICKNESS:1/2°,UNLESS NOTED OTHERWISE. TWO DUCT WIDTHS FROM BRANCH TAKEOFF. M2.1 HVAC PLAN-FIRST FLOOR THEY ARE INSTALLED IN,AND MEET THE REQUIREMENTS OF THE LOCAL BUILDING CODE. b. LINER ADHESIVE:COMPLY WITH NFPA 90A OR NFPA 908 PAID WITH ASTM C 916. I. INSTALL FLEXIBLE CONNECTORS IMMEDIATELY ADJACENT TO EQUIPMENT IN DUCTS ASSOCIATED WITH M2.2 HVAC PLAN-SECOND FLOOR 1.4 SUBMITTALS AND SUBSTITUTIONS c. MECHANICAL FASTENERS:GALVANIZED STEEL SUITABLE FOR ADHESIVE ATTACHMENT, FANS AND MOTORIZED EQUIPMENT SUPPORTED BY VIBRATION ISOLATORS. M3.0 SCHEDULES&DETAILS A SUBMITTAL MATERIALS SHALL BE COMPLETE IN EVERY RESPECT AND SHALL CLEARLY INDICATE MECHANICAL ATTACHMENT,OR WELDING ATTACHMENT TO DUCT WITHOUT DAMAGING LINER WHEN J. CONNECT DIFFUSERS GRILLES TO LOW PRESSURE DUCTS WITH MAXIMUM 8 FEET LENGTHS OF FLEXIBLE O EQUIPMENT FEATURES,DIMENSIONS,WEIGHTS,PERFORMANCE CHALACTERISTICS,AND CAPACITIES. APPLIED AS RECOMMENDED BY MANUFACTURER AND WITHOUT CAUSING LEAKAGE IN DUCT. DUCT CLAMPED OR STRAPPED IN PLACE.CONNECT FLEXIBLE DUCTS TO METAL DUCTS WITH DRAW ppp�ddd{ CAPACITY AND PERFORMANCE CALCULATIONS SHALL BE ADJUSTED TO INDICATE ACTUAL EQUIPMENT D. REFRIGERANT PIPING INSULATION:SUCTION PIPING-FLEXIBLE ELASTOMERIC,1'THICK. BANDS. PERFORMANCE AT THE PROJECT ELEVATION. UTERATURE OR DRAWINGS THAT DESCRIBE MORE THAN 2.4 DUCT ACCESSORIES K. INSTALL BACKDRAFT DAMPERS ON EXHAUST FANS OR EXHAUST DUCTS NEAREST TO OUTSIDE AND ONE MODEL OR SIZE OF EQUIPMENT SHALL BE MARKED WITH ARROWS OR OTHERWISE CLEARLY WHERE INDICATED. INSCRIBED TO IDENTIFY THE ACTUAL EQUIPMENT THAT WILL BE FURNISHED. ALL OPTIONS AND SPECIAL A STANDARD VOLUME DAMPERS:SINGLE OR OPPOSED-BLADE DESIGN,STANDARD LEAKAGE RATING,AND PARTS OF FEATURES SHALL ALSO BE CLEARLY IDENTIFIED. ALL SUBMITTED MATERIALS MUST BE CLEAR, SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS.SHAFTS TO BE FULL LENGTH,GALVANIZED 3.4 HANGING AND SUPPORTING COMPLETE,AND LEGIBLE. ALL SUBMITTALS OF THIS SCOPE MUST BE SUBMITTED AT ONE TIME; STEEL,WITH ZINC-PLATED,DIE-CAST CORE WITH DIAL AND HANDLE MADE OF 3/32-INCH-THICK A SUPPORT HORIZONTAL DUCTS WITHIN 24 INCHES OF EACH ELBOW AND WITHIN 48 INCHES OF EACH J MULTIPLE AND VARIED SUBMITTALS WILL BE REJECTED. ZINC-PLATED STEEL,AND A 3/4-INCH HEXAGON LOCKING NUT.INCLUDE CENTER HOLE TO SUIT BRANCH INTERSECTION. B. SUBMITTALS FOR ALL EQUIPMENT SHALL BE ROUTED THROUGH AND REVIEWED BY THE CONTRACTOR. DAMPER OPERATING-ROD SIZE.INCLUDE ELEVATED PLATFORM FOR INSULATED DUCT MOUNTING. B. SUPPORT VERTICAL DUCTS AT MAXIMUM INTERVALS OF 16 FEET AND AT EACH FLOOR. O LL THE CONTRACTOR SHALL CHECK ALL SUBMITTALS FOR ADEQUATE IDENTIFICATION,CORRECTNESS,AND B. FIRE DAMPERS:CURTAIN TYPE;FIRE DAMPERS SHALL BE LABELED ACCORDING TO UL 555. C. SUPPORT ALL DUCTWORK,PIPING,AND EQUIPMENT AS REQUIRED BY THE LOCAL CODES, LL Z_ COMPLIANCE WITH CONTRACT DRAWINGS AND SPECIFICATIONS AND APPLY A STAMP OF APPROVAL FOR 1. FRAME FABRICATED WITH ROLL-FORMED,0.034-INCH-THICK GALVANIZED STEEL;WITH MITERED MANUFACTURERS RECOMMENDATIONS,AND STANDARD INDUSTRY PRACTICE. (- SUBMITTALS THAT ARE REQUIRED TO BE REVIEWED BY THE ENGINEER,A DIGITAL COPY SHALL BE AND INTERLOCKING CORNERS. D. USE MATERIALS COMPATIBLE WITH ITEMS BEING SUPPORTED TO AVOID ELECTROLYTIC ACTION,AND W LU FORWARDED FOR REVIEW AFTER REVIEW AND APPROVAL BY THE CONTRACTOR. THESE ER. BE 2 BLADES:ROLL-FORMED,INTERLOCKING,0.034-INCH-THICK,GALVANIZED SHEET STEEL IN PLACE CONFORM TO SMACNA,ANSI/ASME B31,NFPA MSS SP-58,69,89. RETURNED AND SHALL BE REVISED AND RESUBMITTED UNTIL ACCEPTED BY THE ENGINEER. PROVIDE OF INTERLOCKING BLADES,USE FULL-LENGTH,0.034-INCH-THICK,GALVANIZED-STEEL BLADE LU _ PRODUCT DATA FOR EACH PIECE OF EQUIPMENT/COMPONENT USTED IN SCHEDULES. CONNECTORS. 3.5 ACCESS DOORS AND PANELS W W Cn C. APPROVED MANUFACTURERS,WHICH MAY SUBMIT EQUAL PRODUCT TO THOSE SPECIFIED,ARE LISTED IN A DUCT ACCESS DOORS:INSTALL DUCT ACCESS DOORS TO ALLOW FOR INSPECTING,ADJUSTING,AND > Q THE EQUIPMENT SCHEDULES.ANY SUBMITTAL FOR CONSIDERATION AS AN EQUAL TO THAT SCHEDULED 3. FUSIBLE UNK:REPLACEABLE,165 DEGREE F RATED. MAINTAINING ACCESSORIES AND TERMINAL UNITS AS FOLLOWS: Q MUST CONTAIN ALL INFORMATION REQUIRED TO EVALUATE THIS CLAIM.MANUFACTURERS NOT LISTED AS C. CEIUNG FIRE DAMPERS:LABELED ACCORDING TO UL 555C;COMPLY WITH CONSTRUCTION DETAILS FOR 1 ADJACENT TO FIRE OR SMOKE DAMPERS,PROVIDING ACCESS TO RESET OR REINSTALL FUSIBLE 0 W EQUAL MUST SUBMIT IN WRITING FOR REVIEW TEN DAYS PRIOR TO BID CLOSING. CONTRACTOR IS TESTED FLOOR-AND ROOF-CEIUNG ASSEMBLIES AS INDICATED IN UCS"FIRE RESISTANCE DIRECTORY.' LINKS. �- o LLI LLI RESPONSIBLE TO ASSURE ANY SUBSTITUTED ITEM MEETS ALL PHYSICAL AND PERFORMANCE 1. FRAME:GALVANIZED SHEET STEEL,ROUND OR RECTANGULAR,SALE TO SUIT CEILING B. ARCHITECTURAL ACCESS DOORS OR PANELS:COORDINATE REQUIREMENTS FOR ACCESS PANELS AND CL W Q > REQUIREMENTS AS AMENDED IN THE DESIGN DOCUMENTS. CONSTRUCTION. CONCEALED BEHIND FINISHED SURFACES. D. APPROVAL OF SUBMITTALS BY THE ENGINEER SHALL NOT WHERE MECHANICAL ITEMS REQUIRING ACCESS ARE CONCR. NOT RELIEVE THE CONTRACTOR FROM 2. BLADES:GALVANIZED SHEET STEEL WITH REFRACTORY INSULATION. (- THIS CONTACTOR SWILL PROVIDE ACCESS PANELS OR DOORS NC SUFFICIENT SIZE TO ALLOW ACCESS RESPONSIBILITY FOR DEVIATIONS FROM DRAWINGS OR SPECIFICATIONS,NOR SHALL IT RELIEVE HIM FROM 3. FUSIBLE UNK:REPLACEABLE,165 DEGREE F RATED. TO HIS WORK THAT REQUIRES ACCESS FOR MAINTENANCE OR INSPECTION. Z �J RESPONSIBILITY FOR ERRORS IN SHOP DRAWINGS OR OTHER SUBMITTAL LITERATURE. D. COMBINATION FIRE/SMOKE DAMPERS:LABELED ACCORDING TO UL 5555.COMBINATION FIRE AND Q W C)E. CONTRACTOR HAS SOLE RESPONSIBILITY TO COORDINATE ANY SUBSTITUTIONS WITH ALL OTHER W m DISCIPUNES.EQUIPMENT OF GREATER POWER,DIMENSIONS,CAPACITIES,AND RATINGS MAY BE SMOKE DAMPERS SHALL BE LABELED ACCORDING TO UL 555 FOR 1-1/2-HOUR RATING. Q FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING 1. FRAME AND BLADES:0.064-INCH THICK,GALVANIZED SHEET STEEL. I- Q LO MECHANICAL AND ELECTRICAL SERVICES,CIRCUIT BREAKERS,CONDUIT,MOTORS,BASES,AND EQUIPMENT 2. MOUNTING SLEEVE:FACTORY-INSTALLED,0.052-INCH THICK,GALVANIZED SHEET STEEL;LENGTH TO Q _ SPACES ARE INCREASED,NO ADDITIONAL COSTS WILL BE ACCEPTED FOR THESE INCREASES,IF LARGER SUIT WALL OR FLOOR APPUCATION. EQUIPMENT IS PROVIDED,IF MINIMUM ENERGY RATINGS OR EFFICIENCIES OF THE EQUIPMENT ARE 3. FUSIBLE LINK:REPLACEABLE,165 DEGREE F RATED. SPECIFIED,THE EQUIPMENT MUST MEET THE DESIGN REQUIREMENTS AND COMMISSIONING REQUIREMENTS. 4. DAMPER MOTORS:MODULATING AND TWO-POSITION ACTION.EQUIP WITH AN INTEGRAL DESIGN OF ELECTRICAL REQUIREMENTS IS BASED ON MECHANICAL EQUIPMENT SPECIFIED. MECHANICAL SCALE: CONTRACTOR SWILL COORDINATE WITH ELECTRICAL CONTRACTOR IF EQUIPMENT PURCHASED IS SPIRAL-SPRING MECHANISM WHERE INDICATED.ENCLOSE ENTIRE SPRING MECHANISM IN A AS NOTED DIFFERENT FROM THAT SPECIFIED STILL MEETS DESIGN INTENT,INCLUDING BUT NOT LIMITED TO REMOVABLE HOUSING DESIGNED FOR SERVICE OR ADJUSTMENTS. OVERCURRENT PROTECTION,LOCAL DISCONNECTION MEANS,WIRE SIZING,AND DESIGN COSTS. 5. ELECTRICAL CONNECTION:115 V,SINGLE PHASE,60 HZ. DATE: E. FLEXIBLE CONNECTORS:FAME-RETARDANT OR NONCOMBUSTIBLE FABRICS,COATINGS,AND ADHESIVES CITY APPROVED PLANS DRAWN B/19 2022 COMPLYING WITH UL 181,CLASS 1.PROVIDE HEAVY METAL EDGE BANDS,SEALED TO PREVENT LEAKAGE. TSM 1. INDOOR SYSTEM,FLEXIBLE CONNECTOR FABRIC:GLASS FABRIC DOUBLE COATED WITH NEOPRENE. Reviewedf or Code Compliance CHECKED BY: 2. OUTDOOR SYSTEM,FLEXIBLE CONNECTOR FABRIC:GLASS FABRIC DOUBLE COATED WITH -� CRA WEATHERPROOF,SYNTHETIC RUBBER RESISTANT TO UV RAYS AND OZONE. F. FLEXIBLE DUCTS:UL 181,CLASS 1,UL 181,CLASS 1,BLACK POLYMER FILM SUPPORTED BY PLANS MUST BE ON JOB SITE HEUCALLY WOUND,SPRING-STEEL WIRE;FIBROUS-GLASS INSULATION;POLYETHYLENE VAPOR BARRIER - F1LM. FOR ALL INSPECTIONS DC ENGINEERING SHEET Careful listening.Oeerinynamic solutions. M O O ....d-in .n et 208.288.2181 Profed:22HMI Page 24 of 97 COMcheck Software Version 4.1.1.0 COMcheck Software Version 4.2.1.0 Mechanical Compliance Certificate 6�( Inspection Checklist Energy Code:2018 IECC Requirements:100.0%were addressed directly in the COMcheck software Project Information Text column is in the"Comments/Assumptions" provided by the user in the COMcheck Requirements screen.For each Energy Code: 2018 IECC requ lrement,the user certifies that a code requirement will be met and how that is documented,or that an exception Pnclect Title: Robert Weed Office is being claimed.Where compliance is itemized in a separate table,a reference to that table is provided. Location: Twin Falls,Idaho Section Climate Zone: 56 # Plan Review Complles7 Comments/Assumptions Pirci Type: New CgnatrUCSlgn &Re,ID C103.2 ',Plans,specifications.and/or ;OComplies ',Requirement will be met. [PR2]r calculations provide all information ODoes Not Construction Site: Owner/Agent: Designer/Contractor: with which compliance can be �ONot Observable', Twin Falls,ID Corey Ahrens 'determined for the mechanical :ONot Applicable DC Engineering :systems and equipment and Twin Falls,ID document where exceptions to the Additional Efficiency Package(s) Twin Falls, ',standard are claimed.Load cahrcalculations peracceptable engineering standards and handbooks. Reduced interior lighting power.Requirements are implicitly enfercetl within irdedor lighting allowance calculations. C406 Plans,specifications,and/or ❑Complies Requirement will be met. Mechanical Systems List [PR9]' calculations provide all information ❑Does Not with which compliance can be ;ONot Observable', ienry Quantity System Type&Description ',determined for the additional energy 1 AH-1/CU-1(Single Zone): c package options. ❑Not Applicable , Split System Heat Pump Additional Comments/Assumptions: Heating Mode:Capacity-34 kBtu/h, Proposed Efficiency-9.50 HSPF,Required Efficiency-8.20 HSPF Cooling Mode:Capacity=35 kBtu/h, Proposed Efficiency=16.00 SEER,Required Efficiency:14.00 SEER Fan System:None 1 AH-2/CU-2(Single Zone): Split System Heat Pump Heating Mode:Capacity=43 kBtu/h, Proposed Efficiency=9.50 HSPF,Required Efficiency=8.20 HSPF Cooling Mode:Capacity=46 kBtu/h, Proposed Efficiency-16.00 SEER,Require!Efficiency:14.00 SEER Fan System:None �t�gs�-p\S7Eoy�� a Qt O y Mechanical Compliance Statement pQ02 Compliance Statement:The proposed mechanical design represented in this document is consistent with the building plans, vV specifications other de tomtI submittedpermit application. proposed m son gnedsehe 2018ECC requirements in COMhVersion 4.1.1.0 d to comply with any applicable mandatry N� P�Olb requirements listed in the Inspection Checklist. Corey Ahrens July 18,22 y pN Name-Title Signature' Date 07/19/2022 O 1 IHigh Impact(Tier 1) Medium Impact(Ter 2) 13 1 Low Impact(Tier 3) Project Title: Robert Weed Office Report date:07/18/22 Project Title: Robert Weed Office Report date:07/18/22 Data filename:\\dce\prolects\2022\22HMW02-Robert Weed Ofhce\Calcs\HVAC\Energy Cocs\Robert Weed Page 1 of 11 Data filename:\\dce\projects\2022\22HMW02-Robert Weed Offce\Calcs\HVAC\Energy Calcs\Robert Weed Page 2 of 11 comcheckcck comcheckcck REQUIRED OSA CALCULATION OUTDOOR ZONE AIR DIST. ` OUTDOOR AIRFLOW BREATHING ZONE 20181MC REQUIRED SYSTEM ZONE NAME ZONE CLASSIFICATION AREA(ftz)[A,]' #OF PEOPLE[P,]z AIRFLOW/PERSON EFFECTIVENESS [i /SgFt[i OSA[B,] [E.]s OSA AH-115t fir lobby/stairs 101 Public Spaces:Corridors 305 sgft 0.0 pe 0.0 cfm 0.06 cfm/sgft 18 cfm 0.8 23 cfm BUILDING office 102 Offices:Office space 90 sgft 0.5 pe 5.0 cfm 0.06 cfm/sqft 8cfm 0.8 10 cfm off!cc 103 Offices:Office space 146 sgft 0.7 pe 5.0 cfm 0.06 cfm/sgft 12 cfm 0.8 16 cfm womens RR 104 Public Spaces:Toilet rooms-public 184 sgft 0.0 pe 0.0 cfm 0.00 cfm/sgft 0cfm 0.8 0cfm mens RR105 Pu bl is Spaces:Toi let rooms-public 145 sgft 0.0 pe 0.0 cfm 0.00 cfm/sqft 0cfm 0.8 Odm break 107 Public Spaces:Corridors 819sgft 0.0 pe 0.0 cfm 0.06 cfm/sqft 49 cfm 0.8 61 cfm System Total= 1,689 sq t 1.2 pe --- --- --- 109 cfm C/) OSA using:165 cfm 2 AH-22nd fir COCS� office 201 Offices:Office space 121 sgft 0.6 pe 5.0 cfm 0.06 cfm/sgft 10 cfm 0.8 13 cfm Cr7 0 break 202 Public Spaces:Corridors 91sgft 0.0 pe 0.0 cfm 0.06 cfm/sgft 5cfm 0.8 7cfm CC�OD w offi ce 203 Offices:Office space 150 sgft 0.8 pe 5.Ocfm 0.06 cfm/sgft 13 cfm 0.8 16 cfm U RR 204 Public Spaces:Toilet rooms-public 57 sgft 0.0 pe 0.0 cfm 0.00 cfm/sgft Ocfm 0.8 Odm J z corridor 205 Public Spaces:Corridors 234 sgft 0.0 pe 0.0 cfm 0.06 cfm/sgft 14 cfm 0.8 18 cfm de Q Q office 207 Offices:Office space 144sgft 0.7 pe 5.0 cfm 0.06 cfm/sqft 12 cfm 0.8 15 cfm 0 LL J LL Z d_ office 206 Offices:Office space 184 sgft 0.9 pe 5.0 cfm 0.06 cfm/sgft 16 cfm 0.8 20Cfm 11-- 2 lounge 208 Public Spaces:Corridors 575sgft O.O pe E m/sgft 35 cfm 0.8 43cfm LU Z O System Total= 1,556 sgft 3.0 0.0 cfm 0.06 pe --- --- --- --- 31 cfm 0W OSA usin:135 cfm > Q Building totals= 3,245 sgft 4.2 pe total office OSA usin:300cfm 0 Q W Notes:"1 Data from Project W LU 2..Data from 20181MC Table 403.3.3.1.1 3.Data from 20181 MC Table 403.3.1.1.1.2 Z LU Z W W LU DD Q BALANCE REPORT EXHAUST CALCULATION a ° _ REQUIRED BEFORE EXHAUST 20181MC REQUIRED SYSTEM ROOM NAME REQUIRED EXHAUST #FIXTURES EXHAUST USING SCALE: FINAL INSPECTION CLASSIFICATION EXHAUST /S NOTED DATE: EF-1 womens RR 104 Toilet 50 cfm/fixture 3 150 cfm 150 cfm 07 19 2022 miens RR 105 Toilet 50 cfm/fixture 4 200 cfm 200 cfm DRAWN BY: EF-2 RR 204 Toilet 70 cfm/fixture 1 70 cfm 70 cfm TSM CHECKED BY: CITY APPROVED PLANS Notes:1.Restroom exhaust fan EF-1 to run continuous during occupied hours,to be switched through the break room lights. -� CRA 2.Restroom exhaustfan EF-2 to run intermittently,switched with the respective restroom lights. Reviewed for Code Compliance PLANS MUST BE ON JOB SITE DC ENGINEERING SHEET Careful listening.Dynamic solutions. M O FOR ALL INSPECTIONS www.dten ineethi.net 208.288.2181 Pcjscl:22HMW02 Page 25 of 97 GENERAL CONSTRUCTION NOTES: 1. THE HVAC WORK IS PARTIALLY DESIGN/BUILD BY THE HVAC CONTRACTOR. THE INTENT OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING,INSTALLATION AND TESTING,COMPLETE AND READY FOR OPERATION OF THE HVAC SYSTEMS,PER CODE. VERIFY ALL DIMENSIONS, SIZES,EIC.ON SITE. COORDINATE ALL WORK WITH THE GENERAL CONTRACTOR. GENERAL NOTES: 3.1 1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF w LOBBY > PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT.PLUMBING VENTS, > I O REGULATOR VENTS,FLUES,AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM SG-3.8 0 m 101 a OF 10 FEET AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. 160 CFM < a w 2. ALL SUPPLY,RETURN AND OUTSIDE AIR DUCT TO BE INSULATED PER DRAWING m m CALL OUT OR 2018 IECC AS A MINIMUM.RECTANGULAR DUCTWORK TO HAVE 1/2"ACOUSTICAL LINER MINIMUM,IF DESIGNATED WITH AN'C.RECTANGULAR F fffff DUCTWORK LOCATED IN THE ATTIC SPACE TO HAVE ADDITIONAL LINER OR°UNER w ^�� AND WRAP'TO MEET R-6 TOTAL VALUE. ALL ROUND SUPPLY AND OUTSIDE AIR RG-2.8"0 DUCTWORK TO BE WRAPPED WITH A MINIMUM OF 1-1/2"DUCT WRAP INSIDE ti i i BUILDING INSULATION ENVELOPE. ALL ROUND DUCTWORK LOCATED IN THE ATTIC rX(�ff0 TO BE WRAPPED TO R-6 MINIMUM, ALL FLEX DUCT LOCATED IN THE ATTIC TO BE R-6 MINIMUM. ---------- - RG- 7----- 3. RECTANGULAR DUCT SIZES ARE SHOWN AS NET FREE INSIDE DIMENSIONS. ----• ADJUST DUCTWORK SIZES TO MEET SIZING AS REQUIRED WITH ACOUSTICAL LINER OFFICE ti THICKNESS AS CALLED FOR IN THE INSULATION SPECIFICATIONS. 102 •" -------- 8 0SA IJIfIfflJlfffA 4. COORDINATE ALL DUCTWORK HEIGHTS CROSSING BELOW THE JOISTS. VERIFY 120 SG 1.7"0 JJ OFFIC' LOCATIONS WITH TH COILING E EL'ONRHfEAIGH HEIGHTS RES. COORDINATE CEILING GRILLE 103 ---------------" 5. ALL SUPPLY GRILLES TO HAVE EITHER AN OBD OR AN ACCESSIBLE MANUAL DAMPER IN THE RUNOUT. �IjJJIJIIJ RG-1.6 0 SG-2.6"0 6. FINAL GRILLE SIZING TO BE BY THE HVAC CONTRACTOR. CFM'S ARE SHOWN O 70 CFM FOR DESIGN PURPOSES. GRILLES STYLES TO MATCH CEILING TYPE. 5\ONAL 7. AIR BALANCE OF OUTSIDE AIR QUANTITY IS REQUIRED.SUPPLY AIR CFM'S ARE bg \ST l ) l ) SHOWN FOR DESIGN PURPOSES ONLY,AND DO NOT REQUIRE AN AIR BALANCE. y� A 3.2 --- 8. COORDINATE FINAL THERMOSTAT LOCATION WITH THE OWNER. 8g02 4 CH 9"05A 1 2A 1013C FIE ICE 9. COORDINATE ALL ELECTRICAL CONNECTIONS WITH THE ELECTRICAL CONTRACTOR. 1 -� SG-2.6'0 RG-O 70 CFM JI JIJJIJJIJIJI�` TG-2.8"0 -L- '� Y pN EG-1.7"0 T KEYED NOTES: ® 07/19/2= 150 CFM WO N'S `' �{ } �_, !! EF RESfR OM ________________ 1. VERIFY MANUFACTURER'S RECOMMENDED INSTALLATION CLEARANCE.COORDINATE 2 �4 _1 •g INSTALLATION WITH ELECTRICAL CONTRACTOR ON UNIT DISCONNECT LOCATION. 1 10 250 CFM1-------------- COORDINATE WITH GENERAL CONTRACTOR TO WHETHER UNITS ARE TO BE SET 0 9 ON CONCRETE OR'CLADLFES'. COORDINATE FINAL LOCATION WITH THE [ DRINKING FOUNTAIN XF L GENERAL CONTRACTOR. ti O t=z' -------- 2. INSTALL INLINE EXHAUST FAN AT AN ACCESSIBLE LOCATION ABOVE THE T-BAR 14"x10"RA HET 9"0SA rrr�rrr --------i T CEILING. ® 10"ORA O JJJ 111 ---------------- 3. INSTALL WALL EXHAUST CAP WITH BACKDRAFT DAMPER,SEAL WFATHERTIGHT. TG_2 O _____ 3.3 O i 4. INSTALL THE COVE HEATER ON THE HIGH SIDEWALL PER MANUFACTURER'S S RAGE Offf Ois - --+ WRITTEN INSTRUCTIONS. COORDINATE FINAL LOCATION WITH THE GENERAL ti BREAKROOM CONTRACTOR PRIOR TO ROUGH IN. ---------------- ti x 106 O O 107 5. L15"05"SUPPLY AND RETURN DUCTS FROM THE SECOND FLOOR CHASE. ALL B' ti Offffff SG 1.9"0 SG 1.9.0 --- DUCT RUNOUTS TO TAP THE DROPS WITH HET TYPE FITTING. trrrr EG-1.8"0 ti ti 210 CFM 210 CFM 6. DUCTWORK ROUTED BELOW THE FLOOR JOISTS AND ABOVE THE CEILING. � 200 CFM. ti COORDINATE HEIGHTS WITH THE GENERAL CONTRACTOR,SPACE IS VERY TIGHT AND LIMITED. 4 CH ffffffffffff 7. OFFSET DUCT UP TO ROUTE BETWEEN THE JOISTS. 2 ti EWS ffffJ Rc-t.s"g JREMST OS SG-2,6"0 90 CFM i I ICIE ,D I L11 CU A A.1 2 g HVAC PLAN-FIRST FLOOR O SCALE:1/4"=1'-0" pC O LL LL J F- LL W r ~ O Q LL W 2 Q Z R. CITY APPROVED PLANS Z W W v F- o� > Reviewed for Code Compliance PLANS MUST BE ON JOB SITE SCALE: FOR ALL INSPECTIONS DATE: AS NOTED 07 19 2022 DRAWN BY: TSM CHECKED BY: -� CPA DC ENGINEERING SHEET Careful listening.Dynamic solutions. ■ .... et dais in-iii.n 208.288.2181 Profed:22HMW02 Page 26 of 97 GENERAL CONSTRUCTION NOTES: 1. THE HVAC WORK IS PARTIALLY DESIGN/BUILD BY THE HVAC CONTRACTOR. THE INTENT OF THE CONTRACT DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS,AND EQUIPMENT,NECESSARY,OR REASONABLY INFERABLE AS BEING NECESSARY,FOR FURNISHING,INSTALLATION AND TESTING,COMPLETE AND READY FOR OPERATION OF THE HVAC SYSTEMS,PER CODE. VERIFY ALL DIMENSIONS, SIZES,ETC.ON SITE. COORDINATE ALL WORK WITH THE GENERAL CONTRACTOR. 3.1 GENERAL NOTES: 1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT.PLUMBING VENTS, 1.7"0 SG 1.7"0 REGULATOR VENTS,FLUES,AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM SG- 14 C"0 145 CFM OF 10 FEET AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. 2. ALL SUPPLY,RETURN AND OUTSIDE AIR DUCT TO BE INSULATED PER DRAWING CALL OUT OR 2018 IECC AS A MINIMUM. RECTANGULAR DUCTWORK TO HAVE 1/2"ACOUSTICAL LINER MINIMUM,IF DESIGNATED WITH AN V. RECTANGULAR DUCTWORK LOCATED IN THE ATTIC SPACE TO HAVE ADDITIONAL LINER OR"LINER T ti AND WRAP"TO MEET R-6 TOTAL VALUE. ALL ROUND SUPPLY AND OUTSIDE AIR ti ti DUCTWORK TO BE WRAPPED WITH A MINIMUM OF 1-1/2"DUCT WRAP INSIDE BUILDINOFFICE RG 1'B i TO BE GWRAPP D¶TTO RN6EMINIMUM. ALL FALL ILEXODUCTORK LOCATED NO THE ATRCIN THETTO 201 ~ BE R-6 MINIMUM. 3. RECTANGULAR DUCT SIZES ARE SHOWN AS NET FREE INSIDE DIMENSIONS. ADJUST DUCTWORK SIZES TO MEET SIZING AS REQUIRED WITH ACOUSTICAL LINER ti THICKNESS AS CALLED FOR IN THE INSULATION SPECIFICATIONS. ti nr SG-1.7"0 4. COORDINATE ALL DUCTWORK HEIGHTS CROSSING BELOW THE JOISTS. VERIFY 110 CFM FINAL CEILING INSTALLATION HEIGHTS AND TYPES. COORDINATE CEILING GRILLE IlGf-W.6" RG-1 8"0LaiLOCATIONS WITH THE ELECTRICAL CONTRACTOR. 90 CFM 5. AIL SUPPLY GRILLES TO HAVE EITHER AN OBD OR AN ACCESSIBLE MANUAL DAMPER IN THE RUNOUT.OFFICE $Sr�I"0 6. FINAL GRILLE SIZING TO BE BY THE HVAC CONTRACTOR. CFM'S ARE SHOWN BITE ROOM 8 203 FOR DESIGN PURPOSES. GRILLES STYLES TO MATCH CEILING TYPE. \\ONAL 02jJJj� , 7. AIR BALANCE of OUTSIDE AIR QUANTITY IS REQUIRED.SUPPLY AIR CFM'S ARE aOF Q„ 3 2 SHOWN FOR DESIGN PURPOSES ONLY,AND DO NOT REQUIRE AN AIR BALANCE. O A O I\ tORRD „1 T AH-1 8. COORDINATE FINAL THERMOSTAT LOCATION WITH THE OWNER. 8602�0 RG_l.9"0 RG-1.12"0 (DE- 6"OEA R If11f 9. COORDINATE ALL ELECTRICAL CONNECTIONS WITH THE ELECTRICAL CONTRACTOR. FY pNQ ff 07/19/2022 2 1, SG-1.8„0 KEYED NOTES: RESTROOM ti 200 CFM 12"OSA 14"0SA 1. INSTALL AIR HANDLERS PER MANUFACTURER'S REQUIREMENTS,MAINTAINING SG 3.5"0 204 O 14"OSA REQUIRED CLEARANCE. ROUTE UNESET TO OUTDOOR UNIT CONCEALED FROM 60 CFM VIEW OUTSIDE THE MECHANICAL PLATFORM,ROUTE CONCEALED IN THE WALL. ROUTE COIL CONDENSATE BY GRAVITY CONCEALED FROM VIEW ABOVE THE JJJJJJJ s��am� `g' O ti FILITERG AND IN THE WALL TO THE MOP RACK ACCESSIBLE FROM MECHANICAL ON PLATTRFMFlRST FLOOR. INSTALL RG-1.8"0�_ @ ffff 2. SUPPORT AIR HANDLERS FROM THE MECHANICAL PLATFORMS. INSTALL J LOUNGE VIBRATION PADS BETWEEN THE SUPPORTS AND THE AIR HANDLERS. INSTALL 3.3 208 FULL THEAI FLEXIBLE CONNECTORS ON BOTH THE RETURN AND SUPPLY SIDE OF R HANDLE fffl Uffrffrfff O 3 MECHANICAL PLATFORM 3. FULL SIZED LINED DUCTWORK. ABOVE OFFICE 208 4. INSTALL UNED RETURN PLENUM. TAP THE PLENUM ON THE TOP WITH A ti qTl RADIUSED ELBOW TURNING TO HORIZONTAL ROUTE ABOVE THE AIR HANDLER. 1� 1 2 ONCE THE RETURN AIR IS PAST THE AIR HANDLER,OFFSET TO ALIGN WITH THE AH 1 SG-1.8"0 1 2 2 LOCATED ON fI1fI1I11I1 170 CFM RETURN AIR DROP INTO THE CHASE. LOCATED ON O MECHANICAL .� 5. FOR BOTH SUPPLY AND RETURN AIR DUCTS,INSTALL RADIUSD ELBOWS,AND OFFICE MECHANICAL PLATFORM ,II J�C I ffffffffffffffffff J ROUTE L15"05"DOWN THE CHASE. SEE SHEET M2.1 FOR CONTINUATION. PLATFORM J��I 206 SG-L B 0 S 0 6. INSTALL WALL EXHAUST CAP WITH BACKDRAFT DAMPER,SEAL WEATHERTIGHT. 190-CFM 170 CFM % 3 7. INSTALL SCREENED OUTSIDE AIR INTAKE CAP,SEAL WEATHER TIGHT. 8"06 19SG S CFM OFFICE C Oo- 00 8. DUCTWORK ROUTED ABOVE THE T-BAR CEILING. 207 14"ORA 3 O o 8"OSA ----------- 7 HVAC PLAN-SECOND FLOOR SCALE:1/4"= 1'-0" O J O O LL LL LL Z z Z LU U O Q r� CL wo Q z 30 �w U OSA BALANCE W m " Q _ OSA BALANCE SYSTEM CFM SCALE:AS NOTED AH-1 165 din DATE: 07 19 2022 CITY APPROVED PLANS AH-2 135 din DRAWN BY: TSM Reviewed for Code Compliance CHECKED BY: CRA PLANS MUST BE ON 10B SITE FOR ALL INSPECTIONS DC ENGINEERING SHEET Careful listening.Dynamic solutions. M2.2 .... et dais in-iii.n 208.288.2181 Profect:22HMW02 Page 27 of 97 AIR HANDLER & HEAT PUMP SPLIT SYSTEM SCHEDULE COOLING HEATING SUPPLYAIR EXT STATIC OUTSIDE ELECTRICAL-INDOORUNITW/ UNIT EQUIPMENTNO. AREA SERVED PRESSURE POSITION AHRI ELECTRICAL-OUTDOOR ELECTRICAL-BACKUP HEAT NOTES (CFM) AIR(CFM) NOMINAL MINIMUM HP CAPACITY- ELEC HEAT (IN.W.C.) SIZE SEER(ARI) CAPACITY pSTAGES MCA MOCP ARI HSPF MBH@AHRI BACKUP MCA MOCP MBH VOLT/PH/HZ AMPS AMPS VOLT/PH/HZ ELECTRIC HEAT VOLT/PH/HZ AMPS AMPS MANUFACTURER OUTDOOR MODEL AIR HANDLER MODEL AH-1/CU-1 1ST FLOOR OFFICES 1200CFM .4" 165 CFM HORIZONTAL 3TON 16.0 35.4MBH 1 208-230/1/60 20.9 35 9.5 34.0 MBH 230/1/60 10 KW 230/1/60 58.5 60 PAYNE 4HP16L36P FB4C_036 1THRU9 AH-2/CU-2 2ND FLOOR OFFICES 16000FM .4" 135 CFM HORIZONTAL I 4TON 1 16.0 46.0 MBH 1 208-230/1/60 25.8 40 9.5 43.0 MBH 230/1/60 15 KW 230/1/60 83.4 90 PAYNE 4HP16L48P FB4C_O48 1THRU9 ALTERNATE MAN UFACTURERS:--BRYANT,LEN NOX,TRAN E,CARRI ER,YORK NOTES: **HVAC CONTRACTOR TO VERIFY VOLTAGE ON SITE,VERIFY ALL MICAS&MOCP'S SHOWN,AND VERIFY BACK-UP HEAT CIRCUITRY&BREAKERS. 1.COOLING CAPACITY RATED@ AHRI COOLING CONDITIONS. 2.HEATING CAPACITY BASED ON AHRI CONDITIONS. 3.VERIFY CORRECTAIR HANDLER/COIL ORIENTATION PRIOR TO ORDERING.FURNISH WITH INDOOR TXV KIT. 4.PROVIDE WITH 1"FILTER RACK WITH 1"MERV 8FILTERS. 5.FURNISH WITH A CONDENSATE OVERFLOW SWITCH FOR THE INDOOR COIL. ( PROVI DE 7-DAY PROGRAMMABLE STAT,HONEYWELL TH8320 OR EQUAL. 7.PROVIDE WITH COIL CONDENSATE TRAPPER MANUFACTURER'S REQUIREMENTS. 8.OUTDOOR UNITTO BE SUPPORTED ON MINIMUM 4"TALL PEDESTALS. 9.VERIFY ALL MAUFACTURER'S REQUIRED CLEARANCES PRIOR TO INSTALLATION. AIR HANDLER/CONDENSING UNIT OPERATION&SETUP: ALL AIR HANDLERS&CONDENSING UNITS: A.STARTUP AND CHECKOUT UNITS PER MANUFACTURERS WRITTEN INSTRUCTIONS.PROVIDE A COPY OF THE SIGNED START-UP SHEETTO THE OWNER. B.P ROVI DE INITIAL THERMOSTAT PROGRAMMING.COORDINATE THE OCCUPIED/UNOCCUPIED SCHEDULE AND TEMPERATURE SET POINTS WITH THE OWNER.FAN TORUN CONTINUOUS DURING OCCUPIED HOURS. �gg\ONAL � C.INSTALL AND WIRE INA CONDENSATE OVERFLOW SWITCH ON THE INDOOR COILTO SHUTDOWN UNIT ON ACTIVATION. ?� D.SET OSA MANUAL BALANCING DAMPER MINIMUM POSITION TO OUTSIDE AIR CFM AS SHOWN IN THIS SCHEDULE.REFER TO HVAC SHEETS FOR DAMPER LOCATIONS AND SIZING. �' 86U2 s N� �O EXHAUST FAN SCHEDULE Q7/19/2= EQUIPMENT E.S.P. MOTOR SERVES TYPE CFM CONTROL MANUFACTURER MODEL NOTES 111uuu NO. (IN.WC) WATTS/AMPS HP VOLT/PH/HZ EF-1 MENS&WOMENS RR'S INLINE 350CFM 0.25" 119W -- 120/1/60 SWITCH WITH FANTECH FG-8 1&2 O BREAKROOM LIGHTS EF-2 RR204 CEILING 70 0.25" 11.0W -- 120/1/60 SWITCH WITH ROOM PANASONIC FV-0511VQ1 3 LIGHTS ALTERNATE MANUFACTURERS:PANASONIC,GREENHECK,COOK,PENNBARRY NOTES: 1.FURNISH WITH WALL MOUNT BRACKET AND SPEED CONTROL.PROVIDE THE SPEED CONTRALTO THE ELECTRICAL CONTRACTOR TO BE MOUNTED AND WIRED ADIACENTTO THE FAN BY THE ELECTRICAL CONTRACTOR, COORDINATE WITH THE ELECTRICAL CONTRACTOR. 2.FAN EF-1 TO BE CONTROLLED THROUGH THE BREAK ROOM LIGHTS,TORUN CONTINUOUS DURING OCCUPIED HOURS. FAN TO BE WIRED TO THE BREAK ROOM LIGHTS BY THE ELECTRICAL CONTRACTOR,COORDINATE WITH THE ELECTRICAL CONTRACTOR. 3.FAN EF-2 TO OPERATE WHENEVER THE RESPECTIVE RESTROOM LIGHTS ARE ON.FAN TO BE WIRED TO THE LIGHTS BY THE ELECTRICAL CONTRACTOR,COORDINATE WITH THE ELECTRICAL CONTRACTOR. ELECTRIC COVE HEATER SCHEDULE EQUIPMENT ELECTRICAL NOMINAL WEIGHT NO AREA SERVED LENGTH (LEIS) MANUFACTURER MODEL NOTES VOLT/PH/HZ WATTS AMPS FAN GUARD OUTDOOR UNIT(STANDARD CH-1 WOMENS RR 104 120/1/60 450 3.1 34" 4 QMARK RCC4512C 1,2 OR DUCTLESS TYPES) CH-2 MENS RR 105 120/1/60 450 3.7 34" 4 QMARK RCC4512C 1,2 GRILLE CAN SAMENR S (2)PANDUITS,ONE ON INNER AND ALTERNATE MANUFACTURERS:BERKO,BRASCH,INDEECO,MARKEL GRILLE SQUAK ONE ON OUTER LINER,SECURE BANDS NOTES: WITH SHEET METAL SCREWS,TYP. SUPPLY HAND DAMPER TYP.,UNLESS 1.FURNISH WITH END CAPS AND MOUNTING BRACKET. A TOP CONNECTIOE SHOWN AT AN ALTERNATE LOCATION OR 2.FURNISH WITH INTEGRAL THERMOSTAT WITH POSITIVE OFF. GRILLE MAY BE USEDE GRILLE IS SPECIFIED WITH AN OBD p ALLOWS. GRILLE CANA �y MINIMUM OF 6"TALLP SUPPORT FLEX DUCT SUPPLY OR RETURN CMD CON PER SMACNA DUCT PER DRAWING REFRIGERANT SUCTION PAINT INSIDE CONCRETE P UNE WITH FLEXIBLE CAN'FLK' J BY GENERAL ELASTOMERIC INSULATION CONTRACTOR, SIZED PER CODE. FI-P(ER PRIG SIZE FLEX DUCT.MAX. LL J OR CLADUTE BY HVAC LENGTH 8'-0" UL CONTRACTOR Z REFRIGERANT COLLAR TO BE MINIMUM Z LIQUID LINE T-BAR T-BAR SQUARE NECK OF 3"ABOVE BOTTOM W W POWER WIRING AND CONDUIT BY CUEING CEILING DIFFUSER OF GRILLE CAN 2 ELECTRICAL CONTRACTOR W W C) CONTROL CONDUIT BY ELECTRICAL CONTRACTOR. N91E$. O Q o2S REFER TO ELECTRICAL DRAWINGS.1. ON STANDARD CONDENSING UNITS, 1. WHERE GRILLEIS SPECIFIED AS SQUARE NECK BY THE SCHEDULE,FACTORY ROUND cr W Cn CONTROL WIRING BY HVAC CONTRACTOR. NECK GRILLE IS NOT ACCEPTABLE. C- W C3 W 2. ON DUCTLESS SPLIT CONDENSING UNITS, 2. THE GRILLE CAN AND FLEX DUCT CONNECTION CRITERIA TO REMAIN THE SAME FOR M W a J CONTROL WIRING BY ELECTRICAL INSTALLATION OF GYP.BOARD GRILLES AND/OR RETURN AND EXHAUST GRILLES. F 3 ZE D CONTRACTOR. 3. IF RUNOUT TO THE GRILLE IS LARGER THAN THE GRILLE CAN,INSTALL A REDUCER AT THE Z 0 CONNECTION TO THE GRILLE CAN. J Q w W W MMA1 AIN MANUFACTURERS RECOMMENDED CLEARANCE REQUIREMENTS W m - a:2 CONDENSING UNIT DETAIL 1 TYPICAL DIFFUSER CONNECTION DETAIL a 2U) SCALE:NTS SCALE:NTS SCALE: AS NOTED DATE., 07 19 2022 DRAWN BY: CITY APPROVED PLANS TSM CHECKED BY: Reviewed for Code Compliance -� CPA PLANS MUST BE ON JOB SITE DC ENGINEERING SHEET FOR ALL INSPECTIONS Carelul listening.Dynamic solutions . M��O -d-ineerin.net 208.288.2181 Profect:22HMW0� Page 28 of 97 22083 Robert Weed Plywood Interior Area Design `�. June 8, 2022 Colby Ricks Laughlin Ricks Architecture, LLC 134 3rd Ave E Twin Falls, ID 83301 Re: Robert Weed Plywood Interior Area Design Dear Mr.Colby Ricks: Noesis Engineering Services (NES) has conducted the design for the Robert Weed Plywood Interior Area Design located at 3351 Eldridge Ave in Twin Falls, ID. If you have any questions, please contact me at (208) 932-2720. Respectfully, Digitally signed by David K.Boyter DN:C=US, E=dboyter@noesis.us,0="Noesis BONA( David K. Boyter Engineering Services,PC", SS N FNC� OU=Engineering,CN=David K. / Boyter mac. S Date:2022.06.0818:39:50-06'00' 10 1 6 676 This document was electronically signed. The digital certificate is identified on the 1"page of the original file. The original 06/08/2022 document is located at Noesis Engineering Services, PC home �q��gTF OF �OQy`�� office server under the job number folder/7.0 Original K g0 Documents. David Boyter, P.E. Reviewed By: Jake Lucido NOESIS ENGINEERING SERVICES, P.C. 1712 Cabellaro Dr. Idaho Falls ID 83406 Attached: Design Report and Structural Drawings CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Noesis Engineering Services Ammon, ID Page 29 of 97 1011 NOESIS ENGINEERING SERVICES, PC Robert Weed Plywood Interior Area Design —Twin Falls, ID Prepared For: Laughlin Ricks Architecture, LLC This document was electronically signed. The digital certificate 1 6 6 76 is identified on the 151 page of the original file. The original 06/08/2022 document is located at Noesis Engineering Services, PC home office server under the job number folder/7.0 Original OF �y�`� Documents. K. 8 Prepared By: David Boyter, P.E. CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Noesis Engineering Services Ammon, ID Page 30 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/`�� 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido SCOPE: The scope of this project is to analyze the gravity loads(dead,live)and the lateral loads(seismic)to design the typical bearing wall framing members, shear wall sheathing and nailing requirements. DESIGN CRITERIA: IBC 2018 American Society of Civil Engineers,Standard 7 2016(ASCE-7-16) American Wood Council,Special Design Provisions for Wind&Seismic 2015(SDPWS) National Design Specification for Wood Construction 2018(NDS) American Concrete Institute Building Code Requirements for Structural Concrete ACI 318-14(ACI) SITE SPECIFIC ASSUMPTIONS VARIABLES FROM LOCAL BUILDING OFFICIALS: R 1 3351 Eldridge Ave,0 Twin Falls.ID 83301 Krnbiry C- This is an existing building,we will be being on the existing 6"slab on grade,the existing slab will be check to see if it passes the code requirement to act as bearing,where it doesn't a new footing will be required. Existing Building information from Original Plans: G. =1,.COR SLAB IN AREA SMALL BE 6' CONCRT' SLAB ON CRADC Wni WWF 6x5A!.6xW1.6. SM S-�;ZET SG-1 'DR S::BGRAH. REINFORCED CONCRETE ;toss 011sW.SE W0 OR SPEC M- , U XWUY MiLFREMI: STMENMH A' 13 WS FUR ALL STRI.MR L CONCRETE SK111 BE 25DO Rrs AND NO SMMAL WSPfC)i DtkL BE RUVREII. POMEVDt, CQM:F? [ FOR SLAM ON GRADE S'eWl 6E PR0FwVrm10NE1) F�M TK MLENT OF CON',.tm MTC Ltf Vile CO Pc'.VE —RD47; of 4000 ?v mm) PgwoE M'CA1lA ixy Alp SEJNICFJt u Y IK.'JP(1<rv, IL IM LION: ALLO4lQU BEAM PAMURE DEAD PLUS WE (Mn 200D PSF SoilBearing = 2000 psf Soil Bearing Capacity of the original slab on grade, as installed CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 1/21 Page 31 of 97 Noesis Engineering Services, Project Number. 22083 DESIGN ENGINEER: �A11 P.C. Proiect Name: Robert Weed Plywood David Boyter, P.E. / � 1712 C2 2720 office Interior Floor Space REVIEWED BY: 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido I =1.0 Seismic importance factor(ASCE 7-16 Table 1.5-2),based on Risk Category II(ASCE 7-16 Table 1.5-1,C1.5) Risk=2 Risk Category for ASCE 7-16 Table 1.5-1,C1.5 SiteClass—6 Site Seismic Classification 1=A;2=B;3=B Est;4=C;5=D stiff;6=D Default;7=E,8=F A - Hard Rock B - Rock B - Estimated (see Section 11*31) C -Very Dense Soil and Soft Rock D - Stiff S;:I E - Soft GAY Soil F -Site Response Analysis LPPLIED LOADINgM DL=15 psf Floor dead load DLceiling—15 psf Ceiling dead load over Office 206 for Equipment Area DLW=8 psf Interior Partition Wall dead load(ASCE 7-10 Table C3-1) LL=80 psf Floor live load LLattics=40 psf Live load above ceiling assumption[over Office 206 for Equipment Area TABLE IWA IBNMWM UNIFORMLY DISTRIBUTED LPlE LOADS.L,,AND MNMIIAI CONCENTRATED LIVE LOADS' oOCYMNCY opt vu UNIM" CoNcammTra IDk1 O�t+dU 12 Oft* 11-1 - above*9 We so RA10 Fie ara owpm route"bt � Y I rRom 34 kv6sm anYris .00 9.000 a�bn �0 am II � i CITY APPROVED PLANS r Reviewed for Code Compliance i u PLANS MUST BE ON JOB SITE j= FOR ALL INSPECTIONS 2/21 Page 32 of 97 Noesis Engineering Services, Project Number. 22083 DESIGN ENGINEER: �A11 P.C. Proiect Name: Robert Weed Plywood David Boyter, P.E. `/ � 1712 C2 2720 office Interior Floor Space REVIEWED BY: �• 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido The second floor space has some'open floor"type space that might be defined as corridors,therefore,80 psf will be assumed for the LL. SEISMIC INPUTS: - Seismic Design Requirements for Structural Components ASCE 7-16 and corresponding Seismic(SEA)Design Map attached to this report Seismic Code=ASCE 7-16 Risk=2 Risk Category for ASCE 7-16 Table 1.5-1,C1.5 SiteClass=6 Site Seismic Classification 1=A;2=B;3=B Est;4=C;5=D stiff,6=D Default;7= E,8=F Ie=1 Seismic importance factor(ASCE 7-16 Table 1.5-2),based on Risk Category II(ASCE 7-16 Table 1.5-1,C1.5) h =18 ft Structural Height.The vertical distance from the base of main floor to the highest level mean of the seismic force-resisting system of the structure.For pitched or sloped roofs,the structural height is from the base to the mean roof height Inputs from ASCE 7: Ct=0.02 ASCE Table 12.8-2 Approximate Period Parameter for"All other structural systems" xl=0.75 R=6.5 ASCE 7 Table 12.2-1 Response Modification Coefficient for"Bearing Wall Systems", "light-frame(wood)walls sheathed with wood structural panels rated for shear resistance." 92=3 ASCE 7 Table 12.2-1 Over-strength Factor Cd=4 ASCE 7 Table 12.2-1 Deflection Amplification Factor p=1 ASCE 7 12.3.4 Redundancy Factor Inputs from Seismic Design Map report(see attached): SS=0.194 SEA Design Maps S I=0.082 SEA Design Maps SDS=0.207 SEA Design Maps SDC=B Seismic Design Category Maps Short Period Response Acceleration Fa=1.6 SEA Design Maps Fv=2.4 SEA Design Maps TL=6 SEA Design Maps Calm SKIS=Fa*SS=0.310 ASCE 7:16 Equation 11.4-1 Spectral Response Acceleration Parameter for Short Periods SMI=Fv*Sl=0.197 ASCE 7:16 Equation 11.4-2 Spectral Response Acceleration Parameter for 1 Sec 2 SDl *SMl—0.13 ASCE 7:16 Equation 11.4-4 Spectral Response Acceleration Parameter for 1 Sec 3 * hmean)<xl) T=Ct 1 s=0.175 s Approximate Fundamental Period 1 ft SDS CSTYP= R =0.032 Seismic Response Coefficient Equation 12.8-2 ASCE 7 Chapter 12 I CITY APPROVED PLANS e Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 3/21 Page 33 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: 1/ P.C. Project Name: Robert Weed Plywood David Boyter,P.E. ` /� 1712 C bellar office Interior Floor Space REVIEWED BY: �. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Need not exceed: SDI CSMaxl T R =0.115 eq 12.8-3 is * I Need not exceed: SDI CSMax2 T =0.115 eq 12.8-4 Is- * IRe Shall not be less than: CSMinl—0.044*SDS*Ie=0.0091 eq 12.8-5 Shall not be less than,if S1 >0.6: S1 =0.082 0.5 *S1 CSMinl =0.0063 eq 12.8-5 R I e Cs2=CSTyp-0.032 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 4/21 Page 34 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. 208-932-2720 office` Interior Floor Space REVIEWED BY:� 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido FOUNDATION - FOOTING SIZING: MM LUNCH—;L l U01INLSIAW-LE REIYFORC NGCROSS-WISE I REINFORCING LENGTHIMISE 'ZE4%C•N J!LD U:AGF: A MARK WMII i.'.NGTII nrPTH •w No. 31Y� LEPIGIH SFS.L'Eidi?I lea. S1I! L3:NC2'•t1 57ALI!rG � ��O'L' R„ 1C., 7 .14 1 7 =Q r 04 r 44 F-T Ll 2 04 11,11 CCt 1,05:R COW NIN SHALL APPLY IURCt FS7.0 7'1)" 7•fl" M, 1 314 1'6' 3 rld 1'-S' rQ 4,RRR I R 11J Cl hYf k l f NI M;OTi ICR74:Sr _S7.75 V.3.4 1-a'3 134 =LZ I rr4 ?'-4' rE. :,R7�, NOTED 6S2.S c"'•5" c•ti" la" 3 IF1 7'..r so 3 u:? EQ 7.6,00 LB 2.0., 1E., 3 44 3' SQ :; a4 a " EQ �A7S'_B ---------I..............................- ----------------...........•••••••... rss-p ;q• ;0• LC-' < wi 2•W _U 4 04 :`_V L,Q 1D,:�Cx710 - ----------------------------------------------------------------- i Hti:urgHrieli . --................'.'--3........._... �.-......__.....1..........�?.........?..3 ...........`Q--...1................_!Ea...... �--��-...... .h!^.. ._T7.G7�IR.... CROSSUOSE y i LC)JCT11iSl:C F5t-.S ?'p•• 1.1.. EC" S 44 3'7 -Ci 1 n,t 3'p' _Q.� .�� 13,7pp tR _ 5 44 3.3' i:U S -U 3•?' EO 1G,n7S ifl .. .: . ...... _..-.-...._.. ............ ... -................-. f' Fa410 11.0„. ,1.0„ 10". 5 :..#4 a G' tiO.... ..5 #n....� y EQ 1 401.6 •-.. ^a.-:- .=`?•._ :7-' ._ .25 .f,•�, ,1.•3., 1C .. . $ #A 3.--1 co I .5.. ..Xt 3`5' EQ 21,�r5i8_- ii .. �ePTH ---......---.... ........................- -......-- -----..-.._... ...... ................ FSd.S Y•S" 1'•6" 1T' S n5 a-0 5 05 ;'9' EQ i!.: L8 F57.75 d'7'. ....1._3.,.... .....1_... S....._....45.. ...�j.... _Q .5.... .-'05... '; E .. .. ''^7s 18.... V.. FSS.D +'a 5'-0" 12" 5 kS.. ...1 B:.. '�...s..-5 -#5 r tQ 3D h3D L8 _ _ r ............... ....... ._ ......... ....... .. .. ....�... .......................... . ..... ..._ ...- -................... S-3" 5'•a"' 12.' 5 •S 9.-3' EQ 1 5 .... #� _ EQ 33.075 Lb �q ... ...... ..... ......................r ... .. .. .. . FSS-s S'-v' S'•61 12" 5 11S 5'-7 EL1 S EC 3t,,04L$ F55.75 s'-9" 5'-9" 111" d a5 -3' EO I G os 5'•B' EQ 39,617S LB FSG.0 V-0" 6,1011 11".. a k5 'a•'-b' Eq... G #s 7.0' •EQ, 43,Iro LB I I 1A'ALL,'6R{OLUL•?NI5MALL .... FC1.3 _'1" CUNT 3" 1 ;y4 i.S, 22"O.C. I 7 AA CDLT EQ :bCe.ID!FT 0 KUL sN CLN:ILK FC1.5 11•O" COW 1.v �12"O.C. � 7 44 MINT EQ 200LBJfT EJIVLCwS E?TNERWISENO-ED FC1.75 1`-9" CANT S" 1 :S 1*-3' 12'O.C', 1 2 #4 CDLT EQ LAM.LB!FT .. .. .. ..... ... ..:.... .._ .. ... ..... FC2_0 V•0 CONT 8" 44 i-v 12 DC 7 ' tt� VONT EQ a,70DLBJFr tE1No5woIG -. FC2.25 2=_"" CONT 1C'.... 2 ...u5 ...1-3'.. ...12'O,C. 2 #4 COLT EQ 3.CCCLBJFT fTEiS54\'ISf i:.,.. - REINFORCING ff . ......... I'-1 F67.5 .'.'-6" ..r. :IT. ••••1C'••• •••1 ....... .....2--O' D.G. 2 COLT rQ ..3G4'LBJFr ...•. � ... .......,.J - [ANY__ - -le ___ 1, AS 2...............3 2'.O.C. ..: 114 C'nL7 rC; 3.7CC LB; .... !E _. V-R"--- -(:A14Y.. ....12.. .....1.......A„_.2. �.D L 2---......`�.........cw,T..--------r.(]..-.. ...- 4CCLB:FT... U Fr1 B '.. •` F%:1.75 7'-:i" CfH�T 17' 2 M` ..2•3 22'Q.C. 2 ...1k4 Cn1N '. ..rQ A.3CC'LB!FT ,., ...... ... ....... . .........7 .. '- rCT�. I'..." CANT t� _ n5 3-?' 1� O.C- 1 2 R,L CC7LT ...G ....GCCLBJFC -....................... ............. ........ .......-................................................................................... 1. Ctlk!F-P r VR,N:-:T1vi:)=cwiritrIP AT 7K;AYs M'A.IL 7r 7,CC?C M: 2. PCACFALE. 0011N.REIN£ORCI'!S INTHE L.C•TTOLa1 UFTHF.=OOTING 1:'fCN 3"Gk.EA1!COtiCtET"COVER{UNOj- 3. ?OI•RE:N-OKCiNC.WaE�EOCC:EKS.SNAL'KC�L0.CEGi1JTrIiTG�f UFTi:'EF`JOT17iLi1'isTN2••'if11%L.UPf.CONCRI-ECYJVfR it EUU1!Wh;Alit LAX1 K-101.E-1LU,Ee3C:1�M:iS SN.^.L BC b"1U11C:t:N�l!.0 l�::DeR T'r1.aa S.n_rs.;lrll- S. srr GrNrI14STRUMURAL NOTP;t0R AC101-nnNAL 9fQuIR?P4r47:. 6. SOME SCHMUEDFOOT1ta155PAAY NOT SE WED,SE-FOOTINGA&VFCUNDAT:ONP LAN FU..FOOTIN(GMARK$. r. ?HIS SLI+LM.6A$$U*16A$Vsl+lA.-UNG511105UkkUP UU0P5F R. INrOSA4 ATION P",VLOCO HCRr:S 0MCMD Bti IMS AND MAY ONLY BE L 10 BY ICR104SION. 9. TI-ILS W..F:rDU:.r WAS AnOP"rn AS PARTO£NrS STANOAROS;N IMv7C1,1;F1JI i.CAI CIA ATIEON PACKAG--.ON fit r IN kri MAIN*mcr. FC1.3=1800 plf FC1.5=2000 plf FC1.75=2400 plf FC2.0=2700 plf FC2.25=3000 plf FC2.5=3300 plf FC2.75=3700 plf FC3.0=4000 plf FC3.25=4300 plf FC3.5=4600 plf FS1.5=2700 lbf FS1.75=3675 lbf FS2.0=4800 lbf FS2.25=6075 lbf FS2.5=7500 IV FS2.75=9075 lbf FS3.0=10800 IV FS3.25=12675 1bf FS3.5=14700 IV FS3.75=16875 lbf FS4.0=19200 lbf FS4.25=21675 lbf FS4.5=24300 lbf FS4.75=27075 1bf FS5.0=30000 IV FS5.25=33075 lbf FS5.5=36300 IV FS5.75=39675 lbf FS6.0=43200 lbf CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 5/21 Page 35 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: � P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/ � 208-932-2720 office Interior Floor Space REVIEWED BY: �. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Slab on Grade Capacitk Per IBC 1906.1 a foundation may be less then 10" per the following 006.1 Scope. The dosryn aril construction of stnictural plain concroto, both cast-in-place and reocast,snill compty wrth tho minimum roqurrornonts of ACI 318.as modihod i r Section 1905. Exception: For Group R•3 occupancies and bt0dings of other occupancies less than two stories above grade plane of light-trarne oonstruction, tie required footing thickness of ACI 318 is permitted to be reduoed to 6 inches 4152 mm). prorided that the footing does nol extend mare than 4 inones 1102 mm)on ether side of the supported well. Capacity6inSlab2x4Wall - SoilBearing *(4 in + 3.5 in + 4 in)= 1916.667 plf requires 2x4 wall Capacity6inSlab2x6Wall - SoilBearing *(4 in + 5.5 in + 4 in) = 2250 plf requires 2x6 wall Capacity6inSlab2x8Wall = SoilBearing *(4 in + 7.25 in + 4 in)= 2541.667 plf requires 2x8 wall Capacity One2x6Spot =SoilBearing *(4 in + 5.5 in + 4 in)* (4 in + 1 * 1.5 in + 4 in) = 1781.25 Ibf requires (1)2x6 post CapacityTwo2x6Spot= SoilBearing *(4 in + 5.5 in + 4 in)*(4 in + 2 * 1.5 in + 4 in) = 2062.5 Ibf requires (2)2x6 post CapacityThree2x6Spot = SoilBearing *(4 in + 5.5 in + 4 in)*(4 in + 3 * 1.5 in + 4 in) = 2343.75 Ibf requires (3)2x6 post CapacityFour2x6Spot1 = SoilBearing * (4 in + 5.5 in + 4 in) *(4 in + 4* 1.5 in + 4 in)= 2625 Ibf requires (4)2x6 post CapacityFive2x6Spot= SoilBearing *(4 in + 5.5 in + 4 in)*(4 in+ 5 * 1.5 in + 4 in)= 2906.25 Ibf requires (5)2x6 post CapacitySix2x6Spot = SoilBearing * (4 in + 5.5 in + 4 in) *(4 in + 6 * 1.5 in + 4 in) = 3187.5 Ibf requires (6)2x6 post Capacity Seven2x6Spot = SoilBearing* (4 in + 5.5 in + 4 in) *(4 in + 7 * 1.5 in + 4 in)= 3468.75 Ibf requires (7)2x6 post CapacityEight2x6Spot - SoilBearing*(4 in + 5.5 in + 4 in) *(4 in + 8 * 1.5 in +4 in)= 3750 Ibf requires (8)2x6 post Capacity =Nine2x6Spot SoilBearing *(4 in + 5.5 in + 4 in)*(4 in + 9* 1.5 in + 4 in) = 4031.25 Ibf requires (9)2x6 post CapacityTen2x6Spot= SoilBearing *(4 in + 5.5 in + 4 in)*(4 in + 10 * 1.5 in + 4 in)= 4312.5 Ibf requires (10)2x6 post CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 6/21 Page 36 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. 1712 C bellar office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Floor Joist Design: if The longest span covers mostly the office and restroom areas with part of the corridor in front of the restroom. The LL could be reduced to the reflect the percentage of area of corridor vs office/restroom area. However,the higher LL will be used but a code min deflection will be accepted. FORTE W E B ��kojl 6 PASSED i plece(s)11 7.2"TJIF)360 @ 16"OC o..ot t«+3rn 1r t- i k 164 l r 0 ::at,ons are"aas,.red ho•t e!Y outsee bee d Wt s,to+o^.for tat u•uewellal.Aldewsars are pwz:rn Swan peal Design Rpueb Ate/al Q Laeatien AYt+eed Rein LOF Load-[etesie~fPablM Jost ue—tw itawr r(to low 0 1B 01:. t000(1'0--. peaaeif t 0: 1:0.10 L Al Sw Il Eua•Q k." Shell'M. lose a it 0 IT 'M ?based(42%) 105 1:0.1.0 L?At SW*i C.O'nTWw Sue•0:ode )B::ott LorMrt IF-4t g, 43N @ i ar alto passed f'OTL) 10o 1:0.10 L W spar$) weq^+vrf+oeocvr -.*;.Odd D*A�P) 0 4310 ft a- a sss passed tLVS1) — 1:0.1.0 L At Spinal T"Load Deg w 0412 G$a- a KID %ased-L3Wi — 1.0 D.1.0 L OA Spero) T}-ro-Racn3 a! e0 ►»sad Cod rleelot:Somoon Strong-Tit O Support Seat LenW Top Festaners Fes*Fntmers Nemtw Fasw•ti•s Aeeasser" .-4pladcrtMarw :23".11 88 V ::C' 1-10dz•.5 .-xt� ,•'s•. F)Nr b MrrssWwr foul Yd rsoxwo top"rrJAMW and use el al 1 Vert"LCod Loca¢on Swc"G N- d (Leer Floor corm mi; 1-vift fps#) 0::" t' le, is: so: 004utcorrrrena .:a,: CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 7/21 Page 37 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. 1712 C bellar office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Ceiling Joist Design: Assuming 14ft span over Office 206 with 15psf dead load,40 psf live load and 300 lbf of dead point load mid span. Discussion with LRA stated that MECH equipment will be approx.two 300 lbf unit. This analysis assumed worst case of 300 lbf per joist. When sizing beam the full (2)x 300 lbf will be directly applied over the beams. :IFORTEWEB ,t.* �,—, A; Pass�D 1 plece(s)11 7r6"TJ16110 A 16"0C 0400 L400%f u r � u o c 4t*trj-w a av reaw-ad*v"Te cva Oa-ace of Wt a.+Peo.I or Un.ar eft rer erW N eaws.<na are pox [ Design Rpultt Actual 0 Lo"Soe Us as Rtsult LIN Lost C 'on 011~%) syslb� root Menw TIve loot wo"ber gesacn fDe) gel o 14 3 t.Y 0101 f 707 Pssaeo(73%) 100 10 0-1.0 L W Seen) s.aCnp Vli St1w(%4 000 @ 3•? t000 c»foo 14^) 100 10 0.19 L IN Stseq C*Tf"ns ew0r0 coot ec 20f3 %form t iTsis l it7t Q'- 3100 es►se0(91%) 100 10 0.10 L W sttnl Do"?MvAosNVf L"Lo"DO C 2.1 0 r 0 400 c asseo 11414) - 10 D.1 0 L(4t Swn) f•W afMON etN O 'i Tcts:cad'-Wm - 040107 0 TOs isased a,e16, - 10 0-I L IAa Seen! connecoor.Simpson Strong-T)e0 S.Ptott feat lager T*9 FatM•as Fate Fastt•trs Mert+tp FasteAws Aottssents TOO udPt"nee rrs111.1133 V 200• a.t0tx'! :.,Ca•.•5 2-S". N'3'4 aW ab+up%oamrw oars ab r•srr cs0+s fir ydpe•rluar 'ane sse of la aorredeas VtrpOsl LoK t LocAte" Soeang Otjl Floor( C*m"Or is 1-LVA"IPSFI 0 to a 7 4" !C 400 NO&-e.:ad I-Poet ID I IMA <A7 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 8/21 Page 38 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/`�� 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Footing Check for Bearing Walls: Max Wall Load 16.5 ft 17.25 ft TribmaxWall + = 16.875 ft 2 2 Demand maxWall =TribmaxWall *(DL+ LL)= 1603.125 plf Demand maxWall = 0.712 Capacity6inSlab2x6Wall The 2x6 walls shown on the ARCH drawings pass the bearing test for these loads with the existing slab on grade acting as the foundation per IBC 1906.1 Beams and Columns: n 1 i � 5 T�- I � i \ I..._........................ ..................................;....................... ........................................................_............................................... J Second floor framing plan CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 9/21 Page 39 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: � P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/ � 208-932-2720 office Interior Floor Space REVIEWED BY: �. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam B Beam lengthB—8.5 ft 11.5 ft TribfloorB =5.75 ft 2 0 ft TribceilingB 2 =0 ft TribAbvWal1B—8 ft DLB= TribfloorB* DL+TribceilingB *DLceiling+TribAbvWallB *DLw=150.25 plf LLB=TribfloorB *LL +TribceilingB *LLattics—460 plf 6,y m 9 J Q U � h m 32C3 8 .1788 8 JO U 3203 8 788 8 DemandBfooting— 3203.8 lbf CapacityBfooting—CapacitySeven2x6Spot—3468.75 lbf Demand Bfooting =0.924 CapacityBfooting CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 10/21 Page 40 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/`�� 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam C Beam lengthC—5.5 ft 11.5 ft TribfloorC =5.75 ft 2 TribceilingC—0 ft TribAbvWa11C—8 ft DLC= TribfloorC* DL+TribceilingC*DLceiling+TribAbvWal1C *DLw=150.25 plf LLC=TribfloorC *LL +TribceilingC*LLattics —460 plf Quo u N V tb792/ItJ2 a182:t•32 DemandCfooting— 1678.2 lbf Capacity Cfooting—CapacityTwo2x6Spot—2062.5 lbf Demand Cfooting =0.814 CapacityCfooting CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 11/21 Page 41 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/`�� 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam D,this is a check on the non-bearing wall load above on the joist Dead load assumed to be 15 psf Live load assumed to be office live load of 50 psf 8 ft*DLw—64 plf Wall Above load ORT FORTEWEB avJowIE eads...a PASSED 1 pwcMs)11 Mr TJ►V 360 @ 16'OC Ow liw'yM 1T 1' 0 O ::ax+s an-18s✓t0 law 014 0,h4t bK*N M 5.000'•I or OR ca tstw.sa;.Al aVwsa+s vt pv%nrlal De$W ReMft AM&]a Locahon Alaoar00 Mavt LOF Loa*Caroleas*a lcaturnl we"te,'Pt» :sat We.-W at#="06) IM o a 1.7 IN":7 N-1 easwo 1*%) 109 10 0.t 0 L tAl:wnu 6.0•0 uw :rya ay 1:43 Q O 1.7 ':0 vuwo(T3%) 100 10 0.1 0 L AI:parn co--&w B:OrQ C40t 6C M S uc-4m rRia) 53310 8 1 1,7 Ol{0 1204w0116%) too 10 0.10 L W Sw o, C-p-yt toftiap -.s LW DM io? 0276 0 8 8 T7 C 666 Fassw 10n) - 1 0 D-1.O 11AI Swd, AM T"L4a0 Dt11(in) 0021 0 8 11.7 C 133 Pa"W(U= - 10 0-10 L W Sw o. T}-Pn0"Aatau3 11 IJ Oa"" - f,Wl"ILotods lotato- Spatoo Its Cm~ts 401091 JAMt ;;V) ov 1 'O ISO -JrAx"SiLF) D t2'`1 .,A 040 The typical floor joist passes with the office live load,this would be the yellow walls below,the green wall has a beam to support the mech loads above office 206 CITY APPROVED PLANS t —- ..................... Reviewed for Code Compliance PLANS MUST BE ON JOB SITE i FOR ALL INSPECTIONS 12/21 Page 42 of 97 Noesis Engineering Services, Project Number. 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter, P.E. 208-932-2720 office Interior Floor Space 1712 Cabellaro Dr. REVIEWED BY: Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam F Beam lengthF— 11.5 ft TribfloorF— 16 in 12.75 ft TribceilingF 2 =6.375 ft TribAbvWal1F—8 ft DLF=TribfloorF* DL+TribceilingF* DLceiling+TribAbvWallF* DLw= 179.625 plf LLF=TribfloorF*LL+TribceilingF* LLattics=361.667 plf Discussion with LRA stated that MECH equipment will be approx.two 300 lbf unit. This analysis assumed worst case the full(2)x 300 lbf will be directly applied over the beam,at 113 and 2.13 location Points loads. u �c v 34154,'..n-o N 0 tSi9t 7 i 2)W• Demand Hooting—3415.4 lbf CapacityFfooting—CapacitySeven2x6Spot—3468.75 lbf DemandFfooting =0.985 CapacityFfooting k'wl Jam Ayes Nm&.Wm W f s1••ers AMftdk us&*Ad"Tt ".I W&I - 61te N� 8 M N' N M A N•d'r I lrl Rl M SAW n53SbJ11.11M • — 3% 11% 2 1Ne "91"13 — 120 SAO 1,3M61I.M 1 1.1N MUMS • • • — M 11% 2% 2% AP01620% 00148- t65 1.b?S'SAM I INS i 21S INC 2.Iq 2.116 2.W$ • • • — 3% 11% 3 2% pA0.152a3K 000. 2% 01S 3% US • • • 3% 11% 3 2% 11pOW93101 0014C 411S i72M 40ma 3%K11 untse • • • • M 11% 3% 3 QZ0.162e3N 110c.162 1 WS SAIS S,Na I Siin POP]56..11a15 . . :' m 5%r30 2% 2% 1(,a1W.21e MOW, 10M6 US I US zx: 11WV3SMIbltgf • • • % 3% 111 3 2% a1Q:31i i1aoul .!W iMMb 4TW-I aaeo CITY APPROVED PLANS NARf ws-ftfi . . . . As 61r32 a141 2% tL2�01M2e3K(IQMx1 as GM Un I SAM M1 MGli1N.1tf7S • — 9M. N033 0 2% 1141161A IblNia ,ALSO — — — 1ai:. Reviewed for Code Compliance IIGlIV3 611 • • • i 3% 11% 0 1 2% am O 1Q a 3K Ip a tM.' 1.t2o w SM3 O.IR► 114a0 awl PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 13/21 Page 43 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: � P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/ � 208-932-2720 office Interior Floor Space REVIEWED BY: �. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam G(BOTH G BEAMS) BeamlcngthG—25 ft 11.5 ft 11.5 ft TribfloorG + = 11.5 ft 2 2 TribceilingG=0 ft TribAbvWal1G=0 ft LL=80 psf DLG=TribfloorG *DL+TribceilingG*DLceiling+ TribAbvWal1G*DLW= 172.5 plf LLG=TribfloorG* LL+TribceilingG * LL attics—920 plf o`� q )115�:•7.15� � )G2�7i/l O O O t]ES6V2062 Iwo Tirm• • O Demand Gfooting— 15430.2 lbf CapacityGfooting—FS3.75= 16875 lbf Demand Gfooting 0.914 CapacityGfooting 1.33ft * 6ft*2000psf=15960lbf CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 14/21 Page 44 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/`�� 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam H Beam lengthH—5 ft 16 in 16.5 ft TribfloorH + 8111lin 2 2 TribceilingH—0 ft TribAbvWa11H—0 ft DLH=TribfloorH *DL+TribceilingH*DLceiling+ TribAbvWa1lH*DLW= 133.75 plf LLH=TribfloorH* LL+TribceilingH *LLattics=713.333 plf Demand Hfooting—2117.7 lbf CapacityHfooting—CapacityThree2x6Spot— 2343.75 lbf DemandHfooting = 0.904 CapacityHfooting ti 01 J � U+ 0 N J U 2117,71334 4 2117.7 r 334.4 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 15/21 Page 45 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/`�� 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam I BeamlengthI—5 ft 5.5 ft 16 in TribfloorI + =3ft 5in 2 2 TribceilingI= 0 ft TribAbvWalll=0 ft DLI=TribfloorI *DL+TribceilingI* DLceiling+TribAbvWaIII* DLw=51.25 plf LLI=Tribfloorl*LL +TribceilingI *LLattics=273.333 plf Demand Hooting—811.5 lbf Capacityftooting—CapacityOne2x6Spot= 1781.25 lbf Demand Ifooting =0.456 CapacityIfooting M Pr sip V N J 0 V 811.51128.1 811.5/128.1 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 16/21 Page 46 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: � P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/ � 208-932-2720 office Interior Floor Space REVIEWED BY: �. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam J Beam lengthJ— 5 ft TribfloorJ—0 ft 5 ft 6.5 ft TribceilingJ 2 + 5.75 ft 2 = TribAbvWal1J—0 ft DLJ=TribfloorJ*DL+TribceilingJ *DLceiling+TribAbvWallJ* DLw=86.25 plf LLJ=TribfloorJ *LL+TribceilingJ*LLattics —230 plf g O J 7006:2156 O 790.6 1215.E DemandJfooting—790.6 lbf Capacity Hooting—CapacityOne2x6Spot— 1781.25 lbf DemandJfooting =0.444 CapacityJfooting CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 17/21 Page 47 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: � P.C. Project Name: Robert Weed Plywood David Boyter,P.E. tj/ � 208-932-2720 office Interior Floor Space REVIEWED BY: �. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Loading and Assumptions for Beam K Beam lengthK—5 ft TribfloorK—0 ft 5 ft 9.25 ft TribceilingK 2 + 7.125 ft 2 = TribAbvWallK—0 ft DLK=TribfloorK *DL+TribceilingK*DLceiling+ TribAbvWal1K*DLW= 106.875 plf LLK=TribfloorK* LL+TribceilingK*LLattics=285 plf Demand Kfooting—980 lbf CapacityKfooting— Capacity0ne2x6Spot— 1781.25 lbf DemandKfooting = 0.550 Cs111;cc'ily ASUUli1i� J �t O U � Y 979.71267 U 979712672 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 18/21 Page 48 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: 1 P.C. Project Name: Robert Weed Plywood David Boyter,P.E. � 208-932-2720 office 1712 Cabellaro Dr. Interior Floor Space REVIEWED BY: Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Member Shape Code Check LoclRl LC Shear Check Loc[R) Dig LC 8M B 2475X11.875FS OAS 5.25 5 OA06 10.5 y 5 COL B 1 7.2X6 0.068 10 5 0 10 5 COL 8 2 7.2X6 0.068 10 5 0 10 5 8MC 1.75X11.875FS 0.273 2?5 5 OA25 5.5 5 COL C 1 2-2X6 0.592 10 5 0 10 5 COL C 2 2-2X6 0.592 10 5 0 10 _ 5 COL F 7-2X6 0 073 i C 5 0 10 _ 5 BM H 1.75X11,875FS 0.311 2.5 5 0.536 5 5 COL H 1 3.2X6 0.239 10 5 0 10 _ 5 COL H 2 3.2X6 U39 10 5 0 10 5 SM F 2.1.75X 1 1.875FS 0.578 575 5 OA65 0 y 5 COL I t 2X6 0121 10 5 0 10 _ 5 COL12 2X6 0121 tc 5 0 10 5 BM I 1.75X14FS 0.087 2.5 5 0.174 5 5 COL. I 2X6 0.334 5 5 0 5 _ 5 COL.2 2X6 0.334 5 5 0 5 _ 5 BM 1 2X12 0.429 2.5 5 0.39 5 5 COL K 1 20 OA14 5 5 0 5 5 COL K 2 2X6 0.414 5 5 0 5 5 EM K 2X12 0.531 2.5 S OA84 S y 5 Member Shape Code Check Loc(kl LC Sheer Check Loc(ft) Dir LC COLG 1 HSS4X4X4 0.241 10 5 0 10 y 5 COL G 2 HSS4X4X4 0.239 10 5 0 10 y 5 BAI G W12X72 0.421 13.021 5 0.1-6 25 y 5 COL G 4 HSS4X4X4 0.213 10 5 0 10 y 5 COL G 3 HSS4X4X4 0.213 10 5 0 10 y 5 BM G RIGHT W12X72 0.347 12.5 5 0.129 25 y 5 Beam D"n Ruie Span De11(Inl RaW LC Defl[in] Rahn LC DeA(in) Ratio LC BM B Typcal 1 -0.044 2845 1(DL) -0.136 929 2(LL) -0.18 700 3(DL-LL) 8M C Typcil 1 -0.007 98" 1(DL) -042 3233 2(LL) -0.027 2437 310L-LL) BM H Tjpcal 1 0 NC 1(DL) -0A22 2775 2(LL) -0A26 2337 3(DL-LL) BM F Typrcal 1 -0.106 1296 1(Du -0.153 899 2(LL) -026 531 3(DL-LL) BAI G Typco 1 -0.169 1774 1(OL) -0.691 433 2(LL) -0.861 30 310L-11) BM I Tjpcal 1 0 NC 1(CL) 0 NC 2(LL) -0.006 9994 3(DL-LL) BM 1 Tjpcal 0 NC 1(CL) -0.011 5282 2(LL) -0016 3641 3(DL-LL) BM K Tjpcai 1 0 NC 1(CL) •0.014 4Z63 2(11I •0.019 3100 3(DL•LL) BM G RGHT T)pcal 1 •0.109 2740 1(CL) -0.584 513 2(LL) -0.693 A32 31DL•LU CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Page 49 of 97 Noesis Engineering Services, Project Number. 22083 DESIGN ENGINEER: P.C. �I Proiect Name: Robert Weed Plywood David Boyter, P.E. �� 208-932-2720 office� Interior Floor Space REVIEWED BY:. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido LATERAL DESIGN: The existing building protects these interior walls from wind forces,the main lateral forces to be designed for shall be the seismic forces. Area 2nd= 1980 ft2 Area of the 2nd floor area AreaMech206— 132 ft2 Area over office 206 where the Mech equipment will be located(two 300 lbf) Length I st interiorWalls— 6.25 ft* 2+ 25.5 ft* 4+20.5 ft* 3+ 10.5 ft* 5+ 32.25 ft*2+5 5.7 5 ft*2=404.5 ft Length of 1 st floor walls Heigthl st=9.5 ft Height of the 1 st floor walls Length2stinteriorWalls— 2 6.7 5 ft* 1 +32.25 ft*3 +5 5.7 5 ft* 2+25 ft* 4+ 21 ft* 3= 398 ft Length of 2nd floor walls Heigth2st=9.5 ft Height of the 2nd floor walls W=(Area2nd* DL+AreaMech206*DLceiling+(Lengthl stinteriorWalls* '5 *Heigthl st+Heigth2st*Length2stinteriorWalls) *DL) = 117215.625 lbf Lateral2ndFloorDia=W* Cs2=3732.867 lbf Demand lateral=Lateral2ndFloorDia= 3732.867 lbf Required Shear Capacitygyp812No6 2 120 plf =60 plf Capacity of 1/2"Gypsum shear walls with No 6 screws(1 1/4")@ 8"O.C.edge 12" field Capacity=Capacitygyp812No6 *(51 + 15.5+32.5+ 12+26.75+51)ft= 11325 lbf Demand lateral =Capacity 0.330 The amount of walls that will be covered with Gypsum passes the required shear capacity by 3x,no additional shear walls are require. CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 20/21 Page 50 of 97 Noesis Engineering Services, Project Number: 22083 DESIGN ENGINEER: P.C. Project Name: Robert Weed Plywood David Boyter,P.E. 208-932-2720 office Interior Floor Space REVIEWED BY: `�. 1712 Cabellaro Dr. Ammon, ID 83406 Date: 06/08/2022 Jake Lucido Strong-Bolt" 2[sign Information Concrete (.xtcti Mud�xn3 Lot 7 bh=S#uVh Dwo WSW Ihv Inb sumfV& A 1V M 1% 1% '.K IK '.K 5K SIK flal llMMa>ifr(IG>uus""11.6111rAQ3118,1/5a1M W) Skew Skew"0Zt Y� K 9iG I100 I= II= 140) It= An1i�� I"f /i 0M !W lLs1Y�r�MFiIlI�rlbW114 Swim IWeAD11&11•e1M0A4 OWdI OYmi [, a 07t ` v3.% :'AO a&7 arw 140 IsSiiMlq l�p�d !� a 1500 IYc 1`,uc ?!� ?SIS ?J50 /500 SJ15 SD00 /500 l000 Aslt a 9aa IAaafar 070 li I test bukd I d 's I 22501bf lbf Capacity anchorbolt =375 — 1/2" dia bolt per 6ft spacing 6 ft ft Demand anchorbolt—Capacitygypg12No6—60 plf Demand anchorbolt =0.16 Capacity anchorbolt CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 21/21 Page 51 of 97 6/3/22,7:02 AM U.S.Seismic Design Maps OSH PD 3351 Eldridge Ave, Twin Falls, ID 83301, USA Latitude, Longitude: 42.5414292, -114.4143279 QLippert Components Krone America 19Alliance Liquid Feeds Q Independent Robert Weed Plywood Meat Distribution Eldridge Ave Eldridge Ave Go gle Map data 02022 Date 6/3/2022,7:02:37 AM Design Code Reference Document ASCE7-16 Risk Category II Site Class D-Default(See Section 11.4.3) Type Value Description Ss 0.194 MCER ground motion.(for 0.2 second period) St 0.082 MCER ground motion.(for 1.0s period) SMS 0.31 Site-modified spectral acceleration value SM1 0.198 Site-modified spectral acceleration value SIDS 0.207 Numeric seismic design value at 0.2 second SA SD1 0.132 Numeric seismic design value at 1.0 second SA Type Value Description SDC B Seismic design category Fa 1.6 Site amplification factor at 0.2 second Fv 2.4 Site amplification factor at 1.0 second PGA 0.085 MCEG peak ground acceleration FPGA 1.6 Site amplification factor at PGA PGAM 0.137 Site modified peak ground acceleration TL 6 Long-period transition period in seconds SsRT 0.194 Probabilistic risk-targeted ground motion.(0.2 second) SsUH 0.211 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration SsD 1.5 Factored deterministic acceleration value.(0.2 second) S1 RT 0.082 Probabilistic risk-targeted ground motion.(1.0 second) S1UH 0.087 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration. CITY APPROVED PLANS S1 D 0.6 Factored deterministic acceleration value.(1.0 second) Reviewed for Code Compliance PGAd 0.5 Factored deterministic acceleration value.(Peak Ground Acceleration) PLANS MUST BE ON JOB SITE CRS 0.919 Mapped value of the risk coefficient at short periods FOR ALL INSPECTIONS CR1 0.944 Mapped value of the risk coefficient at a period of 1 s https://seismicmaps.org Page 52 of 97 1/2 6/3/22,7:02 AM U.S.Seismic Design Maps DISCLAIMER While the information presented on this website is believed to be correct,S.E.A.O.C./OSHPD and its sponsors and contributors assume no responsibility or liability for its accuracy.The material presented in this web application should not be used or relied upon for any specific application without competent examination and verification of its accuracy,suitability and applicability by engineers or other licensed professionals.SEAOC/OSHPD do not intend that the use of this information replace the sound judgment of such competent professionals,having experience and knowledge in the field of practice,nor to substitute for the standard of care required of such professionals in interpreting and applying the results of the seismic data provided by this website.Users of the information from this website assume all liability arising from such use.Use of the output of this website does not imply approval by the governing building code bodies responsible for building code approval and interpretation for the building site described by latitude/longitude location in the search results of this website. CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS https:Hseismicmaps.org Page 53 of 97 2/2 J r O R T G CM MEMBER REPORT PASSED Level,CEILING BRACING 1 piece(s)2 x 8 DF No.2 @ 12"OC Overall Length; 16' 1' 0 0 1 S'6" ❑1 ❑2 All locations are measured from the outside face of left support(or left cantilever end).All dimensions are horizontal. Design Results Actual @ Location Allowed Result LDF Load:Combination(Pattern) System:Floor Member Reaction(Ibs) 1 @ 2 1/2" 1434(2.25") Passed(0%) 1.0 D+1.0 L(All Spans) Member Type:Joist Building Use:Commercial Shear(Ibs) 1 @ 10 3/4" 1305 Passed(0%) 1.00 1.0 D+1.0 L(All Spans) Building Code:IBC 2018 Moment(Ft-Ibs) 3 @ 8'1/2" 1360 Passed(0%) 1.00 1.0 D+1.0 L(All Spans) Design Methodology:ASD Live Load Defl.(in) 0.002 @ 8'1/2" 0.392 Passed(L/999+) 1.0 D+1.0 L(All Spans) Total Load Defl.(in) 0.002 @ 8'1/2" 1 0.783 1 Passed(L/999+) 1.0 D+1.0 L(All Spans) TJ-Pro'""Rating N/A N/A N/A N/A • Deflection criteria:LL(L/480)and TL(L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •A 15%increase in the moment capacity has been added to account for repetitive member usage. •Applicable calculations are based on NDS. • No composite action between deck and joist was considered in analysis. Bearing Length Loads to Supports(Ibs) Supports Total Available Required Dead Floor Live Total Accessories 1-Stud wall-SPF 3.50" 2.25" 1.50" 1 1 1 1/4"Rim Board 2-Stud wall-SPF 3.50" 2.25" 1 1.50" 1 1 1 1/4"Rim Board •Rim Board is assumed to carry all loads applied directly above it,bypassing the member being designed. Lateral Bracing Bracing Intervals Comments Top Edge(Lu) 15'11"o/c Bottom Edge(Lu) 15'11"o/c -Maximum allowable bracing intervals based on applied load. Dead Floor Live Vertical Load Location(Side) Spacing (0.90) (1.00) Comments 1-Uniform(PSF) 0 to 16'1" 12" 0.1 Default Commercial Load Member Notes SELF WEIGHT BENDING CHECK Weyerhaeuser Notes Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values.Weyerhaeuser expressly disclaims any other warranties related to the software.Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction.The designer of record,builder or framer is responsible to assure that this calculation is compatible with the overall project.Accessories(Rim Board,Blocking Panels and Squash Blocks)are not designed by this software.Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards.Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards.For current code evaluation reports,Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application,input design loads,dimensions and support information have been provided by ForteWEB Software Operator CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS ForteWEB Software Operator Job Notes 6/6/2022 9:35:00 PM UTC David Boyter Noesis Engineering Services ForteWEB v3.2, Engine: V8.2.0.17, Data: V8.1.0.16 (208)932-2720 Aage 54 of 97� dboyter@noesis.us Ile Name: Robert Weed Plywood Page 1/ 1 J r O R T G CM MEMBER REPORT PASSED Level,Ceiling:Joist 1 piece(s)11 7/8"TJ1@ 110 @ 16"OC Overall Length:14'7" 0 0 14' 0 All locations are measured from the outside face of left support(or left cantilever end).All dimensions are horizontal. Design Results Actual @ Location Allowed Result LDF Load:Combination(Pattern) System:Roof Member Reaction(Ibs) 661 @ 14'3 1/2" 910(1.75") Passed(73%) 1.00 1.0 D+1.0 L(All Spans) Member Type:Joist Shear(Ibs) 666 @ 3 1/2" 1560 Passed(43%) 1.00 1.0 D+1.0 L(All Spans) Building Use:Commercial Building Code:IBC 2018 Moment(Ft-Ibs) 2871 @ 7' 3160 Passed(91%) 1.00 1.0 D+1.0 L(All Spans) Design Methodology:Aso Live Load Defl.(in) 0.201 @ 7'3" 0.469 Passed(U843) 1.0 D+1.0 L(All Spans) Member Pitch:0/12 Total Load Defl.(in) 0.407 @ 7' 0.704 Passed(U415) 1.0 D+1.0 L(All Spans) • Deflection criteria:LL(L/360)and TL(L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. Bearing Length Loads to Supports(Ibs) Supports Total Available Required Dead Floor Live Total Accessories 1-Stud wall-DF 3.50" 3.50" 1.75" 300 387 687 Blocking 2-Hanger on 11 7/8"DF beam 3.50" Hangers 1 1.75"/-z 291 391 682 See note' •Blocking Panels are assumed to carry no loads applied directly above them and the full load is applied to the member being designed. •At hanger supports,the Total Bearing dimension is equal to the width of the material that is supporting the hanger •s See Connector grid below for additional information and/or requirements. •z Required Bearing Length/Required Bearing Length with Web Stiffeners Lateral Bracing Bracing Intervals Comments Top Edge(Lu) 3'3"o/c Bottom Edge(Lu) 14'4"o/c •TJI joists are only analyzed using Maximum Allowable bracing solutions. -Maximum allowable bracing intervals based on applied load. Connector:Simpson Strong-Tie Support Model Seat Length Top Fasteners Face Fasteners Member Fasteners Accessories 2-Top Mount Hanger ITS1.81/11.88 2.00" 4-10dxl.5 2-10dxl.5 2-Strong-Grip •Refer to manufacturer notes and instructions for proper installation and use of all connectors. Dead Floor Live Vertical Loads Location Spacing (0.90) (1.00) Comments 1-Uniform(PSF) 0 to 14'7" 16" 15.0 40.0 Default Load 2-Point(lb) 7' N/A 300 - Weyerhaeuser Notes Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values.Weyerhaeuser expressly disclaims any other warranties related to the software.Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction.The designer of record,builder or framer is responsible to assure that this calculation is compatible with the overall project.Accessories(Rim Board,Blocking Panels and Squash Blocks)are not designed by this software.Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards.Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards.For current code evaluation reports,Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application,input design loads,dimensions and support information have been provided by ForteWEB Software Operator CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE ForteWEB Software Operator Job Notes FOR ALL INSPECTIONS rc David Boyter Noesis Engineering Services ForteWEB v3.2,Engine:V8.2.0.17, Data:V8.1.0.16 (208)932-2720 Aage 55 of 97� dboyter@noesis.us lle Name: Robert Weed Plywood Page 1/ 1 J r O R T G CM MEMBER REPORT PASSED Level, Floor: Joist 16.5ft under wall 1 piece(s) 11 7/8"TJI@ 360 @ 16"OC Overall Length; 17'5' 0 0 16'6" ❑1 ❑2 All locations are measured from the outside face of left support(or left cantilever end).All dimensions are horizontal. Design Results Actual @ Location Allowed Result LDF Load:Combination(Pattern) System:Floor Member Reaction(Ibs) 1296 @ 4 1/2" 1505(3.50") Passed(86%) 1.00 1.0 D+1.0 L(All Spans) Member Type:Joist Shear(Ibs) 1243 @ 5 1/2" 1705 Passed(73%) 1.00 1.0 D+1.0 L(All Spans) Building Use;Commercial Building Code:IBC 2018 Moment(Ft-Ibs) 5231 @ 8'8 1/2" 6180 Passed(85%) 1.00 1.0 D+1.0 L(All Spans) Design Methodology:ASD Live Load Defl.(in) 0.275 @ 8'8 1/2" 0.556 Passed(L/728) 1.0 D+1.0 L(All Spans) Total Load Defl.(in) 0.621 @ 8'8 1/2" 1 0.833 1 Passed(L/322) 1.0 D+1.0 L(All Spans) TJ-Pro'""Rating 48 40 Passed • Deflection criteria:LL(L/360)and TL(L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •A structural analysis of the deck has not been performed. • Deflection analysis is based on composite action with a single layer of 23/32"Weyerhaeuser EdgeTM Panel(24"Span Rating)that is glued and nailed down. •Additional considerations for the TJ-ProTM Rating include:None. Bearing Length Loads to Supports(Ibs) Supports Total Available Required Dead Floor Live Total Accessories 1-Stud wall-DF 5.50" 4.25" 2.64" 732 581 1313 1 1/4"Rim Board 2-Stud wall-DF 5.50" 4.25" 1 2.64" 732 581 1313 1 1/4"Rim Board •Rim Board is assumed to carry all loads applied directly above it,bypassing the member being designed. Lateral Bracing Bracing Intervals Comments Top Edge(Lu) 3'10"o/c Bottom Edge(Lu) 17'3"o/c •TJI joists are only analyzed using Maximum Allowable bracing solutions. -Maximum allowable bracing intervals based on applied load. Dead Floor Live Vertical Loads Location Spacing (0.90) (1.00) Comments 1-Uniform(PSF) 0 to 17'5" 16" 15.0 50.0 2-Uniform(PLF) 0 to ITS" N/A 64.0 - Weyerhaeuser Notes Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values.Weyerhaeuser expressly disclaims any other warranties related to the software.Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction.The designer of record,builder or framer is responsible to assure that this calculation is compatible with the overall project.Accessories(Rim Board,Blocking Panels and Squash Blocks)are not designed by this software.Products manufactured at Weyerhaeuser facilities are third-parry certified to sustainable forestry standards.Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards.For current code evaluation reports,Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/wGodproducts/document-library. The product application,input design loads,dimensions and support information have been provided by ForteWEB Software Operator CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS ForteWEB Software Operator Job Notes ,.,,,_7 4:17:40 PM UTC David Boyter Noesis Engineering Services ForteWEB v3.2, Engine:V8.2.0.17,Data:V8.1.0.16 (208)932-2720 Aage 56 of 97� dboyter@noesis.us Ile Name: Robert Weed Plywood Page 1/ 1 FO R T E'M MEMBER REPORT PASSED Level,Floor:Joist 16.5ft 1 piece(s)11 7/8"TJ1@ 360 @ 16"OC Overall Length:17'1" 0 0 16'6" ❑1 20 All locations are measured from the outside face of left support(or left cantilever end).All dimensions are horizontal. Design Results Actual @ Location Allowed Result LDF Load:Combination(Pattern) System:Floor Member Reaction(Ibs) 1050 @ 16'9 1/2" 1080(1.75") Passed(97%) 1.00 1.0 D+1.0 L(All Spans) Member Type:Joist Shear(Ibs) 1050 @ 16'9 1/2" 1705 Passed(62%) 1.00 1.0 D+1.0 L(All Spans) Building Use:Commercial Building Code:IBC 2018 Moment(Ft-Ibs) 4354 @ 8'6" 6180 Passed(70%) 1.00 1.0 D+1.0 L(All Spans) Design Methodology:ASD Live Load Defl.(in) 0.431 @ 8'6" 0.553 Passed(L/461) 1.0 D+1.0 L(All Spans) Total Load Defl.(in) 0.512 @ 8'6" 1 0.829 1 Passed(L/389) 1.0 D+1.0 L(All Spans) TJ-Pro'""Rating 45 40 Passed • Deflection criteria:LL(L/360)and TL(L/240). •Allowed moment does not reflect the adjustment for the beam stability factor. •A structural analysis of the deck has not been performed. • Deflection analysis is based on composite action with a single layer of 23/32"Weyerhaeuser EdgeTM Panel(24"Span Rating)that is glued and nailed down. •Additional considerations for the TJ-ProTM Rating include:None. Bearing Length Loads to Supports(Ibs) Supports Total Available Required Dead Floor Live Total Accessories 1-Stud wall-DF 3.50" 2.25" 1.75" 170 907 1077 1 1/4"Rim Board 2-Hanger on 11 7/8"DF beam 3.50" Hangers 1 1.75"/-z 172 916 1088 See note s •Rim Board is assumed to carry all loads applied directly above it,bypassing the member being designed. •At hanger supports,the Total Bearing dimension is equal to the width of the material that is supporting the hanger •s See Connector grid below for additional information and/or requirements. •z Required Bearing Length/Required Bearing Length with Web Stiffeners Lateral Bracing Bracing Intervals Comments Top Edge(Lu) 4'4"o/c Bottom Edge(Lu) 16'8"o/c •TJI joists are only analyzed using Maximum Allowable bracing solutions. -Maximum allowable bracing intervals based on applied load. Connector:Simpson Strong-Tie Support Model Seat Length Top Fasteners Face Fasteners Member Fasteners Accessories 2-Top Mount Hanger ITS2.37/11.88 2.00" 4-10dxl.5 2-10dxl.5 2-Strong-Grip •Refer to manufacturer notes and instructions for proper installation and use of all connectors. CITY APPROVED PLANS Dead Floor Live Vertical Load Location Spacing (0.90) (1.00) Comments Reviewedfor Code Compliance PLANS MUST BE ON 106 SITE 1-Uniform(PSF) 0 to 17'1" 16" 15.0 80.0 Default CommercialLoad FOR ALL INSPECTIONS Weyerhaeuser Notes Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values.Weyerhaeuser expressly disclaims any other warranties related to the software.Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction.The designer of record,builder or framer is responsible to assure that this calculation is compatible with the overall project.Accessories(Rim Board,Blocking Panels and Squash Blocks)are not designed by this software.Products manufactured at Weyerhaeuser facilities are third-party certified to sustainable forestry standards.Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387 and/or tested in accordance with applicable ASTM standards.For current code evaluation reports,Weyerhaeuser product literature and installation details refer to www.weyerhaeuser.com/woodproducts/document-library. The product application,input design loads,dimensions and support information have been provided by ForteWEB Software Operator ForteWEB Software Operator Job Notes 6/7/2022 3:26:26 PM UTC David Boyter Noesis Engineering Services ForteWEB v3.2, Engine: V8.2.0.17, Data: V8.1.0.16 (208)932-2720 age 57 of 9-f dboyter@noesis.us pl;�y,tt. tt Ile Name: Robert Weed Plywood Page 1/ 1 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Proiect Grid Lines No Data to Print... Proiect Grid Arcs No Data to Print... Node Coordinates Label X Ift] Y IN Z ft Detach From Diaphragm 1 N5 0 0 15 2 N6 10.5 0 15 3 N7 10.5 10 15 4 N8 0 10 15 5 N9 0 0 30 6 N10 5.5 0 30 7 N11 5.5 10 30 8 N12 0 10 30 9 N18 21.5 0 60 10 N20 21.5 10 60 11 N21 0 0 75 12 N22 5 0 75 13 N23 0 10 75 14 N24 5 10 75 15 N25 33 10 60 16 N27 33 10 48 17 N28 33 0 48 18 N29 33 10 73 19 N30 33 0 73 20 N31 0 0 90 21 N32 0 10 90 22 N33 5 0 90 23 N34 5 10 90 24 N35 0 0 105 25 N36 0 5 105 26 N37 5 0 105 27 N38 5 5 105 28 N39 0 0 120 29 N40 0 5 120 30 N41 5 0 120 31 N42 5 5 120 32 N43 53 10 48 33 N44 53 0 73 34 N45 53 0 48 35 N46 53 10 73 Node Boundary Conditions Node Label X k/in Y k/in Z k/in X Rot k-ft/rad Y Rot k-ft/rad Z Rot k-ft/rad 1 N29 Reaction 2 N5 Reaction Reaction Reaction Reaction Reaction Reaction 3 N6 Reaction Reaction Reaction Reaction Reaction Reaction 4 N7 Reaction 5 N8 Reaction Reaction 6 N9 Reaction Reaction Reaction Reaction Reaction Reaction 7 N10 Reaction Reaction Reaction Reaction Reaction Reaction 8 N11 Reaction 9 N12 Reaction Reaction 10 N18 Reaction Reaction Reaction Reaction Reaction Reaction 11 N20 Reaction 12 N21 Reaction Reaction Reaction Reaction Reaction Reaction 13 N22 Reaction Reaction Reaction Reaction Reaction Reaction 14 N23 Reaction Reaction 15 N24 Reaction 16 N27 Reaction Reaction 17 N28 Reaction Reaction Reaction Reaction Reaction Reaction 18 N30 Reaction Reaction Reaction Reaction Reaction Reaction 19 N31 Reaction Reaction Reaction Reaction Reaction Reaction 20 N32 Reaction Reaction 21 N33 Reaction Reaction Reaction Reaction Reaction Reaction 22 N34 Reaction CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE RISA-3D Version 20 [MEMBER MODEL.r3d] Page 58 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Node Boundary Conditions(Continued) Node Label X k/in Y k/in Z k/in X Rot k-ft/rad Y Rot k-ft/rad Z Rot k-ft/rad 23 N35 Reaction Reaction Reaction Reaction Reaction Reaction 24 N36 Reaction Reaction 25 N37 Reaction Reaction Reaction Reaction Reaction Reaction 26 N38 Reaction 27 N39 Reaction Reaction Reaction Reaction Reaction Reaction 28 N40 Reaction Reaction 29 N41 Reaction Reaction Reaction Reaction Reaction Reaction 30 N42 Reaction 31 N43 Reaction Reaction 32 N44 Reaction Reaction Reaction Reaction Reaction Reaction 33 N45 Reaction Reaction Reaction Reaction Reaction Reaction 34 N46 Reaction Hot Rolled Steel Properties Label E fpsil G si Nu Therm.Coeff.[le"F-11 Density Ib/ft3 Yield fpsil Rv Fu[psi] Rt 1 A992 2.9e+07 1.115e+07 0.3 0.65 490 50000 1.1 65000 1.1 2 A36 Gr.36 2.9e+07 1.115e+07 0.3 0.65 490 36000 1.5 58000 1.2 3 A572 Gr.50 2.9e+07 1.115e+07 0.3 0.65 490 50000 1.1 65000 1.1 4 A500 Gr.B RND 2.9e+07 1.115e+07 0.3 0.65 527 42000 1.4 58000 1.3 5 A500 Gr.B Rect 2.9e+07 1.115e+07 0.3 0.65 527 46000 1.4 58000 1.3 6 A53 Gr.B 2.9e+07 1.115e+07 0.3 0.65 490 35000 1.6 60000 1.2 7 A1085 2.9e+07 1.115e+07 0.3 0.65 490 50000 1.25 65000 1.15 8 A913 Gr.65 2.9e+07 1.115e+07 0.3 0.65 490 65000 1.1 80000 1.1 Cold Formed Steel Properties Label E si G si Nu Therm.Coeff.NIT DensityIb/ft3 Yield[psi] Fu si 1 A653 SS Gr33 2.95e+07 1.135e+07 0.3 0.65 490 33000 4=0i 2 A653 SS Gr50/1 2.95e+07 1.135e+07 0.3 0.65 490 50000 65000 Wood Properties Label Type Database Species Grade Cm Ci EmodNu Therm.Coeff. 1 e'OF-11 Density Ib/ft3 1 DF2 Solid Sawn Visually Graded Douglas Fir-Larch No.2 1 0.3 0.3 35 2 SP Solid Sawn Visually Graded Southern Pine No.1 1 0.3 0.3 35 3 HF Solid Sawn Visually Graded Hem-Fir No.1 1 0.3 0.3 35 4 SPF Solid Sawn Visually Graded Spruce-Pine-fir No.1 1 0.3 0.3 35 5 24F-1.8E DF Balanced Glulam NDS Table 5A 24F-1.8E DF BAL na 1 0.3 0.3 35 6 24F-1.8E DF Unbalanced Glulam NDS Table 5A 24F-1.8E DF UNBAL na 1 0.3 0.3 35 7 24F-1.8E SP Balanced Glulam NDS Table 5A 24F-1.8E SP BAL na 1 0.3 0.3 35 8 24F-1.8E SP Unbalanced Glulam NDS Table 5A 24F-1.8E SP UNBAL na 1 0.3 0.3 35 9 1.3E-1600F VERSALAM SCL Boise Cascade 1.3E-1600F VERSALAM na 1 0.3 0.3 35 10 1.35E LSL SolidStart SCL Louisiana Pacific 1.35E LSL SolidStart na 1 0.3 0.3 35 11 1.3E RIGIDLAM LVL SCL Roseburg Forest Products 1.3E RIGIDLAM LVL na 1 0.3 0.3 35 12 2.0E DF Parallam PSL SCL TrusJoist 2.0E DF Parallam PSL na 1 0.3 0.3 35 13 LVL PRL 1.5E 2250F Custom N/A LVL PRL 1.5E 2250F na 1 0.3 0.3 35 14 LVL Microlam 1.9E 260OF Custom N/A LVL Microllam 1.9E 260OF na 1 0.3 0.3 35 15 PSL Parallam 2.0E 290OF Custom N/A PSL Parallam 2.0E 290OF na 1 0.3 0.3 35 16 LSL TimberStrand 1.55E 2325F Custom N/A LSL TimberStrand 1.55E 2325F na 1 0.3 0.3 35 Concrete Properties Label E[psil G rpsii Nu Therm.Coeff.rle"F-11 Densitv[lb/ft3l fc rosil Lambda Flex Steel[psi] Shear Steel rosil 1 Conc3000NW 3.156e+061.372e+06 0.15 0.6 145 3000 1 60000 60000 2 Conc3500NW 3.409e+061.482e+06 0.15 0.6 145 3500 1 60000 60000 3 COnc4000NW 3.644e+061.584e+06 0.15 0.6 145 4000 1 60000 60000 4 Conc3000LW 2.085e+06 9.07e+05 0.15 0.6 109.999 3000 0.75 60000 60000 5 Conc3500LW 2.252e+06 9.79e+05 0.15 0.6 109.999 3500 0.75 60000 60000 6 Conc4000LW 2.408e+061.047e+06 0.15 0.6 109.999 4000 0.75 60000 60000 Masonry Properties Label E[psi] G[psi] Nu Therm.Coeff. le"F-' Self Weight Ib/ft3 fm si Flex Steel si Shear Steel psi 1 Concrete Matt 1.35e+06 5.4e+05 0.25 0.6 Custom 1500 60000 60000 2 Clay Matt 1.05e+06 4.2e+05 0.25 1 0.6 Custom 1500 60000 60000 3 Gen Mason 1.05e+06 4.2e+05 0.25 0.6 80 1500 60000 60000 CITY APPROVED PLANS Reviewed for Code C-pli-- RISA-3D Version 20 [MEMBER MODEL.r3d] 2 Page 59 of 97 PLANS MUST ON JOB SITE FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Aluminum Properties Label E[psi] G[psi] Nu Therm.Coeff.[1e1*F-'j Density Ib/ft3 Table B.4 kt Ftu[psi]Ft [psi]Fc [psi]Fsu[psi] Ct 1 3003-1-114 1.01e+07 3.788e+06 0.33 1.3 172.8 Table B.4-1 1 19000 16000 13000 12000 141 2 6061-T6 1.01e+07 3.788e+06 0.33 1.3 172.8 Table B.4-2 1 38000 35000 35000 24000 141 3 6063-T5 1.01 a+07 3.788e+06 0.33 1.3 172.8 Table B.4-2 1 22000 16000 16000 13000 141 4 6063-T6 1.01 e+07 3.788e+06 0.33 1.3 172.8 Table B.4-2 1 30000 25000 25000 19000 141 5 5052-1-134 1.02e+07 3.788e+06 0.33 1.3 172.8 Table B.4-1 1 34000 26000 24000 20000 141 6 6061-T6 W 1.01e+07 3.788e+06 0.33 1.3 172.8 Table B.4-1 1 24000 15000 15000 15000 141 Stainless Steel Properties Label E si G rr)sii Nu Therm.Coeff.[le"IF"I Density Ib/fta n Yield si Fu si 1 A276 S316 2.8e+07 1.078e+07 0.3 0.93 500 5.6 1 30000 1 75000 2 A276 S321 I 2.9e+07 I 1.117e+07 1 0.3 1 0.73 480 5.6 65000 99 3 A276 S304 I 2.8e+07 I 1.078e+07 1 0.3 1 0.93 490 5.6 30000 75000 General Materials Properties Label E[psi] G[psi] Nu Therm.Coeff. ley°F-' Density Ib/ft' Plate Methodology 1 gen Conc3NW 3.155e+6 1.372e+06 0.15 0.6 145 Isotropic 2 gen Conc4NW 3.644e+6 1.584e+06 0.15 0.6 145 Isotropic 3 gen Conc3LW 2.085e+6 9.06e+05 0.15 0.6 109.999 Isotropic 4 gen Conc4LW 2.408e+6 1.047e+06 0.15 0.6 109.999 Isotropic 5 gen Alum 1.01e+7 4.077e+06 0.3 1.29 173 Isotropic 6 cien Steel 2.9e+7 1.115e+07 0.3 0.65 490 Isotropic 7 en PI ood 1.8e+6 38000 0 0.3 35 Isotropic 8 RIGID 1e+9 0.3 0 0 Isotropic Custom Wood Properties Label Fb Ft Fv Fc E E05 Type 1 LVL PRL 1.5E 225OF 2250 1500 220 1950 1.5e+06 1.005e+06 SCL 2 LVL PRL 2.0E 290OF 2900 1900 285 2750 2e+06 1.34e+06 SCL 3 LVL Microllam 1.9E 260OF 2600 1555 285 2510 1.9e+06 1.273e+06 SCL 4 PSL Parallam 2.0E 290OF 2900 2025 290 2900 2e+06 1.34e+06 SCL 5 PSL Parallam 1.8E 2400 1755 180 2500 1.8e+06 1.206e+06 SCL 6 LSL TimberStrand 1.55E 2325F 2325 1070 310 2050 1.55e+06 1.039e+06 SCL 7 LSL TimberStrand 1.3E 170OF 1700 1075 400 1400 1.3e+06 8.71e+05 SCL Hot Rolled Steel Section Sets Label Shape Type Design List Material Design Rule Area in 21 I in 41 Izz rin'l n° 1 I HR1 W10X33 Beam Wide Flange A992 Typical 1 9.71 1 36.6 171 To.583 Cold Formed Steel Section Sets Label Shape Type Desi n List Material Design Rule Area[in] I in° Izz[in'] J in" 1 CF1 8CU1.25XO571 Beam I CU I A653 SS Gr33 Typical 1 0.581 0.057 4.41 0.00063 Wood Section Sets Label Shape T e Desi n List Material Desi n Rule Area in2 I in" Izz in° J in" 1 WOOD1 2X6 Beam Rectan ular Double DF2 T ical 8.25 1.547 20.797 5.125 Concrete Section Sets Label Shape Type Design List Material Desi n Rule Area[in'l I in" Izz in" J in" 1 CONC1 CRECT12X8 Beam Rectangular Conc3000NW Typical 96 512 1152 1187.84 Aluminum Section Sets Label Shape Type Design List Material Design Rule Area in2 I in° Izz[in'l n° ll AL1 AA13X1.64 Beam None 3003-1-114 Typical 1.39 0.522 2.24 0.019 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 60 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Stainless Steel Section Sets Label Shape Type Design List Material Design Rule Area[in'] I in° Izz in 41 n" 1 SS1 W10X33 SS Beam None A276 S316 Typical 9.71 36.6 171 0.583 General Section Sets Label Shape Ty e Material Area inz I in^ Izz in^ J in" 1 GENII RE4X4 Beam en Conc3NW 16 21.333 21.333 31.573 2 RIGID None RIGID 1e+06 le+06 1e+06 le+06 Member Primary Data Label I Node J Node Section/Shape Type Design List Material Design Rule 1 BM B N8 N7 2-1.75X11.875FS Beam None LVL Microlam 1.9E 260OF Typical 2 COL B 1 N5 N8 7-2X6 Column Rectangular DF2 Typical 3 COL B 2 N6 N7 7-2X6 Column Rectangular DF2 Typical 4 BM C N12 N11 1.75X11.875FS Beam None LVL Microlam 1.9E 260OF Typical 5 COL C 1 N9 N12 2-2X6 Column Rectangular DF2 Typical 6 COL C 2 N10 N11 2-2X6 Column Rectangular DF2 Typical 7 COL F N18 N20 7-2X6 Column Rectangular DF2 Typical 8 BM H N23 N24 1.75X11.875FS Beam None LVL Microlam 1.9E 260OF Typical 9 COL H 1 N21 N23 3-2X6 Column Rectan ular DF2 Typical 10 COL H 2 N22 N24 3-2X6 Column Rectangular DF2 Typical 11 BM F N20 N25 2-1.75X11.875FS Beam None LVL Microlam 1.9E 260OF Typical 12 COL G 1 N28 N27 HSS4X4X4 Column Tube A992 Typical 13 COL G 2 N30 N29 HSS4X4X4 Column Tube A992 Typical 14 BM G N29 N27 W12X72 Beam None A992 Typical 15 COL 11 N31 N32 2X6 Column Rectan ular DF2 Typical 16 COL 12 N33 N34 2X6 Column Rectangular DF2 Typical 17 BM I N32 N34 1.75X14FS Beam None LVL Microlam 1.9E 260OF Typical 18 COL J 1 N35 N36 2X6 Column Rectangular DF2 Typical 19 COL J 2 N37 N38 2X6 Column Rectangular DF2 Typical 20 BM J N36 N38 2X12 Beam Rectangular Double DF2 Typical 21 COL K 1 N39 N40 2X6 Column Rectangular DF2 Typical 22 COL K 2 N41 N42 2X6 Column Rectangular DF2 Typical 23 BM K N40 N42 2X12 Beam Rectangular Double DF2 Typical 24 COL G 4 N44 N46 HSS4X4X4 Column Tube A992 Typical 25 COL G 3 N45 N43 HSS4X4X4 Column Tube A992 Typical 26 BM G RIGHT N46 N43 W12X72 Beam None A992 Typical Member Advanced Data Label I Release J Release Physical Deflection Ratio Options Seismic DR 1 BM B BenPIN BenPIN Yes Default None 2 COL B 1 BenPIN Yes **NA** None 3 COL B 2 BenPIN Yes **NA** None 4 BM C BenPIN BenPIN Yes Default None 5 COL C 1 BenPIN Yes **NA** None 6 COL C 2 BenPIN Yes **NA** None 7 COL F BenPIN Yes `*NA** None 8 BM H BenPIN BenPIN Yes Default None 9 COL H 1 BenPIN Yes **NA** None 10 COL H 2 BenPIN Yes **NA** None 11 BM F BenPIN BenPIN Yes Default None 12 COL G 1 BenPIN Yes **NA** None 13 COL G 2 BenPIN Yes **NA** None 14 BM G BenPIN BenPIN Yes Default None 15 COL 11 BenPIN Yes **NA** None 16 COL 12 BenPIN Yes **NA** None 17 BM I BenPIN BenPIN Yes Default None 18 COL J 1 BenPIN Yes **NA** None 19 COL J 2 BenPIN Yes **NA** None 20 BM J BenPIN BenPIN Yes Default None 21 COL K 1 BenPIN Yes **NA** None 22 COL K 2 BenPIN Yes **NA** None 23 BM K BenPIN BenPIN Yes Default None 24 COL G 4 BenPIN Yes "*NA** None 251 5 COL G 3 BenPIN Yes **NA** None 261 BM G RIGHT BenPIN BenPIN Yes Default None CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE 4 Page 61 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Hot Rolled Steel Desiqn Parameters Label Shape Length ft Lcomp to ft Channel Conn. aft Function 1 COL G 1 HSS4X4X4 10 Lb N/A N/A Lateral 2 COL G 2 HSS4X4X4 10 Lb N/A N/A Lateral 3 BM G W12X72 25 Lb N/A N/A Lateral 4 COL G 4 HSS4X4X4 10 Lb N/A N/A Lateral 5 COL G 3 HSS4X4X4 10 Lb N/A N/A Lateral 6 BM G RIGHT W12X72 25 Lb N/A N/A Lateral Cold Formed Steel Design Parameters No Data to Print... Wood Design Parameters Label Shape Len th[ftI let ft le-bend to ft Cr y sway z sway 1 BM B 2-1.75X11.875FS 10.5 Lbyy 2 COL B 1 7-2X6 10 LbyV 3 COL B 2 7-2X6 10 LbVV 4 BM C 1.75X11.875FS 5.5 LbVV 5 COL C 1 2-2X6 10 LbyV 6 COL C 2 2-2X6 10 Lbvy 7 COL F 7-2X6 10 Lbyy 8 BM H 1.75X11.875FS 5 Lbyy 9 COL H 1 3-2X6 10 Lbyy 10 COL H 2 3-2X6 10 Lbvy 11 BM F 2-1.75X11.875FS 11.5 Lbvy 12 COL11 2X6 10 1 Lbyy 13 COL12 2X6 10 1 Lbvy 14 BM I 1.75X14FS 5 Lbyy 15 COL J 1 2X6 5 LbVV 16 COL J 2 2X6 5 LbVV 17 BM J 2X12 5 LbVV 18 COL K 1 2X6 5 LbVV 19 COL K 2 2X6 5 Lbyy 20 BM K 2X12 5 Lbyy Concrete Beam Design Parameters No Data to Print... Concrete Column Design Parameters No Data to Print... Aluminum Design Parameters No Data to Print... Stainless Steel Design Parameters No Data to Print... Member RISA Connection Properties Label Shape Start Conn End Conn Start Release End Release 1 COL G 1 HSS4X4X4 None None Pinned Fixed 2 COL G 2 HSS4X4X4 None None Pinned Fixed 3 BM G W12X72 None None Pinned Pinned 4 COL G 4 HSS4X4X4 None None Pinned Fixed 5 COL G 3 HSS4X4X4 None None Pinned Fixed 6 BM G RIGHT W12X72 None None Pinned Pinned Plate Primary Data No Data to Print... CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 5 Page 62 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Plate Advanced Data No Data to Print... Solid Primary Data No Data to Print... Wall Panel Data No Data to Print... Wall Panel Advanced Data No Data to Print... Diaphragms No Data to Print... Design Size and Code Check Parameters Label Max Axial/Bending Chk Max Shear Chk 1 Typical 1 1 Concrete Rebar Parameters Label O timize Rebar?Min Flex BarMax Flex BarShear BarLe s per Stirru To Column Cover in Bottom Cover in Side Cover in To /Bottom BarsAdd'I Side BarsShear Bar S acin in 1 ica O timize #6 #10 #4 2 1.5 1.5 1.5 2 1 12 Deflection Design Label LC Ratio LC Ratio LC Ratio 1 Typical 1 240 2 360 3 240 Wall Panel U.C.Parameters Label Max Bending Chk Max Shear Chk 1 Typical 1 1 Masonry Wall Panel Parameters Label Block Nom Width Block Grouting Reinforced Wall Area Method 1 Typical 10" Partially Grouted Yes NCMA Masonry Wall Panel In-Plane Parameters Label Vert Bar Size Bars Per Cell Min Bound Zone Width in Max Bound Zone Width[inj Horz Bar Size Transfer Load 1 Typical #5 1 8 40 #5 Masonry Wall Panel Out-of-Plane Parameters Label Bar Size Bar Space Min Bar Space Max Bar Placement Cover in Mortar Type Cement Type Transfer Load 1 Typical 1 #5 1 8" 72" Center Min Type M or S Portland Lime/Mortar Masonry Wall Panel Lintel Parameters Label Depth rinj Bear Length rinj Bar Size Min#Bars Per Layer Max#Bars Per Layer Num of Layers c/c S of La ers in Dist To Pot in StirrupSize Analysis Method 1 T ical 16 8 #5 1 3 1 N/A 3.5 94 1 Simply Supported Wood Wall Panel Parameters Label Top Plate Sill Plate Studs Min Stud Space in Max Stud Space[inj Green Lumber? Header Size Header Matl 1 Typical 2-2X6 2X6 I 2X6 16 16 1 6x8 Same as Wall CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 6 Page 63 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Additional Wood Wall Panel Parameters Label Schedule Min Panel Thick in Max Panel Thick in Double Sided Panel?Max.Nail S acin Min.Nail S acin HD Chords HD Chord Matl Hold Down Chord StrapEccentrici 1 Typical AWC 2015 OSB 0.375 0.75 O timum 6-in. 2-in. 2-2X6 Same as Wall SIMPSON HOIdDownS SIMPSON Chord Straps Concrete Wall Panel Rebar Parameters Label Vert Bar Size Max Vert Bar Space in Min Vert Bar Space in Vert Bar Inc in Horz Bar Size Max Harz Bar Space in Min Horz Bar Space in Horz Bar Inc in Grou Wall 1 Typical #6 18 4 2 #4 18 4 2 Concrete Wall Panel Cover Parameters Label Outer Bars Location Int Cover-z in Ext Cover+z[inj Edge Cover[inj Transfer In Transfer Out 1 T ical Vertical Each Face 1 1 1 2 Frame/HR Seismic Design Rule Label Frame Type Column Ductility Column Overstren th Beam Ductility Connection Beam Overstren thZ Factor Hinge Location in Brace Ductility Brace Overstren th KL/r 1 OCBF Other High Yes Minimal Other/None N/A N/A Minimal 2 SCBF Other High Yes Minimal Other/None Yes N/A N/A Minimal Yes 3 OMF Other High Yes Minimal BUEEP 12 N/A 4 IMF Other High Yes Minimal BFP 12 N/A 5 SMF-RBS Other High Yes Minimal RBS 0.685 14.625 N/A 6 SMF-Kaiser Other High Yes Minimal KBB-B 12 N/A Concrete Wall Seismic Design Rule No Data to Print... Masonry Wall Seismic Design Rule No Data to Print... Connection Design Rules Label Conn Type Type Beam Conn Col/Girder Conn Eccentricit 1 Col/Bm Single Angle Shear Shear Column/Beam Clip Single Angle Shear Bolted Bolted 1.5 2 Col/Bm Double Angle Shear Shear Column/Beam Clip Double Angle Shear Bolted Bolted 0 3 Col/Bm Two Side Clip Angle Shear Shear Column/Beam Clip Double Angle Both Side Shear Bolted Bolted N/A 4 Col/Bm End Plate Shear Shear Column/Beam End-Plate Shear N/A Bolted N/A 5 Col/Bm Shear Tab Shear Shear Column/Beam Shear Tab Shear Bolted N/A 0 6 Girder/Bm Single Angle Shear Shear Girder/Beam Clip Single Angle Shear Bolted Bolted N/A 7 Girder/Bm Double Angle Shear Shear Girder/Beam Clip Double Angle Shear Bolted Bolted N/A 8 Grd/Bm Two Side Clip Angle Shea Shear Girder/Beam Clip Double Angle Both Side Shear Bolted Bolted N/A 9 Girder/Bm End Plate Shear Shear Girder/Beam End-Plate Shear N/A Bolted N/A 10 Girder/Bm Shear Tab Shear Shear Girder/Beam Shear Tab Shear Bolted N/A N/A 11 Beam Shear Splice Shear Beam Shear Tab Splice Bolted N/A N/A 12 Column Shear Splice Shear Column Shear Tab Splice N/A Bolted N/A 13 Col/Bm Ext.End Plate Moment Moment Column/Beam Extended End-Plate Moment N/A N/A N/A 14 of/Bm PartExt.End Plate Moment Moment Column/Beam Partially Extended End-Plate Moment Tension side N/A N/A N/A 15 Col/Bm Flush End Plate Moment Moment Column/Beam Flush End-Plate Moment N/A N/A N/A 16 Col/Bm Flange Plate Moment Moment Column/Beam Flange Plate Moment Bolted N/A N/A 17 Col/Bm Direct Weld Moment Moment Column/Beam Direct Weld Moment Bolted N/A N/A 18 Col/Bm Seismic Moment Moment Column/Beam Seismic Moment N/A N/A N/A 19 Beam Moment Plate Splice Moment Beam Moment Plate Splice Bolted N/A N/A 20 Column Moment Plate Splice Moment Column Moment Plate Splice N/A Bolted N/A 21 Beam Direct Weld Moment Splice Moment Beam Direct Weld Splice Bolted N/A N/A 22 Col Direct Weld Moment Splice Moment Column Direct Weld Splice N/A Bolted N/A 23 Bm Ext.End Plate Moment Splice Moment Beam Extended End Plate Splice Bolted N/A N/A 24 Col Ext.End Plate Moment Splice Moment Column Extended End Plate Splice N/A Bolted N/A 25 Diagonal Vertical Brace Brace Diagonal Vertical Brace N/A N/A N/A 26 Chevron Vertical Brace Brace Chevron Vertical Brace N/A N/A N/A 27 Seismic Diagonal Brace Brace Diagonal Brace Seismic N/A N/A N/A 28 Seismic Chevron Brace Brace Chevron Brace Seismic N/A N/A N/A 29 Knee Brace Brace Knee Brace N/A N/A N/A 30 Single Column Base Plate Base late Single Column Base late N/A N/A N/A 31 Base Plate with Vertical Brace Base late Brace to Column Base Plate N/A N/A N/A 32 HSS Truss Connection Truss HSS T-Connection N/A N/A N/A CITY APPROVED PLANS Reviewed Jor Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 7 Page 64 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Drift Definitions No Data to Print... Nodal Loads and Enforced Displacements No Data to Print... Member Point Loads(BLC 1:Dead Load) Member Label Direction Magnitude lb,lb-ft Location[(ft, 1 BM F Y -300 %33 2 BM F Y -300 %66 Wall Panel Point Loads No Data to Print... Diaphragm Point Loads No Data to Print... Member Distributed Loads(BLC 1:Dead Load) Member Label Direction Start Magnitude Ib/ft,F,psf,lb-ft/ft End Magnitude Ib/ft,F,psf,lb-ft/ft Start Location[(ft,% End Location[(ft, 1 BM B Y -150.25 -150.25 0 %100 2 BM C Y -150.25 -150.25 0 %100 3 BM H Y -133.75 -133.75 0 %100 4 BM F Y -179.625 -179.625 0 %100 5 BM G Y -172.5 -172.5 0 %100 6 BM I Y -51.25 -51.25 0 %100 7 BM J Y -86.25 -86.25 0 %100 8 BM K Y -106.875 -106.875 0 %100 9 BM G RIGHT Y -172.5 -172.5 0 %100 Member Distributed Loads(BLC 2:Live Load) Member Label Direction Start Magnitude Ib/ft,F,psf,lb-ft/ft End Magnitude Ib/ft,F,psf,lb-ft/ft Start Location[(ft,% End Location[(ft, 1 BM B Y -460 -460 0 %100 2 BM C Y -460 -460 0 %100 3 BM H Y -713.33 -713.33 0 %100 4 BM F Y -361.67 -361.67 0 %100 5 BM G Y -920 -920 0 %100 6 BM I Y -273.33 -273.33 0 %100 7 BM J Y 1 -230 -230 0 %100 8 BM K Y -285 -285 0 %100 9 BM G RIGHT Y -920 -920 0 %100 Wall Panel Distributed Loads No Data to Print... Diaphragm Distributed Loads No Data to Print... Member Area Loads No Data to Print... Plate Surface Loads No Data to Print... Wall Panel Surface Loads No Data to Print... Diaphragm Surface Loads No Data to Print... CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 65 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Basic Load Cases BLC Description Category Point Distributed 1 Dead Load DL 2 9 2 Live Load LL 9 Moving Loads No Data to Print... Moving Load Patterns No Data to Print... Time History Loads No Data to Print... Load Combinations Description Solve P-Delta BLC Factor BLC Factor BLC Factor BLC Factor 1 Deflection 1 Yes Y DL 1 2 Deflection 2 Yes Y LL 1 3 Deflection 3 Yes Y DL 1 LL 1 4 IBC 16-8 Yes Y DL 1 NL 1 5 IBC 16-9 Yes Y DL 1 LL 1 LLS 1 NIL 1 Load Combination Design Description CD Service Hot Rolled Cold Formed Wood Concrete Masonry Aluminum Stainless Connection 1 Deflection 1 Yes Yes Yes Yes Yes Yes Yes Yes Yes 2 Deflection 2 Yes Yes Yes Yes Yes Yes Yes Yes Yes 3 Deflection 3 Yes Yes Yes Yes Yes Yes Yes Yes Yes 4 IBC 16-8 0.9 Yes Yes Yes Yes Yes Yes Yes Yes Yes 5 IBC 16-9 Yes Yes Yes Yes Yes Yes Yes Yes Yes Envelope Node Reactions Node Label X[IbI LC Y[lb] LC Z[lb] LC MX[lb-ft LC MY[lb-ft LC MZ[lb-ft LC 1 N29 max 0 5 0 5 0 5 0 5 0 5 0 5 2 min 0 1 0 1 0 1 0 1 0 1 0 1 3 N5 max 0 5 3203.813 5 0 5 0 5 0 5 0 5 4 min 0 1 788.813 1 0 1 0 1 0 1 0 1 5 N6 max 0 5 3203.812 5 0 5 0 5 0 5 0 5 6 min 0 1 788.813 1 0 1 0 1 0 1 0 1 7 N7 max 0 5 0 5 0 5 0 5 0 5 0 5 8 min 0 1 0 1 0 1 0 1 0 1 0 1 9 N8 max 0 5 0 5 0 5 0 5 0 5 0 5 10 min 0 1 0 1 0 1 0 1 0 1 0 1 11 N9 max 0 5 1678.188 5 0 5 0 5 0 5 0 5 12 min 0 1 413.187 1 0 1 0 1 0 1 0 1 13 N 10 max 0 5 1678.188 5 0 5 0 5 0 5 0 5 14 min 0 1 413.188 1 0 1 0 1 0 1 0 1 15 N 11 max 0 5 0 5 0 5 0 5 0 5 0 5 16 min 0 1 0 1 0 1 0 1 0 1 0 1 17 N 12 max 0 5 0 5 0 5 0 5 0 5 0 5 18 min 0 1 0 1 0 1 0 1 0 1 0 1 19 N 18 max 0 5 3415.446 5 3.056 5 0 5 0 5 0 5 20 min 0 1 1335.844 1 0.582 1 0 1 0 1 0 1 21 N20 max 0 5 0 5 -0.582 4 0 5 0 5 0 5 22 min 0 1 0 1 -3.056 3 0 1 0 1 0 1 23 N21 max 0 5 2117.7 5 0 5 0 5 0 5 0 5 24 min 0 1 334.375 1 0 1 0 1 0 1 0 1 25 N22 max 0 5 2117.7 5 0 5 0 5 0 5 0 5 26 min 0 1 334.375 1 0 1 0 1 0 1 0 1 27 N23 max 0 5 0 5 0 5 0 5 0 5 0 5 28 min 0 1 0 1 0 1 0 1 0 1 0 1 29 N24 max 0 5 0 5 0 5 0 5 0 5 0 5 30 min 0 1 0 1 0 1 0 1 0 1 0 1 31 N27 max 0 5 0 5 0 4 0 5 0 5 0 5 32 min 0 1 0 1 0 3 0 1 0 1 0 1 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 66 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... Model Name : Robert Weed Plywood Interiod Members Envelope Node Reactions(Continued) Node Label X[lb] LC Y[lb] LC Z[lb] LC MX[lb-ft LC MY[lb-ft LC MZ[lb-ft LC 331 N28 I max 0 5 15430.385 5 0 5 0 5 0 5 0 5 34 min 0 1 2848.002 1 0 1 0 1 0 1 0 1 35 N30 max 0 5 15291.562 5 0 5 0 5 0 5 0 5 36 min 0 1 2794.342 1 0 1 0 1 0 1 0 1 37 N31 max 0 5 811.45 5 0 5 0 5 0 5 0 5 38 min 0 1 128.125 1 0 1 0 1 0 1 0 1 39 N32 max 0 5 0 5 0 5 0 5 0 5 0 5 40 min 0 1 0 1 0 1 0 1 0 1 0 1 41 N33 max 0 5 811.45 5 0 5 0 5 0 5 0 5 42 min 0 1 128.125 1 0 1 0 1 0 1 0 1 43 N34 max 0 5 0 5 0 5 0 5 0 5 0 5 44 min 0 1 0 1 0 1 0 1 0 1 0 1 45 N35 max 0 5 790.625 5 0 5 0 5 0 5 0 5 46 min 0 1 215.625 1 0 1 0 1 0 1 0 1 47 N36 max 0 5 0 5 0 5 0 5 0 5 0 5 48 min 0 1 0 1 0 1 0 1 0 1 0 1 49 N37 max 0 5 790.625 5 0 5 0 5 0 5 0 5 50 min 0 1 215.625 1 0 1 0 1 0 1 0 1 51 N38 max 0 5 0 5 0 5 0 5 0 5 0 5 52 min 0 1 0 1 0 1 0 1 0 1 0 1 53 N39 max 0 5 979.687 5 0 5 0 5 0 5 0 5 54 min 0 1 267.187 1 0 1 0 1 0 1 0 1 551 N40 max 0 5 0 5 0 5 0 5 0 5 0 5 56 min 0 1 0 1 0 1 0 1 0 1 0 1 57 N41 max 0 5 979.687 5 0 5 0 5 0 5 0 5 58 min 0 1 267.187 1 0 1 0 1 0 1 0 1 59 N42 max 0 5 0 5 0 5 0 5 0 5 0 5 60 min 0 1 0 1 0 1 0 1 0 1 0 1 61 N43 max 0 5 0 5 0 5 0 5 0 5 0 5 62 min 0 1 0 1 0 1 0 1 0 1 0 1 63 N44 max 0 5 13656.25 5 0 5 0 5 0 5 0 5 64 min 0 1 2156.25 1 0 1 0 1 0 1 0 1 65 N45 max 0 5 13656.25 5 0 5 0 5 0 5 0 5 66 min 0 1 2156.25 1 0 1 0 1 0 1 0 1 67 N46 max 0 5 0 5 0 5 0 5 0 5 0 5 68 min 0 1 0 1 0 1 0 1 0 1 0 1 69 Totals: max 0 5 80612.818 5 0 4 70 min 0 1 15585.313 1 0 2 Envelope Node Reactions-Overstrength or Capacity Limit No Data to Print... Envelope Node Displacements Node Label X in LC Yin LC Z in LC X Rotation[rad] LC Y Rotation[rad] LC Z Rotation[rad] LC 1 N5 max 0 5 0 4 0 5 0 5 0 5 0 5 2 min 0 1 0 3 0 1 0 1 0 1 0 1 3 N6 max 0 5 0 4 0 5 0 5 0 5 0 5 4 min 0 1 0 3 0 1 0 1 0 1 0 1 5 N7 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 6 min 0 1 -0.004 3 0 1 0 1 0 1 0 1 7 N8 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 8 min 0 1 -0.004 3 0 1 0 1 0 1 0 1 9 N9 max 0 5 0 4 0 5 0 5 0 5 0 5 10 min 0 1 0 3 0 1 0 1 0 1 0 1 11 N10 max 0 5 0 4 0 5 0 5 0 5 0 5 12 min 0 1 0 3 0 1 0 1 0 1 0 1 13 N 11 max 0 5 -0.002 4 0 5 0 5 0 5 0 5 14 min 0 1 -0.008 3 0 1 0 1 0 1 0 1 15 N12 max 0 5 -0.002 4 0 5 0 5 0 5 0 5 16 min 0 1 -0.008 3 0 1 0 1 0 1 0 1 17 N18 max 0 5 0 4 0 4 0 5 0 5 0 5 18 min 0 1 0 3 0 3 0 1 0 1 0 1 19 N20 max 0 5 -0.002 4 0 5 1.738e-5 5 0 5 0 5 20 min 0 1 -0.004 3 0 1 3.312e-6 1 0 1 0 1 21 N21 max 0 5 0 4 0 5 0 5 0 5 0 5 22 min 0 1 0 3 0 1 0 1 0 1 0 1 23 N22 max 0 5 0 4 0 5 0 5 0 5 0 5 CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] Fevi—df.,code compliance Page 67 of 97 PLANS F RA`LL IN PEECTIONSITE Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Node Displacements(Continued) Node Label X in LC Yin LC Z in LC X Rotation[rad] LC Y Rotation[rad] LC Z Rotation[rad] LC 241 1 min 0 1 0 3 0 1 0 1 0 1 0 1 25 N23 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 26 min 0 1 -0.006 3 0 1 0 1 0 1 0 1 27 N24 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 28 min 0 1 -0.006 3 0 1 0 1 0 1 0 1 29 N25 max 0 5 -0.173 4 0 5 5.185e-4 5 0 5 0 5 30 min 0 1 -0.884 3 0 1 9.879e-5 1 0 1 0 1 31 N27 max 0 5 -0.004 4 0 5 0 5 0 5 0 5 32 min 0 1 -0.024 3 0 1 0 1 0 1 0 1 33 N28 max 0 5 0 4 0 4 0 5 0 5 0 5 34 min 0 1 0 3 0 3 0 1 0 1 0 1 35 N29 max 0 5 -0.004 4 0 5 0 5 0 5 0 5 36 min 0 1 -0.023 3 0 1 0 1 0 1 0 1 37 N30 max 0 5 0 4 0 4 0 5 0 5 0 5 38 min 0 1 0 3 0 3 0 1 0 1 0 1 39 N31 max 0 5 0 4 0 5 0 5 0 5 0 5 40 min 0 1 0 3 0 1 0 1 0 1 0 1 41 N32 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 42 min 0 1 -0.007 3 0 1 0 1 0 1 0 1 43 N33 max 0 5 0 4 0 5 0 5 0 5 0 5 44 min 0 1 0 3 0 1 0 1 0 1 0 1 45 N34 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 46 min 0 1 -0.007 3 0 1 0 1 0 1 0 1 47 N35 max 0 5 0 4 0 5 0 5 0 5 0 5 48 min 0 1 0 3 0 1 0 1 0 1 0 1 49 N36 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 50 min 0 1 -0.004 3 0 1 0 1 0 1 0 1 51 N37 max 0 5 0 4 0 5 0 5 0 5 0 5 52 min 0 1 0 3 0 1 0 1 0 1 0 1 53 N38 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 54 min 0 1 -0.004 3 0 1 0 1 0 1 0 1 55 N39 max 0 5 0 4 0 5 0 5 0 5 0 5 56 min 0 1 0 3 0 1 0 1 0 1 0 1 57 N40 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 58 min 0 1 -0.004 3 0 1 0 1 0 1 0 1 59 N41 max 0 5 0 4 0 5 0 5 0 5 0 5 60 min 0 1 0 3 0 1 0 1 0 1 0 1 61 N42 max 0 5 -0.001 4 0 5 0 5 0 5 0 5 62 min 0 1 -0.004 3 0 1 0 1 0 1 0 1 63 N43 max 0 5 -0.003 4 0 5 0 5 0 5 0 5 64 min 0 1 -0.021 3 0 1 0 1 0 1 0 1 65 N44 max 0 5 0 4 0 5 0 5 0 5 0 5 66 min 0 1 0 3 0 1 0 1 0 1 0 1 67 N45 max 0 5 0 4 0 5 0 5 0 5 0 5 68 min 0 1 0 3 0 1 0 1 0 1 0 1 69 N46 max 0 5 -0.003 4 0 5 0 5 0 5 0 5 70 min 0 1 -0.021 3 0 1 0 1 0 1 0 1 Envelope Member Section Forces Member Sec Axial[lb] LC y Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 1 BM B 1 max 0 5 3203.813 5 0 5 0 5 0 5 0 5 2 min 0 1 788.813 1 0 1 0 1 0 1 0 1 3 2 max 0 5 1601.906 5 0 5 0 5 0 5 -1552.975 4 4 min 0 1 394.406 1 0 1 0 1 0 1 -6307.506 3 5 3 max 0 5 0 5 0 5 0 5 0 5 -2070.633 4 6 min 0 1 0 1 0 1 0 1 0 1 -8410.008 3 7 4 max 0 5 -394.406 4 0 5 0 5 0 5 -1552.975 4 8 min 0 1 -1601.906 3 0 1 0 1 0 1 -6307.506 3 9 5 max 0 5 -788.813 4 0 5 0 5 0 5 0 5 10 min 0 1 -3203.812 3 0 1 0 1 0 1 0 1 11 COL B 1 1 max 3203.813 5 0 5 0 5 0 5 0 5 0 5 12 min 788.813 1 0 1 0 1 0 1 0 1 0 1 13 2 max 3203.813 5 0 5 0 5 0 5 0 5 0 5 14 min 788.813 1 0 1 0 1 0 1 0 1 0 1 15 3 max 3203.813 5 0 5 0 5 0 5 0 5 0 5 16 min 788.813 1 0 1 0 1 0 1 0 1 0 1 17 4 max 3203.813 5 0 5 0 5 0 5 0 5 0 5 18 min 788.813 1 0 1 0 1 0 1 0 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 68 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Forces(Continued) Member Sec Axial[lb] LC y Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 19 5 max 3203.813 5 0 5 0 5 0 5 0 5 0 5 20 min 788.813 1 0 1 0 1 0 1 0 1 0 1 21 COL B 2 1 max 3203.812 5 0 5 0 5 0 5 0 5 0 5 22 min 788.813 1 0 1 0 1 0 1 0 1 0 1 23 2 max 3203.812 5 0 5 0 5 0 5 0 5 0 5 24 min 788.813 1 0 1 0 1 0 1 0 1 0 1 25 3 max 3203.812 5 0 5 0 5 0 5 0 5 0 5 26 min 788.813 1 0 1 0 1 0 1 0 1 0 1 27 4 max 3203.812 5 0 5 0 5 0 5 0 5 0 5 28 min 788.813 1 0 1 0 1 0 1 0 1 0 1 29 5 max 3203.812 5 0 5 0 5 0 5 0 5 0 5 30 min 788.813 1 0 1 0 1 0 1 0 1 0 1 31 BM C 1 max 0 5 1678.188 5 0 5 0 5 0 5 0 5 32 min 0 1 413.187 1 0 1 0 1 0 1 0 1 33 2 max 0 5 839.094 5 0 5 0 5 0 5 -426.1 4 34 min 0 1 206.594 1 0 1 0 1 0 1 -1730.631 3 35 3 max 0 5 0 5 0 5 0 5 0 5 -568.133 4 36 min 0 1 0 1 0 1 0 1 0 1 -2307.508 3 37 4 max 0 5 -206.594 4 0 5 0 5 0 5 -426.1 4 38 min 0 1 -839.094 3 0 1 0 1 0 1 -1730.631 3 39 5 max 0 5 -413.188 4 0 5 0 5 0 5 0 5 40 min 0 1 -1678.188 3 0 1 0 1 0 1 0 1 41 COL C 1 1 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 42 min 413.187 1 0 1 0 1 0 1 0 1 0 1 43 2 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 44 min 413.187 1 0 1 0 1 0 1 0 1 0 1 45 3 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 46 min 413.187 1 0 1 0 1 0 1 0 1 0 1 47 4 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 48 min 413.187 1 0 1 0 1 0 1 0 1 0 1 49 5 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 50 min 413.187 1 0 1 0 1 0 1 0 1 0 1 51 COL C 2 1 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 52 min 413.188 1 0 1 0 1 0 1 0 1 0 1 53 2 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 54 min 413.188 1 0 1 0 1 0 1 0 1 0 1 55 3 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 56 min 413.188 1 0 1 0 1 0 1 0 1 0 1 57 4 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 58 min 413.188 1 0 1 0 1 0 1 0 1 0 1 59 5 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 60 min 413.188 1 0 1 0 1 0 1 0 1 0 1 61 COL F 1 max 3415.446 5 0 5 3.056 5 0 5 0 5 0 5 62 min 1335.844 1 0 1 0.582 1 0 1 0 1 0 1 63 2 max 3415.446 5 0 5 3.056 5 0 5 7.641 5 0 5 64 min 1335.844 1 0 1 0.582 1 0 1 1.456 1 0 1 65 3 max 3415.446 5 0 5 3.056 5 0 5 15.282 5 0 5 66 min 1335.844 1 0 1 0.582 1 0 1 2.912 1 0 1 67 4 max 3415.446 5 0 5 3.056 5 0 5 22.922 5 0 5 68 min 1335.844 1 0 1 0.582 1 0 1 4.368 1 0 1 69 5 max 3415.446 5 0 5 3.056 5 0 5 30.563 5 0 5 70 min 1335.844 1 0 1 0.582 1 0 1 5.824 1 0 1 71 BM H 1 max 0 5 2117.7 5 0 5 0 5 0 5 0 5 72 min 0 1 334.375 1 0 1 0 1 0 1 0 1 73 2 max 0 5 1058.85 5 0 5 0 5 0 5 -313.477 4 74 min 0 1 167.187 1 0 1 0 1 0 1 -1985.344 3 75 3 max 0 5 0 5 0 5 0 5 0 5 -417.969 4 76 min 0 1 0 1 0 1 0 1 0 1 -2647.125 3 77 4 max 0 5 -167.187 4 0 5 0 5 0 5 -313.477 4 78 min 0 1 -1058.85 3 0 1 0 1 0 1 -1985.344 3 79 5 max 0 5 -334.375 4 0 5 0 5 0 5 0 5 80 min 0 1 -2117.7 3 0 1 0 1 0 1 0 1 81 COL H 1 1 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 82 min 334.375 1 0 1 0 1 0 1 0 1 0 1 83 2 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 84 min 334.375 1 0 1 0 1 0 1 0 1 0 1 85 3 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 86 min 334.375 1 0 1 0 1 0 1 0 1 0 1 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 69 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Forces(Continued) Member Sec Axial[lb] LC y Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 87 4 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 88 min 334.375 1 0 1 0 1 0 1 0 1 0 1 89 5 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 90 min 334.375 1 0 1 0 1 0 1 0 1 0 1 91 COL H 2 1 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 92 min 334.375 1 0 1 0 1 0 1 0 1 0 1 93 2 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 94 min 334.375 1 0 1 0 1 0 1 0 1 0 1 95 3 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 96 min 334.375 1 0 1 0 1 0 1 0 1 0 1 97 4 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 98 min 334.375 1 0 1 0 1 0 1 0 1 0 1 99 5 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 100 min 334.375 1 0 1 0 1 0 1 0 1 0 1 101 BM F 1 max 0 5 3415.446 5 0 5 -5.824 4 0 5 0 5 102 min 0 1 1335.844 1 0 1 -30.563 3 0 1 0 1 103 2 max 0 5 1859.223 5 0 5 -5.824 4 0 5 -3098.194 4 104 min 0 1 819.422 1 0 1 -30.563 3 0 1 -7582.337 3 105 3 max 0 5 3 4 0 5 -5.824 4 0 5 -4125.176 4 106 min 0 1 0 2 0 1 -30.563 3 0 1 -10104.033 3 107 4 max 0 5 -813.422 4 0 5 -5.824 4 0 5 -3080.944 4 108 min 0 1 -1853.223 3 0 1 -30.563 3 0 1 -7565.087 3 109 5 max 0 5 -1329.844 4 0 5 -5.824 4 0 5 0 5 110 min 0 1 -3409.446 3 0 1 -30.563 3 0 1 0 1 111 COL G 1 1 max 15430.385 5 0 5 0 5 0 5 0 5 0 5 112 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 113 2 max 15430.385 5 0 5 0 5 0 5 0 5 0 5 114 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 115 3 max 15430.385 5 0 5 0 5 0 5 0 5 0 5 116 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 117 4 max 15430.385 5 0 5 0 5 0 5 0 5 0 5 118 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 119 5 max 15430.385 5 0 5 0 5 0 5 0 5 0 5 120 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 121 COL G 2 1 max 15291.562 5 0 5 0 5 0 5 0 5 0 5 122 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 123 2 max 15291.562 5 0 5 0 5 0 5 0 5 0 5 124 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 125 3 max 15291.562 5 0 5 0 5 0 5 0 5 0 5 126 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 127 4 max 15291.562 5 0 5 0 5 0 5 0 5 0 5 128 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 129 5 max 15291.562 5 0 5 0 5 0 5 0 5 0 5 130 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 131 BM G 1 max 0 5 15291.562 5 0 5 0 5 0 5 0 5 132 min 0 1 2794.342 1 0 1 0 1 0 1 0 1 133 2 max 0 5 8463.437 5 0 5 0 5 0 5 -14095.291 4 134 min 0 1 1716.217 1 0 1 0 1 0 1 -74233.066 3 135 3 max 0 5 1635.312 5 0 5 0 5 0 5 -21452.376 4 136 min 0 1 638.092 1 0 1 0 1 0 1 -105790.825 3 137 4 max 0 5 -1769.877 4 0 5 0 5 0 5 -14430.87 4 138 min 0 1 -8602.26 3 0 1 0 1 0 1 -75102.013 3 139 5 max 0 5 -2848.002 4 0 5 0 5 0 5 0 5 140 min 0 1 -15430.385 3 0 1 0 1 0 1 0 1 141 COL 11 1 max 811.45 5 0 5 0 5 0 5 0 5 0 5 142 min 128.125 1 0 1 0 1 0 1 0 1 0 1 143 2 max 811.45 5 0 5 0 5 0 5 0 5 0 5 144 min 128.125 1 0 1 0 1 0 1 0 1 0 1 145 3 max 811.45 5 0 5 0 5 0 5 0 5 0 5 146 min 128.125 1 0 1 0 1 0 1 0 1 0 1 147 4 max 811.45 5 0 5 0 5 0 5 0 5 0 5 148 min 128.125 1 0 1 0 1 0 1 0 1 0 1 149 5 max 811.45 5 0 5 0 5 0 5 0 5 0 5 150 min 128.125 1 0 1 0 1 0 1 0 1 0 1 151 COL 12 1 max 811.45 5 0 5 0 5 0 5 0 5 0 5 152 min 128.125 1 0 1 0 1 0 1 0 1 0 1 1 531 2 max 811.45 5 0 5 0 5 0 5 0 5 0 5 1541 min 128.125 1 0 1 0 1 0 1 0 1 0 1 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 70 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Forces(Continued) Member Sec Axial[lb] LC y Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 155 3 max 811.45 5 0 5 0 5 0 5 0 5 0 5 156 min 128.125 1 0 1 0 1 0 1 0 1 0 1 157 4 max 811.45 5 0 5 0 5 0 5 0 5 0 5 158 min 128.125 1 0 1 0 1 0 1 0 1 0 1 159 5 max 811.45 5 0 5 0 5 0 5 0 5 0 5 160 min 128.125 1 0 1 0 1 0 1 0 1 0 1 161 BM I 1 max 0 5 811.45 5 0 5 0 5 0 5 0 5 162 min 0 1 128.125 1 0 1 0 1 0 1 0 1 163 2 max 0 5 405.725 5 0 5 0 5 0 5 -120.117 4 164 min 0 1 64.063 1 0 1 0 1 0 1 -760.734 3 165 3 max 0 5 0 5 0 5 0 5 0 5 -160.156 4 166 min 0 1 0 1 0 1 0 1 0 1 -1014.312 3 167 4 max 0 5 -64.063 4 0 5 0 5 0 5 -120.117 4 168 min 0 1 -405.725 3 0 1 0 1 0 1 -760.734 3 169 5 max 0 5 -128.125 4 0 5 0 5 0 5 0 5 170 min 0 1 -811.45 3 0 1 0 1 0 1 0 1 171 COL J 1 1 max 790.625 5 0 5 0 5 0 5 0 5 0 5 172 min 215.625 1 0 1 0 1 0 1 0 1 0 1 173 2 max 790.625 5 0 5 0 5 0 5 0 5 0 5 174 min 215.625 1 0 1 0 1 0 1 0 1 0 1 175 3 max 790.625 5 0 5 0 5 0 5 0 5 0 5 176 min 215.625 1 0 1 0 1 0 1 0 1 0 1 177 4 max 790.625 5 0 5 0 5 0 5 0 5 0 5 178 min 215.625 1 0 1 0 1 0 1 0 1 0 1 179 5 max 790.625 5 0 5 0 5 0 5 0 5 0 5 180 min 215.625 1 0 1 0 1 0 1 0 1 0 1 181 COL J 2 1 max 790.625 5 0 5 0 5 0 5 0 5 0 5 182 min 215.625 1 0 1 0 1 0 1 0 1 0 1 183 2 max 790.625 5 0 5 0 5 0 5 0 5 0 5 184 min 215.625 1 0 1 0 1 0 1 0 1 0 1 185 3 max 790.625 5 0 5 0 5 0 5 0 5 0 5 186 min 215.625 1 0 1 0 1 0 1 0 1 0 1 187 4 max 790.625 5 0 5 0 5 0 5 0 5 0 5 188 min 215.625 1 0 1 0 1 0 1 0 1 0 1 189 5 max 790.625 5 0 5 0 5 0 5 0 5 0 5 190 min 215.625 1 0 1 0 1 0 1 0 1 0 1 191 BM J 1 max 0 5 790.625 5 0 5 0 5 0 5 0 5 192 min 0 1 215.625 1 0 1 0 1 0 1 0 1 193 2 max 0 5 395.312 5 0 5 0 5 0 5 -202.148 4 194 min 0 1 107.812 1 0 1 0 1 0 1 -741.211 3 195 3 max 0 5 0 5 0 5 0 5 0 5 -269.531 4 196 min 0 1 0 1 0 1 0 1 0 1 -988.281 3 197 4 max 0 5 -107.813 4 0 5 0 5 0 5 -202.148 4 198 min 0 1 -395.312 3 0 1 0 1 0 1 -741.211 3 199 5 max 0 5 -215.625 4 0 5 0 5 0 5 0 5 200 min 0 1 -790.625 3 0 1 0 1 0 1 0 1 201 COL K 1 1 max 979.687 5 0 5 0 5 0 5 0 5 0 5 202 min 267.187 1 0 1 0 1 0 1 0 1 0 1 203 2 max 979.687 5 0 5 0 5 0 5 0 5 0 5 204 min 267.187 1 0 1 0 1 0 1 0 1 0 1 205 3 max 979.687 5 0 5 0 5 0 5 0 5 0 5 206 min 267.187 1 0 1 0 1 0 1 0 1 0 1 207 4 max 979.687 5 0 5 0 5 0 5 0 5 0 5 208 min 267.187 1 0 1 0 1 0 1 0 1 0 1 209 5 max 979.687 5 0 5 0 5 0 5 0 5 0 5 210 min 267.187 1 0 1 0 1 0 1 0 1 0 1 211 COL K 2 1 max 979.687 5 0 5 0 5 0 5 0 5 0 5 212 min 267.187 1 0 1 0 1 0 1 0 1 0 1 213 2 max 979.687 5 0 5 0 5 0 5 0 5 0 5 214 min 267.187 1 0 1 0 1 0 1 0 1 0 1 215 3 max 979.687 5 0 5 0 5 0 5 0 5 0 5 216 min 267.187 1 0 1 0 1 0 1 0 1 0 1 217 4 max 979.687 5 0 5 0 5 0 5 0 5 0 5 218 min 267.187 1 0 1 0 1 0 1 0 1 0 1 219 5 max 979.687 5 0 5 0 5 0 5 0 5 0 5 220 min 267.187 1 0 1 0 1 0 1 0 1 0 1 221 BM K 1 max 0 5 979.688 5 0 5 0 5 0 5 0 5 222 min 0 1 267.187 1 0 1 0 1 0 1 0 1 CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] R-i-edf-Code C-pli-ce Page 71 of 97 PL FOR ALL INSPECTIONS SITE Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Forces(Continued) Member Sec Axial[lb] LC y Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 223 2 max 0 5 489.844 5 0 5 0 5 0 5 -250.488 4 224 min 0 1 133.594 1 0 1 0 1 0 1 -918.457 3 225 3 max 0 5 0 5 0 5 0 5 0 5 -333.984 4 226 min 0 1 0 1 0 1 0 1 0 1 -1224.609 3 227 4 max 0 5 -133.594 4 0 5 0 5 0 5 -250.488 4 228 min 0 1 -489.844 3 0 1 0 1 0 1 -918.457 3 229 5 max 0 5 -267.187 4 0 5 0 5 0 5 0 5 230 min 0 1 -979.688 3 0 1 0 1 0 1 0 1 231 COL G 4 1 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 232 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 233 2 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 234 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 235 3 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 236 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 237 4 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 238 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 239 5 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 240 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 241 COL G 3 1 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 242 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 243 2 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 244 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 245 3 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 246 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 247 4 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 248 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 249 5 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 250 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 251 BM G RIGHT 1 max 0 5 13656.25 5 0 5 0 5 0 5 0 5 252 min 0 1 2156.25 1 0 1 0 1 0 1 0 1 253 2 max 0 5 6828.125 5 0 5 0 5 0 5 -10107.422 4 254 min 0 1 1078.125 1 0 1 0 1 0 1 -64013.672 3 255 3 max 0 5 0 5 0 5 0 5 0 5 -13476.563 4 256 min 0 1 0 1 0 1 0 1 0 1 -85351.563 3 257 4 max 0 5 -1078.125 4 0 5 0 5 0 5 -10107.422 4 258 min 0 1 -6828.125 3 0 1 0 1 0 1 -64013.672 3 259 5 max 0 5 -2156.25 4 0 5 0 5 0 5 0 5 260 min 0 1 -13656.25 3 0 1 0 1 0 1 0 1 Envelope Maximum Member Section Forces Member Axial Ib Loc[ftl LC v ShearflblLoc[ftl LC z Shear l bl Loc[ftl LC Tor ue Ib-ft Loc ft LC v-v Moment Ib-ft Loc ft LC z-z Moment Ib-ft Loc ft LC 1 1 BM B max 0 10.5 5 3203.813 0 5 0 10.5 5 0 10.5 5 0 10.5 5 0 10.5 5 2 min 0 0 1 -3203.812 10.5 3 0 0 1 0 0 1 0 0 1 -8410.008 5.25 3 3 COL B 1 max 3203.813 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 4 min 788.813 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 5 COL B 2 max 3203.812 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 6 min 788.813 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 7 BM C max 0 5.5 5 1678.188 0 5 0 5.5 5 0 5.5 5 0 5.5 5 0 5.5 5 8 min 0 0 1 -1678.188 5.5 3 0 0 1 0 0 1 0 0 1 -2307.508 2.75 3 9 COL C 1 max 1678.188 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 10 min 413.187 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 11 COL C 2 max 1678.188 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 12 min 413.188 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 13 COL F max 3415.446 10 5 0 10 5 3.056 10 5 0 10 5 30.563 10 5 0 10 5 14 min 1335.844 0 1 0 0 1 0.582 0 1 0 0 1 0 0 1 0 0 1 15 BM H max 0 5 5 2117.7 0 5 0 5 5 0 5 5 0 5 5 0 5 5 16 min 0 0 1 -2117.7 5 3 0 0 1 0 0 1 0 0 1 -2647.125 2.5 3 17 COL H 1 -nax 2117.7 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 18 min 334.375 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 19 COL H 2 iiax 2117.7 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 20 min 334.375 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 21 BM F iiax 0 11.5 5 3415.446 0 5 0 11.5 5 -5.824 11.5 4 0 11.5 5 0 11.5 5 22 min 0 0 1 -3409.446 11.5 3 0 0 1 -30.563 0 3 0 0 1 -10104.033 5.75 3 23 COL G 1 ma 15430.385 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 24 min 2848.002 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 25 COL G 2 ma 15291.562 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 26 min 2794.342 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 27 BM G ma 0 25 5 15291.562 0 5 0 25 5 0 25 5 0 25 5 0 25 5 CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] Reviewedfor Code Compliance Page 72 of 97 PL FOR ALL INSPECTIONS SITE Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Maximum Member Section Forces(Continued) Member Axial Ib Loc[ftl LC v ShearflblLocrftl LC z Shear l bl Loc[ftl LC Tor ue Ib-ft Loc ft LC v-v Moment Ib-ft Loc ft LC z-z Moment Ib-ft Loc ft LC 281 min 0 0 1 -15430-385 25 3 0 0 1 0 0 1 0 0 1 -106454.851 13.021 3 29 COL 1 1 max 811.45 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 30 min 128.125 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 31 COL 12 max 811.45 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 32 min 128.125 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 33 BM I max 0 5 5 811.45 0 5 0 5 5 0 5 5 0 5 5 0 5 5 34 min 0 0 1 -811.45 5 3 0 0 1 0 0 1 0 0 1 -1014.312 2.5 3 35 COL J 1 max 790.625 5 5 0 5 5 0 5 5 0 5 5 0 5 5 0 5 5 36 min 215.625 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 37 COL J 2 max 790.625 5 5 0 5 5 0 5 5 0 5 5 0 5 5 0 5 5 38 min 215.625 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 39 BM J max 0 5 5 790.625 0 5 0 5 5 0 5 5 0 5 5 0 5 5 40 min 0 0 1 -790.625 5 3 0 0 1 0 0 1 0 0 1 -988.281 2.5 3 41 COL K 1 max 979.687 5 5 0 5 5 0 5 5 0 5 5 0 5 5 0 5 5 42 min 267.187 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 43 COL K 2 max 979.687 5 5 0 5 5 0 5 5 0 5 5 0 5 5 0 5 5 44 min 267.187 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 45 BM K max 0 5 5 979.688 0 5 0 5 5 0 5 5 0 5 5 0 5 5 46 min 0 0 1 -979.688 5 3 0 0 1 0 0 1 0 0 1 -1224.609 2.5 3 47 COL G 4 max 13656.25 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 48 min 2156.25 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 49 COL G 3 maA 13656.25 10 5 0 10 5 0 10 5 0 10 5 0 10 5 0 10 5 50 minl 2156.25 1 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 51 BM G RIGHTma 0 25 5 13656.25 0 5 0 25 5 0 25 5 0 1 25 1 5 1 L 0 25 5 �521 mini 3656.25 25 1 3 1 0 0 1 0 0 1 0 0 1 1 -85351.563 12.5 3 Envelope Member End Reactions Member Member End Axialflbl LC v Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 1 BM B I max 0 5 3203.813 5 0 5 0 5 0 5 0 5 2 min 0 1 788.813 1 0 1 0 1 0 1 0 1 3 J max 0 5 -788.813 4 0 5 0 5 0 5 0 5 4 min 0 1 -3203.812 3 0 1 0 1 0 1 0 1 5 COL B 1 1 max 3203.813 5 0 5 0 5 0 5 0 5 0 5 6 min 788.813 1 0 1 0 1 0 1 0 1 0 1 7 J max 3203.813 5 0 5 0 5 0 5 0 5 0 5 8 min 788.813 1 0 1 0 1 0 1 0 1 0 1 9 COL B 2 1 max 3203.812 5 0 5 0 5 0 5 0 5 0 5 10 min 788.813 1 0 1 0 1 0 1 0 1 0 1 11 J max 3203.812 5 0 5 0 5 0 5 0 5 0 5 12 min 788.813 1 0 1 0 1 0 1 0 1 0 1 13 BM C I max 0 5 1678.188 5 0 5 0 5 0 5 0 5 14 min 0 1 413.187 1 0 1 0 1 0 1 0 1 15 J max 0 5 -413.188 4 0 5 0 5 0 5 0 5 16 min 0 1 -1678.188 3 0 1 0 1 0 1 0 1 17 COL C 1 1 max 1678.188 5 0 5 0 5 0 5 0 5 0 5 18 min 413.187 1 0 1 0 1 0 1 0 1 0 1 19 J max 1678.188 5 0 5 0 5 0 5 0 5 0 5 20 min 413.187 1 0 1 0 1 0 1 0 1 0 1 21 COL C 2 I max 1678.188 5 0 5 0 5 0 5 0 5 0 5 22 min 413.188 1 0 1 0 1 0 1 0 1 0 1 23 J max 1678.188 5 0 5 0 5 0 5 0 5 0 5 24 min 413.188 1 0 1 0 1 0 1 0 1 0 1 25 COL F I max 3415.446 5 0 5 3.056 5 0 5 0 5 0 5 26 min 1335.844 1 0 1 0.582 1 0 1 0 1 0 1 27 J max 3415.446 5 0 5 3.056 5 0 5 30.563 5 0 5 28 min 1335.844 1 0 1 0.582 1 0 1 5.824 1 0 1 29 BM H I max 0 5 2117.7 5 0 5 0 5 0 5 0 5 30 min 0 1 334.375 1 0 1 0 1 0 1 0 1 31 J max 0 5 -334.375 4 0 5 0 5 0 5 0 5 32 min 0 1 -2117.7 3 0 1 0 1 0 1 0 1 33 COL H 1 1 max 2117.7 5 0 5 0 5 0 5 0 5 0 5 34 min 334.375 1 0 1 0 1 0 1 0 1 0 1 35 J max 2117.7 5 0 5 0 5 0 5 0 5 0 5 36 min 334.375 1 0 1 0 1 0 1 0 1 0 1 37 COL H 2 1 max 2117.7 5 0 5 0 5 0 5 0 38 min 334.3751 0 1 0 1 0 1 0 CITY APPROVED PLANS 39 J max 2117.7117.7 5 0 5 0 5 0 5 0 40 min 334.375 1 0 1 0 1 0 1 0 Reviewed for Code Compliance PLANS MUST BE ON JOB SITE RISA-3D Version 20 [MEMBER MODEL.r3d] FOR ALL INSPECTIONS Page 73 of 5r Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... Model Name : Robert Weed Plywood Interiod Members Envelope Member End Reactions(Continued) Member Member End Axial[lb] LC y Shear[lb] LC z Shear[lb] LC Tor ue Ib-ft LC Moment Ib-ft LC z-z Moment Ib-ft LC 41 BM F I max 0 5 3415.446 5 0 5 -5.824 4 0 5 0 5 42 min 0 1 1335.844 1 0 1 -30.563 3 0 1 0 1 43 J max 0 5 -1329.844 4 0 5 -5.824 4 0 5 0 5 44 min 0 1 -3409.446 3 0 1 -30.563 3 0 1 0 1 45 COL G 1 I max 15430.385 5 0 5 0 5 0 5 0 5 0 5 46 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 47 J max 15430.385 5 0 5 0 5 0 5 0 5 0 5 48 min 2848.002 1 0 1 0 1 0 1 0 1 0 1 49 COL G 2 1 max 15291.562 5 0 5 0 5 0 5 0 5 0 5 50 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 51 J max 15291.562 5 0 5 0 5 0 5 0 5 0 5 52 min 2794.342 1 0 1 0 1 0 1 0 1 0 1 53 BM G I max 0 5 15291.562 5 0 5 0 5 0 5 0 5 54 min 0 1 2794.342 1 0 1 0 1 0 1 0 1 55 J max 0 5 -2848.002 4 0 5 0 5 0 5 0 5 56 min 0 1 -15430.385 3 0 1 0 1 0 1 0 1 57 COL 11 1 max 811.45 5 0 5 0 5 0 5 0 5 0 5 58 min 128.125 1 0 1 0 1 0 1 0 1 0 1 59 J max 811.45 5 0 5 0 5 0 5 0 5 0 5 60 min 128.125 1 0 1 0 1 0 1 0 1 0 1 61 COL 12 1 max 811.45 5 0 5 0 5 0 5 0 5 0 5 62 min 128.125 1 0 1 0 1 0 1 0 1 0 1 63 J max 811.45 5 0 5 0 5 0 5 0 5 0 5 64 min 128.125 1 0 1 0 1 0 1 0 1 0 1 65 BM I I max 0 5 811.45 5 0 5 0 5 0 5 0 5 66 min 0 1 128.125 1 0 1 0 1 0 1 0 1 67 J max 0 5 -128.125 4 0 5 0 5 0 5 0 5 68 min 0 1 -811.45 3 0 1 0 1 0 1 0 1 69 COL J 1 1 max 790.625 5 0 5 0 5 0 5 0 5 0 5 70 min 215.625 1 0 1 0 1 0 1 0 1 0 1 71 J max 790.625 5 0 5 0 5 0 5 0 5 0 5 72 min 215.625 1 0 1 0 1 0 1 0 1 0 1 73 COL J 2 1 max 790.625 5 0 5 0 5 0 5 0 5 0 5 74 min 215.625 1 0 1 0 1 0 1 0 1 0 1 75 J max 790.625 5 0 5 0 5 0 5 0 5 0 5 76 min 215.625 1 0 1 0 1 0 1 0 1 0 1 77 BM J I max 0 5 790.625 5 0 5 0 5 0 5 0 5 78 min 0 1 215.625 1 0 1 0 1 0 1 0 1 79 J max 0 5 -215.625 4 0 5 0 5 0 5 0 5 80 min 0 1 -790.625 3 0 1 0 1 0 1 0 1 81 COL K 1 1 max 979.687 5 0 5 0 5 0 5 0 5 0 5 82 min 267.187 1 0 1 0 1 0 1 0 1 0 1 83 J max 979.687 5 0 5 0 5 0 5 0 5 0 5 84 min 267.187 1 0 1 0 1 0 1 0 1 0 1 85 COL K 2 1 max 979.687 5 0 5 0 5 0 5 0 5 0 5 86 min 267.187 1 0 1 0 1 0 1 0 1 0 1 87 J max 979.687 5 0 5 0 5 0 5 0 5 0 5 88 min 267.187 1 0 1 0 1 0 1 0 1 0 1 89 BM K I max 0 5 979.688 5 0 5 0 5 0 5 0 5 90 min 0 1 267.187 1 0 1 0 1 0 1 0 1 91 J max 0 5 -267.187 4 0 5 0 5 0 5 0 5 92 min 0 1 -979.688 3 0 1 0 1 0 1 0 1 93 COL G 4 I max 13656.25 5 0 5 0 5 0 5 0 5 0 5 94 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 95 J max 13656.25 5 0 5 0 5 0 5 0 5 0 5 96 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 97 COL G 3 1 max 13656.25 5 0 5 0 5 0 5 0 5 0 5 98 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 99 J max 13656.25 5 0 5 0 5 0 5 0 5 0 5 100 min 2156.25 1 0 1 0 1 0 1 0 1 0 1 11011,13M G RIGHT I max 0 5 113656.251 5 0 5 0 5 0 5 0 5 1021 min 0 1 2156.25 1 0 1 0 1 0 1 0 1 1031 J max 0 5 -2156.25 4 0 5 0 5 0 5 0 5 1041 min 0 1 -13656.25 3 0 1 0 1 0 1 0 1 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 17 Page 74 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member 2nd/1st Moment Ratios Member Moment[lb-ft 2nd/1st Ratio Loc ft LC z-z Moment[lb-ft 2nd/1st Ratio Loc ft LC 1 BM B max NC NC -6339.375 1 5.25 2 2 min NC NC -2070.633 1 5.25 1 3 COL B 1 max NC NC NC NC 4 min NC NC NC NC 5 COL B 2 max NC NC NC NC 6 min NC NC NC NC 7 BM C max NC NC -568.133 1 2.75 4 8 min NC NC -2307.508 1 2.75 3 9 COL C 1 max NC NC NC NC 10 min NC NC NC NC 11 COL C 2 max NC NC NC NC 12 min NC NC NC NC 13 COL F max 30.563 1 10 5 NC NC 14 min 5.824 1 10 1 NC NC 15 BM H max NC NC -417.969 1 2.5 4 16 min NC NC -2647.125 1 2.5 3 17 COL H 1 max NC NC NC NC 18 min NC NC NC NC 19 COL H 2 max NC NC NC NC 20 min NC NC NC NC 21 BM F max NC NC -5978.857 1 5.75 2 22 min NC NC -10104.033 1 5.75 3 23 COL G 1 max NC NC NC NC 24 min NC NC NC NC 25 COL G 2 max NC NC NC NC 26 min NC NC NC NC 27 BM G max NC NC -84715.264 1 13.021 2 28 min NC NC -106454.851 1 13.021 3 29 COL 11 max NC NC NC NC 30 min NC NC NC NC 31 COL 12 max NC NC NC NC 32 min NC NC NC NC 33 BM I max NC NC -160.156 1 2.5 4 34 min NC NC -1014.312 1 2.5 3 35 COL J 1 max NC NC NC NC 36 min NC NC NC NC 37 COL J 2 max NC NC NC NC 38 min NC NC NC NC 39 BM J max NC NC -269.531 1 2.5 4 40 min NC NC -988.281 1 2.5 3 41 COL K 1 max NC NC NC NC 42 min NC NC NC NC 43 COL K 2 max NC NC NC NC 44 min NC NC NC NC 45 BM K max NC NC -333.984 1 2.5 4 46 min NC NC -1224.609 1 2.5 3 47 COL G 4 max NC NC NC NC 48 min NC NC NC NC 49 COL G 3 max NC NC NC NC 50 min NC NC NC NC 51 BM G RIGHT max NC NC -71875 1 12.5 2 52 min NC NC -85351.563 1 12.5 3 Envelope Member Torsion Stresses Member Sec Tor ue Ib-ft LC Torsion Shear si LC Warp Shear si z-z Warp Shear si z-Top Warp Bend si z-Bot Warp Bend[psi] 1 BM B 1 max 0 5 0 5 NC NC NC NC 2 min 0 1 0 1 NC NC NC NC 3 2 max 0 5 0 5 NC NC NC NC 4 min 0 1 0 1 NC NC NC NC 5 3 max 0 5 0 5 NC NC NC NC 6 min 0 1 0 1 NC NC NC NC 7 4 max 0 5 0 5 NC NC NC NC 8 min 0 1 0 1 NC NC NC NC 9 5 max 0 5 0 5 NC NC NC NC 10 min 0 1 0 1 NC NC NC NC 11 COL B 1 1 max 0 5 0 5 NC NC NC NC 12 min 0 1 0 1 NC NC NC NC CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] Reviewed Jor Code Compliance Page 7 5 of 9 7 PLANS MUST ION SITE FOR ALL INSPECTIONS TIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Torsion Stresses(Continued) Member Sec Tor ue Ib-ft LC Torsion Shearrosil LC Warp Shear si z-z Warp Shear[psi] z-Top Warp Bend si z-Bot War Bend[psi] 13 2 max 1 0 5 0 5 NC NC NC NC 14 min 0 1 0 1 NC NC NC NC 15 3 max 0 5 0 5 NC NC NC NC 16 min 0 1 0 1 NC NC NC NC 17 4 max 0 5 0 5 NC NC NC NC 18 min 0 1 0 1 NC NC NC NC 19 5 max 0 5 0 5 NC NC NC NC 20 min 0 1 0 1 NC NC NC NC 21 COL B 2 1 max 0 5 0 5 NC NC NC NC 22 min 0 1 0 1 NC NC NC NC 23 2 max 0 5 0 5 NC NC NC NC 24 min 0 1 0 1 NC NC NC NC 25 3 max 0 5 0 5 NC NC NC NC 26 min 0 1 0 1 NC NC NC NC 27 4 max 0 5 0 5 NC NC NC NC 28 min 0 1 0 1 NC NC NC NC 29 5 max 0 5 0 5 NC NC NC NC 30 min 0 1 0 1 NC NC NC NC 31 BM C 1 max 0 5 0 5 NC NC NC NC 32 min 0 1 0 1 NC NC NC NC 33 2 max 0 5 0 5 NC NC NC NC 34 min 0 1 0 1 NC NC NC NC 35 3 max 0 5 0 5 NC NC NC NC 36 min 0 1 0 1 NC NC NC NC 37 4 max 0 5 0 5 NC NC NC NC 38 min 0 1 0 1 NC NC NC NC 39 5 max 0 5 0 5 NC NC NC NC 40 min 0 1 0 1 NC NC NC NC 41 COL C 1 1 max 0 5 0 5 NC NC NC NC 42 min 0 1 0 1 NC NC NC NC 43 2 max 0 5 0 5 NC NC NC NC 44 min 0 1 0 1 NC NC NC NC 45 3 max 0 5 0 5 NC NC NC NC 46 min 0 1 0 1 NC NC NC NC 47 4 max 0 5 0 5 NC NC NC NC 48 min 0 1 0 1 NC NC NC NC 49 5 max 0 5 0 5 NC NC NC NC 50 min 0 1 0 1 NC NC NC NC 51 COL C 2 1 max 0 5 0 5 NC NC NC NC 52 min 0 1 0 1 NC NC NC NC 53 2 max 0 5 0 5 NC NC NC NC 54 min 0 1 0 1 NC NC NC NC 55 3 max 0 5 0 5 NC NC NC NC 56 min 0 1 0 1 NC NC NC NC 57 4 max 0 5 0 5 NC NC NC NC 58 min 0 1 0 1 NC NC NC NC 59 5 max 0 5 0 5 NC NC NC NC 60 min 0 1 0 1 NC NC NC NC 61 COL F 1 max 0 5 0 5 NC NC NC NC 62 min 0 1 0 1 NC NC NC NC 63 2 max 0 5 0 5 NC NC NC NC 64 min 0 1 0 1 NC NC NC NC 65 3 max 0 5 0 5 NC NC NC NC 66 min 0 1 0 1 NC NC NC NC 67 4 max 0 5 0 5 NC NC NC NC 68 min 0 1 0 1 NC NC NC NC 69 5 max 0 5 0 5 NC NC NC NC 70 min 0 1 0 1 NC NC NC NC 71 BM H 1 max 0 5 0 5 NC NC NC NC 72 min 0 1 0 1 NC NC NC NC 73 2 max 0 5 0 5 NC NC NC NC 74 min 0 1 0 1 NC NC NC NC 75 3 max 0 5 0 5 NC NC NC NC 76 min 0 1 0 1 NC NC NC NC 77 4 max 0 5 0 5 NC NC NC NC 78 min 0 1 0 1 NC NC NC NC 79 5 max 0 5 0 5 NC NC NC NC 80 min 0 1 0 1 NC NC NC NC CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] Reviewed for Code Compliance Page 76 of 97 PLANS MIST BE ON JOB SITE FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Torsion Stresses(Continued) Member Sec Tor ue Ib-ft LC Torsion Shearrosil LC Warp Shear si z-z Warp Shear[psi] z-Top Warp Bend si z-Bot Warp Bend[psi] 81 COL H 1 1 max 0 5 0 5 NC NC NC NC 82 min 0 1 0 1 NC NC NC NC 83 2 max 0 5 0 5 NC NC NC NC 84 min 0 1 0 1 NC NC NC NC 85 3 max 0 5 0 5 NC NC NC NC 86 min 0 1 0 1 NC NC NC NC 87 4 max 0 5 0 5 NC NC NC NC 88 min 0 1 0 1 NC NC NC NC 89 5 max 0 5 0 5 NC NC NC NC 90 min 0 1 0 1 NC NC NC NC 91 COL H 2 1 max 0 5 0 5 NC NC NC NC 92 min 0 1 0 1 NC NC NC NC 93 2 max 0 5 0 5 NC NC NC NC 94 min 0 1 0 1 NC NC NC NC 95 3 max 0 5 0 5 NC NC NC NC 96 min 0 1 0 1 NC NC NC NC 97 4 max 0 5 0 5 NC NC NC NC 98 min 0 1 0 1 NC NC NC NC 99 5 max 0 5 0 5 NC NC NC NC 100 min 0 1 0 1 NC NC NC NC 101 BM F 1 max -5.824 4 -1.755 4 NC NC NC NC 102 min -30.563 3 -9.208 3 NC NC NC NC 103 2 max -5.824 4 -1.755 4 NC NC NC NC 104 min -30.563 3 -9.208 3 NC NC NC NC 105 3 max -5.824 4 -1.755 4 NC NC NC NC 106 min -30.563 3 -9.208 3 NC NC NC NC 107 4 max -5.824 4 -1.755 4 NC NC NC NC 108 min -30.563 3 -9.208 3 NC NC NC NC 109 5 max -5.824 4 -1.755 4 NC NC NC NC 110 min -30.563 3 -9.208 3 NC NC NC NC 111 COL G 1 1 max 0 5 0 5 NC NC NC NC 112 min 0 1 0 1 NC NC NC NC 113 2 max 0 5 0 5 NC NC NC NC 114 min 0 1 0 1 NC NC NC NC 115 3 max 0 5 0 5 NC NC NC NC 116 min 0 1 0 1 NC NC NC NC 117 4 max 0 5 0 5 NC NC NC NC 118 min 0 1 0 1 NC NC NC NC 119 5 max 0 5 0 5 NC NC NC NC 120 min 0 1 0 1 NC NC NC NC 121 COL G 2 1 max 0 5 0 5 NC NC NC NC 122 min 0 1 0 1 NC NC NC NC 123 2 max 0 5 0 5 NC NC NC NC 124 min 0 1 0 1 NC NC NC NC 125 3 max 0 5 0 5 NC NC NC NC 126 min 0 1 0 1 NC NC NC NC 127 4 max 0 5 0 5 NC NC NC NC 128 min 0 1 0 1 NC NC NC NC 129 5 max 0 5 0 5 NC NC NC NC 130 min 0 1 0 1 NC NC NC NC 131 BM G 1 max 0 5 0 5 NC NC NC NC 132 min 0 1 0 1 NC NC NC NC 133 2 max 0 5 0 5 NC NC NC NC 134 min 0 1 0 1 NC NC NC NC 135 3 max 0 5 0 5 NC NC NC NC 136 min 0 1 0 1 NC NC NC NC 137 4 max 0 5 0 5 NC NC NC NC 138 min 0 1 0 1 NC NC NC NC 139 5 max 0 5 0 5 NC NC NC NC 140 min 0 1 0 1 NC NC NC NC 141 COL 11 1 max 0 5 0 5 NC NC NC NC 142 min 0 1 0 1 NC NC NC NC 143 2 max 0 5 0 5 NC NC NC NC 144 min 0 1 0 1 NC NC NC NC 145 3 max 0 5 0 5 NC NC NC NC 146 min 0 1 0 1 NC NC NC NC 147 4 max 0 5 0 5 NC NC NC NC 148 min 0 1 0 1 NC NC NC CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE RISA-3D Version 20 [MEMBER MODEL.r3d] FOR ALL INSPECTIONS Page 77 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Torsion Stresses(Continued) Member Sec Tor ue Ib-ft LC Torsion Shearrosil LC Warp Shear si z-z Warp Shear[psi] z-Top Warp Bend si z-Bot War Bend[psi] 149 5 max 0 5 0 5 NC NC NC NC 150 min 0 1 0 1 NC NC NC NC 151 COL 12 1 max 0 5 0 5 NC NC NC NC 152 min 0 1 0 1 NC NC NC NC 153 2 max 0 5 0 5 NC NC NC NC 154 min 0 1 0 1 NC NC NC NC 155 3 max 0 5 0 5 NC NC NC NC 156 min 0 1 0 1 NC NC NC NC 157 4 max 0 5 0 5 NC NC NC NC 158 min 0 1 0 1 NC NC NC NC 159 5 max 0 5 0 5 NC NC NC NC 160 min 0 1 0 1 NC NC NC NC 161 BM 1 1 max 0 5 0 5 NC NC NC NC 162 min 0 1 0 1 NC NC NC NC 163 2 max 0 5 0 5 NC NC NC NC 164 min 0 1 0 1 NC NC NC NC 165 3 max 0 5 0 5 NC NC NC NC 166 min 0 1 0 1 NC NC NC NC 167 4 max 0 5 0 5 NC NC NC NC 168 min 0 1 0 1 NC NC NC NC 169 5 max 0 5 0 5 NC NC NC NC 170 min 0 1 0 1 NC NC NC NC 171 COL J 1 1 max 0 5 0 5 NC NC NC NC 172 min 0 1 0 1 NC NC NC NC 173 2 max 0 5 0 5 NC NC NC NC 174 min 0 1 0 1 NC NC NC NC 175 3 max 0 5 0 5 NC NC NC NC 176 min 0 1 0 1 NC NC NC NC 177 4 max 0 5 0 5 NC NC NC NC 178 min 0 1 0 1 NC NC NC NC 179 5 max 0 5 0 5 NC NC NC NC 180 min 0 1 0 1 NC NC NC NC 181 COL J 2 1 max 0 5 0 5 NC NC NC NC 182 min 0 1 0 1 NC NC NC NC 183 2 max 0 5 0 5 NC NC NC NC 184 min 0 1 0 1 NC NC NC NC 185 3 max 0 5 0 5 NC NC NC NC 186 min 0 1 0 1 NC NC NC NC 187 4 max 0 5 0 5 NC NC NC NC 188 min 0 1 0 1 NC NC NC NC 189 5 max 0 5 0 5 NC NC NC NC 190 min 0 1 0 1 NC NC NC NC 191 BM J 1 max 0 5 0 5 NC NC NC NC 192 min 0 1 0 1 NC NC NC NC 193 2 max 0 5 0 5 NC NC NC NC 194 min 0 1 0 1 NC NC NC NC 195 3 max 0 5 0 5 NC NC NC NC 196 min 0 1 0 1 NC NC NC NC 197 4 max 0 5 0 5 NC NC NC NC 198 min 0 1 0 1 NC NC NC NC 199 5 max 0 5 0 5 NC NC NC NC 200 min 0 1 0 1 NC NC NC NC 201 COL K 1 1 max 0 5 0 5 NC NC NC NC 202 min 0 1 0 1 NC NC NC NC 203 2 max 0 5 0 5 NC NC NC NC 204 min 0 1 0 1 NC NC NC NC 205 3 max 0 5 0 5 NC NC NC NC 206 min 0 1 0 1 NC NC NC NC 207 4 max 0 5 0 5 NC NC NC NC 208 min 0 1 0 1 NC NC NC NC 209 5 max 0 5 0 5 NC NC NC NC 210 min 0 1 0 1 NC NC NC NC 211 COL K 2 1 max 0 5 0 5 NC NC NC NC 212 min 0 1 0 1 NC NC NC NC 213 2 max 0 5 0 5 NC NC NC NC 214 min 0 1 0 1 NC NC NC NC 215 3 max 0 5 0 5 NC NC NC NC 216 min 0 1 0 1 NC NC NC NC CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 78 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Torsion Stresses(Continued) Member Sec Tor ue Ib-ft LC Torsion Shearrosil LC Warp Shear si z-z Warp Shear[psi] z-Top Warp Bend si z-Bot War Bend[psi] 217 4 max 0 5 0 5 NC NC NC NC 218 min 0 1 0 1 NC NC NC NC 219 5 max 0 5 0 5 NC NC NC NC 220 min 0 1 0 1 NC NC NC NC 221 BM K 1 max 0 5 0 5 NC NC NC NC 222 min 0 1 0 1 NC NC NC NC 223 2 max 0 5 0 5 NC NC NC NC 224 min 0 1 0 1 NC NC NC NC 225 3 max 0 5 0 5 NC NC NC NC 226 min 0 1 0 1 NC NC NC NC 227 4 max 0 5 0 5 NC NC NC NC 228 min 0 1 0 1 NC NC NC NC 229 5 max 0 5 0 5 NC NC NC NC 230 min 0 1 0 1 NC NC NC NC 231 COL G 4 1 max 0 5 0 5 NC NC NC NC 232 min 0 1 0 1 NC NC NC NC 233 2 max 0 5 0 5 NC NC NC NC 234 min 0 1 0 1 NC NC NC NC 235 3 max 0 5 0 5 NC NC NC NC 236 min 0 1 0 1 NC NC NC NC 237 4 max 0 5 0 5 NC NC NC NC 238 min 0 1 0 1 NC NC NC NC 239 5 max 0 5 0 5 NC NC NC NC 240 min 0 1 0 1 NC NC NC NC 241 COL G 3 1 max 0 5 0 5 NC NC NC NC 242 min 0 1 0 1 NC NC NC NC 243 2 max 0 5 0 5 NC NC NC NC 244 min 0 1 0 1 NC NC NC NC 245 3 max 0 5 0 5 NC NC NC NC 246 min 0 1 0 1 NC NC NC NC 247 4 max 0 5 0 5 NC NC NC NC 248 min 0 1 0 1 NC NC NC NC 249 5 max 0 5 0 5 NC NC NC NC 250 min 0 1 0 1 NC NC NC NC 251 BM G RIGHT 1 max 0 5 0 5 NC NC NC NC 252 min 0 1 0 1 NC NC NC NC 253 2 max 0 5 0 5 NC NC NC NC 254 min 0 1 0 1 NC NC NC NC 255 3 max 0 5 0 5 NC NC NC NC 256 min 0 1 0 1 NC NC NC NC 257 4 max 0 5 0 5 NC NC NC NC 258 min 0 1 0 1 NC NC NC NC 259 5 max 0 5 0 5 NC NC NC NC 260 min 0 1 0 1 NC NC NC NC Envelope Member Section Stresses Member Sec Axial[psil LC y Shearl'osil LC z Shear si LC -To si LC y-Both3sil LC z-To si LC z-Bot si LC 1 BM B 1 maxI 0 5 115.626 5 0 5 0 5 0 5 0 5 0 5 2 min 0 1 28.468 1 0 1 0 1 0 1 0 1 0 1 3 2 max 0 5 57.813 5 0 5 920.142 5 -226.549 4 0 5 0 5 4 min 0 1 14.234 1 0 1 226.549 1 -920.142 3 0 1 0 1 5 3 max 0 5 0 5 0 5 1226.856 5 -302.065 4 0 5 0 5 6 min 0 1 0 1 0 1 302.065 1 -1226.856 3 0 1 0 1 7 4 max 0 5 -14.234 4 0 5 920.142 5 -226.549 4 0 5 0 5 8 min 0 1 -57.813 3 0 1 226.549 1 -920.142 3 0 1 0 1 9 5 max 0 5 -28.468 4 0 5 0 5 0 5 0 5 0 5 10 min 0 1 -115.626 3 0 1 0 1 0 1 0 1 0 1 11 COL B 1 1 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 12 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 13 2 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 14 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 15 3 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 16 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 17 4 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 18 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 19 5 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 20 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 21 COL B 2 1 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] Reviewedfor Code Compliance Page 79 of 97 PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Stresses(Continued) Member Sec Axial[psij LC v Shearrosil LC z Shear si LC -To si LC -Bot si LC z-To si LC z-Botrpsil LC 22 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 23 2 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 24 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 25 3 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 26 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 27 4 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 28 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 29 5 max 55.477 5 0 5 0 5 0 5 0 5 0 5 0 5 30 min 13.659 1 0 1 0 1 0 1 0 1 0 1 0 1 31 BM C 1 max 0 5 121.132 5 0 5 0 5 0 5 0 5 0 5 32 min 0 1 29.824 1 0 1 0 1 0 1 0 1 0 1 33 2 max 0 5 60.566 5 0 5 504.931 5 -124.319 4 0 5 0 5 34 min 0 1 14.912 1 0 1 124.319 1 -504.931 3 0 1 0 1 35 3 max 0 5 0 5 0 5 673.241 5 -165.759 4 0 5 0 5 36 min 0 1 0 1 0 1 165.759 1 -673.241 3 0 1 0 1 37 4 max 0 5 -14.912 4 0 5 504.931 5 -124.319 4 0 5 0 5 38 min 0 1 -60.566 3 0 1 124.319 1 -504.931 3 0 1 0 1 39 5 max 0 5 -29.824 4 0 5 0 5 0 5 0 5 0 5 40 min 0 1 -121.132 3 0 1 0 1 0 1 0 1 0 1 41 COL C 1 1 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 42 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 43 2 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 44 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 45 3 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 46 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 47 4 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 48 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 49 5 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 50 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 51 COL C 2 1 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 52 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 53 2 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 54 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 55 3 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 56 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 57 4 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 58 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 59 5 max 101.708 5 0 5 0 5 0 5 0 5 0 5 0 5 60 min 25.042 1 0 1 0 1 0 1 0 1 0 1 0 1 61 COL F 1 max 59.142 5 0 5 0.079 5 0 5 0 5 0 5 0 5 62 min 23.131 1 0 1 0.015 1 0 1 0 1 0 1 0 1 63 2 max 59.142 5 0 5 0.079 5 0 5 0 5 0.907 5 -0.173 4 64 min 23.131 1 0 1 0.015 1 0 1 0 1 0.173 1 -0.907 3 65 3 max 59.142 5 0 5 0.079 5 0 5 0 5 1.815 5 -0.346 4 66 min 23.131 1 0 1 0.015 1 0 1 0 1 0.346 1 -1.815 3 67 4 max 59.142 5 0 5 0.079 5 0 5 0 5 2.722 5 -0.519 4 68 min 23.131 1 0 1 0.015 1 0 1 0 1 0.519 1 -2.722 3 69 5 max 59.142 5 0 5 0.079 5 0 5 0 5 3.629 5 -0.692 4 70 min 23.131 1 0 1 0.015 1 0 1 0 1 0.692 1 -3.629 3 71 BM H 1 max 0 5 152.857 5 0 5 0 5 0 5 0 5 0 5 72 min 0 1 24.135 1 0 1 0 1 0 1 0 1 0 1 73 2 max 0 5 76.428 5 0 5 579.246 5 -91.46 4 0 5 0 5 74 min 0 1 12.068 1 0 1 91.46 1 -579.246 3 0 1 0 1 75 3 max 0 5 0 5 0 5 772.328 5 -121.947 4 0 5 0 5 76 min 0 1 0 1 0 1 121.947 1 -772.328 3 0 1 0 1 77 4 max 0 5 -12.068 4 0 5 579.246 5 -91.46 4 0 5 0 5 78 min 0 1 -76.428 3 0 1 91.46 1 -579.246 3 0 1 0 1 79 5 max 0 5 -24.135 4 0 5 0 5 0 5 0 5 0 5 80 min 0 1 -152.857 3 0 1 0 1 0 1 0 1 0 1 81 COL H 1 1 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 82 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 83 2 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 84 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 85 3 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 86 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 87 4 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 88 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 89 5 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 80 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Stresses(Continued) Member Sec Axial[psij LC v Shearrosil LC z Shear si LC -To si LC -Bot si LC z-To si LC z-Botrpsil LC 90 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 91 COL H 2 1 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 92 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 93 2 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 94 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 95 3 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 96 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 97 4 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 98 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 99 5 max 85.564 5 0 5 0 5 0 5 0 5 0 5 0 5 100 min 13.51 1 0 1 0 1 0 1 0 1 0 1 0 1 101 BM F 1 max 0 5 123.264 5 0 5 0 5 0 5 0 5 0 5 102 min 0 1 48.211 1 0 1 0 1 0 1 0 1 0 1 103 2 max 0 5 67.1 5 0 5 1106.115 5 -451.966 4 0 5 0 5 104 min 0 1 29.573 1 0 1 451.966 1 -1106.115 3 0 1 0 1 105 3 max 0 5 0.108 4 0 5 1473.981 5 -601.783 4 0 5 0 5 106 min 0 1 0 2 0 1 601.783 1 -1473.981 3 0 1 0 1 107 4 max 0 5 -29.357 4 0 5 1103.599 5 -449.45 4 0 5 0 5 108 min 0 1 -66.883 3 0 1 449.45 1 -1103.599 3 0 1 0 1 109 5 max 0 5 -47.994 4 0 5 0 5 0 5 0 5 0 5 110 min 0 1 -123.048 3 0 1 0 1 0 1 0 1 0 1 111 COL G 1 1 max 4578.749 5 0 5 0 5 0 5 0 5 0 5 0 5 112 min 845.104 1 0 1 0 1 0 1 0 1 0 1 0 1 113 2 max 4578.749 5 0 5 0 5 0 5 0 5 0 5 0 5 114 min 845.104 1 0 1 0 1 0 1 0 1 0 1 0 1 115 3 max 4578.749 5 0 5 0 5 0 5 0 5 0 5 0 5 116 min 845.104 1 0 1 0 1 0 1 0 1 0 1 0 1 117 4 max 4578.749 5 0 5 0 5 0 5 0 5 0 5 0 5 118 min 845.104 1 0 1 0 1 0 1 0 1 0 1 0 1 119 5 max 4578.749 5 0 5 0 5 0 5 0 5 0 5 0 5 120 min 845.104 1 0 1 0 1 0 1 0 1 0 1 0 1 121 COL G 2 1 max 4537.555 5 0 5 0 5 0 5 0 5 0 5 0 5 122 min 829.182 1 0 1 0 1 0 1 0 1 0 1 0 1 123 2 max 4537.555 5 0 5 0 5 0 5 0 5 0 5 0 5 124 min 829.182 1 0 1 0 1 0 1 0 1 0 1 0 1 125 3 max 4537.555 5 0 5 0 5 0 5 0 5 0 5 0 5 126 min 829.182 1 0 1 0 1 0 1 0 1 0 1 0 1 127 4 max 4537.555 5 0 5 0 5 0 5 0 5 0 5 0 5 128 min 829.182 1 0 1 0 1 0 1 0 1 0 1 0 1 129 5 max 4537.555 5 0 5 0 5 0 5 0 5 0 5 0 5 130 min 829.182 1 0 1 0 1 0 1 0 1 0 1 0 1 131 BM G 1 max 0 5 2891.201 5 0 5 0 5 0 5 0 5 0 5 132 min 0 1 528.331 1 0 1 0 1 0 1 0 1 0 1 133 2 max 0 5 1600.196 5 0 5 9176.55 5 -1742.433 4 0 5 0 5 134 min 0 1 324.488 1 0 1 1742.433 1 -9176.55 3 0 1 0 1 135 3 max 0 5 309.191 5 0 5 13077.66 5 -2651.902 4 0 5 0 5 136 min 0 1 120.645 1 0 1 2651.902 1 -13077.66 3 0 1 0 1 137 4 max 0 5 334.634 4 0 5 9283.967 5 1783.917 4 0 5 0 5 138 min 0 1 -1626.443 3 0 1 1783.917 1 -9283.967 3 0 1 0 1 139 5 max 0 5 -538.476 4 0 5 0 5 0 5 0 5 0 5 140 min 0 1 -2917.448 3 0 1 0 1 0 1 0 1 0 1 141 COL 11 1 maxl 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 142 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 143 2 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 144 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 145 3 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 146 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 147 4 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 148 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 149 5 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 150 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 151 COL 12 1 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 152 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 153 2 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 154 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 155 3 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 156 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 157 4 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 81 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Stresses(Continued) Member Sec Axial[psil LC v Shearrosil LC z Shear si LC -To si LC -Bot si LC z-To si LC z-Botrpsil LC 158 min 1 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 159 5 max 98.358 5 0 5 0 5 0 5 0 5 0 5 0 5 160 min 15.53 1 0 1 0 1 0 1 0 1 0 1 0 1 161 BM I 1 max 0 5 49.681 5 0 5 0 5 0 5 0 5 0 5 162 min 0 1 7.844 1 0 1 0 1 0 1 0 1 0 1 163 2 max 0 5 24.84 5 0 5 159.688 5 -25.214 4 0 5 0 5 164 min 0 1 3.922 1 0 1 25.214 1 -159.688 3 0 1 0 1 165 3 max 0 5 0 5 0 5 212.917 5 -33.619 4 0 5 0 5 166 min 0 1 0 1 0 1 33.619 1 -212.917 3 0 1 0 1 167 4 max 0 5 -3.922 4 0 5 159.688 5 -25.214 4 0 5 0 5 168 min 0 1 -24.84 3 0 1 25.214 1 -159.688 3 0 1 0 1 169 5 max 0 5 -7.844 4 0 5 0 5 0 5 0 5 0 5 170 min 0 1 -49.681 3 0 1 0 1 0 1 0 1 0 1 171 COL J 1 1 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 172 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 173 2 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 174 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 175 3 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 176 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 177 4 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 178 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 179 5 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 180 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 181 COL J 2 1 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 182 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 183 2 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 184 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 185 3 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 186 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 187 4 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 188 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 189 5 max 95.833 5 0 5 0 5 0 5 0 5 0 5 0 5 190 min 26.136 1 0 1 0 1 0 1 0 1 0 1 0 1 191 BM J 1 max 0 5 70.278 5 0 5 0 5 0 5 0 5 0 5 192 min 0 1 19.167 1 0 1 0 1 0 1 0 1 0 1 193 2 max 0 5 35.139 5 0 5 281.111 5 -76.667 4 0 5 0 5 194 min 0 1 9.583 1 0 1 76.667 1 -281.111 3 0 1 0 1 195 3 max 0 5 0 5 0 5 374.815 5 -102.222 4 0 5 0 5 196 min 0 1 0 1 0 1 102.222 1 -374.815 3 0 1 0 1 197 4 max 0 5 -9.583 4 0 5 281.111 5 -76.667 4 0 5 0 5 198 min 0 1 -35.139 3 0 1 76.667 1 -281.111 3 0 1 0 1 199 5 max 0 5 -19.167 4 0 5 0 5 0 5 0 5 0 5 200 min 0 1 -70.278 3 0 1 0 1 0 1 0 1 0 1 201 COL K 1 1 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 202 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 203 2 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 204 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 205 3 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 206 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 207 4 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 208 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 209 5 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 210 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 211 COL K 2 1 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 212 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 213 2 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 214 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 215 3 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 216 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 217 4 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 218 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 219 5 max 118.75 5 0 5 0 5 0 5 0 5 0 5 0 5 220 min 32.386 1 0 1 0 1 0 1 0 1 0 1 0 1 221 BM K 1 max 0 5 87.083 5 0 5 0 5 0 5 0 5 0 5 222 min 0 1 23.75 1 0 1 0 1 0 1 0 1 0 1 223 2 max 0 5 43.542 5 0 5 348.333 5 -95 4 0 5 0 5 224 min 0 1 11.875 1 0 1 95 1 -348.333 3 0 1 0 1 225 3 max 0 5 0 5 0 5 464.444 5 -126.667 4 0 5 0 5 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 82 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Stresses(Continued) Member Sec Axial[psij LC v Shearrosil LC z Shearfpsij LC -To si LC -Bot si LC z-To si LC z-Botrpsil LC 226 min 0 1 0 1 0 1 126.667 1 -464.444 3 0 1 0 1 227 4 max 0 5 -11.875 4 0 5 348.333 5 -95 4 0 5 0 5 228 min 0 1 -43.542 3 0 1 95 1 -348.333 3 0 1 0 1 229 5 max 0 5 -23.75 4 0 5 0 5 0 5 0 5 0 5 230 min 0 1 -87.083 3 0 1 0 1 0 1 0 1 0 1 231 COL G 4 1 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 232 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 233 2 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 234 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 235 3 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 236 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 237 4 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 238 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 239 5 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 240 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 241 COL G 3 1 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 242 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 243 2 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 244 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 245 3 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 246 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 247 4 maxl 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 248 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 249 5 max 4052.3 5 0 5 0 5 0 5 0 5 0 5 0 5 250 min 639.837 1 0 1 0 1 0 1 0 1 0 1 0 1 251 BM G RIGHT 1 max 0 5 2582.01 5 0 5 0 5 0 5 0 5 0 5 252 min 0 1 407.686 1 0 1 0 1 0 1 0 1 0 1 253 2 max 0 5 1291.005 5 0 5 7913.248 5 -1249.46 4 0 5 0 5 254 min 0 1 203.843 1 0 1 1249.46 1 -7913.248 3 0 1 0 1 255 3 max 0 5 0 5 0 5 10550.997 5 -1665.947 4 0 5 0 5 256 min 0 1 0 1 0 1 1665.947 1 -10550.997 3 0 1 0 1 257 4 max 0 5 -203.843 4 0 5 7913.248 5 -1249.46 4 0 5 0 5 258 min 0 1 -1291.005 3 0 1 1249.46 1 -7913.248 3 0 1 0 1 259 5 max 0 5 -407.686 4 0 5 0 5 0 5 0 5 0 5 260 min 0 1 -2582.01 3 0 1 0 1 0 1 0 1 0 1 Envelope Member Section Deflections-Service Member Sec x in LC v rinlLC z in LC x Rotate rad LC n L/ 'Ratio LC n L/z'Ratio LC 1 BM B 1 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 2 min 0 1 -0.004 3 0 1 0 1 NC 1 NC 1 3 2 max 0 5 -0.033 4 0 5 0 5 3993.675 4 NC 5 4 min 0 1 -0.132 3 0 1 0 1 983.285 3 NC 1 5 3 max 0 5 -0.045 4 0 5 0 5 2845.494 4 NC 5 6 min 0 1 -0.184 3 0 1 0 1 700.591 3 NC 1 7 4 max 0 5 -0.033 4 0 5 0 5 3993.675 4 NC 5 8 min 0 1 -0.132 3 0 1 0 1 983.285 3 NC 1 9 5 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 10 min 0 1 -0.004 3 0 1 0 1 NC 1 NC 1 11 COL B 1 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 12 min 0 1 0 1 0 1 0 1 NC 1 NC 1 13 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 14 min -0.001 3 0 1 0 1 0 1 NC 1 NC 1 15 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 16 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 17 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 18 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 19 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 20 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 21 COL B 2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 22 min 0 1 0 1 0 1 0 1 NC 1 NC 1 23 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 24 min -0.001 3 0 1 0 1 0 1 NC 1 NC 1 25 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 26 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 27 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 28 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 29 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 30 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 83 of 97 FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Deflections-Service(Continued) Member Sec x in LC in LC z in LC x Rotate rad LC n L/ 'Ratio LC n L/z'Ratio LC 31 BM C 1 max 0 5 -0.002 4 0 5 0 5 NC 5 NC 5 32 min 0 1 -0.008 3 0 1 0 1 NC 1 NC 1 33 2 max 0 5 -0.007 4 0 5 0 5 NC 4 NC 5 34 min 0 1 -0.027 3 0 1 0 1 3420.812 3 NC 1 35 3 max 0 5 -0.009 4 0 5 0 5 9899.367 4 NC 5 36 min 0 1 -0.035 3 0 1 0 1 2437.329 3 NC 1 37 4 max 0 5 -0.007 4 0 5 0 5 NC 4 NC 5 38 min 0 1 -0.027 3 0 1 0 1 3420.812 3 NC 1 39 5 max 0 5 -0.002 4 0 5 0 5 NC 5 NC 5 40 min 0 1 -0.008 3 0 1 0 1 NC 1 NC 1 41 COL C 1 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 42 min 0 1 0 1 0 1 0 1 NC 1 NC 1 43 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 44 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 45 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 46 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 47 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 48 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 49 5 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 50 min -0.008 3 0 1 0 1 0 1 NC 1 NC 1 51 COL C 2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 52 min 0 1 0 1 0 1 0 1 NC 1 NC 1 53 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 54 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 55 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 56 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 57 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 58 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 59 5 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 60 min -0.008 3 0 1 0 1 0 1 NC 1 NC 1 61 COL F 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 62 min 0 1 0 1 0 1 0 1 NC 1 NC 1 63 2 max 0 4 0 5 0 4 0 5 NC 5 NC 5 64 min -0.001 3 0 1 0 3 0 1 NC 1 NC 1 65 3 max -0.001 4 0 5 0 4 0 5 NC 5 NC 5 66 min -0.002 3 0 1 0 3 0 1 NC 1 NC 1 67 4 max -0.001 4 0 5 0 4 0 5 NC 5 NC 5 68 min -0.003 3 0 1 0 3 0 1 NC 1 NC 1 69 5 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 70 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 71 BM H 1 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 72 min 0 1 -0.006 3 0 1 0 1 NC 1 NC 1 73 2 max 0 5 -0.004 4 0 5 0 5 NC 4 NC 5 74 min 0 1 -0.025 3 0 1 0 1 3280.127 3 NC 1 75 3 max 0 5 -0.005 4 0 5 0 5 NC 4 NC 5 76 min 0 1 -0.032 3 0 1 0 1 2337.091 3 NC 1 77 4 max 0 5 -0.004 4 0 5 0 5 NC 4 NC 5 78 min 0 1 -0.025 3 0 1 0 1 3280.127 3 NC 1 79 5 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 80 min 0 1 -0.006 3 0 1 0 1 NC 1 NC 1 81 COL H 1 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 82 min 0 1 0 1 0 1 0 1 NC 1 NC 1 83 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 84 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 85 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 86 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 87 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 88 min -0.005 3 0 1 0 1 0 1 NC 1 NC 1 89 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 90 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 91 COL H 2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 92 min 0 1 0 1 0 1 0 1 NC 1 NC 1 93 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 94 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 95 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 96 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 97 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 98 min -0.005 3 0 1 0 1 0 1 NC 1 NC 1 CITY APPROVED PLANS Reviewed for Code Compliance RISA-3D Version 20 [MEMBER MODEL.r3d] PLANS MUST BE ON JOB SITE Page 84 of 9 i FOR ALL INSPECTIONS Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Deflections-Service(Continued) Member Sec x in LC in LC z in LC x Rotate rad LC n L/ 'Ratio LC n L/z'Ratio LC 99 5 1 max -0.001 4 0 5 0 5 0 5 INC 5 NC 5 100 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 101 BM F 1 max 0 5 -0.002 4 0 5 0 5 INC 5 NC 5 102 min 0 1 -0.004 3 0 1 0 1 NC 1 NC 1 103 2 max 0 5 -0.12 4 0 5 0 5 1821.681 4 NC 5 104 min 0 1 -0.409 3 0 1 0 1 745.819 3 NC 1 105 3 max 0 5 -0.194 4 0 5 0 5 1296.714 4 NC 5 106 min 0 1 -0.704 3 0 1 0 1 531.189 3 NC 1 107 4 max 0 5 -0.206 4 0 5 0 5 1823.484 4 NC 5 108 min 0 1 -0.849 3 0 1 0 1 746.121 3 NC 1 109 5 max 0 5 -0.173 4 0 5 0.001 5 NC 5 NC 5 110 min 0 1 -0.884 3 0 1 0 1 NC 1 NC 1 111 COL G 1 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 112 min 0 1 0 1 0 1 0 1 NC 1 NC 1 113 2 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 114 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 115 3 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 116 min -0.012 3 0 1 0 1 0 1 NC 1 NC 1 117 4 max -0.003 4 0 5 0 5 0 5 INC 5 NC 5 118 min -0.018 3 0 1 0 1 0 1 NC 1 NC 1 119 5 max -0.004 4 0 5 0 5 0 5 NC 5 NC 5 120 min -0.024 3 0 1 0 1 0 1 NC 1 NC 1 121 COL G 2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 122 min 0 1 0 1 0 1 0 1 NC 1 NC 1 123 2 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 124 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 125 3 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 126 min -0.012 3 0 1 0 1 0 1 NC 1 NC 1 127 4 max -0.003 4 0 5 0 5 0 5 NC 5 NC 5 128 min -0.018 3 0 1 0 1 0 1 NC 1 NC 1 129 5 max -0.004 4 0 5 0 5 0 5 NC 5 NC 5 130 min -0.023 3 0 1 0 1 0 1 INC 1 NC 1 131 BM G 1 max 0 5 -0.004 4 0 5 0 5 INC 5 NC 5 132 min 0 1 -0.023 3 0 1 0 1 NC 1 NC 1 133 2 max 0 5 -0.122 4 0 5 0 5 2553.498 4 NC 5 134 min 0 1 -0.626 3 0 1 0 1 498.047 3 NC 1 135 3 max 0 5 -0.173 4 0 5 0 5 1775.012 4 NC 5 136 min 0 1 -0.884 3 0 1 0 1 348.735 3 NC 1 137 4 max 0 5 -0.123 4 0 5 0 5 2530.792 4 NC 5 138 min 0 1 -0.629 3 0 1 0 1 495.314 3 NC 1 139 5 max 0 5 -0.004 4 0 5 0 5 NC 5 NC 5 140 min 0 1 -0.024 3 0 1 0 1 NC 1 NC 1 141 COL 11 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 142 min 0 1 0 1 0 1 0 1 NC 1 NC 1 143 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 144 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 145 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 146 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 147 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 148 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 149 5 max -0.001 4 0 5 0 5 0 5 INC 5 NC 5 150 min -0.007 3 0 1 0 1 0 1 NC 1 NC 1 151 COLI2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 152 min 0 1 0 1 0 1 0 1 NC 1 NC 1 153 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 154 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 155 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 156 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 157 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 158 min -0.006 3 0 1 0 1 0 1 NC 1 NC 1 159 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 160 min -0.007 3 0 1 0 1 0 1 NC 1 NC 1 161 BM 1 1 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 162 min 0 1 -0.007 3 0 1 0 1 NC 1 NC 1 163 2 max 0 5 -0.002 4 0 5 0 5 NC 5 NC 5 164 min 0 1 -0.012 3 0 1 0 1 NC 1 NC 1 165 3 max 0 5 -0.002 4 0 5 0 5 INC 4 NC 5 166 min 0 1 -0.013 3 0 1 0 1 9994.509 3 NC 1 CITY APPROVED PLANS RISA-3D Version 20 [MEMBER MODEL.r3d] Feviewedfor Code Compliance Page 85 of 97 PL FOR ALL INSPECTIONS SITE Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Deflections-Service(Continued) Member Sec x in LC in LC z in LC x Rotate rad LC n L/ 'Ratio LC n L/z'Ratio LC 167 4 1 max 0 1 5 -0.002 4 0 5 0 5 INC 5 NC 5 168 min 0 1 -0.012 3 0 1 0 1 NC 1 NC 1 169 5 max 0 5 -0.001 4 0 5 0 5 INC 5 NC 5 170 min 0 1 -0.007 3 0 1 0 1 NC 1 NC 1 171 COL J 1 1 max 0 5 0 5 0 5 0 5 INC 5 NC 5 172 min 0 1 0 1 0 1 0 1 NC 1 NC 1 173 2 max 0 4 0 5 0 5 0 5 INC 5 NC 5 174 min -0.001 3 0 1 0 1 0 1 NC 1 NC 1 175 3 max 0 4 0 5 0 5 0 5 NC 5 NC 5 176 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 177 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 178 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 179 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 180 min -0.004 3 0 1 0 1 0 1 INC 1 NC 1 181 COL J 2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 182 min 0 1 0 1 0 1 0 1 NC 1 NC 1 183 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 184 min -0.001 3 0 1 0 1 0 1 NC 1 NC 1 185 3 max 0 4 0 5 0 5 0 5 INC 5 NC 5 186 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 187 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 188 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 189 5 max -0.001 4 0 5 0 5 0 5 INC 5 NC 5 190 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 191 BM J 1 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 192 min 0 1 -0.004 3 0 1 0 1 INC 1 NC 1 193 2 max 0 5 -0.004 4 0 5 0 5 NC 4 NC 5 194 min 0 1 -0.015 3 0 1 0 1 5392.136 3 NC 1 195 3 max 0 5 -0.005 4 0 5 0 5 NC 4 NC 5 196 min 0 1 -0.019 3 0 1 0 1 3841.897 3 NC 1 197 4 max 0 5 -0.004 4 0 5 0 5 NC 4 NC 5 198 min 0 1 -0.015 3 0 1 0 1 5392.136 3 NC 1 199 5 max 0 5 -0.001 4 0 5 0 5 INC 5 NC 5 200 min 0 1 -0.004 3 0 1 0 1 NC 1 NC 1 201 COL K 1 1 max 0 5 0 5 0 5 0 5 INC 5 NC 5 202 min 0 1 0 1 0 1 0 1 NC 1 NC 1 203 2 max 0 4 0 5 0 5 0 5 INC 5 NC 5 204 min -0.001 3 0 1 0 1 0 1 NC 1 NC 1 205 3 max -0.001 4 0 5 0 5 0 5 INC 5 NC 5 206 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 207 4 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 208 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 209 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 210 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 211 COL K 2 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 212 min 0 1 0 1 0 1 0 1 INC 1 NC 1 213 2 max 0 4 0 5 0 5 0 5 NC 5 NC 5 214 min -0.001 3 0 1 0 1 0 1 NC 1 NC 1 215 3 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 216 min -0.002 3 0 1 0 1 0 1 NC 1 NC 1 217 4 max -0.001 4 0 5 0 5 0 5 INC 5 NC 5 218 min -0.003 3 0 1 0 1 0 1 NC 1 NC 1 219 5 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 220 min -0.004 3 0 1 0 1 0 1 NC 1 NC 1 221 BM K 1 max 0 5 -0.001 4 0 5 0 5 INC 5 NC 5 222 min 0 1 -0.004 3 0 1 0 1 NC 1 NC 1 223 2 max 0 5 -0.005 4 0 5 0 5 NC 4 NC 5 224 min 0 1 -0.018 3 0 1 0 1 4351.549 3 NC 1 225 3 max 0 5 -0.006 4 0 5 0 5 NC 4 NC 5 226 min 0 1 -0.024 3 0 1 0 1 3100.478 3 NC 1 227 4 max 0 5 -0.005 4 0 5 0 5 NC 4 NC 5 228 min 0 1 -0.018 3 0 1 0 1 4351.549 3 NC 1 229 5 max 0 5 -0.001 4 0 5 0 5 NC 5 NC 5 230 min 0 1 -0.004 3 0 1 0 1 INC 1 NC 1 231 COL G 4 1 max 0 5 0 5 0 5 0 5 INC 5 NC 5 232 min 0 1 0 1 0 1 0 1 NC 1 NC 1 233 2 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 234 min -0.005 3 0 1 0 1 0 1 NC 1 NC 1 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE RISA-3D Version 20 [MEMBER MODEL.r3d] FOR ALL INSPECTIONS Page 86 of 97 Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope Member Section Deflections-Service(Continued) Member Sec x in LC in LC z in LC x Rotate rad LC n L/ 'Ratio LC n L/z'Ratio LC 235 3 1 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 236 min -0.01 3 0 1 0 1 0 1 NC 1 NC 1 237 4 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 238 min -0.016 3 0 1 0 1 0 1 NC 1 NC 1 239 5 max -0.003 4 0 5 0 5 0 5 NC 5 NC 5 240 min -0.021 3 0 1 0 1 0 1 NC 1 NC 1 241 COL G 3 1 max 0 5 0 5 0 5 0 5 NC 5 NC 5 242 min 0 1 0 1 0 1 0 1 NC 1 NC 1 243 2 max -0.001 4 0 5 0 5 0 5 NC 5 NC 5 244 min -0.005 3 0 1 0 1 0 1 NC 1 NC 1 245 3 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 246 min -0.01 3 0 1 0 1 0 1 NC 1 NC 1 247 4 max -0.002 4 0 5 0 5 0 5 NC 5 NC 5 248 min -0.016 3 0 1 0 1 0 1 NC 1 NC 1 249 5 max -0.003 4 0 5 0 5 0 5 NC 5 NC 5 250 min -0.021 3 0 1 0 1 0 1 NC 1 NC 1 251 BM G RIGHT 1 max 0 5 -0.003 4 0 5 0 5 NC 5 NC 5 252 min 0 1 -0.021 3 0 1 0 1 NC 1 NC 1 253 2 max 0 5 -0.081 4 0 5 0 5 3846.512 4 NC 5 254 min 0 1 -0.515 3 0 1 0 1 607.344 3 NC 1 255 3 max 0 5 -0.113 4 0 5 0 5 2740.64 4 NC 5 256 min 0 1 -0.714 3 0 1 0 1 432.733 3 NC 1 257 4 max 0 5 -0.081 4 0 5 0 5 3846.512 4 NC 5 258 min 0 1 -0.515 3 0 1 0 1 607.344 3 NC 1 259 5 max 0 5 -0.003 4 0 5 0 5 NC 5 NC 5 260 min 0 1 -0.021 3 0 1 0 1 NC 1 NC 1 Envelope Member Section Deflections-Strength No Data to Print... Envelope Beam Deflections Member Label San Location ft in n L'/ 'Ratio LC 1 BM B 1 max 10.391 -0.001 NC 4 2 1 min 5.25 -0.18 700 3 3 BM C 1 max 5.214 -0.001 NC 4 4 1 min 2.75 -0.027 2437 3 5 BM H 1 max 0.417 -0.001 NC 4 6 1 min 2.5 -0.026 2337 3 7 BM F 1 max 11.38 -0.004 NC 4 8 1 min 5.75 -0.26 531 3 9 BM G 1 max 0.26 -0.005 NC 4 10 1 min 12.76 -0.861 348 3 11 BM 1 1 max 0.313 -0.001 NC 2 12 1 min 2.5 -0.006 9994 3 13 BM J 1 max 0.104 -0.001 NC 5 14 1 min 2.5 -0.016 3841 3 15 BM K 1 max 4.688 -0.001 NC 4 16 1 min 2.5 -0.019 3100 3 17 BM G RIGHT 1 max 0.26 -0.004 NC 4 18 1 min 12.5 -0.693 432 3 Envelope Beam Deflection Checks Beam Design Rule San Defl in Ratio LC Defl in Ratio LC Defl in Ratio LC 1 BM B Typical 1 -0.044 2845 1 DL -0.136 929 2 LL -0.18 700 3 DL+LL 2 BM C Typical 1 -0.007 9899 1 DL -0.02 3233 2 LL -0.027 2437 3 DL+LL 3 BM H Typical 1 0 NC 1 DL -0.022 2775 2 LL -0.026 2337 3 DL+LL 4 BM F Typical 1 -0.106 1296 1 DL -0.153 899 2 LL -0.26 531 3 DL+LL 5 BM G Typical 1 -0.169 1774 1 DL -0.691 433 2 LL -0.861 348 3 DL+LL 6 BM I Typical 1 0 NC 1 DL 0 NC 2 LL -0.006 9994 3 DL+LL 7 BM J Typical 1 0 NC 1 DL -0.011 5282 2 LL -0.016 3841 3 DL+LL 8 BM K TVpical 1 0 NC 1 DL -0.014 4263 2 LL -0.019 3100 3 DL+LL 9 BM G RIGHT Typical 1 -0.109 2740 1 DL -0.584 513 2 LL -0.693 432 3 DL+LL CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE RISA-3D Version 20 [MEMBER MODEL.r3d] FOR ALL INSPECTIONS Page 87 of � , Company Noesis Engineering Services 6/7/2022 11RISA Designer David Boyter,PE 6:24:46 PM Job Number : 22083 Checked By:Jake Lucid... ,,- Model Name : Robert Weed Plywood Interiod Members Envelope AISC 15TH(360-16):ASD Member Steel Code Checks Member Shape Code Check Loc ft LC Shear Check Loc ft Dir LC Pnc/om flbl Pnt/om rlbl Mn /om[lb-ft Mnzz/om[lb-ft Cb E n 1 COL G 1 IHSS4X4X4 0.241 10 5 0 10 y 5 64020.94 100898.204 11701.597 11701.597 1 H1-1a* 2 COL G 2 HSS4X4X4 0.239 10 5 0 10 y 5 64020.94 100898.204 11701.597 11701.597 1 H1-1a* 3 BM G W12X72 0.421 13.021 5 0.146 25 y 5 309953.627631736.527 122754.491 252970.511 1.17 H1-1b 4 COL G 4 HSS4X4X4 0.213 10 5 0 10 v 5 64020.94 100898.204 11701.597 11701.597 1 H1-1a* 5 COL G 3 HSS4X4X4 0.213 10 5 0 10 y 5 64020.94 100898.204 11701.597 11701.597 1 H1-1a* 6 BM G RIGHT W12X72 0.347 12.5 5 0.129 25 y 5 309953.627631736.527 122754.491 245690.836 1.136 H1-1b Envelope AISI S100-16:ASD Member Cold Formed Steel Code Checks No Data to Print... Envelope AWC NDS-18:ASD Member Wood Code Checks Member Shape Code Check Loc ft LC Shear Check Loc[ftj Dir LC Fc'[psi]Ft'[psi]Fb1'[psi]Fb2'[psi]Fv'[psi] RB CL CP E n 1 BM B 2-1.75X1 1.875FS 0.48 5.25 5 0.406 10.5 V 5 370.064 1555 2555.335 2600 285 11.052 0.983 0.147 3.9-3 2 COL B 1 7-2X6 0.068 10 5 0 10 z 5 812.758 747.5 1169.411 1170 180 2.447 0.999 0.547 3.6.3 3 COL B 2 7-2X6 0.068 10 5 0 10 z 5 812.758 747.5 1169.411 1170 180 2.447 0.999 0.547 3.6.3 4 BM C 1.75X11.875FS 0.273 2.75 5 0.425 5.5 y 5 563.943 1555 2464.63 2600 285 15.997 0.948 0.225 3.9-3 5 COL C 1 2-2X6 0.592 10 5 0 10 z 5 171.947 747.5 1161.966 1170 180 8.563 0.993 0.116 3.6.3 6 COL C 2 2-2X6 0.592 10 5 0 10 z 5 171.947 747.5 1161.966 1170 180 8.563 0.993 0.116 3.6.3 7 COL F 7-2X6 0.073 10 5 0 10 z 5 812.758 747.5 1169.411 1345.5 180 2.447 0.999 0.547 3.6.3 8 BM H 1.75X11.875FS 0.311 2.5 5 0.536 5 v 5 677.129 1555 2485.347 2600 285 15.253 0.956 0.27 3.9-3 9 COL H 1 3-2X6 0.239 10 5 0 10 z 5 357.478 747.5 11 66.65E 1170 180 5.709 0.997 0.241 3.6.3 10 COL H 2 3-2X6 0.239 10 5 0 10 z 5 357.478 747.5 11 66.65E 1170 180 5.709 0.997 0.241 3.6.3 11 BM F 2-1.75X1 1.875FS 0.578 5.75 5 0.465 0 Y 5 310.49 1555 2549.664 2600 285 11.566 0.981 0.124 3.9-3 12 COL 1 1 2X6 0.121 10 5 0 10 z 5 812.758 747.5 1120.58 1170 180 17.127 0.958 0.547 3.6.3 13 COL 1 2 2X6 0.121 10 5 0 10 z 5 812.758 747.5 1120.58 1170 180 17.127 0.958 0.547 3.6.3 14 BM I 1.75X14FS 0.087 2.5 5 0.174 5 Y 5 677.129 1555 2446.294 2600 285 16.562 0.941 0.27 3.9-3 15 COL J 1 2X6 0.334 5 5 0 5 z 5 286.578 747.5 1151.731 1170 180 12.1110.984 0.193 3.6.3 16 COL J 2 2X6 0.334 5 5 0 5 z 5 286.578 747.5 1151.731 1170 180 12.1110.984 0.193 3.6.3 17 BM J 2X12 0.429 2.5 5 0.39 5 Y 5 285.027 575 873.917 900 180 17.321 0.971 0.211 3.9-3 18 COL K 1 2X6 0.414 5 5 0 5 z 5 286.578 747.5 1151.731 1170 180 12.1110.984 0.193 3.6.3 19 COL K 2 2X6 0.414 5 5 0 5 z 5 286.578 747.5 1151.731 1170 180 12.1110.984 0.193 3.6.3 20 BM K 2X12 0.531 2.5 5 0.484 5 y 5 285.027 575 873.917 900 180 17.321 0.971 0.211 3.9-3 Envelope Concrete Beam Design Results No Data to Print... Envelope Concrete Column Design Results No Data to Print... Envelope AA ADM1-15:ASD-BUILDING Member Aluminum Code Checks No Data to Print... Envelope AISC 14TH(360-10):ASD Member Stainless Steel Code Checks No Data to Print... Concrete Beam Bending Reinforcement No Data to Print... Concrete Beam Shear Reinforcement No Data to Print... Concrete Column Bending Reinforcement No Data to Print... Concrete Column Shear Reinforcement No Data to Print... CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 31 Page 88 of 97 111RISA Company Noesis Engineering Services 62 Designer : David Boyter,PE 6:24:46:24:46 PM Job Number 22083 Checked By:Jake Lucid... Model Name Robert Weed Plywood Interiod Members Member Suggested Designs Section Set/Member Current Shape Suggested Shape Controlling Criteria Use Suggested? 1 COL B 1 7-2X6 4X4 Strength Yes 2 COL B 2 7-2X6 4X4 Strength Yes 3 COL C 1 2-2X6 3X4 Strength Yes 4 COL C 2 2-2X6 3X4 Strength Yes 5 COL F 7-2X6 4X4 Strength Yes 6 COL H 1 3-2X6 4X4 Strength Yes 7 COL H 2 3-2X6 4X4 Strength Yes 8 COL G 1 HSS4X4X4 HSS3X3X2 Strength Yes 9 COL G 2 HSS4X4X4 HSS3X3X2 Strength Yes 10 COL 11 2X6 2X4 Strength Yes 11 COL 12 2X6 2X4 Strength Yes 12 COL J 1 2X6 2X3 Strength Yes 13 COL J 2 2X6 2X3 Strength Yes 14 BM J 2X12 2-2X6 Strength Yes 15 COL K 1 2X6 2X3 Strength Yes 16 COL K 2 2X6 2X3 Strength Yes 17 BM K 2X12 2-2X6 Strength Yes 18 COL G 4 HSS4X4X4 HSS3.5X2.5X2 Strength Yes 19 COL G 3 HSS4X4X4 HSS3.5X2.5X2 Strength Yes Envelope Plate Principal Stresses No Data to Print... Envelope Plate Forces(per ft) No Data to Print... Envelope Plate/Shell Corner Forces No Data to Print... Envelope Solid Stresses No Data to Print... Envelope Solid Principal Stresses No Data to Print... Envelope Solid Corner Forces No Data to Print... Envelope Wall Panel Forces No Data to Print... Concrete Wall Reinforcement No Data to Print... Masonry Wall Reinforcement No Data to Print... Masonry Lintel Reinforcement No Data to Print... ACl 318-14 Wall Panel Concrete Code Checks(In-Plane) No Data to Print... ACl 318-14 Wall Panel Concrete Code Checks(Out-of-Plane) No Data to Print... TMS 402-16:ASD Wall Panel Masonry Code Checks(In-Plane) No Data to Print... CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 32 Page 89 of 97 111RISA Company Noesis Engineering Services 62 Designer : David Boyter,PE 6:24:46:24:46 PM Job Number 22083 Checked By:Jake Lucid... Model Name Robert Weed Plywood Interiod Members TMS 402-16:ASD Wall Panel Masonry Code Checks(Out-of-Plane) No Data to Print... Wall Panel TMS 402-16:ASD Masonry Code Checks for Lintels No Data to Print... AWC NDS-18:ASD Wall Panel Wood Code Checks(Axial) No Data to Print... AWC NDS-18:ASD Wall Panel Wood Code Checks(In-Plane) No Data to Print... AWC NDS-18:ASD Wall Panel Wood Code Checks(Header) No Data to Print... AISI S100-16:ASD Wall Panel CFS Code Checks(Axial) No Data to Print... AISI S100-16:ASD Wall Panel CFS Code Checks(In-Plane) No Data to Print... ACI 318-14 Wall Panel Concrete Code Checks(Seismic) No Data to Print... TMS 402-16:ASD Wall Panel Masonry Code Checks(Seismic) No Data to Print... Masonry Wall Suggested Design No Data to Print... Wood Wall Suggested Design No Data to Print... Envelope X-Direction Story Drift-Service No Data to Print... Envelope Z-Direction Story Drift-Service No Data to Print... Envelope X-Direction Story Drift-Strength No Data to Print... Envelope Z-Direction Story Drift-Strength No Data to Print... CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS RISA-3D Version 20 [MEMBER MODEL.r3d] Page 33 Page 90 of 97 R/SA Connection version 12.0.2 111RISA 06.08.2022 ASD BM G 1 - COL G 2:ASD Results Report Column/Beam Shear Tab Shear Connection Material Properties: Column HSS4X4X4 A992 FY=50000.00 psi F.=65000.00 psi Beam W12X72 A992 FY=50000.00 psi Fu=65000.00 psi Plate P0.31x3.50x9.0 A36 FY=36000.00 psi Fu=58000.00 psi 0 Input Data: Shear Load 15291.56 Ibs User Input Shear Load Axial Load 0.00 Ibs User Input Axial Force Column Force 15291.56 Ibs User Input Column Force Column Moment 0.00 lb-ft User Input Column Moment Governing LC: 3D-3- Deflection 3 Note:Unless specified,all code references are from AISC 360-16 Limit State Required Available Unity Check Result HISS Limitations PASS Geometry Restrictions at Beam PASS Column Weld Limitations PASS Rotational Ductility,Erection Stability PASS Beam Shear Yield 15291.56 Ibs 105780.00 Ibs 0.14 PASS Plate Shear Yield 15291.56 Ibs 40500.00 Ibs 0.38 PASS Beam Shear Rupture 15291.56 Ibs 81124.88 Ibs 0.19 PASS Plate Shear Rupture at Beam 15291.56 Ibs 34664.06 Ibs 0.44 PASS Beam Block Shear 15291.56 Ibs 103451.56 Ibs 0.15 PASS Plate Block Shear 15291.56 Ibs 34941.41 Ibs 0.44 PASS Lateral Stability/Stabilizer Plates 15291.56 Ibs 193756.93 Ibs 0.08 PASS Plate Flexural Yield 0.19 PASS Plate Flexural Rupture 0.25 PASS Plate Flexural Buckling 15291.56 Ibs 33557.28 Ibs 0.46 PASS Bolt Bearing on Beam 15291.56 Ibs 35784.70 Ibs 0.43 PASS Bolt Bearing on Plate at Beam 15291.56 Ibs 35751.00 Ibs 0.43 PASS Bolt Shear at Beam 15291.56 Ibs 26543.90 Ibs 0.58 PASS Bolt Group Eccentricity 0.74 Weld at Column 33981.25 Ibs/ft 89088.00 Ibs/ft 0.38 PASS HSS Punching Shear 2548.59 lb-ft 10222.88 lb-ft 0.25 pots CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS I of 1 Page 91 of 97 6 COMcheck Software Version 4.1.5.3 �( Interior Lighting Compliance Certificate Project Information Energy Code: 2018 IECC Project Title: Robert Weed Plywood Project Type: Alteration Construction Site: Owner/Agent: Designer/Contractor: 3351 Eldridge Ave Colby Ricks Twin Falls, ID 83301 Laughlin Ricks Architecture 134 3rd Ave E Twin Falls, ID 83301 208-736-8050 Allowed Interior Lighting Power A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts/ft2 (B X C) 1-Office 3650 0.79 2884 Total Allowed Watts= 2884 Proposed Interior Lighting Power A B C D E Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) Fixture Fixtures Watt. Office(3650 sq.ft.) LED 1:Other: 2 4 35 140 LED 2:Other: 4 37 40 1495 LED 3:Other: 4 5 40 202 Total Proposed Watts= 1837 Interior • Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. R. Colby Ricks 6-15-2022 Name-Title Signature Date CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Project Title: Robert Weed Plywood Report date: 06/15/22 Data filename: W:\COMcheck\Robert Weed.cck Page 1 of 6 Page 92 of 97 COMcheck Software Version 4.1.5.3 Inspection Checklist Energy Code: 2018 IECC Requirements: 0.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review Complies? Comments/Assumptions & Req.ID C103.2 Plans, specifications, and/or ❑Complies [PR4]1 calculations provide all information ❑Does Not with which compliance can be determined for the interior lighting ❑Not Observable and electrical systems and equipment ❑Not Applicable and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts,transformers and control devices. Additional Comments/Assumptions: CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 1 I High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3) Project Title: Robert Weed Plywood Report date: 06/15/22 Data filename: W:\COMcheck\Robert Weed.cck Page 2 of 6 Page 93 of 97 Section # Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID C405.2.2. .Spaces required to have light- ❑Complies 2 reduction controls have a manual ❑Does Not [EL22]1 control that allows the occupant to reduce the connected lighting load in ❑Not Observable a reasonably uniform illumination '❑Not Applicable pattern >= 50 percent. C405.2.1, Occupancy sensors installed in I❑Complies C405.2.1. classrooms/lecture/training rooms, :❑Does Not 1 conference/meeting/multipurpose [EL18]1 rooms, copy/print rooms, ❑Not Observable lounges/breakrooms, enclosed offices, ❑Not Applicable open plan office areas, restrooms, storage rooms, locker rooms, warehouse storage areas, and other spaces <= 300 sqft that are enclosed by floor-to-ceiling height partitions. Reference section language C405.2.1.2 for control function in warehouses and section C405.2.1.3 for open plan office spaces. C405.2.1. Occupancy sensors control function in ❑Complies 2 warehouses: In warehouses,the :❑Does Not [EL19]1 lighting in aisleways and open areas is controlled with occupant sensors that ❑Not Observable automatically reduce lighting power '❑Not Applicable by 50%or more when the areas are unoccupied.The occupant sensors control lighting in each aisleway independently and do not control lighting beyond the aisleway being controlled by the sensor. C405.2.1. Occupant sensor control function in ❑Complies 3 open plan office areas: Occupant j❑Does Not [EL20]1 sensor controls in open office spaces ❑Not Observable >= 300 sq.ft. have controls 1) ❑Not Applicable configured so that general lighting can pp e be controlled separately in control zones with floor areas <= 600 sq.ft. within the space, 2) automatically turn off general lighting in all control zones within 20 minutes after all occupants have left the space, 3)are configured so that general lighting power in each control zone is reduced by >= 80%of the full zone general lighting power within 20 minutes of all occupants leaving that control zone, and 4) are configured such that any daylight responsive control will activate space general lighting or control zone general lighting only when occupancy for the same area is detected. C405.2.2, Each area not served by occupancy ❑Complies C405.2.2, sensors(per C405.2.1) have time- ❑Does Not 1, switch controls and functions detailed C405.2.2. in sections C405.2.2.1 and C405.2.2.2. ❑Not Observable 2 ❑Not Applicable [EL21]z CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Robert Weed Plywood Report date: 06/15/22 Data filename: W:\COMcheck\Robert Weed.cck Page 3 of 6 Page 94 of 97 Section # Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID C405.2.3, ;Daylight zones provided with ❑Complies C405.2.3. individual controls that control the I❑Does Not 1, lights independent of general area C405.2.3. lighting. See code section C405.2.3 ❑Not Observable 2 Daylight-responsive controls for ;❑Not Applicable [EL23]2 applicable spaces, C405.2.3.1 Daylight, responsive control function and section C405.2.3.2 Sidelit zone. C405.2.4 Separate lighting control devices for ❑Complies [EL26]1 specific uses installed per approved I❑Does Not lighting plans. ❑Not Observable ❑Not Applicable C405.2.4 Additional interior lighting power ❑Complies [EL27]1 allowed for special functions per the I❑Does Not approved lighting plans and is automatically controlled and ❑Not Observable separated from general lighting. ❑Not Applicable C405.3 Exit signs do not exceed 5 watts per ❑Complies [EL6]1 face. ❑Does Not ❑Not Observable ❑Not Applicable C405. Low-voltage dry-type distribution ❑Complies [EL26] electric transformers meet the ❑Does Not minimum efficiency requirements of ❑ 'Table C405.6. Not Observable ❑Not Applicable C405.7 Electric motors meet the minimum ❑Complies [EL27]2 efficiency requirements of Tables :❑Does Not C405.7(1)through C405.7(4). ❑Not Observable Efficiency verified through certification under an approved certification ❑Not Applicable program or the equipment efficiency ratings shall be provided by motor manufacturer(where certification programs do not exist). C405.8.2, Escalators and moving walks comply ❑Complies C405.8.2. with ASME A17.1/CSA B44 and have j❑Does Not 1 j automatic controls configured to [EL28]2 'reduce speed to the minimum ❑Not Observable permitted speed in accordance with I❑Not Applicable ASME A17.1/CSA B44 or applicable local code when not conveying passengers. C405. Total voltage drop across the ❑Complies [EL29] combination of feeders and branch ❑Does Not circuits <= 5%. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: CITY APPROVED PLANS Reviewed for code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS r1 I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Robert Weed Plywood Report date: 06/15/22 Data filename: W:\COMcheck\Robert Weed.cck Page 4 of 6 Page 95 of 97 Section # Final Inspection Complies? Comments/Assumptions & Req.ID C303.3, Furnished O&M instructions for ❑Complies C408.2.5. systems and equipment to the j❑Does Not 2 building owner or designated [F117]3 representative. ❑Not Observable ; ❑Not Applicable C405.4.1 Interior installed lamp and fixture ❑Complies see the Interior Lighting fixture schedule for values. [F118]1 lighting power is consistent with what :❑Does Not is shown on the approved lighting plans, demonstrating proposed watts ❑Not Observable are less than or equal to allowed ❑Not Applicable watts. C408.1.1 Building operations and maintenance ❑Complies [F157]1 documents will be provided to the ❑Does Not owner. Documents will cover manufacturers' information, ❑Not Observable specifications, programming ❑Not Applicable procedures and means of illustrating to owner how building, equipment and systems are intended to be installed, maintained, and operated. C408.2.5. Furnished as-built drawings for �E]Complies 1 electric power systems within 90 days :❑Does Not [F116]3 of system acceptance. ❑Not Observable ❑Not Applicable C408.3 Lighting systems have been tested to ;❑Complies [F133]1 ensure proper calibration, adjustment, ;❑Does Not programming, and operation. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS 1 I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3) Project Title: Robert Weed Plywood Report date: 06/15/22 Data filename: W:\COMcheck\Robert Weed.cck Page 5 of 6 Page 96 of 97 CITY APPROVED PLANS Reviewed for Code Compliance PLANS MUST BE ON JOB SITE FOR ALL INSPECTIONS Project Title: Robert Weed Plywood Report date: 06/15/22 Data filename: W:\COMcheck\Robert Weed.cck Page 6 of 6 Page 97 of 97