An inspection was performed today for:
Permit #: 21-4998
Address: 214 CHENEY DR
Inspection Type: Shear Wall Inspection
Inspection Result: FAIL
Inspector Comments: John 749-7514 Please follow all blocking and nailing called out in shear wall schedule detail
2/S6.01 (nail patterns, 3x blocking, SDS to top plate connections, etc.), install missing OSB rip pieces in shear wall (not
concerned about fur down cripple walls above canopy area, but do need it installed in the actual shear walls), over driven
nails into OSB shear walls need to be re-nailed (1/16" over driven okay-deeper needs to be re-nailed), some HD"s are
missing and some nuts are not installed on HD's, please note there is a lot of drag struts and other connections designed
that we will inspect at framing inspection. Due to this being a Category IV building, we will need to follow the engineered
design very closely.