HomeMy WebLinkAbout17-1969 1925 Fillmore St #100 Restaurant TI Plan 6 COMcheck Software Version 4.0.6.2 �( Interior Lighting Compliance Certificate Project Information Energy Code: 2012 IECC Project Title: Blaze Pizza Project Type: Alteration Construction Site: Owner/Agent: Designer/Contractor: 2150 Filmore St. Aedifica Case Twin Falls, ID 83301 796 Merus Court St. Louis, MO 63026 636.349.1600 aedifica.com Allowed Interior Lighting Power A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts/ft2 (B X C) 1-Common Space Types:Bar/lounge/leisure dining 2896 1.40 4054 Total Allowed Watts= 4054 Proposed Interior Lighting Power A B C D E Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) Fixture Fixtures Watt. Common Space Types:Bar/lounge/leisure dining (2896 sq.ft.) PENDANT 1:PA1:Other: 1 11 10 104 PENDANT 1 copy 1: PA2:Other: 1 1 25 25 PENDANT 3:PA3:Other: Electronic: 1 10 10 95 LED 1: R1:Other: 1 19 14 266 LED 2: R2:Other: 1 9 14 126 Track lighting 1:CURRENT LIMITING: Wattage based on current limiting device capacity 0 0 120 120 Track lighting 1 copy 1:CURRENT LIMITING: Wattage based on current limiting device 0 0 120 120 capacity FLOURESCENT 1:FR6:Other: 2 7 28 196 LED 3:SA1:Other: 1 2 32 64 LED 4:SC3:Other: 1 4 5 22 LED 4 copy 1:TM1S:Other: 1 12 10 120 Linear Fluorescent 4: LF1:46"T5 54W: Electronic: 1 3 62 186 Total Proposed Watts= 1444 Interior Lighting PASSES Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been designed to meet the 2012 IECC requirements in COMcheck Version 4.0.6.2 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Pr Title: Bla Pizz Report date: 08/30/17 Dat Jena N 0 e gn Gro \BI a Iti 1-1#2' ID\Docs\Twin Falls, ID Page 1 of 7 C .c k y5\ONIAL FN Darrell R. Case 9316 08/30/2017 Name-Title Signature Date 09gTF OF 9FLL R•G Project Title: Blaze Pizza Report date: 08/30/17 Data filename: N:\2017\Lingle Design Group\Blaze Pizza\xlti-01-17 Twin Falls, ID\Docs\Twin Falls, ID Page 2 of 7 Comcheck.cck COMcheck Software Version 4.0.6.2 Inspection Checklist Energy Code: 2012 IECC Requirements: 100.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review Complies? Comments/Assumptions & Req.ID C103.2 Plans, specifications, and/or ❑Complies Requirement will be met. [PR4]1 calculations provide all information ❑Does Not with which compliance can be determined for the interior lighting ❑Not Observable and electrical systems and equipment ❑Not Applicable and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts,transformers and control devices. Additional Comments/Assumptions: 111 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Blaze Pizza Report date: 08/30/17 Data filename: N:\2017\Lingle Design Group\Blaze Pizza\xlti-01-17 Twin Falls, ID\Docs\Twin Falls, ID Page 3 of 7 Comcheck.cck Section # Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID C405.2.2. ;Automatic controls to shut off all ❑Complies Requirement will be met. 1 :building lighting installed in all j❑Does Not [EL22]2 buildings. ❑Not Observable j❑Not Applicable C405.2.1. Independent lighting controls installed ❑Complies Requirement will be met. 1 per approved lighting plans and all ❑Does Not [EL23]2 manual controls readily accessible and visible to occupants. ❑Not Observable ❑Not Applicable C405.2.1. Lighting controls installed to uniformly ❑Complies Requirement will be met. 2 reduce the lighting load by at least :❑Does Not [EL15]1 50%. ❑Not Observable UNot Applicable C405.2.2. Daylight zones provided with ❑Complies Requirement will be met. 3 individual controls that control the :❑Does Not [EL16]2 :lights independent of general area lighting. ❑Not Observable j❑Not Applicable C405.2. Sleeping units have at least one ❑Complies Exception: Requirement does not apply. [EL17] master switch at the main entry door :❑Does Not that controls wired luminaires and switched receptacles. ❑Not Observable ❑Not Applicable C405.2.2 Occupancy sensors installed in I❑Complies Requirement will be met. 2 required spaces. ❑Does Not [EL18]1 ❑Not Observable ❑Not Applicable C405.2.2. Primary sidelighted areas are ❑Complies Requirement will be met. 3 equipped with required lighting ❑Does Not [EL20]1 controls. ❑Not Observable ❑Not Applicable C405.2.2. Enclosed spaces with daylight area ❑Complies Exception: Requirement does not apply. 3 under skylights and rooftop monitors :❑Does Not [EL21]1 are equipped with required lighting controls. ❑Not Observable ❑Not Applicable C405.2.3 Separate lighting control devices for ;❑Complies Requirement will be met. [EL4]1 specific uses installed per approved I❑Does Not lighting plans. ❑Not Observable ❑Not Applicable C405.3 Fluorescent luminaires with odd ❑Complies Requirement will be met. [EL19]3 numbered lamp configurations that :❑Does Not are within 10 feet center to center(if recess mounted) or are within 1 foot ❑Not Observable edge to edge (if pendant or surface :❑Not Applicable mounted)shall be tandem wired. C405.4 Exit signs do not exceed 5 watts per ❑Complies Requirement will be met. [EL6]1 face. ❑Does Not ❑Not Observable j❑Not Applicable C405.2.3 Additional interior lighting power I❑Complies Requirement will be met. [EL8]1 allowed for special functions per the j❑Does Not approved lighting plans and is automatically controlled and ❑Not Observable separated from general lighting. '❑Not Applicable Additional Comments/Assumptions: 111 High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3) Project Title: Blaze Pizza Report date: 08/30/17 Data filename: N:\2017\Lingle Design Group\Blaze Pizza\xlti-01-17 Twin Falls, ID\Docs\Twin Falls, ID Page 4 of 7 Comcheck.cck I I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3) Project Title: Blaze Pizza Report date: 08/30/17 Data filename: N:\2017\Lingle Design Group\Blaze Pizza\xlti-01-17 Twin Falls, ID\Docs\Twin Falls, ID Page 5 of 7 Comcheck.cck Section # Final Inspection Complies? Comments/Assumptions & Req.ID C408.2.5. ;Furnished as-built drawings for ❑Complies Requirement will be met. 1 :electric power systems within 30 days :❑Does Not [F116]3 ;of system acceptance. ❑Not Observable ❑Not Applicable C303.3, Furnished O&M instructions for ❑Complies Requirement will be met. C408.2 systems and equipment to the j❑Does Not 2 building owner or designated [F117]3 representative. ❑Not Observable ❑Not Applicable C405.5.2 Interior installed lamp and fixture ❑Complies see the Interior Lighting fixture schedule for values. [F118]1 lighting power is consistent with what :❑Does Not is shown on the approved lighting plans, demonstrating proposed watts ❑Not Observable are less than or equal to allowed ❑Not Applicable watts. C408.3 Lighting systems have been tested to ❑Complies Requirement will be met. [F133]1 ensure proper calibration, adjustment, :❑Does Not programming, and operation. ❑Not Observable j❑Not Applicable Additional Comments/Assumptions: 1 I High Impact(Tier 1) 2 1 Medium Impact(Tier 2) 3 1 Low Impact(Tier 3) Project Title: Blaze Pizza Report date: 08/30/17 Data filename: N:\2017\Lingle Design Group\Blaze Pizza\xlti-01-17 Twin Falls, ID\Docs\Twin Falls, ID Page 6 of 7 Comcheck.cck Project Title: Blaze Pizza Report date: 08/30/17 Data filename: N:\2017\Lingle Design Group\Blaze Pizza\xlti-01-17 Twin Falls, ID\Docs\Twin Falls, ID Page 7 of 7 Comcheck.cck RESPONSIBILITY MATRIX PROJECT TEAM DIRECTORY SHEETINDEX w OWNER/OPERATOR F Q a ) L22 f U P2 I DD SHEET# TITLE REV DATE 0 NOTE: SEE EQUIPMENT SCHEDULE FOR DMSION OF EQUIPMENT ORDER,SUPPLY AND COMPANY NAME: PEACE,LOVE,AND PIZZA COVER SHEETS E w o NO INSTALLATION RESPONSIBILITY. r; CONTACT NAME: RACHELLE FENDERSON G001 ITITHE SHEET - - 0 In G.C.TO COORDINATE RESPONSIBILITY MATRIX'NTH TENANT REPRESENTATIVE/C.M. D G002 GENERAL NOTES o 3 w NO 3 ADDRESS: G003 VENDOR LIST r? m m J o¢J ILL LANDLORD,T=TENANT,G.C.=TENANT'S GENERAL CONTRACTOR,EXT=EXISTING PHONE: (907)750-1731 D G100 ACCESSIBILITY PLAN J - -w a 4 3 N EMAIL: bl02e@peacelovefronchises.com ARCHITECTURAL m o SMOOTH,LEVEL CONCRETE FLOOR WITH ADA TRANSITION REQUIREMENTS LL/G.0 LL/G.0 LANDLORD A100 EXISTING CONDITION PLAN m SAW CUT SLAB FOR NEW IN-FLOOR PLUMBING FIXTURES G.C. G.C. COMPANY NAME: D A110 CONSTRUCTION PLAN&DOOR SCHEDULE o�w 4 3 REPAIR,LEVEL AND SLOPE FINISHES AND TRANSITIONS G.C. G.C. CONTACT NAME: A A111 WALL TYPES z QUARRY TILE,BASE AND GROUT G.C. G.C. p CERAMIC TILE,BASE AND GROUT G.C. G.C. ADDRESS: A120 FINISH PLAN D CONCRETE STAIN/DYE G.C. G.C. PHONE: A130 REFLECTED CEILING PLAN FURRING AND INSULATION ILL ILL FAX: LOCATED AT: A200 EXTERIOR ELEVATIONS �0 2 SEPARATE ENTRY/EXIT DOORS AND HARDWARE LL LL EMAIL: p A300 INTERIOR ELEVATIONS J" SERVICE/EXIT DOOR AND HARDWARE LL LL CORPORATE CONTACT 19250 00"OFILLMORE ST Ste 100 w o_ ALUMINUM STOREFRONT AND GLAZING(1"INSULATED GLASS) LL LL COMPANY NAME: BLAZE PIZZA,INC. p Z Z 9 A400 ENLARGED RESTROOM PLAN GYPSUM BOARD G.C. G.C. CONTACT NAME: DAMES TRQO I TWIN FALLS ID 83301 A600 DETAILS 6"METAL STUD FRAMING LL LL PHONE: (626)584-5880 A610 FURNITURE PLAN -"' NSULATION,GYP.BD.,TAPED,SANDED AND READY TO RECEIVE TENANT FINISHES G.C. G.C. EMAIL: JAMES.TRUONGOBLAZEPIZZA.COM 3 (FIRE RATING IF APPLICABLE) "�• Q110 EQUIPMENT PLAN U.L.PENETRATION CAULKING AT RATED WALLS G.C. G.C. ARCHITECT g dad[®plea PLUMBING FRAMING,PLYWOOD BLOCKING AND GYP. G.C. G.C. COMPANY NAME: MINGLE DESIGN GROUP,INC. P100 PLUMBING LEGEND IS NOTES F.R.P.PANELS,WAINSCOTS,AND TILE WALL G.C. G.C. CONTACT NAME: MICHAEL PUCKETT Pilo SPECIFICATIONS&ISOMETRICS PONY WALL G.C. G.C. 1860 W.EVANS AVE. ADDRESS: P120 PLUMBING DETAILS z SNEEZE GUARD G.C. G.C. ENGLEWOOD,CO 80110 F STAINLESS STEEL CAP G.C. G.C. PHONE: (303)974-5873 P200 WASTE&VENT PIPING PLAN STAINLESS STEEL WALL FINISH G.C. G.C. EMAIL: MPUCKETT®LINGLEDESIGN.COM P210 DOMESTIC WATER PIPING PLAN PAINTING OR STAINING G.C. G.C. ATAS METAL PANELS G.C. G.C. MEP ENGINEER P220 GAS PIPING PLAN _ GYPSUM BOARD CEILING AND SOFFIT G.C. G.C. COMPANY NAME: AEDIFICA CASE ENGINEERING MECHANICAL LAY IN CEILING WITH SUSPENSION SYSTEM G.C. G.C. p CONTACT NAME: LINDSEY WNCRON `gy M100 SPECIFICATIONS DOORS,FRAMES AND HARDWARE G.C. G.C. 796 MERLE COURT ADDRESS:MENU BOARD SOFFIT G.C. G.C. ST.LOUIS,MISSOURI 63026 M200 HVAC PLAN MILLWORK VENDORT G.C. I PHONE: (636)349-1600 M210 HVAC ROOF PLAN _ COUNTERS VENDOR G.C. FAX: M300 DETAILS ®Au DRAW Ncs AND WRITTEN MATERIAL ODINTFURNITURE VENDOR G.C. EMAIL: LWINGRON®AEDIFICA.COM ME LINGLDE ovMx GROUPEINC.IR EY MAY 62 M400 DETAILS NOT BE REMSED,COPIED,AEUSED,OR KITCHEN EQUIPMENT VENDOR VENDOR DISCLOSED IN MY MANNER YATHOUT WRITTEN " OUTDOOR TABLES/CHAIRS/UMBRELLAS(IF SHOWN) VENDOR G.C. M410 DETAILS AUTHORIZATION FROM THE ARCHITECT EXTERIOR SIGN(SEPARATE PERMIT) VENDOR VENDOR ELECTRICAL C MENU BOARDS VENDOR G.C. AUG 30,2017 PLAN WINDOW GELS VEND R G.C. � E100 LIGHTING PLAN C F_ STENCIL LETTERING VENDOR G.C. a E300 ONLINE NOTES&SCHEDULES 1ARfC���F N EMPLOYEE WASH HANDS(LAVATORY) G.C. G.C. aV j• CAREt-••�n�� RESTROOM SIGNAGE G.C. G.C. �nT 4 4 E400 ONE-LINE NOTES&SCHEDULES BLAZE EMBLEM&HOURS VENDOR G.C. HVAC ROOF TOP UNIT(S),CURBS AND DROPS ROOF SPACE AND SUPPORT FOR HVAC EQUIPMENT LL LL ROOF REPAIRS AND FLASHING(USE LANDLORDS WARRANTY ROOFING CONTRACTOR). G.C. G.C. t� G�ixAZATE110lit OXXp\` WIRING AND CONNECTIONS G.C. G.C. DUCTWORK,DAMPERS AND GRILLES G.C. G.C. STATEMENT OF COMPLIANCE HEREBY CERTIFY THAT THESE PLANS WERE PREPARED UNDER THERMOSTATS AND CONTROLS LL LL MY DIRECT SUPERVISION AND TO THE BEST OF MY KNOWLEDGE AUG 30,2017 TOILET EXHAUST FAN G.C..C. G.C..C. AND BELIEF COMPLY WITH ALL APPLICABLE LAWS,CODES& CODE COMPLIANT AREA FOR EXHAUST FANS,MUA,ETC. G.C. G.C. ❑ ORDINANCES. \XXAAXAAQIAPI AAAZ7xi SANITARY WASTE LINE TO SPACE ILL ILL ❑ 0 gE ....•«y/)��i� GREASE TRAP OR GREASE LINE STUBBED INTO SPACE LL LL / 1_ tp�.•�q�L �FO�� f WATER METER AND SERVICE STUBBED TO PREMISES(MIN 1.5"LINE) LL LL I/�yl`/JI _ r-) CIS GAS METER AND SERVCE TO SPACE LL LL FINAL CONNECTIONS G.C. G.C. SI 0 GNATURE: �o\ a HVAC CONNECTIONS ILL ILL p O�r SA ARCHITECT/EN WEER ;Z. F w CO GAS PIPING A/C LL ILL I1 1L REGISTRATION NO.: AR 2319 �ipxxZZTEIp i XXXp ilk O _ WATER HEATERS G.C. G.C. L EXP.DATE: 09/24/2017 O _E Cf) PLUMBING FIXTURES G.C. G.C. L J J SEPARATELY METERED 400 AMP,120/208V,3 PHASE,4W SERVICE LL LL Li Q FLUSH MOUNTED PANEL WITH BREAKERS AND WITH 200 AMP BREAKER PANEL LL LL L1 FOR TENANTS SUB PANEL Q PHONE DEMARC BOX AND 2"CONDUIT WITH PULL STRINGS FROM DEMARC TO z TENANT SPACE PLANS ANALYSIS N 62 PHONE PANEL,EQUIPMENT AND CABLE PULLS G.C. G.C. SITE PLAN o LIGHT FIXTURES,MOUNTING ACCESSORIES,AND LAMPS(G.C.PURCHASED) VENDOR G.C. N N.T.S. BUILDING INFORMATION MUSIC SYSTEM AND SPEAKERS VENDOR VENDOR BUILDING CODES: B EXIT/EMERGENCY LIGHT SYSTEM G.C. G.C. BUILDING:INTERNATIONAL BUILDING CODE 2012 P.O.S.CONDUIT,CABLES&JACKS G.C. G.Q. N o final VICINITY MAP CONSTRUCTION PHASE NOTE MECHANICAL:INTERNATIONAL MECHANICAL&FUEL GAS CODE 2012 P.O.S.EQUIPMENT INSTALLATION T T SPRINKLER SYSTEM-BASE BUILDING AS REQUIRED PER NFPA INCLUDING 1 DROP ..... PLUMBING:IDAHO STATE PLUMBING CODE 2015 PER 150 S.F.INCLUDING CENTRAL BUILDING ALARM SYSTEM AND ALL ON PREMISE Certificate of ARCHITECTS DESIGN WITHOUT CONSTRUCTION PHASE SERVICES ALARM DEVISES SUITABLE FOR TENANTS SERVICE,ILL TO COORDINATE WITH TENANT ILLILLELECTRICAL NATIONAL ELECTRICAL CODE 2017 REGARDING REQUIRED FIRE ALARM PROVISIONS AND INTEGRATIONS WITH BASE SINCE DIRECT CONSTRUCTION OBSERVATIONS AND REVIEW OF THE CONTRACTOR'S PERFORMANCE IS NOT FIRE:INTERNATIONAL FIRE CODE 2012 BUILDING SYSTEM. INCLUDED AS PART OF THE ARCHITECT'S BASIC SERVICES,IT IS UNDERSTOOD THAT SUCH RESPONSIBILITIES _ MODIFYING EXISTING SPRINKLER SYSTEM(IF APPLICABLE) G.C. G.C. rr WILL BE ASSUMED BY OTHERS.LINGLE DESIGN GROUP AVAILS ITSELF TO THE CLIENT,THE CONTRACTOR,AND ENERGY:INTERNATIONAL ENERGY CONSERVATION CODE 2012 " ALARM SYSTEM-TIE INTO BASE BUILDING ALARM SYSTEM(IF APPLICABLE) G.C. G.C. Occupancy ANY OTHER PARTIES AS NECESSARY(VIA TELEPHONE,FAX,AND EMAIL)IN ORDER TO ASSIST IN PROVIDING ACCESSIBILITY:ICC/ANSI A117.1 shell �.•, CLARIFICATIONS OR RESOLVING ISSUES AND PROBLEMS THAT MAY ARISE.ALTHOUGH MANY ISSUES CAN BE until the S h e I I EASILY ADDRESSED WITHOUT THE ARCHITECTS INVOLVEMENT, HERE ARE MES WHEN PARTICIPATION IS BUILDING INFORMATION: ADVISABLE.DETERMINATION OF WHEN INVOLVEMENT IS APPROPRIATE IS LEFT TO THE PROFESSIONAL BUILDING HEIGHT:1 STORY DISCRETION OF THE CONTRACTOR.IT IS UNDERSTOOD THAT THE CLIENT AND/OR THE CONTRACTOR ASSUMES CONSTRUCTION I -B ALL RESPONSIBILITY FOR INTERPRETATION OF THE DRAWINGS,AND ANY OTHER SUPPLEMENTAL INFORMATION, TENANT SPACE INFORMATION: building has AND WHEN THE ARCHITECT IS DENIED THE OPPORTUNITY TO PROVIDE CLARIFICATIONS OR PARTICIPATE IN SCOPE OF WORK TENANT BUILD OUT CHANGES TO THE DESIGN OR THE RESOLUTION OF ISSUES OR PROBLEMS,ALL PARTIES WAIVE ANY CLAIMS LEASE AR :T023 S.F. AGAINST THE ARCHITECT THAT MAY BE IN ANY WAY CONNECTED THERETO.LINGLE DESIGN GROUP IS HELD HARMLESS FROM LOSS,CLAIM,OR COSTS ARISING OR RESULTING FROM MODIFICATIONS OR CHANGES MADE TO FIRE PROTECTION:SPRINKLED,ALARMED,AND PORTABLE FIRE EXTINGUISHERS NOTE: THE DESIGN(WITHOUT THE KNOWLEDGE OF THE ARCHITECT)DUE TO CONDITIONS OR CIRCUMSTANCES NUMBER OF EMPLOYEES a THESE DRAWINGS WERE PRODUCED FROM EXISTING BASE been f i n a I e d. (ANTICIPATED OR NOT)BEYOND THE ARCHITECT'S CONTROL. OCCUPANC A2 SHELL INFORMATION PROVIDED TO LINGLE DESIGN GROUP, INC.BY OTHERS, LINGLE DESIGN GROUP,INC.DID NOT CRITICAL PLUMBING NOTE OCCUPANT LOAD:88 > 1,d PERFORM A SITE SURVEY OF THE EXISTING CONDITIONS AND DOES NOT WARRANT THE ACCURACY OF THE - - THE RELATIONSHIP BETWEEN FLOOR SINKS AND NEW WALLS IS CRITICAL TO THE FINAL FIXTURE/EQUIPMENT EXISTING BASE SHELL SPACE. NOTE: LAYOUT.FLOOR SINKS AS SHOWN ON THE PLUMBING PLANS ARE DIMENSIONALLY LOCATED OFF OF NEW CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID,TO CONFIRM FIELD CONDITIONS FOR DUCTWORK RUNS,EXHAUST PARTITIONS,AND THEREFORE THE CONTRACTOR MUST COMPLETE PLAN LAYOUT ON SLAB PRIOR TO FINAL PROD NUMB 7-420 AND CHASE LOCATIONS. LOCATION OF FLOOR SINKS FOR ACCURATE FINAL PLACEMENT. ABBREVIATIONS DRA BY: RP EC CH MP m DIAMETER BLKG. BLOCKING DS. DOWN SPOUT F.H. FIRE HYDRANT HT. HEIGHT MTL METAL R.O.W. RIGHT OF WAY T. TREAD W/ WTH SYMBOL LEGEND SHEE OF SQUARE FOOT/FEET TWO. DRAWING F.O.F. FACE OF FINISH H.M. HOLLOW METAL MFR. MANUFACTURER PARTIN. PARTITION T.B. TOP OF BEAM W.C. WATER CLOSET A ® AT C/J CEILING JOIST F.O.M. FACE OF MASONRY NOR. HORIZONTAL M.H. MANHOLE P.L. PROPERTY LINE S. SOUTH T.B.D. TO BE DETERMINED W. WOOD DETAIL NUMBER # A c CENTERLINE CMG. CEILING E. EAST F.O.S FACE OF STUD HOWD. HARDWOOD MIN. MINIMUM PEAS. PLASTER &A.N. SCALE AS NOTED TEE. TELEPHONE W.H. WATER HEATER DETAIL NUMBER @ POUND OR NUMBER CUR. CLEAR EA. EACH F/S FLOOR SINK HVAC HEATING,VENTILATION AND AIR MISC. MISCELLANEOUS PLBG. PLUMBING S.A.T. SUSPENDED ACOUSTIC TILE T&G TONGUE AND GROOVE W/O WITHOUT FINISH TYPE MARKER ITLE (E) EXISTING C.M. CONSTRUCTION MANAGER ELEG ELECTRICAL F.S.R. FIRE SPRINKLER RISER CONDITIONING M.O. MASONRY OPENING FUND. PLYWOOD S.C. SOLID CORE LIN. THICKNESS W.R. WATER RESISTANT (/�/��/�(� SHEET NUMBER (N) NEW C.M.U. CONCRETE MASONRY UNIT EL. ELEVATION FT FOOT/FEET MTD. MOUNTED P.T. PRESSURE TREATED SCHED. SCHEDULE TO TOP OF CURB ` `SHEET NUMBER R SH T C/O CLEANOUT E.P. ELECTRICAL PANEL FLO. FOOTING I.O. INSIDE DIAMETER MUL. MULLION SECT. SECTION T.O.P. TOP OF PARAPET DOOR&WINDOW TYPE A.B. ANCHOR BOLT GONG CONCRETE EQ. EQUAL PUT. FUTURE IN. INCH Q.T. QUARRY TILE SUIT. SHEET TO.S. TOP OF SHEATHING Building Plans ha a EXTERIOR ELEVATION MARKER SECTION MARKER A/C AIR CONDITIONING COIN. CONNECTION EQUIP. EQUIPMENT INSUL. INSULATION N. NORTH SNTG. SHEATHING T.O.W. TOP OF WALL been reviewed and a roved CODED NOTE REFERENCE ACOUS. ACOUSTICAL CONSTR. CONSTRUCTION E.W. EACH WAY GA. GAUGE INT. INTERIOR N.I.C. NOT IN CONTRACT R. RISER SIM. SIMILAR TYP. TYPICAL A.F.F. ABOVE FINISH FLOOR CONT CONTINUOUS EXIS. EXISTING CALV. GALVANIZED JT. JOINT NO. NUMBER FAX RADIUS SPEC. SPECIFICATION UBC UNIFORM BUILDING CODE H ALUM. ALUMINUM COMM CONTRACTOR EXT. EXTERIOR G.C. GENERAL CONTRACTOR N.T.S. NOT TO SCALE R.D. ROOF DRAIN SO. SQUARE U.N.O. UNLESS OTHERWISE NOTED All Construction Subj Ct to SUB-DETAIL NUMBER 1F� SHEE UMBER: aAPROx. APPROXIMATE G.I. GALVANIZED IRON LAM. LAMINATED REF. REFERENCE SSK. SERVCE SINK DETAIL NUMBER DETAIL NUMBER WALL TYPE MARKER Field Inspectio ARCH. ARCHITECTURAL DBE. DOUBLE F.F. FINISH FLOOR Ci. GLASS LAN. LAVATORY O.A. OVERALL REFR. REFRIGERATOR SS. STAINLESS STEEL V.B. VINYL BASE J A.S.R. AUTOMATIC SPRINKLER SYSTEM DEPT. DEPARTMENT FIN. FINISH GND. GROUND Li. LIGHT O.C. ON CENTER RED*. REINFORCED ITS. STANDARD VERT. VERTICAL # # # #N# DET. DETAIL FIXT. FIXTURE OR. GRADE O.D. OUTSIDE DIAMETER REO'D. REQUIRED SR. STEEL V.C.T. VINYL COMPOSITION TILE Page.#: 8 of 38 SHEET NUMBER SHEET NUMBER EQUIPMENT TYPE BD. BOARD D.F. DRINKING FOUNTAIN OUR. FLOOR GYP. GYPSUM MAX. MAXIMUM OFD. OVERFLOW DRAIN RESIL RESILIENT STOP. STORAGE STRUCTURAL V.T.R. VENT THROUGH ROOF # CL TYP. BLDG. BUILDING CIA DIAMETER F.L. FLOW LINE HDR. HEADER M.B. MACHINE BOLT OPG. OPENING RM. ROOM SYM. SYMMETRICAL +- BLK. BLOCK DIM. DIMENSION FLOUR. FLUORESCENT HOW. HARDWARE MECH. MECHANICAL OPP. OPPOSITE R.O. ROUGH OPENING W. WEST Date: 9/8/17 INTERIOR ELEVATION MARKER DETAIL MARKER ELEVATIO • w o N f w m N o DIVISION 1 -GENERAL CONDITIONS DIVISION 1-GENERAL CONDITIONS DIVISION 1-GENERAL CONDITIONS DIVISION 1 -GENERAL CONDITIONS LANDLORD WORK LETTER o -o ¢0. m z_ .0 Nomm CJ ¢� ¢U m. A)CONSTRUCTION OBSERVATION SERVICES 6. LOADS AND CODE RESTRICTIONS FOR ALL DESIGN CONSIDERATIONS SHALL CONFORM TO 7. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED ACCESSORIES, 4. ALL MATERIALS AND FINISHES INDICATED ON DRAWINGS SHALL BE NEW AND UNUSED. b.ROOF ACCESS: FURNISH AND INSTALL A CODE COMPLIANT AND OSHA APPROVED ROOF ACCESS �_ F� w o N m°w LOCAL,STATE AND ALL GOVERNING CODES. OPTIONS,MOUNTING HARDWARE AND FIELD FABRICATION REQUIRED TO PROPERLY ADAPT THE 5. NO MATERIAL SUBSTITUTIONS WILL BE PERMITTED UNLESS AUTHORIZATION HAS BEEN LADDER OR STAIR,OUTSIDE OF TENANT'S LEASED PREMISES,FOR TENANT'S USE. ROOF ACCESS m d 3°o m m u 1.) DIRECT CONSTRUCTION OBSERVATIONS AND REVIEW OF THE CONTRACTOR'S PERFORMANCE IS 7. THE CONTRACTOR SHALL ARRANGE FOR ALL INSPECTIONS NECESSARY TO OBTAIN FIXTURES TO THE SPECIFIC APPLICATIONS. GRANTED BY THE BRAND OWNER DESIGN AND CONSTRUCTION DEPARTMENT AND THE FRANCHISEE. IS TO BE UNOBSTRUCTED AND ACCESSIBLE TO TENANT 24 HOURS A DAY,7 DAYS A WEEK,365 m w w o w ..m CERTIFICATE OF OCCUPANCY. 8. ELECTRICAL CONTRACTOR SHALL CLEARLY LABEL PANEL BOARD CIRCUITING AS TO ANY MATERIAL SUBSTITUTIONS WITHOUT AUTHORIZATION WILL SUBJECT THE CONTRACTOR TO DAYS A YEAR. z;i 3 NOT INCLUDED AS PART OF THE ARCHITECT'S&ENGINEER'S BASIC SERVICES. IT IS UNDERSTOOD u m m o¢ THAT SUCH RESPONSIBILITIES WILL BE ASSUMED BY OTHERS. LINGLE DESIGN GROUP&THEIR B. THE CONTRACTOR SHALL MAINTAIN,FOR THE ENTIRE LENGTH OF HIS CONTRACT,EXITS,EXIT OPERATION. REPLACEMENT OF SUCH SUBSTITUTED MATERIALS NTH APPROVED MATERIALS AT THE SOLE z N z x 3 CONSULTANTS AVAIL THEMSELVES TO THE CLIENT,CONTRACTOR AND OTHER PARTIES AS LIGHTING,FIRE PROTECTIVE DEVICES,AND ALARMS TO CONFORM TO LOCAL BUILDING CODE 9. ALL ELECTRICAL DEVICES SHALL BEAR THE U.L. LABEL. EXPENSE OF THE CONTRACTOR. c.WALLS: 7 w a NECESSARY(VIA TELEPHONE,FAX AND E-MAIL)IN ORDER TO ASSIST IN PROVIDING REQUIREMENTS AND LANDLORD REQUIREMENTS. 10. ALL ELECTRICAL WORK SHALL FOLLOW ALL APPLICABLE NATIONAL,STATE&LOCAL CODES, 6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE TIMELY ARRIVAL OF ALL SPECIFIED CLARIFICATIONS OR RESOLVING ISSUES AND PROBLEMS. 9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING REGULATIONS AND LAWS. FINISH MATERIALS,EQUIPMENT,LIGHT FIXTURES,AND ANY OTHER MATERIALS TO BE UTILIZED IN H.FURNISH AND INSTALL DEMISING WALLS TO BE FULL HEIGHT WOOD OR METAL STUD WALLS WORK DURING CONSTRUCTION AGAINST DAMAGE,BREAKAGE,COLLAPSE,DISTORTION AND/OR 11. REFER TO LIGHT FIXTURE SCHEDULE FOR FINISH OF LIGHT FIXTURE TRIM. THE PROJECT. THE G.C. SHALL NOTIFY THE ARCHITECT/DESIGNER IN WRITING WITHIN 10 DAYS FRAMED WITH 20GA STUDS AT 16"ON CENTER AND FINISHED WITH 5/8"DRYWALL ON ADJACENT MISALIGNMENT IN ACCORDANCE WITH APPLICABLE CODES,STANDARDS AND GOOD PRACTICE. 12. WHERE/IF EXISTING CEILINGS ARE SCHEDULED TO REMAIN,&ARE DAMAGED OR OTHERWISE OF DATE OF CONTRACT OF THOSE ITEMS SPECIFIED THAT ARE NOT READILY AVAILABLE. IF TENANT SPACE(SO THAT A RATED WALL ASSEMBLY EXISTS ONCE TENANT SIDE IS FINISHED). B)EXAMINATION 10. WORK AND/OR CONSTRUCTION OPERATIONS SHALL NOT UNDERMINE THE STRUCTURAL MODIFIED TO ACCOMMODATE THE NEW LAYOUT,THE G.C. SHALL PATCH,REPAIR OR RESTORE AS NOTIFICATION IS NOT RECEIVED,THE G.C. ACCEPTS RESPONSIBILITY FOR THE PROPER ORDERING ALL PENETRATIONS TO BE FIRE RATED AND SEALED PER CODE. INTEGRITY OF THE BUILDING. REQUIRED TO"LIKE NEW"CONDITION. AND FOLLOW-UP OF SPECIFIED ITEMS SO AS NOT TO CREATE A HARDSHIP ON THE OWNER,AND ii.FURNISH AND INSTALL APPROPRIATE FUMING AND INSULATION(R-19 MINIMUM)ON ALL EXTERIOR D 1. DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE COMPLIMENTARY. SPECIFIC 11. WHERE A FIRE RESISTANCE CLASSIFICATION IS INDICATED OR REQUIRED FOR CONSTRUCTION, 13. IF ANY LIGHTS ARE SPECIFIED IN A LOCATION EXPOSED TO THE WEATHER,ELECTRICAL NOT TO DELAY PROGRESS OF THE WORK. NO EXTENSION OF TIME TO THE CONTRACT WILL BE WALLS. D INFORMATION MAY BE FOUND IN EITHER OR BOTH. PROVIDE MATERIALS,ACCESSORIES AND APPLICATION PROCEDURES WHICH COMPLY WITH THE CONTRACTOR SHALL OBTAIN A SIMILAR FIXTURE RATED FOR EXTERIOR APPLICATION. ALLOWED FOR G.C.'S INABILITY TO SECURE SPECIFIED ITEMS. 2. THE CONTRACTOR IS HEREBY SPECIFICALLY DIRECTED,AS A CONDITION OF THE CONTRACT, REQUIREMENTS OF ILL"FIRE RESISTANCE INDEX"FOR THE ILL DESIGN NUMBERS CORRESPONDING 14. IF EXISTING MECHANICAL AND FIRE PROTECTION SYSTEMS ARE PRESENT,CONTRACTOR 7. COORDINATE WITH OWNER'S REPRESENTATIVE FOR DELIVERY AND PLACEMENT OF OWNER d.CEILING: PROVIDE AN OPEN STRUCTURE ABOVE WITH A MINIMUM 14'CLEARANCE. ALL LANDLORD TO ACQUAINT HIMSELF WITH THE ARTICLES CONTAINED IN THE GENERAL NOTES,AND TO NOTIFY WITH THE CONSTRUCTION ASSEMBLIES INDICATED. SHALL REWORK THE SYSTEMS TO ACCOMMODATE THE NEW CEILING AND WALL LAYOUTS. SUPPLIED ITEMS AND FURNISHINGS. OBSTRUCTION H.E.DUCTWORK,FIRE SPRINKLERS,WATER LINES,GAS LINES,ETC.)MUST BE ib AND APPRISE ALL SUBCONTRACTORS AND ALL OTHER PARTIES OF THE CONTRACT OF,AND BIND 12. ALL COMBUSTIBLE MATERIALS SHALL MEET APPLICABLE CODES. WOOD SHALL BE 15. USE OF THE ABOVE CEILING PLENUM AREA AS A RETURN AIR SYSTEM IS NOT ACCEPTABLE. 8. REFER TO FINISH SCHEDULE FOR SPECIFIED FINISHES. ABOVE TWELVE FEET(12'). THEM TO ITS CONDITIONS. FIRE-RETARDANT TREATED WHERE REQUIRED BY LOCAL BUILDING CODES. RETURN AIR SHALL BE DUCTED TO THE CEILING. 9. ALL DOOR AND WINDOW FRAMES SHALL BE CAULKED AROUND ENTIRE PERIMETER. 3. PRIOR TO SUBMITTING BID,CONTRACTOR SHALL OBTAIN A COPY OF THE LEASE/TENANT 13. THE CONTRACTOR SHALL PROVIDE BACK FLOW DEVICES AS REQUIRED BY LOCAL,STATE AND 16. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY TESTING AND BALANCING 10. CONTRACTOR SHALL CAULK BETWEEN BASE AND FLOOR WITH CLEAR SILICONE SEALANT. e.STOREFRONT: AGREEMENT,AND ANY EXHIBITS AND/OR DESIGN CRITERIA THAT PERTAIN TO TENANT BUILD OUT. FEDERAL CODES. OF ANY REWORKED MECHANICAL SYSTEM. 11. CONTRACTOR SHALL SHALL TAPE AND BED ALL WALLS FOR A SMOOTH PAINTED FINISH. ALL INFORMATION SHALL BE NOTED FOR RESPONSIBILITIES AND COORDINATION. 14. THE GENERAL CONTRACTOR SHALL INSTALL SAFETY BARRIERS DURING CONSTRUCTION AS 12. G.C.IS RESPONSIBLE FOR THE SECURITY,CARE AND DAMAGE PREVENTION OF ALL H.FURNISH AND INSTALL AN ANODIZED ALUMINUM INSULATED GLAZING SYSTEM WITH 1"CLEAR,LOW 4. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN PARTITION LOCATIONS,DIMENSIONS NECESSARY TO PROTECT THE PUBLIC FROM INJURY AND ACCESS TO THE SITE. REVIEW SPECIFIC 1)OWNER FURNISHED ITEMS MATERIALS AFTER DELIVERY TO JOB SITE. G.C.WILL BE CHARGED FOR DAMAGES AND MISSING E AND TEMPERED GLASS. THE STOREFRONT SYSTEM TO BE DEPICTED ON TENANT'S PLANS, AND TYPES. DOOR AND WINDOW LOCATIONS SHALL BE AS SHOWN ON CONSTRUCTION PLAN. IN REQUIREMENTS WITH THE BUILDING,MUNICIPAL,AND LANDLORD'S TENANT COORDINATOR PRIOR TO ITEMS. DELIVER AND STORE MATERIAL IN SEALED CONTAINERS FULLY IDENTIFIED WITH SUBJECT TO LANDLORD'S APPROVAL AND MUST MEET ALL CODE REQUIRED IMPACT-RATING CASE OF CONFLICT,NOTIFY DESIGNER/ARCHITECT FOR WRITTEN CLARIFICATION PRIOR TO BEGINNING CONSTRUCTION. 1. PRODUCTS TO BE FURNISHED AND PAID FOR BY THE OWNER AND INSTALLED BY THE MANUFACTURERS NAME,BRAND,TYPE AND GRADE. PROTECT MATERIALS FROM CORROSION AND AND/OR TEMPERED GLAZING REQUIREMENTS. PROCEEDING WITH CONSTRUCTION. CONTRACTOR ARE INDICATED AS"OWNER SUPPLIED"IN THE EQUIPMENT SCHEDULE. DAMAGE. STORE IN A DRY VENTILATED SPACE OFF OF THE GROUND. COORDINATE ALL ii.FURNISH AND INSTALL ONE(1)SET OF MATCHING STOREFRONT DOUBLE DOORS(6'-O"X 7'-01 5. ANY DETAILS OR NOTES REQUIRING FIELD VERIFICATION BY THE CONTRACTOR ARE TO BE 2. OWNER'S RESPONSIBILITIES FOR OWNER FURNISHED PRODUCTS: DELIVERIES WITH THE LANDLORD AND TENANT SUPPLIED MATERIAL VENDORS. WITH CODE COMPLIANT PANIC HARDWARE. DOORS TO BE LOCATED PER TENANT'S PLANS, DONE DURING THE BID PROCESS. DISCREPANCIES FOUND AFTER THE CONTRACTOR IS SELECTED G)LAYOUT OF WORK -SUPPLY CONTRACTOR WITH PRODUCT LITERATURE,OWNER REVIEWED. SUBJECT TO LANDLORD'S APPROVAL. WILL BE THE RESPONSIBILITY OF THE CONTRACTOR AND CORRECTED AT THE CONTRACTORS -PRODUCT DATA AND SAMPLES. 1. EXERCISE PROPER PRECAUTIONS TO VERIFY ALL EXISTING CONDITIONS AND LAYOUT OF -PAY FOR PRODUCT DELIVERY TO SITE. 0)GENERAL CLEANING EXPENSE. f.REAR EXIT DOOR: FURNISH AND INSTALL ONE(1)3'-0"X T-O"GLASS AND ALUMINUM DOOR 6. THE CONSTRUCTION MANAGER SHALL BE IMMEDIATELY NOTIFIED OF ANY APPARENT WORK. CONTRACTOR IS RESPONSIBLE FOR ANY ERROR RESULTING FROM FAILURE TO EXERCISE -REVIEW DAMAGED PRODUCTS WITH CONTRACTOR PROMPTLY. WITH PANIC HARDWARE AS REQUIRED BY CODE,KICK PLATE AND PEEPHOLE. DOOR TO BE CONFLICTS,ERRORS,OR OMISSIONS IN THE CONSTRUCTION DRAWINGS; ANY APPARENT SUCH PRECAUTIONS. ANY SUCH ERROR WILL NOT BE CONSIDERED AS A BASIS FOR EXTRA -SUBMIT CLAIMS FOR DAMAGE. REPLACE DAMAGED,DEFECTIVE OR DEFICIENT ITEMS. 1. THE CONTRACTOR IS RESPONSIBLE FOR ALL TRASH REMOVAL,INCLUDING TRASH MADE BY LOCATED WHERE SHOWN ON TENANT'S PLANS,SUBJECT TO LANDLORD'S APPROVAL. MISAPPLICATION OF ANY PRODUCT,SYSTEM OR ASSEMBLY FOR THE INTENDED USE,OR ANY COMPENSATION. -ARRANGE FOR MANUFACTURER'S WARRANTIES,INSPECTIONS AND SERVICE. ALL OTHER TRADES. INDIVIDUAL TRADES SHALL KEEP THE SPACE CLEAN AND CLEAR OF REFUSE DISCOVERED EXISTING CONDITIONS THAT ARE CONTRARY TO THE CONDITIONS INDICATED IN THE 2. CONTRACTOR SHALL PROMPTLY NOTIFY ARCHITECT IF SUBSURFACE OR OTHERWISE AT ALL TIMES. CONDUCT CLEANING&DISPOSAL OPERATION TO COMPLY WITH CODES, g.FLOOR: FURNISH AND INSTALL,THROUGHOUT THE LEASED PREMISES,A LEVEL AND COMPACTED CONSTRUCTION DRAWINGS. THE CONSTRUCTION MANAGER SHALL PROVIDE INTERPRETATION AND CONCEALED PHYSICAL CONDITIONS DIFFER MATERIALLY FROM THOSE INDICATED IN THE CONTRACT 3. CONTRACTOR'S RESPONSIBILITIES FOR OWNER FURNISHED PRODUCTS: ORDINANCES,REGULATIONS&LANDLORD REQUIREMENTS. AT COMPLETION OF PROJECT, SUBGRADE,SUBBASE AND BASE PER CODE TO 4"BELOW FINISHED FLOOR ELEVATION(CAPABLE CLARIFICATION AND,IF REQUIRED,MAKE APPROPRIATE REVISIONS TO THE CONSTRUCTION DOCUMENTS,OR DIFFER FROM THOSE CONDITIONS ORDINARILY FOUND TO EXIST&GENERALLY -REVIEW SHOP DRAWINGS,PRODUCT DATA AND SAMPLES TO ADEQUATELY ACQUAINT CONTRACTOR SHALL REMOVE ALL CONTRACTOR'S TOOLS,CONSTRUCTION EQUIPMENT,MACHINERY OF SUPPORTING TENANT'S 6,000 ITS.OVEN). DRAWINGS. ANY RFI'S SHALL GO THIRD CONSTRUCTION MANAGER TO DESIGNER/ARCHITECT. RECOGNIZED AS INHERENT IN CONSTRUCTION ACTIVITIES OF THIS NATURE. HIMSELF WITH THE SCOPE OF WORK. &SURPLUS MATERIALS FROM THE JOB SITE,&SHALL HIRE A PROFESSIONAL CLEANING COMPANY FAILURE TO NOTIFY THE CONSTRUCTION MANAGER PRIOR TO PROCEEDING WITH RELATED WORK 3. THE CONTRACTOR SHALL NOT SCALE THE DRAWINGS. -REVIEW THE ORDER; SCHEDULE THE DELIVERY; RECEIVE,UNLOAD AND STORE PRODUCTS FOR FINAL CLEANUP BEFORE TURNING COMPLETED STORE OVER TO OWNER/TENANT. h.ELECTRICAL: WILL RESULT IN THE CONTRACTOR CORRECTING SUCH ITEMS AT THE CONTRACTOR'S EXPENSE. 4. CONTRACTOR IS RESPONSIBLE FOR LAY OUT OF ALL WORK AND IS RESPONSIBLE FOR ALL AT SITE. 7. THE CONSTRUCTION DRAWINGS ARE GENERAL DIAGRAMMATIC REPRESENTATIONS OF THE LINES AND MEASUREMENTS OF THE BUILDING,UTILITIES,AND OTHER WORK EXECUTED UNDER THE -INSPECT FOR COMPLETE OR DAMAGE. IF ITEMS ARE DAMAGED,CONTRACTOR TO NOTIFY I.FURNISH AND INSTALL ONE 400 AMP 120 208 VOLT,3 PHASE,4 WIRE CLEAN ELECTRICAL WORK,AND DO NOT INDICATE OR SPECIFY IN DETAIL,EVERY CONDITION AND COMPONENT OF CONTRACT(INCLUDING THE WORK OF ALL TRADES),&SHALL ENSURE THAT THE WORK PERFORMED PROJECT MANAGER AND OWNER. P)ACCESSIBILITY SERVICE(SEPARATELY METERED)WITH APPROPRIATELY SIZED METER BASE,CONDUIT AND CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL LABOR,MATERIALS AND EQUIPMENT, COMPLIES WITH APPROVED DRAWINGS. DISCONNECT. 0ALL DRA'MNGS AND RRITTEN MATERIAL FABRICATE ALL ASSEMBLIES AND INSTALL ALL EQUIPMENT AND SYSTEMS TO PRODUCE A 5. PARTITIONS ARE DIMENSIONED FROM FACE OF STUD TO FACE OF STUD,UNLESS OTHERWISE 1. NOTE: FOLLOWING ARE ADA GUIDELINES AND FOR CONTRACTOR INFORMATION ONLY. LISTED ii.FURNISH AND INSTALL ONE 60-POLE,400 AMP,120/208 VOLT,4 WIRE FLUSH MOUNT MAIN CONTAINED HEREIN ARE ME PROPERTY OF COMPLETE,INTEGRATED AND FULLY FUNCTIONAL WORK PRODUCT IN ACCORDANCE WITH ALL NOTED. DIMENSIONS MARKED"CLEAR"SHALL BE MAINTAINED AND SHALL ALLOW FOR THICKNESS AALTERATIONS/DEMOLITION(IF APPLICABLE) ITEMS DO NOT REPLACE OR AMEND FEDERAL,STATE OR LOCAL CODES. IN CASE OF CONFLICT IN DISTRIBUTION PANEL. TIE UNG_E DESIa DROOP,INC.THEY MAY BE OF FINISHES INCLUDING TILE,FRP,ETC. DIMENSIONS MARKED"CLEAR"ARE TO BE WITHIN,g" THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION,THE MOST RESTRICTIVE REQUIREMENTS iii.FURNISH AND INSTALL ONE 42-POLE,225 AMP 120208 VOLT,3 PHASE,4 WIRE FLUSH olscNOT roseD IN .COP lnwIED,REUSED,OR x ANv MANNER ouT nRITTEN MATERIAL AND EQUIPMENT MANUFACTURER'S REQUIREMENTS,INDUSTRY STANDARDS AND FEDERAL, ALONG FULL HEIGHT AND FULL WIDTH OF WALLS. 1. ARRANGE NTH LANDLORD MEANS/OF OWNER A CONVENIENT TIME TO PERFORM ALL WORK AND INSTALL SHALL GOVERN. MOUNTED SUB PANEL. AUTHGRIZATON MOM WE ARCHITECT. 8. PRIOR TO ACCEPTANCE OF SUB-CONTRACTOR BIDS AND COMMENCEMENT OF CONSTRUCTION, STATE AND LOCAL LAWS,CODES AND REGULATIONS. 6. ALL ROUGH OPENINGS AND DIMENSIONS LABELED"HOLD"ARE CRITICAL AND ARE NOT TO BE TEMPORARY PROTECTED EGRESS FROM REQUIRED EXITS,INCLUDING TEMPORARY 2. ALL LOCKSETS SHALL HAVE A LEVER HANDLE UNLESS NOTED OTHERWISE&SHALL OPEN iv.FURNISH AND INSTALL 1"ELECTRICAL CONDUIT FROM THE SUB PANEL TO THE FRONT,BACK AND C CONTRACTOR TO PROVIDE ALL SUB-CONTRACTORS ACCESS TO A FULL SET OF CONSTRUCTION ADJUSTED WITHOUT WRITTEN CONSENT OF ARCHITECT/DESIGNER. LIGHTING AND SAFETY DEVICES IN ACCORDANCE WITH GOVERNING STATE AND LOCAL CODE AND FROM INSIDE OF THE SPACE WITH ONE MOTION AND REQUIRE NO SPECIAL KNOWLEDGE OR SIDE FASCIA FOR SIGNAGE. AUG1 DOCUMENTS, 7. ALL WALL FLOOR PLATES ARE TO BE LOCATED AND POSITIONING CONFIRMED WITH FLOOR BUILDING MANAGEMENT REQUIREMENTS. EFFORT. THUMBTURNS OR SEPARATE DEADBOLTS ARE NOT ALLOWED ON EGRESS DOORS. COMMENCIN9 THE G CONSTRUCTION SHALL &SHALL MAINTAIN NAWINGS ARE THE ONE COPY AT THE LATEST SITE NCLUDINPRIORTO BEAN DIMENSIONPRIOR TO S DRYWALL INSTALLATION. FOLLOWS,OUNLESS OTHERWISE NOTED: 2CONSDERED AND PARTALL OF THISTCOONTRAACTREQUIRED AND 0 ALL BETEXECCUTEDUNTION FOR THIS ACCORDANCE WITH THE IS 3THAN 1 2.THRESHOLDS SHALL NOT EXCEED Yz"IN HEIGHT AND SHALL HAVE A SLOPE NO GREATER I.MECHANICAL: Yvp 0A...J� ADDENDA,CHANGE ORDERS&FIELD CHANGES. -TO INSIDE FACE OF JAMB AT DOORS&OTHER OPENINGS LANDLORD'S REQUIREMENTS. ITEMS INDICATED AS EXISTING TO REMAIN MUST BE INSPECTED BY 4. ALL EMERGENCY EXITING ALARM AND SIGNAGE TO COMPLY WITH FEDERAL,STATE AND H.FURNISH AND INSTALL A MECHANICAL SYSTEM THAT PROVIDES SUFFICIENT COOLING BASED ON �-.. `L'•;FC 10. CONTRACTOR SHALL VISIT PROPOSED JOB SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING -TO TOP OF FINISHED FLOORS THE G.C.TO DETERMINE ACCEPTABILITY FOR REUSE. AT COMPLETION OF CONSTRUCTION ALL MUNICIPAL CODES FOR ACCESSIBILITY. TENANT'S PLANS,EQUIPMENT AND OCCUPANCY CALCULATIONS,SUBJECT TO LANDLORD'S g p: CAR �a -TO BOTTOM OF FINISHED CEILINGS MATERIALS SHALL BE IN"LIKE NEW"CONDITION. 5. CONTRACTOR SHALL ALLOW FOR APPLIED FINISH DIMENSIONS IN ADDITION TO STANDARD APPROVAL AND IN ACCORDANCE WITH ANY APPLICABLE CODES. V G CONDITIONS/LOCATIONS OF UTILITIES AND THE PROCEDURES THE OWNER OR LANDLORD EXPECTS CONSTRUCTION TOLERANCES IN ACHIEVING ALL ACCESSIBILITY CLEARANCES PER DRAWINGS ii.FURNISH AND INSTALL A MAIN TRUNK LINE WITHIN THE LEASED PREMISES FOR TENANT THE CONTRACTOR TO FOLLOW DURING CONSTRUCTION. THIS REFERS TO ACCESS TO THE -TO INSIDE FACE OF FINISHED MILLWORK 3. ALL DEMOLISHED WORK SHALL BE REMOVED FROM THE SITE AND DISPOSED OF IN A LEGAL o CONSTRUCTION SITE,TRASH REMOVAL DURING CONSTRUCTION,PARKING OF CONSTRUCTION 9. CONTRACTOR SHALL INSTALL PORTABLE FIRE EXTINGUISHERS(1.O.B.C. TYPE 2A&TYPE K MANNER PER STATE,LOCAL,AND LANDLORD REQUIREMENTS. AND/OR ADA GUIDELINES. DISTRIBUTION. �O VEHICLES,DELIVERIES,STORAGE,STAGING AREAS&ANY OTHER ITEMS NECESSARY TO COMPLY FOR SERVICING FRYER IN KITCHEN AREA)PER PC SECTION 906. 4. THE CONTRACTOR SHALL REMOVE,REPAIR,RESTORE AND REPLACE ANY WORK NECESSARY 6. EMERGENCY WARNING SYSTEMS SHALL COMPLY WITH ADA REQUIREMENTS FOR THE HEARING iii.FURNISH AND INSTALL SMOKE DETECTORS AND THERMOSTATS IF REQUIRED BY CODE. WITH ALL ASPECTS OF THE LEASE AND TENANT OBLIGATIONS. FAILURE OF CONTRACTOR TO VISIT 10. FOR BUILT-IN WORK SURROUNDED BY PARTITIONS,INCLUDING BUT NOT LIMITED TO OR INDICATED ON THE DRAWINGS. CUT ALL NECESSARY OPENINGS AND REPAIR AFTER CUTTING IMPAIRED. VISUAL WARNING STROBE LIGHTS TO BE DESIGNED TO HAVE A FREQUENCY OF NOT i,PROVIDE START-UP FOR ALL UNITS AND TRANSFER WARRANTIES TO TENANT. �i/TIE G N`vNNO� JOB SITE PRIOR TO BIDDING WILL RESULT IN FORFEITURE OF EXTRA COMPENSATION FOR TIME AND APPLIANCES AND FURNISHINGS,CONTRACTOR SHALL CONFIRM THAT FLOOR SLAB DOES NOT VARY WHERE NECESSARY. ALL PROTRUSIONS,MARKS,CRACKS,OR OTHER EVIDENCE OF A DEFICIENT MORE THAN 60 FLASHES PER MINUTE. v.FURNISH AND INSTALL ANY ROOF SCREENING THAT IS REQUIRED TO HIDE MECHANICAL SYSTEMS. //UID❑t MONEY. BY MORE THAN Y,"IN 20'-0". NOTIFY ARCHITECT/DESIGNER IF THIS TOLERANCE IS EXCEEDED. OR DAMAGED CONDITION SHALL BE ELIMINATED UNLESS SPECIFICALLY NOTED OTHERWISE. ANY 7. REFER TO TOILET ROOM ELEVATIONS FOR ACCESSIBILITY REQUIREMENTS/MOUNTING HEIGHTS. 11. THE CONTRACTOR SHALL CONTACT LOCAL UTILITY COMPANIES TO VERIFY ALL ELEVATIONS, 11. NEW GYPSUM BOARD CONSTRUCTION ADJOINING EXISTING CONSTRUCTION IN THE SAME ITEMS WHICH ARE SPLIT,CRACKED,CHIPPED,SPALLED,BROKEN,MISSING,OUT OF ALIGNMENT OR 8. WATER CLOSET AND URINAL FLUSH VALVE CONTROLS,&FAUCET AND OPERATING j.WATER: FURNISH AND INSTALL ONE 1-1/2"WATER LINE SERVICE(SEPARATELY METERED)WITH A SIZES,LOCATIONS AND CONNECTION POINTS FOR ALL UTILITIES AFFECTED BY THIS PROJECT. THE PLANE SHALL BE FLUSH WITH NO VISIBLE JOINTS,UNLESS OTHERWISE NOTED. ADJUSTMENT,MECHANICALLY OR STRUCTURALLY UNSAFE OR UNSOUND,BENT,TORN,OR MECHANISM CONTROLS SHALL BE OPERABLE WITH ONE HAND,SHALL NOT REQUIRE TIGHT MINIMUM OF 60 PSI,BACKFLOW DEVICES AND SHUT OFF VALVE RATED FOR 200 PSI. CONTRACTOR SHALL COORDINATE AND OBTAIN ALL APPLICATIONS FOR,AND ENSURE ALL UTILITIES 12. DIMENSIONS KNOWN AS V.LF. SHALL BE VERIFIED BY THE CONTRACTOR IN THE FIELD BY OTHERWISE DEFICIENT OR DAMAGED IN ANY MANNER SHALL BE REMOVED,REPLACED,RESTORED GRASPING,PINCHING OR TWISTING OF THE WRIST,AND SHALL BE MOUNTED NO MORE THAN 44" ARE TURNED ON PRIOR TO COMPLETION OF WORK. LAYING OUT THE PARTITIONS. CONTRACTOR SHALL NOTIFY CONSTRUCTION MANAGER AND OR SATISFACTORILY REPAIRED AS DIRECTED BY THE OWNER'S REPRESENTATIVE. ABOVE THE FLOOR. k.GAS: FURNISH AND INSTALL ONE 1600MBH GAS SERVICE(SEPARATELY METERED)WITH MANIFOLD ARCHITECT OF ANY DISCREPANCY IN DIMENSIONS PRIOR TO PROCEEDING WITH THE WORK IN THAT 5. PERFORM DEMOLITION WORK AND SUCH SPRINKLER WORK,CONCRETE SAW CUTTING,PAINTING 9. THE FORCE REQUIRED TO ACTIVATE WATER CLOSET AND URINAL FLUSH VALVE CONTROLS,& AND APPROPRIATELY SIZED REGULATOR FOR A MINIMUM PRESSURE OF k"PSI(7"WATER AREA. AND SIMILAR WORK CAUSING EXCESSIVE NOISE,DUST OR ODORS DISTURBING BUILDING FAUCET AND OPERATING MECHANISM CONTROLS SHALL BE NO GREATER THAN 5 LES. COLUMN)AT THE LEASED PREMISES. O o C)USE/OWNERSHIP OF DRAWINGS 13. THE ARCHITECT AND HIS CONSULTANTS WILL NOT HAVE CONTROL OVER,NOR CHARGE OF, OCCUPANTS,OR ANY WORK DISRUPTING TENANTS OR PUBLIC TRAFFIC WITHIN THE BUILDING, 10. SELF_CLOSING FAUCET CONTROL VALVES ARE ALLOWED IF THE FAUCET REMAINS OPEN FOR I.SEWER: . O NOR BE RESPONSIBLE FOR,THE CONSTRUCTION MEANS,METHODS,TECHNIQUES,SEQUENCES OR AFTER HOURS OR AT TIMES AND IN SUCH MANNER AS OTHERWISE APPROVED BY AT LEAST 10 SECONDS. R G� 1. THE ARCHITECT,THE ARCHITECT'S CONSULTANTS AND BLAZE PIZZA SHALL BE DEEMED THE PROCEDURES,THE SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK,THE LANDLORD/OWNER. 11. REFER TO ACCESSIBILITY DETAILS IN PLANS FOR TYPICAL ACCESSIBILITY GUIDELINES. - N � AUTHORS&JOINT OWNERS OF THEIR RESPECTIVE INSTRUMENTS OF SERVICE,INCLUDING THE CONTRACTOR'S FAILURE TO PERFORM THE WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE 6. SPECIAL ATTENTION SHALL BE GIVEN TO EXISTING AREAS SURROUNDING THE EXTERIOR OF H.FURNISH AND INSTALL ONE 4"CAST IRON OR PVC SEWER LINE LEADING TO THE LANDLORD a r--) DRAWINGS AND SPECIFICATIONS,&WILL RETAIN ALL COMMON LAW,STATUTORY AND OTHER CONSTRUCTION DRAWINGS OR CONTRACT,OR THE ACTS OR OMISSIONS OF THE CONTRACTOR, THE PROJECT SPACE. ALL CONSTRUCTION AND INSTALLED EQUIPMENT,WALKS,AND LANDSCAPED PROVIDED CODE COMPLIANT GREASE INTERCEPTOR. • - LL J 00 RESERVED RIGHTS,INCLUDING COPYRIGHTS. SUBCONTRACTORS,OR THEIR AGENTS OR EMPLOYEES OR ANY OTHER PERSONS OR ENTITIES AREAS SHALL BE PROTECTED AND GUARDED BY BARRIERS OR OTHER MEANS NECESSARY TO 0)PUNCH LIST/CLOSE-OUT ii.FURNISH AND INSTALL ONE 4"CAST IRON OR PVC SEWER LINE LEADING TO THE MAIN SANITARY I. a IT' 0 2. THE ARCHITECT,TENANT,OR THE BRAND OWNER ASSUME NO RESPONSIBILITY OR LIABILITY PERFORMING PORTIONS OF THE WORK. PROTECT AREAS FROM DAMAGE DURING CONSTRUCTION. ALL AREAS DAMAGED'MLL BE SEWER LINE. 0 C) - iii.ALL LINES TO HAVE APPROPRIATE SLOPE PER CODE. t FOR THE USE OF THESE DOCUMENTS FOR ANY PURPOSE OTHER THEN SPECIFICALLY AUTHORIZED 14. WORK NOT PARTICULARLY DETAILED,NOTED OR SPECIFIED,SHALL BE THE SAME AS SIMILAR RESTORED TO THEIR ORIGINAL CONDITION PRIOR TO FINAL PAYMENT AT THE SOLE EXPENSE OF 1. UPON NOTIFICATION BY THE CONTRACTOR THAT THE WORK IS SUBSTANTIALLY COMPLETE, a ® J Cn BY THE AFOREMENTIONED AND SIGNED AND SEALED FOR THE SPECIFIC LOCATION IN THE STATE PARTS THAT ARE DETAILED,NOTED OR SPECIFIED. THE CONTRACTOR. THE OWNER'S REPRESENTATIVE SHALL PREPARE A PUNCH LIST OF THE PROJECT AND THE _J m. GREASE INTERCEPTOR: FURNISH AND INSTALL ONE GREASE INTERCEPTOR WITH LINE(SEE SHOWN ON THE DRAWINGS AND SEAL. 15. IN THE EVENT OF INCONSISTENCIES AMONG THE CONTRACT DOCUMENTS,THE CONTRACTOR SHALL MAKE GOOD ALL PUNCH LIST ITEMS TO THE SATISFACTION OF THE OWNER'S APPLICABLE SEWER SECTION ABOVE)SIZED FOR OUR USE PER LOCAL CODES AND REGULATIONS n n n L` Q DESIGNER/ARCHITECT SHALL INTERPRET THEM WHEN ASKED TO DO SO BY THE OWNER OR K)HAZARDOUS MATERIALS REPRESENTATIVE PRIOR TO FINAL PAYMENT. (TYPICALLY A MINIMUM OF 1,250 GALLONS). INTERCEPTORS SUBJECT TO VEHICULAR TRAFFIC T___�A O Li CONTRACTOR. THE DESIGNER/ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE RESULTS OF SUCH 2. CONTRACTOR AND HIS JOB SUPERVISOR SHALL TEST ALL EQUIPMENT FOR PROPER SHALL BE TRAFFIC RATED. G Ln z D)CONTRACTS INTERPRETATIONS MADE BY OTHERS. 1. ASBESTOS AND HAZARDOUS WASTE EXCLUSION: THE ARCHITECT HEREBY STATES,AND THE OPERATION,IN THE PRESENCE OF THE OWNERS REPRESENTATIVE,BEFORE TURNING COMPLETED _ 16, THE GENERAL CHARACTER OF DETAIL WORK IS SHOWN ON THE CONTRACT DOCUMENTS. OWNER ACKNOWLEDGES,THAT THE ARCHITECT HAS NO PROFESSIONAL LIABILITY OR OTHER STORE OVER TO FRANCHISEE. I 11 " 1. THE LATEST EDITION OF THE"GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION", SUBSEQUENT CLARIFICATIONS MAY BE MADE BY ADDITIONAL LAYOUTS OR LARGE SCALE OR FULL INSURANCE(AND IS UNABLE TO REASONABLY OBTAIN SUCH INSURANCE)FOR CLAIMS ARISING � AIA 201,PUBLISHED BY THE AMERICAN INSTITUTE OF ARCHITECTS,ARE HEREBY MADE PART OF SIZE DETAILS. OUT OF THE PERFORMANCE OF OR THE FAILURE TO PERFORM PROFESSIONAL SERVICES, n.TELECOMMUNICATIONS: B THESE DRAWINGS AND SPECIFICATIONS. 17. DRAWINGS AND DIAGRAMS FOR MECHANICAL AND ELECTRICAL WORK SHALL BE CONSIDERED INCLUDING BUT NOT LIMITED TO,THE PREPARATION OF REPORTS,DESIGNS,DRAWINGS,AND R)RECORD DRAWINGS/WARRANTEE B 2. THREE DAYS BEFORE CONSTRUCTION COMMENCEMENT. THE CONTRACTOR SHALL PROVIDE AS DIAGRAMMATIC ONLY,NOT TO BE USED FOR ANY STRUCTURAL GUIDANCE OR PHYSICAL SPECIFICATIONS,AND RELATED TO THE INVESTIGATION DETECTION OF HAZARDOUS MATERIALS ON H.FURNISH AND INSTALL 2"CONDUIT WITH PULL STRINGS FROM THE LANDLORD'S THE ARCHITECT,FRANCHISEE,BRAND OWNER AND THE CONSTRUCTION MANAGER WITH A DETAILED LAYOUT. IN CASE OF CONFLICT,UNLESS OTHERWISE NOTED,THE ARCHITECTURAL DRAWINGS THE SITE. 1. THE CONTRACTOR SHALL LEAVE A COPY OF RECLINED AS-BUILT DRAWINGS AT THE STORE TELECOMMUNICATION ROOM/MAIN DEMARCATION POINT TO THE LEASED PREMISES FOR TELEPHONE AND COMPLETE CONSTRUCTION SCHEDULE,SHOWING ALL TRADES WITH STARTING AND COMPLETION SHOWING LOCATIONS FOR MECHANICAL AND ELECTRICAL ITEMS AND ACCESSORIES SHALL TAKE 2. IF THE CONTRACTOR ENCOUNTERS HAZARDOUS MATERIALS,&IF REASONABLE PRECAUTIONS NOTING ALL REVISIONS OF WORK UPON COMPLETION OF CONSTRUCTION. DRAWINGS SHALL BE SERVICE. DATES. A COMPLETE LIST OF ALL SUBCONTRACTORS MUST ALSO BE INCLUDED WITH THE PRECEDENCE. WILL BE INADEQUATE TO PREVENT FORESEEABLE BODILY INJURY OR DEATH TO PERSONS PLACED IN A 36"LONG 4"PVC PIPE WITH A CAP. PVC PIPE SHALL BE ATTACHED TO WALL AT ii.FURNISH AND INSTALL 2"CONDUIT INCLUDING A T1 OR HIGH SPEED INTERNET LINE FROM SCHEDULE. THE CONTRACTOR IS TO NOTIFY ALL PARTIES IN RECEIPT OF PROJECT SCHEDULE IF 18. UNLESS OTHERWISE NOTED,IT IS THE INTENTION OF THE DRAWINGS AND SPECIFICATIONS FOR RESULTING FROM A MATERIAL OR SUBSTANCE ENCOUNTERED ON THE SITE,THE CONTRACTOR LOCATION AS SPECIFIED BY THE PROJECT MANAGER. LANDLORD'S TELECOMMUNICATON ROOM MAIN DEMARCATION POINT TO THE LEASED PREMISES. ANY CHANGES OCCUR WHICH AFFECT THE COMPLETION DATE. FAILURE TO COMPLETE THE ALL WORK,EQUIPMENT,CASEWORK,MECHANICAL,ELECTRICAL AND SIMILAR DEVICES OF WHATEVER SHALL,UPON RECOGNIZING THE CONDITION,IMMEDIATELY STOP WORK IN THE AFFECTED AREA& 2. UPON COMPLETION OF THE WORK AND BEFORE FINAL PAYMENT IS MADE,THE CONTRACTOR / PROJECT AS SCHEDULED MAY RESULT IN PENALTIES INCURRED BY THE CONTRACTOR REGARDING NATURE,TO BE NEW&FREE OF DEFECTS,AND BE COMPLETELY INSTALLED,HOOKED-UP,MADE REPORT THE CONDITION TO THE OWNER IN WRITING. SHALL SECURE AND DELIVER TO THE OWNER ALL GUARANTEES AND/OR WARRANTIES ON ALL o.IMPACT FEES: LANDLORD SHALL BE RESPONSIBLE FOR ANY AND ALL IMPACT FEES THAT MAY BE FINAL PAYMENT. OPERATIONAL AND FUNCTIONAL FOR THE PURPOSE INTENDED,AND THAT ALL COSTS FOR THIS BE EQUIPMENT SUPPLIED AND/OR INSTALLED BY THE CONTRACTOR AND HIS SUB-CONTRACTORS,AND INCURRED DUE TO TENANTS'USE. 3. GENERAL CONTRACTOR SHALL SUBMIT WEEKLY PROGRESS REPORTS AND PHOTOGRAPHS OF INCLUDED IN THE CONTRACTOR'S PROPOSAL. L)CONTRACTOR USE OF PREMISES ALL PROVIDE TWO COPIES OF OPERATIONS/MAINTENANCE MANUALS. WORK TO OWNER'S REPRESENTATIVE VIA FTP PROJECT MANAGEMENT WEBSITE. 19. THE CONTRACTOR SHALL,IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS,APPLY, INSTALL,CONNECT,ERECT,CLEAN AND/OR CONDITION MANUFACTURED ARTICLES,MATERIALS 1. CONSTRUCTION OPERATIONS: LIMITED TO AREAS NOTED ON DRAWINGS. p.RESTROOMS: PROVIDE ALLOWANCE FOR TWO(2)ADA COMPLIANT RESTROOMS(S)PER TENANT'S AND/OR EQUIPMENT PER MANUFACTURER'S INSTRUCTIONS. IN CASE OF CONFLICT BETWEEN 2. TIME RESTRICTIONS FOR PERFORMING WORK: VERIFY WITH LANDLORD/OWNER&LOCAL S)GUARANTEE PLAN. ALLOWANCE SHALL INCLUDE COST OF ALL TENANTS FINISHES AND ACCESSORIES. EIINSURANCE MANUFACTURER'S INSTRUCTIONS AND THE CONTRACT DOCUMENTS,THE CONTRACTOR SHALL NOTIFY CODES. THE PROJECT MANAGER AND THE ARCHITECT BEFORE PROCEEDING. 3. UTILITY OUTAGES AND SHUTDOWN SHALL BE COORDINATED WITH THE LANDLORD/OWNER. 1. THE CONTRACTOR SHALL GUARANTEE IN WRITING ALL MATERIALS&LABOR FOR ONE(1) q.SPRINKLER: 1. ALL CONTRACTORS(GENERAL AND SUBCONTRACTORS)SHALL COMPLY WITH THE 20. THE CONTRACTOR SHALL COORDINATE AND SCHEDULE WORK BY OUTSIDE VENDORS 4. AT ALL TMES CONDUCT OPERATONS TO INSURE THE LEAST INCONVENIENCE TO THE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER,AND WILL,AT HIS OWN COST, REQUIREMENTS FOR INSURANCE,BONDS AND WAIVERS OF LIEN,AS OUTLINED IN THE LATEST INCLUDING BUT NOT LIMITED TO,TELEPHONE,DATA AND"OWNER'S FORCES"ITEMS. CONTRACTOR GENERAL PUBLIC. COMPLY WITH APPLICABLE CODES AND ORDINANCES FOR SAFETY. REPAIR OR REPLACE ALL WORK OR DAMAGES CAUSED BY THE WORK WHICH BECOMES DEFECTIVE H.FURNISH AND INSTALL AN AUTOMATIC SPRINKLER SYSTEM THAT COMPLIES WITH ALL STATE, EDITION OF THE"GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION",AIA 201, SHALL COORDINATE EXACT LOCATIONS AND SHALL DO THE CUTTING,FITTING AND PATCHING 5. ASSUME FULL RESPONSIBILITY FOR THE PROTECTION AND SAFEKEEPING OF PRODUCTS DURING THE TERM OF THE GUARANTEE. THE TERM OF THE GUARANTEE MAY BE MODIFIED OR LOCAL NFPA AND LOCAL JURISDICTIONAL REQUIREMENTS. SPRINKLER SYSTEM SHALL INCLUDE PUBLISHED BY THE AMERICAN INSTITUTE OF ARCHITECTS AND SHALL MEET THE OWNER/LL.COI REQUIRED TO RECEIVE THE WORK OF OTHERS AS SHOWN OR REASONABLY IMPLIED BY THE STORED ON THE SITE UNDER THIS CONTRACT. EXTENDED BY THE OWNER/CONTRACTOR AGREEMENT. ALL PIPING,FIRE RISER(LOCATED OUTSIDE OF THE TENANT SPACE)AND STANDARD GRID REQUIREMENTS. DRAWINGS AND SPECIFICATIONS. 6. COORDINATE USE OF PREMISES FOR WORK&STORAGE WITH THE LANDLORD/OWNER,&TO 2 OWNER MAY WITHHOLD FINAL PAYMENT UNTIL CONTRACTOR SUPPLIES OWNER WITH A DISTRIBUTION. - 2. TO THE FULLEST EXTENT PERMITTED BY LAW,THE CONTRACTOR SHALL INDEMNIFY AND HOLD 21. ANY CHANGES IN THE SCOPE OF WORK INVOLVING A CHANGE IN THE CONSTRUCTION COST AREAS PERMITTED BY APPLICABLE LAWS,STATUTES,ORDINANCES&CODES. WARRANTY LETTER AND SUBCONTRACTORS LIEN WAIVERS. ii.IF LANDLORD'S SUBCONTRACTOR IS REQUIRED FOR TENANT WORK THEN SUBCONTRACTOR MUST HARMLESS THE OWNER,ARCHITECT,ARCHITECT'S CONSULTANTS,AND AGENTS AND EMPLOYEES OF OR TIME SHALL BE APPROVED BY THE OWNER IN WRITING PRIOR TO THE CONTRACTOR 7. LIMIT USE OF SITE FOR WORK AND STORAGE TO AREAS DESIGNATED UNLESS SPECIFIC BE COMPETITIVELY PRICED AND ABLE TO MEET TENANT'S CONSTRUCTION SCHEDULE. ANY OF THEM FROM&AGAINST CLAIMS/DAMAGES ARISING OUT OF OR RESULTING FROM COMMENCING WITH THE WORK SCOPE CHANGE. ADDITIONAL AREAS ARE ALLOWED IN WRITING BY THE LANDLORD/OWNER. \' PERFORMANCE OF THE WORK,PROVIDED THAT SUCH CLAIM,DAMAGE,LOSS OR EXPENSE IS 22. THE G.C.ASSUMES RESPONSIBILITY FOR THE WORK OF THIS PROJECT TO ASSURE THAT ALL 8. IN THE EVENT OF DAMAGES TO MATERIALS/WORK,CONTRACTOR OR RESPONSIBLE T)DEFINITIONS r.FIRE ALARM: - - - Q ATTRIBUTABLE TO BODILY INJURY,SICKNESS,DISEASE OR DEATH,OR TO INJURY TO OR ASSEMBLIES,COMPONENTS AND PARTS INDICATED OR REQUIRED COMPLY WITH CONTRACT SUBCONTRACTORS SHALL IMMEDIATELY MAKE ALL REPAIRS AND REPLACEMENTS NECESSARY AT _ �sw DESTRUCTION OF TANGIBLE PROPERTY,BUT ONLY TO THE EXTENT CAUSED BY THE NEGLIGENT DOCUMENTS. ANY SUBSTITUTIONS MADE BY THE CONTRACTORS WITHOUT PRIOR WRITTEN NO ADDITIONAL COST TO THE OWNER. 1. "FURNISH"-SUPPLY AND DELIVER TO THE PROJECT SITE,READY FOR UNLOADING, ACTS OR OMISSIONS OF THE CONTRACTOR,A SUBCONTRACTOR,ANYONE DIRECTLY OR INDIRECTLY APPROVAL OF THE ARCHITECT AND OWNER WILL BE REPLACED AT THE CONTRACTORS EXPENSE. 9. TEMPORARY SANITARY FACILITIES FOR THE WORKERS SHALL BE FURNISHED,INSTALLED AND UNPACKING,ASSEMBLY,INSTALLATION AND SIMILAR OPERATIONS. H.FURNISH AND INSTALL ONE(1)1"CONDUIT WITH PULL STRING FOR FIRE ALARM CONNECTION, EMPLOYED BY THEM OR ANYONE FOR WHOSE ACTS THEY MAY BE LIABLE,REGARDLESS OF ALL COMPONENTS SPECIFIED OR REQUIRED TO SATISFACTORILY COMPLETE THE INSTALLATION ARE MAINTAINED BY THE CONTRACTOR,IF"CONTRACTOR-USE"FACILITIES DO NOT EXIST ON SITE. 2. "INSTALL"-OPERATIONS AT THE PROJECT SITE INCLUDING THE ACTUAL UNLOADING, ONE(1)ANNUNCIATOR PANEL IN AN AGREED UPON LOCATION WITHIN PREMISES,INTERFACED TO WHETHER OR NOT SUCH CLAIM,DAMAGE,LOSS OR EXPENSE IS CAUSED IN PART BY A PARTY TO BE COMPATIBLE WITH EACH OTHER WITH ADJOINING SUBSTRATES,MATERIALS AND WORK BY PERMANENT TOILETS INSTALLED ON THE PROJECT SHALL NOT BE USED DURING CONSTRUCTION OF UNPACKING,ASSEMBLY,ERECTING,PLACING,ANCHORING,APPLYING,WORKING TO DIMENSION, BUILDING SYSTEM,AND ONE(1)HOM AND STROBE IN AN AGREED UPON LOCATIONS,OR MINIMUM INDEMNIFIED HEREUNDER. OTHER TRADES,AND WITH THE CONDITIONS OF INSTALLATION AND EXPECTED USE. THE PROJECT. ALL SUCH FACILITIES AND SERVICES SHALL BE FURNISHED IN STRICT FINISHING,CURING,PROTECTING,CLEANING AND SIMILAR OPERATIONS. IF MEET CODE. F1111 OJECT NUMBER: 17-420 ACCORDANCE WITH EXISTING GOVERNING HEALTH REGULATIONS. ii.IF LANDLORD'S SUBCONTRACTOR IS REQUIRED FOR TENANT WORK THEN SUBCONTRACTOR MUST AWN BY: RP 10. PARKING TO BE DESIGNATED BY LANDLORD. 3. "PROVIDE"-FURNISH AND INSTALL,COMPLETE AND READY FOR INTENDED USE. BE COMPETITIVELY PRICED AND ABLE TO MEET TENANTS CONSTRUCTION SCHEDULE. ECKED BY: MP F)STANDARDS AND CODES H)REFLECTED CEILING PLAN NOTES 4. "OWNER SUPPLIED"-SUPPLIED BY TENANT. M)TEMPORARY JOB SITE SIGN E.CO2 SYSTEM: WHERE ALLOWED BY CODE,TENANT SHALL BE ALLOWED TO PLACE ITS BULK CO2 1. GIVE ALL NOTICES AND COMPLY WITH ALL NATIONAL,STATE AND LOCAL LAWS,ORDINANCES, 1. REFER TO MECHANICAL,ELECTRICAL DRAWINGS AND SPECIFICATONS FOR DESIGN OF THESE LANDLORD WORK LETTER WITHIN THE LEASED PREMISES WITH SUFFICIENT VENTING,ACCESS FOR USE AND REFILLING. SHEET TITLE. A CODES,RULES AND REGULATIONS BEARING ON THE CONDUCT OF THE WORK. IF THE CONTRACTOR SYSTEMS(DUCT SIZES,CIRCUITING,ETC.)AND FOR ADDITIONAL REQUIREMENTS. LOCATIONS OF 1. GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL A TEMPORARY JOB SITE SIGN LOCATED A OBSERVES THAT THE DRAWINGS AND SPECIFICATIONS ARE AT VARIANCE THEREWITH,PROMPTLY FIXTURES,REGISTERS,SWITCHES,ETC. SHALL BE AS SHOWN ON THE ARCHITECTURAL PLANS. AS DIRECTED CONSTRUCTION MANAGER. SIGN SHALL BE PREPARED BY OTHERS COORDINATE WITH t.OUTDOOR PATIO: FURNISH AND INSTALL AN APPROXIMATELY 400-SQUARE FEET CONCRETE NOTIFY THE DESIGNER/ARCHITECT. NECESSARY CHANGES SHALL BE MADE IN ACCORDANCE WITH NOTIFY ARCHITECT/DESIGNER OF ANY CONFLICTS PRIOR TO COMMENCING CONSTRUCTION. CONSTRUCTION MANAGER. LANDLORD RESERVES THE RIGHT TO FURTHER REVIEW AND POSSIBLE MODIFICATION IF REQUIRED BY OUTDOOR DINING/PATIO PAD LOCATED ON THE SIDE OR FRONT OF THE TENANTS LEASED GENERAL THE GENERAL CONDITIONS. 2. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL PLUMBING AND STRUCTURAL ELEMENTS EXISTING BUILDING PLANS. LANDLORD SHALL PROVIDE(AT ITS SOLE COST)ALL OF THE FOLLOWING PREMISES WITH A STOREFRONT GLASS DOOR LEADING TO IT. 2. THE CONTRACTOR SHALL FILE,OBTAIN AND PAY FEES FOR BUILDING DEPARTMENT AND ALL AND OTHER APPLICABLE ITEMS, NOTIFY ARCHITECT/DESIGNER OF INADEQUATE CLEARANCES FOR IMPROVEMENTS IN THE LEASED PREMISES PER APPLICABLE CODE AND TENANT'S PLANS,SUBJECT TO NOTES OTHER AGENCY APPROVALS AND PERMITS,CONTROLLED INSPECTIONS,AND FINAL WRITE-OFFS FOR CEILING LAYOUT. LANDLORD'S APPROVAL. IF LANDLORD CHOOSES NOT TO PROVIDE AN IMPROVEMENT ITEM LISTED U.TRASH/RECYCLING: PROVIDE A CLEAN,WELL-LIT AREA FOR A CODE COMPLIANT TRASH PROJECT COMPLETION. COPIES OF TRANSACTIONS ARE TO BE FORWARDED TO THE PROJECT 3. ALL REGISTERS,SPRINKLER HEADS AND LIGHTING FIXTURES SHALL OCCUR WITHIN GRID LINES. NO FINISH NOTES BELOW THEN LANDLORD IS TO PROVIDE TENANT WITH A COMPETITIVE ALLOWANCE(FOR EACH ITEM ENCLOSURE FOR TENANT'S USE, ENCLOSURE AND SURROUNDING PAD TO MEET ALL APPLICABLE MANAGER. INCANDESCENT FIXTURES OR OTHER ELEMENTS SHALL BE LOCATED AT THE CENTER OF NOT PROVIDED)SO THAT THE TENANT CAN COMPLETE THE ITEM(S). ON FOR ACCESS AND REQUIREMENTS OF THE WASTE AND RECYCLING REMOVAL SERVICE 3. IF THE CONTRACTOR KNOWINGLY PERFORMS ANY WORK WHICH IS CONTRARY TO SUCH LAWS, ACOUSTICAL TILES UNLESS NOTED OTHERWISE. 1. ENSURE THAT SURFACE TO RECEIVE FINISHES ARE CLEAN,TRUE AND FREE OF COMPANY. ORDINANCES,CODES,RULES AND REGULATIONS,HE SHALL PROMPTLY MAKE CHANGES AS 4. CUT-OUTS AT FIXTURES IN LAY-IN CEILINGS SHALL BE PRECISE WITH NO GAPS,CHIPS OR IRREGULARITIES AND ARE ACCEPTABLE TO RECEIVE NEW FINISHES. DO NOT PROCEED WITH WORK a.ROOF: REQUIRED TO COMPLY THEREWITH AND BEAR ALL COSTS ARISING THEREFROM. IRREGULARITIES. UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED. COMMENCEMENT OF WORK SHALL 4. CONFLICTS: IN CASE OF CONFLICTS IN THE REQUIREMENTS OF AUTHORITIES HAVING 5. CEILING GRID SHALL BE LEVEL WITHIN A TOLERANCE OF Ye"IN A SPAN OF 10'-O". INDICATE INSTALLER'S ACCEPTANCE OF SUBSTRATE. I.FURNISH AND INSTALL WATERTIGHT,INSULATED(R-30 MINIMUM),AND STRUCTURALLY SOUND BUILDING ENVELOPE: PRIOR TO DELIVERY TO THE TENANT,THE LANDLORD SHALL PROVIDE THE SHEET NUMBER: JURISDICTION,THE MOST RESTRICTIVE REQUIREMENTS SHALL GOVERN. 6. LAY-IN LIGHTING FIXTURES SHALL NOT RELY ON THE CEILING SYSTEM ALONE FOR SUPPORT. 2. ALL CODE-REQUIRED LABELS SUCH AS"UL,"FACTORY MUTUAL OR ANY EQUIPMENT (CAPABLE OF SUPPORTING LOADS FOR TENANT'S EQUIPMENT LOCATED ABOVE AND BELOW TENANT WITH DOCUMENTATON VERIFYING THE BUILDING,AS DELIVERED,COMPLIES WITH MOST 5. WHERE CODES OR REGULATIONS OTHER THAN THOSE LISTED IN THIS SECTION ARE REFERRED LAY-IN LIGHTNG FIXTURES SHALL BE SUPPORTED FROM THE STRUCTURE BY NO LESS THAN TWO IDENTIFICATION,PERFORMANCE RATING,NAME OR NOMENCLATURE PLATES SHALL REMAIN STRUCTURE)ROOF SYSTEM WITH ALL APPLICABLE WARRANTIES IN EFFECT. CURRENT REQUIREMENTS IC THE CALIFORNIAYAPPLY). ENERGY CODE SPACE INTERNATIONAL ENERGY TO IN VARIOUS SECTIONS OF THE DOCUMENTS,IT SHALL BE UNDERSTOOD THAT THEY APPLY TO HANGER WIRES AND SECURED TO THE CEILING GRID SYSTEM WITH THE APPROPRIATE ATTACHMENT READABLE AND NOT PAINTED. ii.IF LANDLORD'S SUBCONTRACTOR IS REQUIRED FOR TENANT WORK THEN SUBCONTRACTOR MUST CONSERVATION CODE(WHICHEVER MAY APPLY). IF THE SPACE IS CURRENTLY NON-CONDITIONED •/�� THIS WORK AS FULLY AS IF CITED HEREIN. HARDWARE. 3. THE CONTRACTOR SHALL PATCH SURFACES AS NECESSARY TO MATCH ADJACENT IN A SPACE,THE LANDLORD SHALL SPECIFICALLY PROVIDE COMPLIANCE DOCUMENTATION THAT THE TENANT O02 MANNER SUITABLE TO RECEIVE FINISHES. BE COMPETITIVELY PRICED AND ABLE TO MEET TENANT'S CONSTRUCTION SCHEDULE. PREMISES(BUILDING ENVELOPE)DEMONSTRATES COMPLIANCE AS A CONDITIONED SPACE. V W 0 N f ' NN Cl CORPORATE VENDOR LIST CORPORATE VENDOR LIST a a <O KITCHEN EQUIPMENT SUPPLIER COCA COLA z z❑ m m m COMPANY NAME: ICONCEPT SERVICES CONTACT NAME: KYLE MCCARTHY z < w U CONTACT NAME: MATT BATTEN PHONE: (949)241-9086 o DO DO N i ADDRESS: EMAIL: KMCCARTHY®COCA-COLA.COM o 3 w o w DO z x 3 PHONE: (512)343-3100 ROMA/PERFORMANCE FOOD GROUP z N J DO a L`3 EMAIL: MBATTEN®CONCEPTSERV.COM CONTACT NAME: RON JOHNSON PHONE: (714)222-6263 KITCHEN EQUIPMENT SUPPLIER EMAIL: RON.JOHNSON®PFGC.COM COMPANY NAME: JAVANTI CONTACT NAME: MARIAH MCMANAMAN ECOLAB-WATER FILTRATION D ADDRESS: CONTACT NAME: MARK ALTHOUSE D ADDRESS: 370 WABASHA ST PHONE: (916)261-0105 N ST PAUL,MN 55102 EMAIL: MM®AVANTICO-----E.COM CELL: (740)225-4063 EMAIL: MARK.ALTHOUSE@ECOLAB.COM MILLWORK SUPPLIER COMPANY NAME: IMIDWEST CABINETS ECOLAB-CHEMICALS CONTACT NAME: IJEREMY STONE CHARLIE DANIELS ADDRESS: CONTACT: (SENIOR ACCT MGR) PHONE (913)220-7503 PHONE (785)242-8181 x16 : EMAIL: CHARLIE.DANIELS®ECOLAB.COM EMAIL: JSTONE@MIDWESTCABINET.COM CLAYTON-KENDALL,INC. MILLWORK SUPPLIER CONTACT NAME: ROBERT MENZER COMPANY NAME: ICCS 167 DEXTER DRIVE CONTACT NAME: JASON HOOD ADDRESS: MONROEVILLE,PA 15146 ADDRESS: PHONE: (412)798-7120 PHONE: (714)850-0520 x320 FAX: (412)798-7353 EMAIL: IASONH@CCS-IND.COM HARDWARE SPECIALTIES-SNEEZEGUARD HARDWARE CONTACT NAME: STEVE SALDANA MILLWORK SUPPLIER 761 E.FRANCIS STREET,UNIT B COMPANY NAME: CHARTER-HOUSE ADDRESS: ONTARI0,CA 91761 CONTACT NAME: IBARB ZILM PHONE: (909)975-4853 ADDRESS: FAX: (909)975-4863 CAI OR"...AND WRITTEN MATERIAL CONTAINED HEREIN ARE THE PROPERTY OF PHONE (317)691-6930 EMAIL: STEVE®HARDWARESPECIALTIES.COM THE UNDUE oEvcx GROUP,INC.wEr MAY NOi BE REUSED,COPIED,REUSED,OR EMAIL: BARBARA.ZILM®CHARTER-HOUSE.COM DISCLOSED IN MY MANNER WTHOUT WRITTEN ROLL-A-SHADE-WINDOW SHADES AJwORIZARON FROM THE ARCHITECT LIGHTING SUPPLIER CONTACT NAME: RIC BERG C 12101 MADERA WAY C AUG17 COMPANY NAME: IVILLA LIGHTING SUPPLY,INC ADDRESS: RIVERSIDE,CA 92503 CONTACT NAME: 292E CHAOUTEAU PHONE: (951)245-5077 , AR12/1 �I ADDRESS: FAX: (951)245-5075 ��; ST.LOUIS,MO 63103 V?••CARLI-•'CI PHONE: (314)633-0554 EMAIL: RIC.BERWOLLASHADE.COM 3 L1(i 5 CELL: (314)633-0537 = c SIGNAGE •;�03 LIGHTING SUPPLIER COMPANY NAME: VISIBLE GRAPHICS COMPANY NAME: REGENCY LIGHTING CONTACT NAME: DAVE MAHN G;ix2Y4 E110 CONTACT NAME: BRANDON MELTON PHONE: (818)787-0477 EMAIL: DAVEMVISIBLEGRAPHICS.COM ADDRESS: PHONE: 800-284-2024 SIGNAGE CELL: (303)748-8971 COMPANY NAME: ATLAS SIGN INDUSTRIES EMAIL: BLAZEPIZZA®REGENCYLIGHTING.COM CONTACT NAME: JIM ADINOLFE G ADDRESS: o HOOD SUPPLIER PHONE: (561)722-3596 c ~ COMPANY NAME: WOOD STONE CORPORATION G�9 N r7 CONTACT NAME: JANA BJORNSTAD EMAIL: JIM.A®ATLASSIGNINDUSTRIES.US Lil 00 ADDRESS: 1801 W.BAKERMEW ROAD f a FURNITURE O PHONE (8000))988-8103 BEL WA 98226 COMPANY NAME: DESIGNFORM FURNISHINGS : 988- CONTACT NAME: BURKE SCHECHTEL L J FAX: (360)650-1166 J PHONE: (714)662-7300 EMAIL: JANAB®WOODSTONENET EMAIL: BURKE®GLOBALSOUSALSOURCEINDUSTRIE c)� TILE SUPPLIER z SOUND ATTENUATION COMPANY NAME: DAL-TILE N CONTACT NAME: TAMARA GRANDUSKY COMPANY NAME: ACOUSTICAL SOLUTIONS INC. PHONE: (877)556-5728 CONTACT NAME: CORY DIGGS B ADDRESS: 2420 GRENOBLE ROAD B RICHMOND,VA 23294 WINDOW TINT PHONE: (800)782-5742 x132 COMPANY NAME: SOLAR GRAPHICS CONTACT NAME: SUE CARDEN FAX: (804)346-8808 12167 49TH STREET,STE 900 EMAIL: WCD®ACOOTSTICALSOLUTTONS.COM ADDRESS: CLEARWATER,FL 33762 PHONE: (800)869-8468 COMPANY RECLAIMED WOOD COMPANY NAME: VIRIDIAN RECLAIMED WOOD WALL GRAPHIC SUPPLIER CONTACT NAME: COMPANY NAME: CREAl1VE SOLUTIONS ADDRESS: 8638 NORTH CRAWFORD STREET CONTACT NAME: RICHIE BARRY (877)PORT 09 OR,97203 PHONE: (877)909-9663 ADDRESS: FAX PHONE (310)739-5556 EMAIL: INFO®NRIDIANWOOD.COM EMAIL: RICHIEB6CREA1IVESOLUTIONSBO.COM ALAS DISTRIBUTOR-PRESTIGE PRODUCTS LLC CONTACT NAME: ALEX BRUSSOW ADDRESS: PHONE: (616)862-3113 EMAIL: ALEX®PRESTTGEPRODUCTSLLC.COM MUSIC SPEAKERS COMPANY NAME: DYNAMIC MEDIA PROJECT NUMBER: 17-420 CONTACT NAME: LEM ROUSE DRAWN BY: RP 38271 MOUND RD.#300 CHECKED BY: MP ADDRESS STERLING HEIGHTS,MI 48310 PHONE: (586)693-1076 SHEET TITLE: A FAX: (586)693-1076 A EMAIL LROOSE®DM-US.COM POINT-OF-SALE VENDOR LIST COMPANY NAME: SDCR CONTACT NAME: NADIA CARPENTER (MAJOR ACCOUNTS MANAGER) ADDRESS: 7940 ARJONS DRIVE SAN DIEGO,CA 92126 PHONE: (949)278-5696 _TEET NUMBER: EMAIL: NCARPENTER®SDCR.COM G003 TYPICAL ACCESSIBILITY DETAILS CALCULATED OCCUPANCY LOAD: Do w ASSEMBLY AREAS TOTAL CALCULATED ACTUAL rc m o a m Cm v 2'-0"" 4'-0"" 2'0"" OCCUPANT LOAD SEAT COUNT [D z- a❑ tom m DINING: z a�o >w m m W MAX. MIN. MAX. TT TTTTTTTFFTTT fT 15 SO FT.PER OCCUPANT 411 SQ.FT. 28 55 _ E w w o 'h m N FIXED BENCH SEATING: z 3 00 mDO m Mill 438 L.I. 25 12 3 w 18 LINEAL INCHES PER OCCUPANT is ED m o a¢3; Ila FIXED BOOTH SEATING z `" z T 1i 24 LINEAL INCHES PER OCCUPANT 336 L.I. 14 14 w STANDING SPACE: 66%FT. 14 5 SO.FT.PER OCCUPANT CLEAR WIDTH OF AN ACCESSIBLE - KITCHEN: 665 SQ.FT. 4 - ROUTE - 200 SQ.FT.PER OCCUPANT O �� ACCESSORY/STORAGE: 337 SO.FT. 2 - D 12" 36 MIN 12 F 300 SQ.FT.PER OCCUPANT M — OFFICE: I MI 21 SQ.FT. 1 - T,30�rIN DD - -100 SQ.FT.PER OCCUPANT TOTAL INTERIOR OCCUPANTS: 88 81 PATIO: 15 SQ.FT.PER OCCUPANT 0 SQ.FT. 0 0 s FIXED(PATIO)BENCH SEATING: 0 L.I. 0 0 18 LINEAL INCHES PER OCCUPANT \ / TOTAL EXTERIOR OCCUPANTS: 0 0 TOTAL OCCUPANTS: 88 81 X 60 IN DIAMETER SIZE OF CLEAR TT-SHAPE } SPACE FLOOR SPACE TURNS -_-CORRIDORS: O O { < -- } NOTE: DIMENSIONS SHOWN APPLY WHEN X<48' - - 0 SO.FT.PER OCCUPANT L �-- --� J ` u _ ACCESSIBLE SEATING CALCULATIONS TOTAL TOT L SEATING: 81 81SEA TS ld - - \ { \ TOTAL REQUIRED ACCESSIBLE INTERIOR SEATING(5%OF TOTAL) 5 — fl IE REQUIRED ACCESSIBLE PATIO SEATING(5%Of TOTAL) 0 _ p — 4 4 REQUIRED EGRESS WIDTH ®ALL NRAWNCS AND xxmEN MAMMAL TO GE 36" 48" 36" 42" X 42" CONTAINED HEREIN ARE THE PRWERTY OF /o \ \F 337$Q.FF. BUILDING EGRESS THE UN ED OESICN fROUP,INC.THEY NAY Y-6" IN MIN MIN MIN MIN NOT BE REAM,COPIED,REUSED,OR TOTAL EGRESS WIDTH REQUIRED: DISCLOSED IN ANY MANNER MTHOUT RIM 90'TURN 180'TURN 88 MAX INT.OCCUR.X.2"= 18 AUTHORIZAMON FROM THE ARCHITECT. NOTE: DIMENSIONS SHOWN APPLY WHEN X<48" TOTAL EGRESS WIDTH PROVIDED: C ———— 1=6" _--- INU N'CLEAR DOOR EXITS LEAFS=10f C AUG17 4'-0 5 0 MAIN ENTRANCE �xpt11UIII1/7ry7„ �C WIDTH REQUIRED(1/2 OCCUPANT LOAD): �Xx�QQ ARCyjJ�i� CHANGES IN LEVEL - 88 INTERIOR OCCUR./2= 44 X.20=9" { \ CLEAR WIDTH PROVIDED:10Y � — 2 NUMBER OF EXITS: 2 REQUIRED-2 PRDMDED o PisG FT = I i Y IJ BUILDING occuPANcv CALCULATIONS PLUMBINGl ............ E o 1`YY"`�� Dam36 36" MAXIMUM OCCUPANTS(GREATEST OF OCCUPANCY CALCULATIONS OR SEAT BOOTH SEATING - __ / BEVELED CHANGES IN LEVEL MIN MIN COUNT NUMBERS= 88 -48"L.L(EACH) �-�} 180-TURN EXCEPTION -33fi"L.I.(GROSS) - �: �:; ] .,_ � I' - (EXCEPTION) 509,MALE AND 507,FEMALE= 88/2= 44 NOTE:X=12"IF DOOR HAS BOTH NOTE: Y=48"MIN.IF DOOR HAS NOTE: Y=48"MIN.IF FEMALE-REQUIRED FIXTURES 1-25- I CLOSER AND LATCH BOTH LATCH AND CLOSER DOOR HAS CLOSER W.C. W.C. r I�. �P 6655Q FF I: r , IF DOOR _____ MALE-REQUIRED FIXTURES 1-50= MALE UR.MALE FEMALE LAV.MALE/FEMALE O r 58"MIN. T 1 r REQUIRED URINALS 1-200= HAS BOTH C JnL _ - w _ V 12" LATCH AND- R QU RED LAV 1 150 1 2 1 EACH O ---- I I L D� E ATORIES 1 ■ - � -I f '� MIN. CLOSER r �l"4°MIN.' MALE FEMALE ■ ~ - \ _ .:; \, PUSH X 22 I 1 q TYPE OF FIXTURE N r7 o = SIDE I� REQUIRED PRO, ED REQUIRED PROVIDED o Do n n I �oip r. - WATER I CLOSET 1 1 2 2 f Q .... pQ' ::: : 4 - P IN. R$18°MIN 36" 4°MIN. URINAL 1 1 _____________ N/q _____________ ` r IH�1I ],I'II UI. EX.DRS 24 IN MIN. LILL AVATORIES 1 1 1 1 O Cn _ICI -. .: �\ z // I / SERVICE SINK 1 PROVIDED ■ _J SIDEi I GENERAL NOTES G� ----—------- ------ -------—-------—-- — fi6SO.FT. I I I G.C.TO VERIFY QUANTITY&LOCATIONS OF FIRE EXTINGUISHERS WITH LOCAL AUTHORITIES.FIRE G O Z -- -------------------- ------------------------------------------------- ----—---- L_PULL SIDE_J _________ L_____J A EXTINGUISHERS TO BE SUPPLIED BY G.C.-DETAIL D1/0110 N ----- ------- ------- ---_-_-___-_-_-_-_ -_-_-_-_ -_-_-_-_- _-_-_-_- _ - -_-_- _-_- FRONT APPROACHES-SWINGING HINGE SIDE LATCH SIDE G.C.TO PRONDE FIRE DEPARTMENT REQUIRED KEY BOX. COORDINATE LOCATION AND TYPE WITH LOCAL -- -=44'" GRESS PATH.-- ------------------------------------ DOORS APPROACHES-SWINGING DOORS APPROACHES-S'MNGING DOORS B AUTHORITIES. B -FIXED SEATING_ C SEE MEP DRAWINGS AND RESPONSIBILITY SCHEDULE FOR INFORMATION REGARDING SPRINKLER AND FIRE - -------- ALARM SYSTEM- 16 SQ,FT. -- --438"L.I.-_ ■■■■ ■■■■■■ ■■■■ ■■■■■■■ MEMO EMERGENCY LIGHTS IN DINING AREAS SUCH THAT THEY DO NOT INTERFERE WITH WALL DECOR OR DINING SYSTEM Y GENERAL CONTRACTOR ______ ____ _ - ------ 48" \ D. ALL EART ------- -- ------ - - ----- - - - ----- - ■ \ \ // E L FLOOR SPACE AND TURNING SPACE TO BE NO GREATER THAN 2%SLOPE PER ADA 304.2& ______ ■ \ \ MIN. ------- - ------ DIIG ■ � � CODED NOTES .�_ ______ 9950.FT. ® - -- _---_--_- 48 MIN. 60" O TACTILE SIGNAGE AT EXTERIOR EXIT DOORS,SIGNAGE TO READ:"EXIT",PER IBC 1011.4-SEE DETAIL —I - r---------- -_F-Rr_ MIN. 1 A5/G100. ® _ _ - _ _tL-z497—______ __ �__-_�s- TWO HINGED DOORS IN SERIES TWO HINGED DOORS IN SERIES TWO HINGED DOORS IN SERIES O SIGNAGE"MAXIMUM OCCUPANCY 88 PERSONS". --- --44"EGRESS PATIL=____ ____ __ ■ 3-6„ X NOTE: ® _----------------------------------- ■ x v SHALL BE 48"MAX WHEN x IS 20°MAX: LEGEND DINING _ _ ■ Y ALL BE 44"MAX NHEN X IS>20-25"MAR. X -- -- 77 SQ.FT. - - - INDICATES 36"MIN.EGRESS z PATH UNLESS NOTED OTHERWISE 140S.FT. - - ■ - - 0' NOIE 18 MIN IF O"MAX,16 Y--O MAX 4� ADA ROOM ----- - - - - _ ■ If X>10-24"MAX,11-QJ Y�I6"MAX IDENTIFICATION o -_-_-_-_ ------------------------------------------------------------- _-_- HIGH AND LOW SIDE MAXIMUM SIDE REACH UNOBSTRUCTED MAXIMUM FORWARD EXIT �� - -_-_------ ------ -------- ------- --------- -------- - -------- --------_ -_-_-_- r- ■ _-_- REACH LIMITS OVER OBSTRUCTION. FORWARD REACH REACH OVER A HIGH SIGN GRADE 2 "5.+ __------- ------ ---- ---- ---- ---- ---- --_-_- _-_ r : -- SIDE REACH FRONT REACH OBSTRUCTION --- ---� BRAILLE ------- ----44'rEGRESS PATH-----------------44 EGRESS PATH-------- - t= - -- _—_—_—_—_--- ---------------------------------------- -- — -- / PLAN RA ----- � —fl— R- / PROJECT NUMBER: 17-420 DNING T� DRAWN BY: RP 79$O.FT. 2 -- _��-- _ ---______- MN, 48" w EXIT CHECKED BY: P _r 1'-� 1 _„-�__ _p_Q 44"EGRESS PATFi-____ - { MIN. / —' - • ----- _ _____ O z_ < / GRADE -- MIN. 6" --- 1'-6" 25"MAx BRAILLE A tHARAT ACTILE 4 C ERS ACCESSIBILITY 30 PREFERRED ACCESSIBLE SIGNAGE NOTES PLAN MIN' _ \ LOCATION OF 1. CHARACTERS AND SYMBOLS SHALL CONTRAST 33'-8" \ ADA ROOM WITH THEIR BACKGROUND. I DISTANCE BETWEEN EXITS N ACCESSIBLE SEATING \ _ \ IDENTIFICATION 2. IDENTIFICATION SYMBOLS ARE TO BE CENTERED SIGN ON DOOR 60"ABOVE FLOOR AND ARE TO BE DISTINCTLY DIFFERENT FROM THE DOOR IN \ COLOR AND CONTRAST. o \ 3. LETTERS AND NUMBERS ON SIGNS SHALL BE SHEET NUMBER: 81 MAX OCCUPANCY \ RAISED 1/32"MIN.SHALL BE 5/8"MIN.HIGH AND SHALL BE SANS-SERIF UPPERCASE a ACCESSIBILITY PLAN SIGN TO BE POSTED C EXIT SIGNAGE DETAIL BHHARAETERS ACCOMPANIED BY GRADE 2 �1 0 0 ` SCALE:114"=1'-0" AJ ScRle:112'=1'-0' V GENERALNOTES w ^� A. GENERAL CONTRACTOR TO DEMO EXISTING SPACE,AS REQUIRED,TO ACCOMMODATE ALL NEW o DO rn CONSTRUCTION. B. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO INSPECT THE ENTIRE PROJECT SPACE PRIOR TO i a`� > m`m°o BID TO BECOME AWARE OF ALL THE TYPES OF MATERIALS AND QUANTITIES OF SUCH THAT WILL HAVE - d m o 1O m w N� TO BE REMOVED. m a ° ;o m- C. THE GENERAL CONTRACTOR IS TO PROVIDE ADEQUATE PROTECTION FOR ALL EXISTING ELEMENTS(PUBLIC m 3 w o w m z HALLWAYS,SURROUNDING TENANTS,ETC.)WHICH ARE ADJACENT TO THE CONSTRUCTION AREA AD DO m o¢3 D. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE HANDLING AND DUMPING COSTS FOR THE j `�' w a L 3 REMOVAL OF ALL DEMOLISHED MATERIAL,TRASH AND REFUSE ACCUMULATED ON THE JOB SITE BY ALL SUBCONTRACTORS.THE G.C.IS RESPONSIBLE TO INSURE THAT THE SPACE AND ALL SURFACES ARE DISPOSED OF IN A SAFE AND LEGAL MANNER. E. GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATION OF ALL EXISTING LIGHTING,HVAC EQUIPMENT,SPEAKERS,FIRE PROTECTION SYSTEMS,ELECTRICAL SYSTEMS,SECURITY SYSTEMS AND ALL OTHER EQUIPMENT.G.C.TO RELOCATE OF IN CONFLICT WITH NEW CONSTRUCTION. D F. GENERAL CONTRACTOR IS TO CONTACT UNCLE DESIGN GROUP INC.FOR THE RESOLUTION OF ANY D CONFLICTS OF INFORMAPON ON DRAWINGS DURING DEMOLITION OR CONSTRUCTION DUE TO UNFORESEEN ELEMENTS. G. GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY PATCHING REQUIRED INSIDE&OUTSIDE OF THE CONSTRUCTION AREA,WHERE AFFECTED BY DEMOLITION. H. COORDINATION OF THE LOCATION OF DUMPSTER USED FOR REMOVAL OR DEMOLISHED MATERIAL WITH BUILDING MANAGEMENT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. I. "UNDER CONSTRUCTION"BARRIERS,WINDOW PAPER,AND SIGNAGE TO BE TAPED INSIDE WINDOWS AT THE START OF CONSTRUCTION CODED NOTES EXISTING FINISHES TO BE REMOVED AND SURFACE TO BE PREPPED TO RECEIVE NEW FINISH PER PLAN EXISTING CEILING/LIGHTING TO BE REMOVED K EXISTING FLOORING TO BE REMOVED AND SURFACE TO BE PREPPED TO RECEIVE NEW FINISH PER PLAN O4 EXISTING STOREFRONT TO REMAIN-CAULK AND SEAL TO BE LIKE NEW EXISTING OPEN FRAMED DEMISING WALL TO REMAIN INFILL 7'-4"BLOCK-OUT WITH NEW CONCRETE SLAB TO MATCH EXISTING AFTER UNDERGROUND PLUMBING HAS BEEN INSTALLED.SEE DETAIL B5/A100 O7 EXISTING COLUMN TO REMAIN WALL LEGEND: INDICATES EXISTING WALL,COLUMN,OR CONSTRUCTION TO REMAIN, 0 U.N.O. PATCH+PAINT AS NEEDED ®Au DRAWN S AND WRITTEN MATEM& INDICATES DEMO WALL CONTuNED HEREIN ARE THE PROPERTY OF THE NNGSE DESCR GROUP,INC.THEY MAY 1 ®EXISTING STOREFRONT W/FlXED GLAZING. EUSED,OR pD�f�INNAAxCOPIED. MANNER Wx DUTT RIM AUTHORIZATION FROM THE ARCHITECT. G Au n 2 S ARcy7)Gi , •tFp v<vi CA GL :as a u =_ oix7jAAPg1p W`YY���p O Q ■ a ■ F­zzo O w 00 a O 1 ■ J *CONTROL JOINTS TYPICAL EVERY 10'-0"MIN TO 15-0"MAX. a G Ln z 6x6-W1.4xW1.4 Wh4F #4 RECAP®12"O.C.COREDRILLED AND N ANCHORED INTO EXISTING SLAB WITH HILT] HY150 ADHESIVE. [NEW 4°MIN.CEMENT SLAB-ALIGN TOP B WITH ADJACENT EXISTING SLAB ALIGN 1 4 ff x _— EXIST ING�SLAB SAW CUT JOINTS SAME DAY AS CONSTRUCTION POUR 1/4 SLAB DEPTH FILL 2 S EXISTING FILL WITH MASTIC NEW FILL AS REQUIRED !! B5 SLAB IWFILL DETAIL SCALE:314'=1'-0' F N TYPICAL®NEW ALL CEMENT USED SHALL CONFORM TO THE LATEST ASTM SANITARY SEWER PIPE SPECIFICATION C 150,TYPE 3.ONLY ONE(1)BRAND OF - PORTLAND CEMENT SHALL BE USED IN ANY ONE STRUCTURE. q CONCRETE MIXTURE SHALL BE DESIGNED TO PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI IN 3 DAYS. 5 CONIC SLAB INFILL WITH#3 BARS®12" PROVIDE(3000 PSI)GONG FLOOR OC PARALLEL WITH TRENCH®MID DEPTH. SLAB ON 10 MIL POLYETHELENE VAPOR BARRIER ON EXIST COMPACTED PROJECT NUMBER: 17-420 #3 BARS 18"LONG®96"OC FILL.DEPTH TO MATCH EXISTING SLAB DRAWN BY: RP (STAGGERED)EACH SIDE.DRILL& THICKNESS. CHECKED BY: MP 1 4 T 4 T 4 1 ADHERE INTO EXISTING SLAB WITH FINISHED JOINT SHALL BE SMOOTH 3-1/2"EMBEDMENT. AND STRAIGHT SHEET TITLE: O -6 EXIST CONC SLAB-ON-GRADE A TOP of CONC SLAE„ EXISTING CONDITIONS LIM POROUS FILL MATERIAL TO MATCH \ PLAN EXIST .�\�\ AGENT SLAB&APPLY BONDING GENT COMPACT FILL TO 95%DRY DENSITY IN ACCORDANCE w/ASTM D698 UTILITY PIPE OR CONDUIT,COORD W SHEET NUMBER: (COMPACT IN 8"LIFTS MAX) MECHANICAL,PLUMBING AND ELECTRICAL DRAWINGS EXISTING CONDITIONS PLAN SAW CUT POUR BACK DETAIL Al 00 � SCALE:1/4"=1'-0" „� Scale:112'=1'-O' DOOR SCHEDULE DOOR TYPES CODED NOTES w "" Fa Q❑ mvz DOOR FRAME 1O 1"SPACING BETWEEN OVEN AND WALL rc " m m? z� z❑ omw TEMP. Z INSTALL 5/8"PLYWOOD BACKING BEHIND WALL MOUNTED SHELVING&HAND SINKS(+24"-72"AFT OR E w m o N m o GLASS/ / +36"-84"A.F.F.) m- 0 CD Q 30 INSTALL BOTTLE CAP CATCHER AS LOCATED ON PLAN Ow 3 w 0 w -- OEXISTING S-O"X 7'-0"X 1�" / / m w m o 0 101 A AL EXISTING AL EXISTING GROUP 1 G.C.TO PROVIDE STUBS FOR THE SODA SYRUP&CONDENSER'LINES',COLD WATER&FOR ELECTRICAL. z " w a 3 (PAIR) (V.I.F.) Oq PANIC, PUSH-PAD OR 3'-0"X T-0"X 1�" \ \ HOLLOW FIELD VERIFY.REFER TO KITCHEN DRAWINGS FOR MORE INFORMATION. 101A EXISTING (V.I.F.) A AL EXISTING AL EXISTING GROUP 1 \ \ METAL G.C.TO PROVIDE AND INSTALL CONDUIT FOR CO,/SYRUP LINES-BAG N BOX/CO2.FIELD VERIFY LEVER HARDWARE THAT ( \\ \\ O LOCATION AT BEVERAGE STATION.VERIFY ACCESS POINT WITH BLAZE PIZZA CONSTRUCTION 103 NEW(BY MW/INSTALL BY G.C.) - 16 GA SS COORDINATOR. DEACTIVATES LOCK IN A - -- -- -- -- KICK PLATE SINGLE MOTION. O (2)1'-6"X 7'-0"X o ALUM. O G.C.TO HARD PIPE GAS AND HARD WIRE ELECTRIC AT OVEN 106 NEW 1Y7 D SC AL SS -- GROUP 5 O7 24"X 24"STAINLESS STEEL ACCESS PANEL AT STAINLESS STEEL SHROUD-SEE D3 A600 D D DOOR TYPEA DOOR TYPEB / 106 NEW S-O"X 7'-0"X 1%" C HM PT P-6 HM PT P-3 GROUP 4 ® CASEWORK BY VENDOR-REFER TO MILLWORK SHOP DRAWINGS 48'-7y"(V.I.F.) S-0"X 7'-0"X 1%" /\ O9 EXISTING STOREFRONT DOOR AND GLAZING 109 EXISTING A AL EXISTING AL EXISTING GROUP 1 6 4" 7,-3„ 3,-0„ 5_6�e 4'-5)/4" r--12._i 4" TS'_8„ (V.I.F.) 9°x14" n 110 NEW 3'-0"X 7-0"X 13�" C SC PT P-6 HM PT P-3 GROUP 2 a ACRriIC G.C.TO ENSURE 6'-0"X 8'-0"ENTRY OPENING FOR OVEN DELIVERY MNDOW OVEN LEVEL WITHIN 12'RADIUS-NO MORE THAN 1/4"CHANGE IN GRADE UNDER OVEN-OVEN CANNOT BE SHIMMED 105NEW 3'-0"X T-0'X 1 C SC PT P-6 HM PT P-3 GROUP 2 SOLID CORE \ EpASONSCP-4 12 WALK-IN DOOR SWEEP TO BE INSTALLED TO SWING 1"ABOVE FLOOR TILE 16 GA SS 13 G.C.TO CUTOUT OPENING FOR(2)BAIN MARIE PANS AT GREET STATION-(1)1/9 PAN&(1)1Y- COORDINATE SIZE AND LOCATION WITH BLAZE CORPORATE KICK PLATE L B5 1 DX® 14 CUTOUT OPENING FOR(1)BAIN MARIE 1/9 PAN AT 3&Z TABLE-COORDINATE SIZE AND O D7 Di O DOOR TYPEC DOOR TYPED / 1100 MATERIAL KEY: FINISH KEY: LOCATION WITH BLAZE CORPORATE 4 L- AL-ALUMINUM AL-ANODIZED ALUMINUM(CLEAR)MATCH EXISTING 'NOT ALL DOORS SHOWN ARE USED 5 SNEEZE GUARD POSTS TO BE SPACED EVENLY-S-6"GLASS SPANS MAX-SILICONE GLASS IN PLACE HM-HOLLOW METAL PT-PAINTED WOMEN'S -J r- SC-SOLID CORE SL-STOCK LAMINATE(SOLID COLOR:FOG) 16 UNDERGROUND BEVERAGE CHASE-SEE DETAIL A4 A600 RESTROOM - -- WALK-IN SS-STAINLESS STEEL pp -� COOLER 17 GIVEN PROVIDE OUT UPON REQUES PERMANENTLY EIXED SIGN AT POS COUNTER THAT READS"COMPLIMENTARY WATER CUP =tea - MEN HARDWARE SCHEDULE RES;ROOOM �f_-� 12 o o _ ` GROUPI-ENTRY DOORS(VAR.-PROVIDE IF NOT EXISTING) GROUP4.OFFICEDOOR G NERALNOTES: YI A. HEALTH DEPARTMENT REQUIRES SNEEZE GUARD TO BE PLACED AT ALL OPEN FOOD AREAS - n o o , Y i Y= EA. EXIT DENCE PANIC BAR(FACTORY INSTALLED) 3 PR. HINGE STANLEY-FBB179-4 1/2"x4 1/2° B. MAX EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 LOS.FOR BOTH EXTERIOR DOORS AND =_= E2 J� — — 1 EA LOCK RIM CYLINDER-80-129 VERIFY CAM.&FINISH MAT'L 1 EA. LATCH SCHLAGE—AL-405 SAT 626—(PRIVACY HDW.) INTERIOR DOORS,SUCH PULL OR PUSH EFFORT BEING APPLIED AT RIGHT ANGLES TO HINGED 1 EA. CLOSER HEAVY DUTY CLOSER,LCN-4041(4040 SERIES) 1 EA. CLOSER DORMA—7414 AR DOORS.COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET STORAGE Al 1 EA. DOOR PULL KAWNEER—CO-9(OR EQUAL)—COLOR TO MATCH STOREFRONT 3 EA. SILENCERS IVES—KP10X34-32D THE ABOVE STANDARDS. ®AIL DRAWNCS MD wRI Ex MA ExA 105 / 1 EA. SIGNAGE SIGNAGE"DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS" 2 EA. KICK PLATE 12"x34"KICK PLATE,16 GA.SS C. ADD DUROCK CEMENT BOARD OR EQUAL FROM FINISH FLOOR TO 24"A.F.F.ON ALL KITCHEN CONTAINED IEFflN ARE THE PROPERTY OF WALLS AND BATHROOM WALLS,PROVIDED DUROCK CEMENT BOARD OR EQUAL TOP TO BOTTOM 1HE DNG1 OE9CR GROUP,INC.THEY MAY 1 EA. SIGNAGE SIGNAGE"MAXIMUM OCCUPANCY".POST AT MAIN ENTRY 1 EA. STOP WALL MOUNTED-DON-JO-1407-630 NOT BE REAM,COPIED,REUSED,OR E2 0 \ E2 E4 / THRESHOLD TO MATCH DOOR TYPE AND FLOOR CONDITION ON ALL WALLS IN MOP SINK STALL. [A ES IN A MxNER MT40UT wRI EN 1 EA. THRESHOLD GROUP 5-ELIASON DOOR-MODEL#SCP4 D. VERIFY SEALANT&CONCRE E FLOORING SAMPLE WI H THE CORPORA E CONSTRUCTION AUTHORIZAl1ON FROM THE ARC4IITECT. / / (PROVIDE POSITIVE SEAL AGAINST AIR PENETRATION) 2 EA. HINGE EZ SWING MANAGER AND OWNER PRIOR TO INSTALLATION OF ANY MATERIALS. VERIFY CORRECT MOISTURE C \ --- -------------- -—/ 16 1 EA. SWEEP PROVIDE DOOR SWEEP TO MATCH THRESHOLD(MATCH STOREFRONT) LEVELS PRIOR TO ANY TILE AND/OR STAINING INSTALLATION. / 2 EA. WINDOW 9"X14"SINGLE PANE BLACK RUBBER MOLDING AUG17 / GROUP DOORS PASSAGE SET E. SEE ENLARGED RESTROOM PLANS ON SHEET A400 DIMENSIONS,ELEVATIONS,AND DETAILS. / 2 EA. KICK PLATE 12"H KICK PLATE,20 GA.SS TIMTUD/gpT OFFICEF. USE DUROCK CEMENT CLEANING N 3 PR. HINGE STANLEY-FBB179-4 1 2"x4 1/2 DOOR AND HARDWARE NOTES: H. DIMENSIONS ARE INSULATION IN WALL FACE SCD OR EQUAL AT HEDULED N W WALLS& ALL TYPES. YP PLUMBING FIXTURES. AR ' A400 108 / AREA 1 EA. DOOR PULL HIAWATHA 200DX523E-FINISH US26D 1. PERIMETER DOORS TO BE KEYED ALIKE.PROVIDE KEYWAY AT EXT. Al HALLWAY / 106 FACE. _ 109 Al rr 1 EA. PUSH PLATE HIAWATHA 200D-FINISH US26D I. ALL GLAZING SHALL BE FIRMLY SUPPORTED ON ALL FOUR EDGES. g`UZvr CART-L '�nas 1 L/ 1 EA. CLOSER DORMA-7414 AR 2. G.C.TO FURNISH&INSTALL CYLINDER IN ALL INTERIOR H.M.DOORS. J. ALL STATIONARY FOOD SERVICE EQUIPMENT MUST BE SEALED TO BOTH CURBS AND WALLS WITH 4'-5• 8'-11/" 13'-4y" 5'-6y" ALL INTERIOR DOORS TO BE KEYED ALIKE.PROVDE KEYWAY AT EXT. CLEAR CAULK. Z / 3 EA. SILENCERS IVES-KP10X34-32D FACE. 1 Al 4 / / \ / 2 EA. KICK PLATE 12"x34"KICK PLATE,16 GA.SS 3. ALL HOLLOW METAL DOOR FRAMES ARE TO BE WELDED. LEGEND, l 0 E1 B ,� - / - - 11 - 1 EA. WOMEN'S-SIGN:"WOMEN"(SEE SIGN ON SHEET A400) 4. EGRESS DOOR HARDWARE SHALL BE READILY OPERABLE FROM THE -- /t(\ 1 EA SIGN MEN'S-SIGN:"MEN" SEE SIGN DTL ON SHEET A400 EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR ��ipZZTE10 1`YYxSO� Al �, A7 Al Al ( ) INDICATES EXISTING WALL,COLUMN,OR CONSTRUCTION TO REMAIN, - EFFORT,PER SECTION 1008.1.8. 0 L L 106 1 EA. STOP FLOOR MOUNTED-DON-JO-1443-626 5. DOOR HANDLES,PULLS,LATCHES,LOCKS AND OTHER DEVICES ON U.N.O. PATCH+PAINT AS NEEDED PROVIDE IF NOT EXISTING) DOORS REQUIRED TO BE ACCESSIBLE SHALL NOT REQUIRE TIGHT ®INDICATES NEW WALL.(SEE WALL ASSEMBLIES) GRASPING,TIGHT PINCHING OR TWISTING OF THE WRIST TO OPERATE, \ L- L- 3 PR. HINGE STANLEY-C6179-4 1 2 x4 1 2 ®INDICATES NEW HALF HEIGHT WALL.(SEE WALL ASSEMBLIES) L L Fi EA. LOCK C CINDER W/REMOVABLE CORE PER SECTION 1008.1.8.1 IH1 6. DOOR STOPS AND BUMPERS TO BE INSTALLED BEHIND ALL DOORS. =EEEEEEll EXISTING STOREFRONT W/FIXED GLAZING. F1 1 EA. CLOSER HEAVY DUTY CLOSER,LCN-4041(4040 SERIES) 7. ALL HOW,TO BE US-26D BRUSHED CHROME,CLEAR ANODIZED FINISH. ®INDICATES NEW AND/OR RELOCATED GLAZING p COOKING ��� /^/ Y / 14 1 EA. ALARM DETER,EXIT ALARM EAX-3500(FLUSH MOUNTED) 8. AT ALL EXISTING DOORS THE CONTRACTOR SHALL VERIFY THAT n / r i 1 EA. THRESHOLD PEMKO-#171A-SIZE AS REQUIRED EXISTING HOW.HAS ALL FUNCTIONS LISTED IN THE HOW.SETS AND IS 103 L. j// \ / z -1� 2 2 1 - 1 EA. SWEEP PEMKO-#307AV-SIZE AS REQUIRED IN PROPER WORKING ORDER-TO MATCH BLAZE PIZZA'SHl- WALL TYPES-SEE SHEET A111 a O 103 r- ___ // // ppA -=j �1 7- =j�=SERVICE 9 - 1 EA. WEATHER STRIP PEMKO-303AV-SIZE AS REQUIRED SPECIFICATIONS O N r7 ARIA D2C 1-2Y 3'-6 0 ( ) )OQ( DOOR TAG-SEE SHEET A110 F a LL J00 1 EA. KICK PLATE 24"x34" 16 GA.STAINLESS STEEL FINISH _ n __ / / /�� 13 600 Y STOREFRONT TAG-SEE SHEET A110 a C) 0 r Al III AREA- III 3%"20GA.®16"O.C.STEM WALL J D-A A600 Cl BY G.C. %"TYPE"X"GYP.BOARD EXTERIOR DOOR&STOREFRONT O L_ / / 3 3'-2"MIN. A6?O Q Ln z 3Og 15 18' 11y° 5'-2" SEE FINISH PLAN AND ELEVATIONSFORHES N m THRESHOLD SET IN FULL BED OF SEALANT B 16 /// 9 YA"TEMPERED GLASS B BARRIER 8 W THRESHOLD TO BE Y2-HIGH MAXIMUM SEE SHELL �BUILDING P fyl= W FRAME ❑ BEE A300ZE LFOR OVERALUMINUM L QDIMENSIONS ax =T ®i / ❑ 3%"20GA.4D 16"O.C.STEM BY WALL 8 TYPE°X"GYP.BOARD o //// ❑ ❑ AIRI PEMKO 1665_THRESHOLD OR MODIFY EXISTING.G.C.TO INSTALL USING 101 3'-6" SEE FINISH PLAN AND ELEVATION FOR NO.10x1-1/2"FHWS,PHILLIPS(FACTORY PROVIDED) M ® // / ❑ c---] ❑ FINISHES EXTERIOR EXPANSION JOINT FOR REFERENCE ONLY // ❑ ❑ ❑ B4 PREP ROOM WINDOW DETAIL B5 THRESHOLD AT EXTERIOR DOOR / Stale:N.T.S. ❑ ___ ❑ Scale:3/4"=,'-0" z <% n Q 5" I, SEE WALL TYPE ❑ ❑ 2^ 2-20 GAUGE METAL STUDS ON EITHER SIDE OF DOOR TO 5 CAULK TO MATCH DOORFRAME UNDERSIDE OF SLAB.PROVIDE 20 GAUGE METAL STUD o O O O O O O "'� BRACE AT 45 DEG.TO UNDERSIDE OF SLAB ON LATCH HOLLOW METAL FRAME W/STOP SIDE OF DOOR ❑ ___ ❑ - (3)ANCHORS PER JAMB H- \\ z PROVIDE SIGN AT SODA STATION, s SUPPORT To (2)METAL STUDS,TYP EACH SIDE UNDERSIDE OF SLAB "COMPLIMENTARY WATER CUPS OF FRAME GIVEN OUT UPON REQUEST." n r n -1 g 5/8"GYPSUM BOARD,FINISH AS 3 PROJECT NUMBER: 17-420 SCHEDULED SEE SHEET A120 5/8"GYPSUM BOARD w DRAWN BY: RP ON 3 5/8"METAL CHECKED BY: MP ( 10 B5 A A ( STUDS BS 9 9 9 _ METAL ANCHOR 110 ---J 110 DX CAULK TO MATCH DOORFRAME METAL FRAME A SHEET TITLE - - �' `' I - '� HOLLOW METAL FRAME W/O STOP DOOR JAMB CONSTRUCTION 101A 101 (3)ANCHORS PER JAMB HEAD 3'TO EDGE OF DOOR U.N.O. (2)META STUDS,TYP EACH SIDE PLAN OF / LOCATE SWITCH 8"FROM DOOR AND DOOR i SCHEDULE L-- --J L-- -- 5/8"GYPSUM BOARD,FINISH AS / STOPD SEE SCHEpU FLOOR MOUNTED DOOR SCHEDULED SEE SHEET A120 ALTERNATE SWITCH LOCATION 6" SHEET NUMBER: B -5/8"WHEN ADJACENT TO DRYWALL OR FROM DOOR CONSTRUCTION PLAN TILE;7/8"WHEN ADJACENT TO WOOD A 110 TYPICAL DOOR JAMB DETAILS TYP.DOOR JAMB&PLACEMENT DETAIL � SDALE,/4'=,'-o" A4 stale:N.is. A5 Scale:3'=,'-0' m NOTE:ROOF DECK_ EXISTING ROOF STRUCTURE EXISTING WALL w m -G.C.TO VERIFY/MAINTAIN CONSTRUCTION(VERIFY IN 111 o m ao ¢mm m ROOF FIRE RATING PER LOCAL CODE FIELD) STRUCTURE L.L.PROVIDED METAL E w - in m w SEE BELOW SCHEDULE EXISTING STRUCTURE(V.LF.) i a m �� m�o A4B CAULK ALL WALL FOR SUBSTRATE MECHANICALLY FASTEN BOTTOM m w �in d FRAMING AND INSULATION 2y" %" STAINLESS STEEL WALL CAP WITH 2" ° m- Att� SCTIONPENETRATIONS14PER UL& - OF DECK ¢ 3 0 DOWNTURN BOTH SIDES-BY G.C. o z 0 3 ..m J SECTION 714 OF THE 2012 IBC DO w L.L.PROVIDED-(1)LAYER(s) RUN STUDS UP ALONG 0 STAINLESS STEEL WALL CAP WITH m' ><3 _ 2X8 BLOCKING AT TOP OF 20 GA. i m m z o¢ 5/8"TYPE"X"GYP.BD.,BOTH SIDES OF ROOF 2'DOWNTURN BOTH SIDES N -z x 4 3 PATCHED AND REPAIRED TO A _L METAL TRACK ME.FRAMING AS MTL.STUD 16"0/C- a 3 RUN STUDS UP ALONG SIDES-FIRE TAPED AND STRUCTURE SMOOTH LEVEL SURFACE FREE � SCHEDULED BELOW CONTRACTOR PROVIDED AND SIDES OF ROOF T.O.WALL STUDS TO BE CAULKED AT ALL PENETRATIONS WF-1 STRUCTURE OF VISIBLE IMPERFECTIONS. INSTALLED INIS SEE FINISH PLAN AND ELEVATIONS 12"ABOVE FINISHED WF-5 CEILING FOR FINISH,REFER TO WALL FINISH R-11 NON-COMBUSTIBLE TYPES AND INTERIOR ELEVATIONS �"FIRE TREATED PLYWOOD ACOUSTICAL BATT INSULATION A5A ji AT SOUND PARTITIONS WHERE 5/8"FIRE TREATED PLYWOOD A111 - s/e"DUROCK CEMENT BOARD FULL HEIGHT G.C.TO CONFIRM&INSTALL INDICATED-SEE SHEET A110 OR 5 8 GYPSUM BOARD-SEE MTL.STUD®16"0/C- D CONTRACTOR PROVIDED AND - #l0 x 2"HWH PTD FASTENER W/WASHER 'DUROCK CEMENT BOARD CONSTRUCTION PLAN A110 D INSTALLED -ANCHOR AT EVERY LOW POINT OF PANEL OR EQUAL UP 2'-C"A.F.F. NOTE: < IF NOT PRESENT-SEEri -G.C.TO VERIFY STUD SIZE ANDTLA111 R-11 NON-COMBUSTIBLE ACOUSTICAL G.C.TO REMOVE GYP.BD.AND o o WALL ANCHOR BASE AT 48"O.C. DETAIL A1/A600 NOTE: SPACING. BATT INSULATION AT SOUND REPLACE WITH(1)LAYER(S)YY8" ATAS CHANNEL WITH 2"X2"FURRING STRIP -G.C.TO VERIFY STUD SIZE AND %7 DUROCK CEMENT BOARD OR EQUAL UP AT EXISTING WALLS WHEREPARTEICH WHERE INDICATED BELOW DUROCK CEMENT BOARD OR EQUAL - - SPACING. - 2 0"A.F.F. PROVIDE M 1 FINISH 12"UP B-1 NOTE: 34"DUROCK CEMENT INSULATION IS REQUIRED UP 2'-0'A.F.F.ON TENANT SIDE- -AT EXISTING WALLS WHERE INSULATION WALL&12"AT FLOOR PERIMETER-REFER REFER TO WALL FINISH TYPES AND FIRE TAPED AND CAULKED AT ALL BOARD OR EQUAL TO BE REFER TO WALL FINISH TYPES VERIFY/INSTALL R-11. M-1 -12"UP WALL&12"AT FLOOR USED FOR WATERPROOF IS REQUIRED,VERIFY/INSTALL R-11. AND TO ELEVATIONS TO Al/A600 t - -ALL DRYWALL SHALL BE PATCHEDINTERIOR ELEVATIONS PENETRATIONS -ALL DRYWALL SHALL BE PATCHED AND 3-5 8"20GA.SILL TRACK- DETAIL,WHERE FINISH WILL B5AND REPAIRED TO A SMOOTH LEVE REPAIRED TO A SMOOTH LEVEL SURFACE NOTE: _ UN-PUNCHED SET IN BE TILE&IN WET AREAS. ,11 SURFACE FREE OF VISIBLE G.C.TO PROVIDE WATERPROOFING ON NT FREE OF VISIBLE IMPERFECTIONS. BASE SEE FINISH PLAN A120 IMPERFECTIONS. B3 B5 j LTENANT LEASE SIDE AT ALL DEMISING WALLS-SEE DETAIL Al/A600 EXISTING PROVDED WALL CONSTRUCTION-CONTRACTOR A'il Al 3N"MTL.STUD A3 6"ME.STUD SERVICE KITCHEN SIDE DX TO CONFIRM DRYWALL IS INSTALLED 6"MIN.ABOVE I-I EXISTING LANDLORD E1 3%"MTL.STUD E3 6"MTL STUD L— _PROVDED INTERIOR BX LANDLORD PROVIDED DEMISING WALL C1 3V MTL.STUD FINISHED CEILING WALL 33§"MTL.STUD W/ 6"MTL.STUD W/ 1-HOUR FIRE BARRIER(GA-WP 1072) Di 3%' MTL STUD 02 6"MTL.STUD E2 3%"MTL STUD W/BATT E4 6"MTL STUD W/ / BATT INSULATION BATT INSULATION INSULATION BATT INSULATION KITCHEN Fi 3-5 8"MTL.STUD TYPE"A"-PARTIAL HEIGHT WALL TYPE'B"-DEMISING WALL TYPE"C"-HALF HEIGHT WALL TYPE"D"-FURRED WALL TYPE I -FULL HEIGHT WALL TYPE"F"-HALF HEIGHT WALL D1 WALL TYPES S.I.:1"=VHOI ATTACH 362T150 TRACK TO ATTACH 362T150 TRACK TO STUD W/(2)#8 AT 32" STUD W/(2)#8 AT 32" O.C.(MAX)CENTERED AT EXPOSED ROOF O.C.(MAX)CENTERED AT t-- REFER SEE CEILING PLAN EACH STUD AND EACH END STRUCTURE(V.LF.) EACH STUD AND EACH END ON SHEET A130 SEE CEILING PLAN ®ALL DRAWNGS AND WRITTEN MATERIAL 5 P4CONTAINED HEREINARE THE PROPERTYOFMTL.JOIST AT i6'O.C. /e"MOISTURE 336"MTL.J0157 AT 16"O.C. ON SHEET A130 THE UNGIE DESIGN GROuP,INL THEr MAY C3 RESISTANT GYP.BD. SEE FINISH PLAN AND NOT BEREwSED,CORIED,Rd•.Tlsn,OR "GYP.BD. Cl SEE CEILING PLAN C3 �§"GYP.BD.-PAINT P4 U.N.O. INIS ELEVATIONS-WF-4 IS DISCLOSED IN MY MANNER NEED' WITTEN RE TREATED PLYWOOD ON SHEET A130 AIR GAP PER MANUFACTURER SEE INTERIOR ELEVATIONS,FINISH AUTHmrznnON mOM THE AP4 SEE CEILING PLAN RECOMMENDATIONS PAINT PLAN,AND DETAIL D3/A111 TYP.AT QUEUE U.N.O.0 ON SHEET A130 "TYPE"X"GYP.BD. %"MOISTURE RESISTANT GYP.BOARD 4¢"TYPE X"GYP.BD. A 17 TYPE"X"GYP.BD. SEE INTERIOR ELEVATIONS COOLER WALL SEE DETAIL B2/A111' B3 A111 WFJ SEE DETAIL 82/A111(SEE FINISH PLAN) -B (SEE FINISH PLAN)WT-2 SEE DETAIL B4/A111 / X"DUROCK CEMENT BOARD OR �"' �C DUROCK CEMENT BOARD OR EQUAL UP "'UROCK CEMENT BOARD OR 3g"DUROCK CEMENT BOARD OR ADHE MOUNTED WITH CONSTRUCTION GRADE �rEQUAL UP 2'-0"A.F.F.- w2'-0"A.F.F.-PROVIDE M-1 FINISH 12"UP w I. iP'ADHESIVE-NO MECHANICAL FASTENERSDUROCK CEMENT BOARD OR L UP 2'-0"A.F.F.- EQUAL UP 2'-O"A.F.F.- PROVIDE M-1 FINISH 12"UP WALL WALL&12"AT FLOOR PERIMETER BEHIND L •�EQUAL UP 2'-0"A.F.F.-PROVIDE J &12"AT FLOOR PERIMETER- J V DUROCK CEMENT BOARDIDE M-1 FINISH 12"UP WALL PROVIDE M-1 FINISH 12"UP WALL 3 BEVERAGE STATION-REFER Al/A600 3 OR EQUAL UP 2-0"A.F.F.M-1 FINISH 12"UP WALL&12"AT "AT FLOOR PERIMETER- REFER TO Al/A600 FLOOR PERIMETER-REFER Al A600 &1ER AT FLOOR PERIMETER- SCHLUER ANTERIOR TRIM OR EQUIV. Q/ TO A1/A600 REFER TO A1/A600 SCHLUTER ASOAGRB TRIM OR EQUIV. _11,B-2 B-3 BJ B-1 SEE INTERIOR ELEVATIONS RESTROOM STORAGE CLEANING PREP AREA COOKING SERVICE AREA COOLER BEVERAGE STATION HALLS QUEUE LINE DINING C1 WALL FINISH 1 RESTROOMa _1.R C2 WALL FINISH 2 B.O.H. 6�a.,-,Q WALL FINISH 3 COOKING a -1-0 WALL FINISH 4(COOLER)A C4 WALL FINISH 4 BEVERAGEIHALLS D C5 WALL FINISH 5 QUEUE LINEIDINING C2.1 U u t 2 0161 "URBAN PUTTY"(TAN) [ O SEE FINISH PLAN N PAINT AND ELEVATIONS L 1 Q 0139 "CRISP LINEN"(CREAM) CD P-0 KIII 36MOD1P4 "BLACK" [ a C)6 Q 0190 "ARCTIC WHITE"(WHITE) 0190 "AR TIC WHITE" [ J J 2 ROWS SEE WALL TYPE FOR MATERIAL n n n � SEE REFLECTED CEILING PLAN PAINT SEE FINISH PLAN Li Q NO CEILING DIRECTLY ABOVE OVEN AND ELEVATIONS 2 ROWS O Li Q Ln z 3§"FIRE RESISTANT GYP.SUM N I BOARD TYPE"X" 4 ROWS TMETAL TRACK WITH 2-#10 EKS ATTACHED 4,0" EA 16"O.C.STUD AS REQ'D.(ESR B �i * WT-I-CERAMIC TILE ARRANGED _ #1976) B WFJ WT 1 TO THIS DIAGRAM AND THE VI PROVIDE HILTI X-DNI 32 P8S15 RATIO SPECIFIED ABOVE ®3'-O' O.C.(ESR#1663) 11"SUBORN CEMENT BOARD OR 8 ROWS 3 EQUAL UP 2'-0"A.F.F.—PROVIDE —3 TO BE LINED UP O.C.NTH � FLOOR CONNECTION DETAIL TYPICAL M-1 FINISH 12"UP WALL&12"AT SCHLUER SEAMS FLOOR PERIMETER-REFER Al/A600 / p J l Scale:N.T.S. SCHLUER ASOAGRB TRIM OR EQUIV. 3 ROWS ETAL BEHIND OVEN B-0 83 B 2 y nP ANNGLE BRAE @ 48M O/C w/(3)#10 EA END WALL FINISH 6(OVEN) WAINSCOT DETAIL @DINING TILE DETAIL @KITCHEN TILE DETAIL @ RESTROOMS YP. 2 ga.3"x 3"O T ANGLE w/(6)#10 INTO TOP TRACK Scale:l'=1'-0" Scale:N.T.S. Scale:N.T.S. Scala:N.T.S. 362 T-200-33 TRACK w/ z #10 EA FACE,EA STUD& 4 2 TYPICAL INTERIOR NON-LOAD BEARING STUD WALL-SLIP (2)#1ox 1"®16"O/C Y" WALL FRAMING AS SCHEDULED •I INTO(E)DECKING w TRACK AT TOP FINISH AS SCHEDULED SUBSTRATE AS (SIDE VIEW) o a STUDS TO BE USED(ICC-ES#ESR-3016): 12 SUBSTRATE AS SCHEDULED A TRACK BRACING SCHEDULED .. TOP-"SLIP" } .¢ MINERAL WOOL 9 c ALLOWABLE BOTTOM TRACK TRACK WALL FRAMING AS SCHEDULED ROOF DECK ABO 4 �+ SIZE SPACING TRACK 362 T-200-54 SLIP TRACK w/#10 EA FACE,EA 5 HEIGHT GAUGE GAGE(3" STUD&(2)#8 x 2"®16"O/C INTO(E)JOIST DEEP TRACK) —SUBSTRATE AS SCHEDULED MA 3V-25C STN 16" 15.4' 20 18 A111 12 ga.3"x 3"ANGLE CLIP x 9" DO NOT FASTEN GYP.END PROJECT NUMBER: 17-420 3V-ZOO STIR 16" 17.0' 2C 18 /f SOFTFORMS SKB KNEE // LNG w/(8)#lox 1"INTO(E) FIRE CAULK) TO PRIMARY RUNNER. DRAWN BY: RP 3S/a"-18 G HDS 16" 22.6, 20 18 BRACE KIT®48"O.C. SUBSTRATE AS SCHEDULED 1 B) DECK CONTINUOUS S/a TYPE"X ATTACH ONLY TO VERTICAL CHECKED BY: MP 6"-20G SIR 16" 24.5' 20 18 MAX(OR EQUAL) BOTH SIDES • GYP.BRD-TYP STUDS AND SECONDARY 6"-18G BOB 16" 33.6' 20 18 - POWDER COATED MATTE BLACK INCLUDING ALL HARDWARE 3%"20 GA.METAL ANGLE o e a VERTICLIP 362 w "x�"HEX SELF DRILLING / SHEET TITLE: NOES: SCREW®12"O.C. i BRACE 0 48' O/C w/(3) (2)#8 EACH LEG A 1. BOTTOM TRACK GAGES MAY BE 1Ya'SQUARE TUBING J ABA #10 EA END 9" FIRE RATED SLIP TRACK A BUILDING CODE REQUIRES THAT INTERIOR PARTITION WALLS BE 111 B DESIGNED FOR A LATERAL LOAD OF 5 PSI.THE FOLLOWING SUBSTITUTED FOR TOP-SLIP TRACK GAGES 3 IF STUDS ARE PERMANENTLY ATTACHED TO CHANNEL FOR Ya"GLASS "A"PLAN VIEW 1,34 4"TYP WALL GUIDELINES ARE BASED AL THIS LOAD.ALL STUDS GIVEN ARE BOTH FLANGES OF THE TRACK WITH 10 B5 W x 5"BASE PLATE I 1 ASSUMED TO BE EQUIVALENT TO THOSE MANUFACTURED BY # SCREWS TO BE#R X 2$"MIN. 111 12 ga.3"x 3"ANGLE TYPES DIETRICH INDUSTRIES,INC.ALL STUDS AND TRACKS ARE SCREWS. w/(4) "x3Yz"MASONRY BOLTS ASSUMED TO HAVE AN F 33.0 KSI.ALL STUDS ARE 2. ATTACH BOTTOM TRACK TO SLAB WITH w/EXPANSION SHIELDS CLIP x 9"LNG w/ + \ 362 T-200-33 TRACK w/#10 EA S Y HILT I X-DNI 32 PSS15®S-O"O.C. NOTES: (8)pox 1"INTO(E) FACE,EA STUD&(2)#8 x 2"®16" ASSUMED TO HAVE/a"GYP.BD.ON BOTH FACES FOR THE FULL ?� HEIGHT OR ARE PROVIDED WITH BRIDGING AS REQUIRED.DETAILS 3. IF GYP.BD.IS ON ONE SIDE ONLY,ADD 2) •PROVIDE AT EACH WALL END AND AT DECK � + � � 0/C INTO(E)JOIST OR BLOCKING ARE PROVIDED TO ACCOMMODATE VERTICAL MOVEMENT AT THE HORIZONTAL BRIDGING AT 5'-0"O.C. EACH/ THAN CHANGE SKBHEI IN DIRECTION TOP USING A 3"DEEP TRACK CONNECTION OR NO MOVEMENT. VERTICALLY. •FINAL WALL HEIGHT TO BE MIN 2"HIGHER SUBSTRATE AS SCHEDULED MAXIMUM HORIZONTAL DEFLECTION IS ASSUMED TO BE LIMITED 4.IF YOU HAVE A CASE THAT DIFFERS 336"20 GA.METAL ANGLE C STANDARD HEAD DETAIL SHEET NUMBER: TO H/240.PROVIDE LATERAL BRACING PER SCHEDULE. FROM THE ABOVE,PLEASE CONTACT THE "B"SECTION BRACE®48' O/C w/(3) STUD SIZE CHART ARCH TE SNEEZE GUARD DETAIL TYP.LOW WALL SUPPORT DETAIL SOFFIT BRACE DETAIL (A) #10 EA END HEAD TRACK DETAILS A 111 Al A2 Bale:2"=,'.D" A3 Bale:N.T.B. A4 Gcale:3"_>'-o" A5 Scale:3"=1'-0" GENERAL NOTES INTERIOR FINISH SCHEDULE w o MARK DESCRIPTION MANUFACTURER&SPEC REMARKS n Do ¢m m a NOTE: A. G.C.TO SUBMIT SAMPLES OF ALL FINISH MATERIAL TO HEALTH DEPARTMENT FOR RENEW PRIOR TO PURCHASE AND INSTALLATION. o m❑ DO m? 26 8 B. ALL FLOOR FINISHES SHALL BE INSTALLED WITH TOP EDGES LEVEL WITH ADJACENT MATERIAL TOP EDGES.CONFIRM TILE THICKNESS PAINT E� ^ ¢❑ -STAINLESS STEEL CORNER GUARDS AND WALLCAPS PROVIDED& (VA.F.) AS THESE MAY VARY.CONFIRM THAT NO OVERALL FLOATING OF FLOOR IS REQUIRED. z a w INSTALLED BY G.C. DUNN EDWARDS-COLOR:UNTAMED ORANGE-DEA110 E w o N -CORNER GUARD TO BE INSTALLED WITH CLEAR SILICONE ADHESIVE C. COORDINATE FLOORING TRANSITIONS AND BASE TILE INSTALLATION WITH MILLWORK SHOP DRAWINGS AND FIELD CONDITIONS. BENJAMIN MOORE-COLOR: FLAME SEE PLAN-PAINT ALL EXPOSED m o f m D. ALL THRESHOLDS SHALL HAVE A MAXIMUM HEIGHT OF 1 2"ABOVE EXISTING CONCRETE SLAB AND/OR INTERIOR FINISHES. P-1 PAINT-UNTAMED ORANGE w w a 3 0 m z / / STERWINI WILLIAMS-COLOR: OBSTINATE ORANGE COLUMNS o z m w 4'-0"---9'-0"------1l'-7%"--2'-Oy" E. TILE TRANSITION BETWEEN ROOMS TO BE CENTERED ON DOOR FRAME. -FINISH:EGGSHELL 3 m z x 3 FINISH AS VIF VIF V F. VIF F. SEE PLUMBING DRAWINGS FOR DIMENSIONS AND LOCATIONS OF FLOOR DRAINS AND FLOOR SINKS. DUNK EDWARDS-COLOR:MINK-DE6392 z umi m i i 3 18 GA.SS END GUARD PROP GO FINISH ASj SCHEDULED ( ) ( ) ( ) ( ) G. G.C.TO LEAVE ONSITE,UPON COMPLETION OF JOB(1)BOX EACH OF ALL WALL,FLOOR AND CEILING TILE USED. BENJAMIN MOORE-COLOR: BLACK BEAN SOUP PAINT ALL HVAC DUCTS& ^w a 3 AND INSTALLED BY GC SCHEDULED H. ALL FINISH MATERIALS TO BE IBC CHAPTER 8 COMPLIANT. P-2 PAINT-MINK SHERWIN WILLIAMS-COLOR: BLACK BEAN DISTRIBUTIONS SUBSTRATE ETPEER `i_YPE _ I. ALL INTERIOR FINISHES TO HAVE A FLAME SPREAD RATING OF 25 OR LESS.WITH A MAXIMUM SMOKE GENERATION FACTOR OF 450. -FINISH:EGGSHELL _ - J. TILE INSTALLER SHALL COORDINATE WITH GENERAL CONTRACTOR AND PROVIDE LAYOUT OF ALL WALL TILE PRIOR TO INSTALLATION. DUNN EDWARDS-COLOR:DEA187 18 GA.SS CORNER GENERAL CONTRACTOR. SHALL PREPARE WALLS AS TO MINIMIZE CUT TILES IN THE HORIZONTAL DIRECTION AND ELIMINATE CUT TILES P-3 PAINT-BLACK -FINISH:EGGSHELL SEE PLAN GUARD PROVIDED AND - IN THE VERTICAL DIRECTION ON ANY WALLS.CONTACT ARCHITECT OF ANY DISCREPANCIES IN DIMENSIONS FOR DIRECTION PRIOR TO (OR CORPORATE-APPROVED EQUIVALENT) FRAMING INSTALLED BY GC INSTALLATION,FAILURE TO ADHERE TO THESE REQUIREMENTS RESULTING IN ANY REMEDIATION REQUIRED TO MEET DESIGN INTENT WILL D SUBSTRATE PER WALL BE AT CONTRACTORS COST. DUNN EDWARDS-COLOR:CRISP MUSLIN-DE6212 D PER WALL TYPE - K. ALL WALL MOUNTED HVAC VENT REGISTERS AND GRILLS TO BE PAINTED TO MATCH ASSOCIATED WALL SURFACE. P-4 PAINT-CRISP MUSLIN BENJAMIN MOORE-COLOR: SONNET PAINT ALL EXPOSED ROOF TYPE L. ALL GYPSUM BOARD WALLS TO RECEIVE PAINT TO HAVE LEVEL 5 FINISH SHERVNN WILLIAMS-COLOR: NATURAL CHOICE STRUCTURE •h M. ALL EXPOSED CONCRETE FLOORS TO BE POLISHED CONCRETE BY RETROPLATE INSTALLER(CERTIFIED BY ADVANCED FLOOR -FINISH:EGGSHELL PRODUCTS). INSTALLER TO POLISH TO A MINIMUM 1200 GRIT LEVEL 3 FINISH. DUNN EDWARDS-COLOR:DRIFTING-DEC770 FINISH ASNIH A P-5 PAINT-DRIFTING ENJAMIN MOORE COLOR: PLYMOUTH ROCK SEE PLAN SCHEDULED SCHEDULED CODED NOTES SHERWIN WILLIAMS-COLOR: MEGA GREIGE END CAP —FINIS":EGGSHELL CORNER GUARD O1 STAINLESS STEEL CLOSURE STRIP AT VOID SPACES BETWEEN WALK-IN AND WALL SURFACES. DUNN EDWARDS-COLOR:CASTLE ROCK-DE6375 P-6 PAINT-CASTLE ROCK BENJAMIN MOORE-COLOR: STORM SEE PLAN D1 TYP.SS CORNER GUARD DETAIL D2 WALL MURAL ELEVATION O2 STAINLESS STEEL CLOSURE STRIPS BETWEEN OVEN AND WALL S"ERNISH:EGGSHELL COLOR: GRAY MATTERS N.T.S Scale 118"=1'-0' STAINLESS STEEL CORNER GUARD TO BE 2"WIDE&FULL HEIGHT&CLEAR COATED FINISH(ADHERE TO WALL W/CLEAR SILICON-NO DUNN EDWARDS-COLOR:SUMMER LAKE-DE5838 O SCREWS).FURNISHED&INSTALLED BY G.C..-SEE DETAIL Dl/Al20 P-7 PAINT-SUMMER LAKE SHERWIN WILLIAMS-COLOR: BLUE PLATE -SW6796 SEE PLAN n -FINISH:EGGSHELL O4 WALL GRAPHICS-VERIFY FINAL GRAPHIC PACKAGE AND LOCATION WITH FRANCHISOR,CLIENT,AND VENDOR. WALL FINISH OEXPO AND POS COUNTER TO SIT FLUSH TO F-1 FLOOR-TILE BASE AND FLOOR BELOW TO BE FINISHED AFTER MILLWORK IS SET IN DALTILE-SERIES: MODERN DIMENSIONS PLACE -SIZE: 4x8(4-1/4%8-1/2") -COLOR: ARCTIC WHITE#0190 © DO NOT INSTALL WF-3 BEHIND BOOTH BACK.PAINT P-5 INSTEAD.SEE INTERIOR ELEVATION -GROUT:CUSTOM CHARCOAL#60 DALTILE-SERIES: MODERN DIMENSIONS BULLNOSE TILE TO BE USED AT OPEN EDGES OF TILE-INSTALL WF-2 M-1 B-3 M-1 B-3 1 1'-0" WT-1 WALL TILE _-COLOR4x8RBAN PUTTY#0161 FULL HEIGHT IN SERVICE AREA AC21 MIN. AC31 -GROUT:CUSTOM CHARCOAL#60 DEIAIN B3/A IN CUSTOMER FOR LAYOUT SEE DALTILE-SERIES: MODERN DIMENSIONS -W SIZE: 4x8(4-1/4"x8-1/2") ALK-IN ®ALL COOLER ORA'MNGS AND WITTEN MATERI& i C3 -COLOR: CRISP LINEN#0139 107 A111 -GROUT:CUSTOM CHARCOAL#60 CONiuNED IE1mN ARE THE PROPERTY OF C2 THE UNG1 DES GROUP,INC.THEY MAY WOMEN'S MEWS DALTILE-SERIES: RITTENHOUSE A111 F-2 NOT BE REAM,COPIED.REUSED,WT40 OR RESTROOM RESTROOM -SIZE: 3x6 MODULAR p5GO5E0 IN ANY MANNER M1HWT WRITiFN 111 n0 M-1 -COLOR: ARCTIC WHITE#0190 BULLNOSE TILE TO BE USED AT AUTHORIZA11ON FROM THE ARCHIIECT. i-0 T 111 TI -GROUT:CUSTOM CHARCOAL#60 OPEN EDGES OF TILE-INSTALL IN _ F-3 F-3 -----11- Pd - MIN. q .I._ W1-2 WALL TILE DALTILE-SERIES: RITIENHOUSE RESTROOMS-SEE DETAIL B4/A111 AUG17 C M-1 M-1 _ ____ 1 M-1 B-3 -SIZE: 3x6 MODULAR FOR LAYOUT --- -COLOR: BLACK#K11136 MODIP4 \`xxptMUl HI/try///// Ci Ci _ STORAGE a WF-2 M-1 B-3 -GROUT:CUSTOM CHARCOAL#60 ALL A5 A5 A111 105 ATAS INTERNATIONAL A120 A120 2•CARI-T- "'tnas C2 WF-1 CORRUGATED METAL PANELS -COLOR: SEE INT.ELEVS.-SHEET A300 INSTALL AT CUSTOMER SIDE OF YJT-2 Pd M-1 B-2 WF-2 P-0 M-1 B-2 7A111 SERVICE LINE -SIZE:SEE TNT.ELEVS.-SHEET A300 Di WF-2 TRIP WALL PANEL "MARLITE"INC.#P-100;PEBBLE FIBERGLASS REINFORCED INSTALL FULL HEIGHT IN B.O.H.NOT .t0 P-1 P-2 Pd WF-3 B-1 P-1 P-2 Pd WF-3 B-0 A120 POLYESTER PANELS WITH MATCHING TRIM AND SEAMS IN CUSTOMER VIEW 2' WF-2 M-1 B-3 m INSTALL AT DINING ROOM WALLS- �i/ TE O X VOA C5 q C4 C4 A111 WF-3 WAINSCOT VALCHROMATE COLOR:BLACK SEE TT PLAN-APPLY WITH ADHESIVE TT HALL ////1Upiip UNYYV 8 111- A111 A111 F-1 A111 F-2 r WA ONLY&NO FASTENERS 109 M-1 OFFICE F-2 3 G.C.TO PREP WALLS AS REQUIRED P-5 WF-3 B-1 100 CLEANING M-1 AND PROVIDE A LEVEL 4 FINISH. - - C2 3 ARC WE-4 BLAZE PIZZA MURAL CUSTOM WALL MURAL PROVIDE 1 COAT OF ZINSSER 123 A111 FOLLOWED-FULL HEIGHT:FROM M-1 C2 FLOOR OR WAINSCOT TO CEILING m B1 3 A111 VIRIDIAN WOOD-SERIES:GOOD NEIGHBOR SEE ELEVATIONS FOR INSTALLATION O Q CS " Bi ll A111 ® WF-5 RECLAIMED WOOD STRIPES -SIZE: 5"x3'-5"x44" PATTERN-COORDINATE'NTH � o A111 A1 WF-2 M-1 B3 -COLOR: WEATHERED REDWOOD BLAZE CORPORATE R O BASE - Cn z 4YT-1 8-3 INSTALL AT DINING AREA&FACE ` W � B-1 GALVANIZED STEEL BASE -6"W/MIN.%7 RADIUS COVE f y- a � B-1 B-3 OF SERVICE LINE C2.1 _ C2.1 _ L _ AREA O c ( A111 A111 104 DALTILE INSTALL AT RESTROOMS-GROUT C/7 8 WF1 COOKING SERVICE .1 ( B-2 SANITARY COVE BASE 6"x6 W/MIN.�C RADIUS COVE TO MATCH ADJACENT FLOOR IL O _J 3 I M-1 B-3 AREA D1C -COLOR:ARCTIC WHITE#0190 F-2 AREA M-1 B-3 t C2.1 m n n n Li q� C1.151 e..I a 103 �A111 102 mm DALTILE-MODEL: Q3565 Q F-2 A111 Li AS Pd WF-2-- - Pd ---� M-1 B-3 COVE BASE -6"X6"W/MIN.i/e"RADIUS COVE INSTALL AT B.O.H 120 M-1 B-3 C2 -COLOR:ASHEN GRAY#0190 G _� z c B-1 _______ A111 FLOOR cV D1C INSTALL THROUGHOUT DINING AND ~ a SB A111 - 1"/T WF-2 RETROPLATE 99-RETROGUARD SYSTEM HALLWAY AREA G.C.SUPPLIED AND B ��0 O B 1I' q M-1 BJ Y M-1 B-3 F-1 POLISHED CONCRETE -COLOR:CLEAR INSTALLED RETROPLATE AUTHORIZED B - L®`4-r WARRANTY INFO TO BE PRESENTED AT WALK THROUGH INSTALLERS ONLY SEE VENDOR LIST �I FOR MORE INFORMATION P-2 DALTILE-MODEL: OT03 SS B-1 WF-1 B-1 ' WF-0 B-0 WF-3- -SIZE:6x6 ---_-- WF-0 P-4 ---_-- -----�---- "-------s WF-0 Pd ------J 6-1 F-2 TILE -COLOR: ASHEN GRAY INSTALL AT B.O.H.&INSIDE GROUT:CUSTOM BUILDING PRODUCTS-CEG-IG 1007 WALK-IN COOLER C5 SOLIDS INDUSTRIAL GRADE EPDXY GROUT-CHARCOAL#60 111 � DALTILE-MODEL: P543 0 -SIZE: 1 MOD 4 - F-3 TILE -COLOR: VERANDA-ROCK INSTALL AT RESTROOMS -GROUT:CUSTOM BUILDING PRODUCTS-CEG-IG 100% SOLIDS INDUSTRIAL GRADE EPDXY GROUT-CHARCOAL#60 O MISCELLANEOUS < - _❑. M-1 LATICRETE 9235 AND WATERPROOFING/ANTI-FRACTURE FABRIC INSTALL AT ALL WET WALLS& DEMISING WALL(S)-SEE Al/A600 SS. STAINLESS STEEL LIGHT GAUGE METAL INSTALL AROUND HOOD F N a6-e _ s -❑ _ _ _ _ DINING _ _ INSTALL ON STOREFRONT WINDOW _ Uo AREA C5 " WG-1 WINDOW GEL SOLAR GRAPHICS-COLOR: AMBER (APPROVED BY/LL/CORP/CLIENT) 101 A111 v G.C.SUPPLIED AND INSTALLED C 4 a A111 m ca`.-a �� a a �. a .. INSTALL ON STOREFRONT WINDOW --- `.�" (APPROVED BY/LL/CORP/CLIENT)WG-2 WINDOW GEL SOLAR GRAPHICS-COLOR: FLAME � o D2 G.C.SUPPLIED AND INSTALLED a �� INSTALL ON STOREFRONT WINDOW w �� - �/ -C O O - -OJ ,� �l - /J -✓� - - WG-3 WINDOW GEL SOLAR GRAPHICS-COLOR: BRIGHT BLUE (APPROVED BY/LL/CORP/CLIENT) a a a a G.C.SUPPLIED AND INSTALLED INSTALL ON STOREFRONT WINDOW PROJECT NUMBER: 17-420 WG-4 WINDOW GEL SOLAR GRAPHICS-COLOR: CHARCOAL (APPROVED BY/LL/CORCLIENT) DRANK BY: RP G.C.SUPPLIED AND INSTATALLED CHECKED BY: MP ROLL-A-SHADE-SHEERWEAVE STYLE 2000 INSTALL AT FENESTRATION WHEN m WS-1 WINDOW SHADE -COLOR: CHARCOAL CHESTNUT NEEDED,TO SHADE FOR DIRECT SHEET TITLE A ^7 _ _ _ _ _ _ -5%OPENNESS LIGHT(WEST&SOUTH FACADES) A 3 cs1 F- -, IF FINISH ( P PLAN C1E GUARD- 1 - - 111 . - - EDGE h sq JOHNSONITE MODEL LE P-6 WF3 B-1 - P-6 WF-3 &1 EMA G XX W COLOR TO TC T H CONCREE ;Kill, c CONCRETE SHEET NUMBER� FINISH PLAN A5 TYP.TILE TRANSITION DETAIL Al 20 SCALE:-=1'-0" GENERAL NOTES: LIGHT FIXTURE SCHEDULE m LAY IN CEILING A. VERIFY ALL PLACEMENTS of LIGHTS NTH SYMBOL MANUFACTURER & MODEL #: DESCRIPTION 'a o a m 9? /12-GAUG \ T / \ __ OWNER PRIOR TO INSTALLATION /HANGER WIRE \ \.i/ / / \ - SUSPENDED PENDANT W/METAL REFLECTOR SHADE-MOUNT®T-0" p z ❑ 0 m. .yam BOTTOM OF CEILING B. SEE ELECTRICAL PLANS FOR ADDITIONAL ®PA1 HI-LITE#H-9216036-BK01-CCB/CGU-RIB/CB14-BK01/GU24 A.F.F.,U.N.O.-14'FLEX CORD a'0 >w m m w \ LIGHTING INFORMATION _ E w o N B L__ STRUCTURE ABOVE I SEE PLAN C. ALL CEILING MATERIAL SHALL NOT EXCEED P�� BARTCO#IEL8R-25W-PM18-BL SUSPENDED PENDANT W/TB GEL SLEEVE-ROSCOLENE ORANGE-CENTER m d 3°o m'^i _ FLAME CLASS II-FLAME SPREAD INDEX 25-75 OVER POS o z m 0 m J \ / <TEE CEILING CLIP D. GENERAL CONTRACTOR SHALL BE RESPONSIBLE SUSPENDED PENDANT W BLACK LAMP GUARD&AMBER GLASS-MOUNT �'wVERPCAL TILE /FOR COORDINATING THE WORK OF ALL RADES ®PA3 HI-LITE#H-FGU-BK0I-AM/CBB-BK01/GU24 J m m r; o fA 8'-0"A.F.F.,U.N.O-8'BLACK CORD z m z CL 312GAUGE / INVOLVED IN THE CEILING WORK TO ENSURE w aHANGER VWRE / WALL MOUNTED W/FLUSH DRYWALL FEED BOX/MOUNTING PLATE-NON TOP OF COOLER THAT PROPER CLEARANCES FOR DUCTS,LIGHTS, BARTCO BZG-28W-0-U-PRS-SIN-CF-BL-OR ppq # DIMMING-MOUNT IN HALLWAY CORNER®10'-0"A.F.F.-BLACK FINISH, EL.+9'-0"A.F.F. PIPING,ETC.ARE MET AND THAT THE CEILING ORANGE GEL HEIGHTS NOTED ON THE DRAWING ARE INDEPENDENT CADDY CR MAINTAINED °LT-0 SUSPEND W/JUNO T90 PENDANT STEMS(48"MAX)-MOUNT®T-O"TO SUPPORT CLIP®EACH MAIN RUNNER JUNO TRAC-CITES SINGLE CIRCUIT RACK R4BL&R8BL LIGHT FIXTURE CONNECTION E. GENERAL CONTRACTOR TO VERIFY LT-e 12'-C"A.F.F.,U.N.O.-SEE SHEET A300 NOTE: WALK-IN COOLER REQUIREMENTS AND QUANTITIES OF FIRE ALL WIRE TIES ARE TO BE THREE TIGHT TURNS AROUND ITSELF VMTHIN THREE PROTECTION DEVICES INCLUDING SMOKE �TL1 JUNO TRAC-CITES R600L/27K/F/BL RACK MOUNTED WITH 10W INTEGRAL LED LIGHT D P. INCHES.TWELVE GAGE HANGER WIRE SPACED 4 FOOT ON CENTER DETECTORS,DUCT SMOKE DETECTORS,FIRE <TL2 JUNO TRAC-CITES R71BL LED MR16 MENU BOARD TRACK LIGHTING TY SUSPENDED CEILING LAYIN CEILING TURNDOWN AT COOLER ALARMS,RELATED SPEAKERS,STROBES,ETC. DTL D1 D3 LIFE SAFETY INSTALLATIONS TO MEET �TM1S JUNO TRAC-UTES R60OL/27K/F/BL/T40N-BL MONOPOINT LED LAMP-MOUNT®9'-0"TO 10'-0'A.F.F.,U.N.O. Scale:N.T.S. Style:114'=1'-0" REQUIREMENTS OF ALL APPLICABLE CODES AND ORDINANCES Q HOUSING: ELITE LED#L -14W-DIMR-120 Rf MODULE: ELITE LED#RL607607-14W-DMITR-120-30K-MB-BK 6"RECESSED DOWNLIGHT W/BLACK RING. EM FIXTURES SHALL HAVE A E. (6)WEEK LEAD TIME ON ACOUSTICAL CEILING 0R1-EM ISOLITE INVERTER:#IMI-12-V1 OR MMI-25-V1 90 MIN.BATTERY BACKUP-CENTER IN 2x4 CEILING TILE TILES AND CEILING GRID. HOUSING: LITON LH71CA-GU24-LBL1326 EQ EQ EQ EQ 4'-0" G. ELECTRICAL CONTRACTOR SHALL SUPPLY 10% Q R2 MODULE: LITON#LH7A-LBL15/LRS40B-B CENTERED ABOV 6"RECESSED E FIOOD RAYSIGHT,BLACK RING FINISH-INSTALL ADDITIONAL SPARE,OF ALL LAMP TYPE.TO BE LEFT AT JOB SITE AT END OF JOB.TILE COOPER/METALUX#2GR8-332A-UNV-EB81-U 2'x4'RECESSED FLUORESCENT TROFFER W/0.125"THICK PATTERNED H. G.C.TO SUPPLY( UNOPENED CASE OF EACH FR6 ACRYLIC SHIELD. FIXTURES DESIGNATED FOR EMERGENCY LIGHTING SHALL TYPE OF CEILING TILE USED. COOPER/METALUX#2GR8-332A-UNV-EL-EB81-U HAVE 90 MIN.BATTERY BACKUP L E1- ALL LIGHTING SHALL BE 20 PC AT 30"A.F.F., CO-) _ \ z CEILING HT. ACC RECESSED FLUORESCENT TROFFER W 0.125"THICK PATTERNED 8 D3 \ +/-12'-6"A.F.F. LIGHTING ABOVE FOOD OR UTENSILS SHALL BE / o � �!} � o _ ` SHATTERPROOF. COOPER/METALUX#2GR8-2U6T8A-UNV-EB81-U ACRYLIC SHIELD. FIXTURES DESIGNATED FOR EMERGENCY LIGHTING SHALL R1 o "'R1 _ D130 L / d CAULK JOINTS BETWEEN CEILING GRID AND HAVE 90 MIN.BATTERY BACKUP WOMEN S N MENS V ADJACENT SURFACES. SURFACE MOUNT BLACK TEXTURE VAPOR JAR W/LAMP GUARDS-WET RESTROOM RESTROOM, WALK-IN K. EXISTING CONDITIONS CEILING CONDITIONS WHICH ®SA1 HI-LITE#H-FGU-FB-BK0I-RIB/GU24 LISTED FOR OUTDOOR USE 11 - 110 I 'I J L- =J i COOLER CAUSE ATYPICAL CHANGES MUST BE VERIFIED WALL MOUNT SCONCE BLACK TEXTURE W/LAMP GUARDS- MOUNT o L_ Ci \ 1W WITH CLENT,CORPORATION,AND LIGHTING QSC1 HI-LITE#H-FGU-HB-BKOI-RIB/GU24/10/LBL -�� '�" -� 1 �` L- - 44 / VENDORI 7'-0 A.F.F.,U.N.O \ EXTERIOR WALL MOUNT BLACK TEXTURE SCONCE W/LAMP GUARDS- OR1 �SC2 HI-LITE#H-FGU-IB-BK0I-AM/GU24/10/LBL MOUNT®T-0"A.F.F.,U.N.O CEILING H7. FR6 Z ,I== � °•^� INTERIOR WALL MOUNT ORANGE FINISH SCONCE W/25D LAMP- MOUNT �3 HI-LITE#H-922046/24-1-141 A.F.F. R 6'-3"A.F.F.,U.N.O C3 w C3 HI-LITE#9216036-BKOI-CCB/CGU-RIB//B-1-BK01GU24/10/LBL EXTERIOR WALL MOUNT SCONCE W/METAL REFLECTOR SHADE-MOUNT Y STORAGE �SC4 7-0 A.F.F.,LINO ®ALL DRAWINGS AND MHIIIEN MAIEINAL �Rt EM Ri E SCi 105 �� HI-LITE H-922048/36-1-141 INTERIOR WALL MOUNT ORANGE FINISH SCONCE W/25D LAMP- MOUNT CONTAINED HEREIN ARE THE PROPERTY OF _ SCS R 6'-3°A.F.F.,U.N.O THE UNCLE DMGN GROUP,INC.THEY MAY ° 2 0" 2 0" BULK HEAD HT. NOT BE REVISED,COPIED,REUSED,OR HI-LITE H-922046 SP-B-16-141 2-LITE INTERIOR WALL MOUNT ORANGE FINISH SCONCE W/25D LAMPS- MOUNT MSCLOGm IN ANY MANNER WT DUT RIM / / AUTH(XNZARON FROM 7HE ARCHITECT. BULKHEAD HT. SC6 ®6'-3°A.F.F., +/-8'-0"A.F.F. 1'-10 EQ. 4 0 EQ. EMi Y EXITRONIX#VEX-U-BP-WB-WH-EL90 EXIT/UNIT COMBO EMERGENCY LIGHT WITH 90 MIN.BATTERY BACKUP C AUG17 C S 3 1S EM3-� / OFFICE Di CLEANING EM3 EXITRONIX#LL50H EMERGENCY LIGHT W/90 MIN.BATTERY BACKUP,SUSPEND HORIZONTALLY \YYIIMUIIII/try/// - C3 106LERE Ci A130 AREA ON CEILING-BLACK FINISH TO BE USED IF INSTALLED AT GRAPHIC WALL Oxx�p ARCy��' lik CEILING HT. 'HALLWAY ip6 Q{ PROVIDED AND INSTALLED BY DMX PROVIDED AND INSTALLED BY DMX 2?:' •.F� +/-9'-0"A.F.F. B30 109 P 1 FRfi FRfi Z Z CEILING HT. BARTCO CB5-54-U-PRS-CM96-SIN-BL-BLACK EXTERIOR ACCENT LIGHTING-LENGTH,ORIENTATION,&GEL COLOR VARIES- gip;+•CART-L •t0 +/-9'-0"A.F.F. LFi FINISH COORDINATE WITH BLAZE CORPORATE AMERICAN LIGHTING COMMERCIAL GRADE LIGHT STRING: E)Cr+- LS-MS-24-48-BK,24"BULB SPA CING,SUSPEND ED MEDIUM EXTERIOR COMMERCIAL GRADE LED LIGHT STRING,EDISON DROP - •t0 poi - - �� BULK HEAD HT. BASE,LAMP*S14-LED-WW-PREM •,t.. r-- n, T F =� ��„tlY6 8 8'-0"A.F.F. U.N.O.ALL FIXTURES ARE CONTRACTOR FURNISHED,CONTRACTOR INSTALLED /7/lllllll I1U s 3 CEILING_ - EDUCE _ _ NG FINISH SCHEDULE A— - \ _—- ---L L_ DESCRIPTION: LOCATION(S): NOTES: COOKING I o MFG: ARMSTRONG-672 G.C.TO SUPPLY AND T $ A � �_.--0 0 0 () Ri Ri Ri RI-EM R1 Ri R1 MATERIAL 24"x48"VINYL FACED INSTALL GRID 103REA � ; FOOD PREP- �E 3 _ CEILING HT. SERVICE Ci COLOR WHITE B.O.H 0 0 gq 5 D1 AREA y/ - +/-10'-0"A.F.F. FINISH. VINYL FACED,SMOOTH ■ Q Ri{M Ri 102 C3 EQ.I EQ GRID: FACTORY FINISHED BLACK ■ S 3 AS CEILING HT. CEILING: EXPOSED TO STRUCTURE ~ 0 TMiS 00 TL2 Ri Ri L2 L2 ` TL2 ` 'TL2 HVAC DUCTWORK TO BE ■ 1 _ PAINTED P-2;SOUND - N r� ATTENUATION FOR 60% B 0 0 34' 10y \ A13 +/-9'-0"A.F.F. C2 FINISH: PAINT P4 DINING ROOM o LLJ L LTB _ PREP I EXISTING STRUCTURE OF DECK ANISH f C3 AREA �` CEILING: INSTALL 5/8"GYP.BD.CEILING iDd `L SOFFIT T. SEE PLAN O 0 Q Q 0 Q 0 Q `n 0 Q _ `YL. +/-6'-6"A.F.F. FINISH: PAINT P4 U.N.O. t R2 R2 yyPA2 R2 R2 R2 R2 R2 R2 R2 CONT 20 GA TRACK IL J o MECHANICALLY \ 0 MFG: CERTAINTEED ECOPHON-3542 7308 G.C. LL SUPPLY AND o J MATERIAL 24"x48"FIBERGLASS INSTALL GRID n n n L- - 1 FASTENED TO EXISTING COLOR: WHITE FOOD PREP- Q 5'-1" STRUCTURE \\ ® R � Li I 3 0 2 2 2 8 -I \�\ FINISH: HYGIENE PERFORMANCE A-VOC COMPLIANT SERVICE AREA O S 3 - - - - - 35-11Y4"-- T_m S TMiS TMiS 3%a"20 GA.METAL \ \ GRID: FACTORY FINISHED BLACK Q z TMiS TMis. TMiS TMiS 0_ MFG: ACOUSTICAL SOLUTIONS OPTIONAL: TO COVER 60%OF 6'-0"TYP. 6'-8 4" ANGLE BRACE AS ` N REQUIRED COLOR: WHITE DINING ROOM CEILING B Li Li 5 _0„ 5,_9y., 11 5'-0" 6,_9" 4 „ 2,-7„ — 101 _ CODED NOTES B o -0 EE PLAN - - PAINT ALL EXPOSED ROOF STRUCTURE P4(CRISP MUSLIN)-INSTALL SCRIM SHEETING AT INSULATION- _ _ FOR HGT. 1 PA O DO NOT APPLY PAINT DIRECTLY TO INSULATION.ALL HVAC DUCTING&DISTRIBUTION PAINT P2(MINK). Li 5/8"GYPSUM°I %� 11 tPA PA1 A PA1 PA3 PA3 fol 2 ALL WALL MOUNTED GRILLES IN PUBLIC AREAS SHALL BE PAINTED TO MATCH WALL SURFACE-ALL TMiS iA 3%"20 GA.METAL O GRILLES IN NON-PUBLIC AREAS SHALL BE WHITE. ® / TL1 STUDS 016" SEE PLAN O SEE MECHANICAL PLANS FOR ALL HOOD AND HVAC INFORMATION 4 LF1 "TL1 5/8"GYPSUM FOR HGT. Oq NO CEILING ABOVE WALK-IN OR OVEN. El LT-0 CEILIN HT. DINING SEE FINISH PLAN FOR O NON-ILLUMINATED MENU BOARD.ADJUSTABLE TRACK HEAD LIGHTS TO SHINE ON MENU BOARD-HUNG "A.F.F. AREA 1 FINISH SCHEDULE 5 WITH BLACK CHAIN TLi F1 C2 C5 2 PL ❑ - - © "ONLINE ORDERING"NON-ILLUMINATED GRAPHIC TL1 O LIGHT FEATURE-3 LF1 FIXTURES-COORDINATE PLACEMENT,LENGTH,&GEL COLOR VMTH BLAZE PA1 BULKHEAD DETAIL CORPORATE `\ o o B4 OB CEILING GRID ORIGIN POINT TLi -V11 - PA1PAiAl PA1 LF16,_0EM1 12' 8" 7,_2" 7,_2„ O 9'_0y" Li EXISTING STRUCTURE M - Li `\Q\ EXISTING STRUCTURE CIS \\ CONT.20 GA.TRACK \ \ gili, � ABOVEPAi - :� jl�� MECHANICALLY \ o CONT.20 GA.RACK vR N FASTENED TO EXISTING 1 -MECHANICALLY STRUCTURE \ 4 \ \ FASTENED-SEE PROJECT NUMBER: 17-420 PA3 PA3 BY: RP - - PA3 - - ®A3 - - - P - - - P - - - P 3%"20 GA.METAL \\ 0i `° r' \ 0" DETAIL A5/A111 CHEDRACKED BY: MP ANGLE BRACE AS \ lot E 1 EM REQUIRED SEE PLAN FOR HGT. \ \ 35/e"20 GA.METAL STUDS \ @16"O.GTYP. SHEET TITLE: r----I 101 101 `Q 1 o a mF,SEE PLAN \ \ 1 a/e"PLYWOOD SUBSTRATE LJ� LA FDR HOT. _ r 01 REFLECTED 0 �\ TRIM METAL PANEL& CEILING 4'-6y" 6'-0"TYP. 6'-7" 6'-7" 4 33f,"20 GA.METAL \\ RIM-SEE DETAIL 6' 11}" STUDS 016" SEE PLAN SEE PLAN 336"20 GA.METAL ANGLE PLAN 5, GYPSUM FOR HGT. B.O.CEILING _ BRACE AS REQUIRED FINISH NISH PLAN SCHEDULE FOR o o B.OB PLV SEE PLAN SHEET NUMBER: 5/8"GYPSUM-SEE REFLECTED CEILING PLAN A4 BULKHEAD DETAIL A5 SCHEDULE SOFFIT DETAIL FINISH PLAN FOR FINISH Al 30 a SCALE:114'=1'-0' Scale:314"=1'-0" Scale:314"=1'-0" WINDOW GEL SCHEDULE CODED NOTES w MARK MANUFACTURER&SPEC REMARKS Oj REUSED&NEW GLASS STOREFRONT W/NEW WINDOW GEL rc m o ¢DO m z z z❑ omm O INSTALL ON STOREFRONT WINDOW(APPROVED u E w d EXISTING TRELLIS AND AWNING TO BE PAINTED P-2 - _ WG-1 SOLAR GRAPHICS-COLOR: AMBER BY/LL/CORP/CLIENT) m m o _ G.C.SUPPLIED AND INSTALLED O NEW BLAZE PIZZA SIGNAGE(UNDER SEPARATE PERMIT)-ACCESS PANEL TO BACK OF SIGNAGE 3 w ❑w m 1A j TO BE INSTALLED BY G.C.-COORDINATE NTH SIGNAGE VENDOR INSTALL ON STOREFRONT WINDOW(APPROVED z DO J m z o 3 WG-2 SOLAR GRAPHICS-COLOR:FLAME BY/LL/CORP/CLIENT) O4 LEASE LINE 7 - w a G.C.SUPPLIED AND INSTALLED OS REPLACE EXISTING STOREFRONT GLASS'NTH NEW SPANDREL GLASS(SHADED) INSTALL ON STOREFRONT WINDOW(APPROVED WG-3 SOLAR GRAPHICS-COLOR:BRIGHT BLUE BY/LL/CORP/CLIENT) ©G.C.SUPPLIED AND INSTALLED EXISTING WALL LIGHTING TO REMAIN D D INSTALL ON STOREFRONT WINDOW(APPROVED WG-4 SOLAR GRAPHICS-COLOR:CHARCOAL BY/LL/CORP/CLIENT) G.C.SUPPLIED AND INSTALLED Signage by separate permitting process I� ®ALL DRAWINGS AND MHITIEN MATEM& CONTAINED HEREIN ARE THE PROPERTY OF THE UNDISM GROUP.INC.TH NOT BE RREEAM,COPIED.REUIED,OR NAY I I US OSED IN ANY MANNER WT T NROIEN AUTHORI IION FROM THE ARCHITECT. C G I I AU 17 ola,nADnfnori AHcy'o' L---- --------J �\`2•CARL •TFc - V G _ 2 WG4 WG-1 WG-1 l �prrrrTE10 I``Y""� TG-1Pil ❑ WG-3 Tom'�, WG2 2 WGA WG-1 WG-2 Z v , I 6 6 O / WG-3 WG2 7WG4 / \ \ 7WG-3 O U) `� o W C)o \ -Mr-7 / f a r E:l-11 CFG Qw I Flo Signage by separate G� o permitting process G _� z B1 NORTH ELEVATION SOUTH ELEVATION 6wle:,l4"=,.0° B3 Sale:1T4'=1'-0 a N B3 B A200 3 ®O ------- ------------i s 2__ I I I I L--------- ----------J III���III C Ell 2 is PROJECT NUMBER: 17-420 El El CHECKED BY: RP CHECKED BY: MP \ 8 ❑ ❑ SHEET 11TLE: 6 6 B ❑__❑ ❑ ❑ ❑ A wG-a wGI wc4 0 0 O El OO OOO OOOo EXTERIOR ❑� ❑ ❑__❑ ELEVATIONS WG-2 `-LJ-� `-LJ� O fl • �J SHEET B1 DD Al WEST ELEVATION EXTERIOR ELEVATIONS KEY PLAN N.T.S. A 2oo Scale:114"=1'-0' CODED NOTES pSTAINLESS STEEL OVEN SHROUD: 1 ATAS PALLETS-FLUSH WITH TOP&BOTTOM OF SOFFIT METAL PANEL COLOR SCHEDULE ® 11 1 I-I 1 ■___-18� � _Inilll 1�.6■.,n■I-�I nll—!I�� � � � • ® ® ® m ® "vum.— mill 1 i=.., - PENI�I�--_ _____ _____ ______ •• •• _ ., , 1 Ilia iii , - ---- ----- -- - --- ----- ---- --- - ----- --------- - -- I - ' _= Inn■nn 'I"�' _ _ _ _ _ _ III II �� rl-. -_ �__._ --------- i=i u ��� IIIIIIII'=��I •■ i i''-r' 1�1�1■I■I■I_I■11 - ilMENE . ----- -' - - - •- -e101 ■ o I � i i t � d II II II I111=11•p; IIIm mW ■� m ® ¢ • 1 1 a ■ w Q J DO _ ® No ® p ® — ----- --------- ------ ------ --------- ------ _ _ ,• ® -_ ___ ti .�IIIIeI IC��__ all■ � "`� nZ1_�_____ ®____��' IE._____.,;__ ®___, _____--■ ® /oo III OPEN Ell EYOND _______ - __ L--■`� _ •_ If •SIR © _ .•�_ I��v__ I -■I 11■_I■a,�___��i _ -1■�_■ I_- � _■ ��� `+IIIIIII =•m■����■` �__�la�_sa_ �.,l1_e_ __� i>•!ia 1lnu�r!!!I u!_IIIIllllua■!nlIII!_li�ii �._:,■r�■!I ® il.•.I ENRON ■■ �� �� 1 i ® ■ ■ ■ ■ ■ !0 SHEETTITLE _ 1 ---- ®1 - ................. ■iFIE- _ .�. .�. .�. INTERIOR BEYOND ELEVATIONS .• ■■1__- --111111_,-' _���•4.�• - .• - iii-illl.� ■!! ■�■�ll�!!!!!... ..III! ��■!•■!!!! SHEET NUMBER� ■I 11 ■■III I I _� 'i_ 1 NOTES •••M FIXTURE SCHEDULE A SEE SHEET A110 FOR ADDITIONAL �® USE MOISTURE RESISTANT GYPSUM BOAR,AT DESCRIPTION MODEL ' PROVIDE:ATT , WALLS, BEHIND PLUMBING, , , D. ALL ACCESSORIES SHALL BE INSTALLED AT 40"MAXIMUM TO THE CENTERLINE OF THE OPERATING PART FROM FINISHED FLOOR SURFACE. ;,.. EXPOSED MOUNTING SERIES B-6106 U-SHAPE OR LOOP IMMEDIATELY BELOW THE LATCH ON THE INSIDE AND OUTSIDE OF THE PARITION DOOR.(IF APPLICABLE) FINISH TAG SEE FINISH SCHEDULE ON SHEET A120 NESSEEMIN A.F.F.TO CENTER OF SUPPORT GRAB BAR. PRO'ADE 2X6 BLOCKING AS NEEDED (HANDICAPPED STALL flSSUE DISPENSER) ®® F. FIXTURES ARE DIMENSIONED FROM CENTER OF FIXTURE TO FACE OF TILE. DOOR TAG SEE DOOR SCHEDULE ON SHEET A110 EXPOSED MOUNTING SERIES B-6106 (1)2X6'S 4 0�LONG CENTER MOUNTED 0 33- WATER CLOSETS MEME� HIGHLINE MODEL K3999 16.5"WHITE VITREOUS CHINA FLOOR MOUNTED 0 0 © TO WALL , �... . F.F.To CENTER OF SUPPORT(LAVATORIES) o o ... O CENTER OF SUPPORT(PAPER TOWEL DISP.) HAND DRYER-OPTIONN; ' o DMOUNTED , • . . . .. . ' . . . .ROAR • . � .. BY DISTRIBUTOR KOALA KARE#KB208,WHITE GRANITE HORIZONTAL UNIT 0 „ mill ON INSTALL MAX.40" .CLARIFICATION , RESTROOM STALL LAMINATE COLOR 1-11-11-211-01 BLOCKING NOTE: PARTITIONS AT PARTITION WALL ANCHORS �• i' m1.ALL FIXTURES&ACCESSORIES MUST MEET ALL NATIONAL AND LOCAL CODES AND ADA REQUIREMENTS. PROVIDE SOLID FIRE TREATED BLOCKING AT ALL WALL MOUNTED FIXTURES FOR SECURE ANCHORING, LOCATION ,NS. CLEAR SILICONE CAULK ALL FIXTURES TO PARTITION. , .',• •, , 2.WATER CLOSET AND URINAL FLUSH VALVE CONTROLS,AND FAUCET AND OPERATING MECHANISM CONTROLS,SHALL BE OPERABLE WITH ONE HAND,SHALL NOT REQUIRE flGHT GRASPING, INSTALL FLUSH HANDLES Q • ® 1�1 OPEN SIDEOF • MIMI I a • '- �m ========ME 11�mmmmmmmmm mm������ iImm �mmmmmm�====I �mmmmm�mmmmmmm■Immm mmmmm■ O O O 111-IN mmmm q ol �m lMMll MM■ a�=======ME I��■_n��■1����==�i1 11-i���====M.■� I ������ ����I■��MON ==1 sommuNNINwrab.M�����1 \..������rO�rO �0�---��v���ICI �■I===��I�1 mmmmm��ME I .�mmmm�L�������I■��--------���1 �mmmm���■I��������I'�I =a ymmmmm�■ 1�1■gym �j�iJ■ �I��mmmm Mimi ��������f��mmmm■I======= m mmmm ■�������� 1 � l, =AN ==m=mMmE ICI �■I�mmm�I .��1 1 MMMM�� ■� .mmmmmmm ======I ===I O 0■e.■■NONE PROJECT NUMBER: 17-42 mmmmmm.1mmm1�' =======I ��l 1��OMEN mmmm■ I Irl■====�����rnn --]NMI�■i���������1, ommmmmma��■ I�mmmmm■ ���, =ME I��� ������I I ■■Immmmm�����lil f �`�=-�J���m■ ■mmmmmmmmf. t�������w■ �I������■ ���•---------•a��I����L—!•�������1 I ■■1��������■�_,— �■I�I■�����I�O>,��I■��Ir��_--^J. I� O� i ENLARGED ��■—I—I—■in��mmmmmm■ ommmmmmmmmo I===== ========I I ■ I=====�����0`•I•YII■ �---i�����■ 1�1 ■��m�■ ��ILJI mi 1m m��======1 ������������������������■ I ■���������■ r• ■ ■�����ICI �[ I�����1 ■I� I��������■ �����������I����r7��������1 I ■■I����������r I I�r�������� ill■�����► ��1 ■■�I■■■■■■■�■■■■■■■■■� ■■■■■■■■■■■■■� ■■■■■■■■ �� I■I■■■■■■■■■■■ ■■ ■■■■■■■■I on SHEET NUMBER� NOTE: VERTICAL STEEL 8„ PANELS FOR TRAY > m STAINLESS STEEL OVEN SHROUD TO BE PROVIDED TROUGH n v a DID °`v STAINLESS STEEL WALL CAP WITH AND INSTALLED BY GC.ENSURE IT IS FIXED IN PLACE rc m❑ m 2"DOWNTURN BOTH SIDES IT IS RECOMMENDED TO STUD WELD AND BOLT TO 28 14y" 1Nx"SQUARE STEEL - PROVIDE 2X CONTINUOUS BLOCKING AS NEEDED i z m Emi m m o OVEN TOP. TUBE FRAME- E w o m w 2X8 BLOCKING AT TOP OF 20 GA.METAL TRACK POWDER COAT BLACK m a 3 00 m 3-5/8"20GA.TRACK VERTICAL STEEL 3/4"PLYWOOD SHELVES W/MELAMINE ON EXPOSED 3 w ❑ 16 GA.STAINLESS STEEL 24" 3" RECYCLING FOR `i FACES,TYP. J m m w a 3 PONY WALL CAP SERVICE AREA DETAIL 25" 2s" z m SHROUD 8" STEEL PLATE STAINLESS STEEL WALL CAP WITH AROUND OPENING TRASH 777—ADJUSTABLE SHELVES&STANDARDS,TYP. CHUTE 2"DOWNTURN BOTH SIDES CUTOUT FOR OVEN HOOD DRUM 2x BLOCKING AS REQUIRED,TYP. 2X8 BLOCKING AT TOP OF 20 GA.METAL TRACK M 50 GALLON STEEL 2-6 &DOLLY 2'-4" D 3-5/8"20GA.TRACK DESK TOP W/4"BACKSPLASH,PLASTIC LAMINATE D PIANO HINGE B PONY WALL CAP GRAB&GO DETAIL DOUGLAS FIR 24"x24"AccEss PANEL fiff > (LOCATION ON SHROUD - STAINLESS STEEL WALL CAP WITH i NOTE: VERIFY SHOWN®SHEET A110) 3/4"PLYWOOD SUPPORT PANEL,BOTH ENDS 2"DOWNTURN BOTH SIDES 9 i� DIMENSIONS&FINISH 2X6 BLOCKING AT TOP OF 20 GA.METAL TRACK /Yp < � WITH SHOP DRAWINGS 3-5/8"20GA.TRACK i�g9''I" CLOSURE WITH %-16XJ"THREADED STUD& A PONY WALL CAP DETAIL WING BOLT — BASE 1Y"MOUNTING FLANGE D2 TYPICAL PONY WALL CAP DETAILS D3 STAINLESS STEEL OVEN SHROUD DETAIL D4 TRASH RECEPTACLE D5 OFFICE DESK AND SHELVING Scale:1"=1'0' Scale:N.T.S. Stale:N.T.S. Scale:1 1YY'=1'-0" NOTE: 3/4"PLYWOOD SHELVES W/MELAMI G.C.TO COORDINATE INSTALLATION REQUIREMENTS WITH VENDOR, ON EXPOSED FACES,TYP. REGULATOR AND FOAM ON BEER DETECTORS TO BE MOUNTED IN 90 DEGREE ORIENTATION IN THE WALK—IN TO SAVE WALL SPACE. ATTACH ANGLE W/(2)#14X 1 HEX HEAD TEK ADJUSTABLE SHELVES& GLYCOL CHILLER—HOOKUP SCREWS(TYP.EACH END) BY VENDOR—HARDWIRED STANDARDS,TYP. ELECTRICAL BY G.C.—SEE PATCH PANEL MEP PLANS L 4X4XJX48 PREFAB W/BRC PLATE AND P[��FIRDWALL STUDS MOEM NOTE: NOTE: SLEEVE FILLED SOLID WITH ROUTER COORDINATE CLEARANCES WITH PLUMBING CONTRACTOR SHALL LOCATE&CONCEAL EXPANSIVE FOAM AFTER BATTERY BACKUP ALL DRAWINGS AND WRITTEN MATEM& PLUMBING ROUGH—INS FOR WATER ALL PIPING WITHIN BUILDING WALLS TO THE TUBING INSTALLATION—BY CONTAINED HEREIN ARE THE PROPERTY OF HEATER INSTALLATION. GREATEST EXTENT POSSIBLE. VENDOR FILE SERVER THE ANGLE DESICR fRWP,INC.THEY MAY NOT BE REAM,COPIED,REUSED,OR WALK—IN COOLER WALL SWITCH DEEP SHELVES DISCLOSED IN ANY MANNER'MTHWT RIM SWITCH AUTHORIZARON FROM THE ARCHITECT. GLYCOL LINES C MONITOR ekoo ICI GAS MIXER-BY VENDOR 11 SEES TERMINAL BACKBOARD-BY _ ❑D KEY MICKEY BOARD O�xxxQp'ARCly7J' VENDOR EQUIP. SUPPORT BEAMS SEE PLUMBING DRAWINGS FOR ALL DESK TOP `�2'•CART-1- "'�nas UTILITIES CONNECTION ------- SEE PLUMBING DRAWINGS FOR VERIFY MIN.(2)#10 WOOD SCREWS INTO WALK-IN INSULATED TOP BOTH SUPPORT PANEL, _ ALL UTILITIES CONNECTION IoI PLYWOOD BLOCKING TOP&BOTTOM TYP. PANELS - BOTH ENDS FOAM ON BEER DETECTOR- SAFE BY VENDOR = OO o �pAY77�El0 1``Yxxp� 4"CONCRETE SLAB WITH TILE WATER HEATER-SEE WATER HEATER-SEE PLUMBING 111 PLUMBING DRAWINGS O DRAWINGS REGULATOR-BY VENDOR �� COMPRESSOR MOUNTING DETAIL - VERIFY MIN.(2)#10 WOOD SCREWS INTO Scale:N.T.S. CC MANAGER'S DESK PLYWOOD BLOCKING TOP&BOTTOM TYP. KEG COUPLERS-BY VENDOR NI111 _ COMPRESSORS TO BE SUPPLIED WITH 4-WAY VALVE, T DRAIN CONNECTION,AND REGULATORS.INSTALL COMPRESSOR DRYER ADJACENT AS NECESSARY. 1/4" DIAMETER THRU BOLT SLEEVE FILLED SOLID WITH WITH TOGGLE TYP OF 2 Q O UTILITY SHELF- EXPANSIVE FOAM AFTER 6" COORDINATE w/BLAZE CM S.S.WALL CAP TUBING INSTALLATION-BY LEA 2 GYP BE. o Do MOP RACK BY G.C. '-0" VENDOR CLEAR PAN HEAD SCREWS f W a � 0 METAL STRAP (TYP. OF 2) � O ICI THE PROJECT, GENERAL a O J 1/2" CIA. HOLE IN BOTTOM CAP NOTE: UPON COMPLETION OF t Cn ,¢ 4-6" DIAMETER PVC TUBE PLAN CONTRACTOR MUST RUN A NE SEE PLAN MOP RACK BY G.C. SEE PLAN n n n BLUEPRINT SET FOR THE Q I I COMPLETED STORE DRAWINGS � � Li SERVICE FAUCET L - — — J - z o (ARCHITECTURAL, MECHANICAL G _0 AND ELECTRICAL) AND PLACE N 3-5/8"20GA.®16"O.C. BLUEPRINTS INTO THE PLAN oI oI = PROVIDE HANDLE ON THE TOP TUBE HOLDER, LABEL (WITH B CAP TO EASE THE REMOVING CLEAR TAPE) STATING THIS = OF THE CAP TUBE CONTAINS STORE m m m m DRAWINGS AND IS NOT TO BE SERVICE FAUCET 3/4" X 2" POPLAR TRIM PAINT REMOVED WITHOUT THE LABEL CONSENT OF THE STORE W.H.T&P DRAIN,SEE PLUMBING DWGS. MANAGER. TENANT G.C. TO IoI IoI STAINLESS STEEL MOP SINK = ®®®® 4"-6" DIAMETER PVC TUBE SUPPLY AND INSTALL DRAWING MOP SINK Ml TUBE ASSEMBLY ABOVE DOOR 6" .� 2L METAL STRAP (TYP. OF 2) OR OTHER APPROVED LOCATION SCHEDULED FLR.&BASE SCHEDULED FLR.&BASE TILE,SEE SHEET TO BE DETERMINED. IoI IoI TILE,SEE SHEET A120. n IN Al 20. 'LEA CLEAR 2'-0" 1'-0" PVC BOTTOM CAP GLUED IN -7 77CO2 AND NITROGEN TANKS CLEAR CLEAR PLACE. G.C. TO RILL 1/2" DIA. opp qqF�F� � BEER LINE CHASE-A4 A6OO S o HOLE IN CENTER OF BOTTOM CAP ELEVATION FIF�PLR: V BEER KEGS BY OWNER / 61 SECTION AT MOP SINK B2 SECTION AT MOP SINK 63 BEER MANIFOLD DIAGRAM 64 AIR COMPRESSOR CLEARANCE C PLANS STORAGE Scale:314"=1'-D" Scale:314'=1'-0' Style:N.T.S. Scale:N.T.S. B5 Scale.N.T.S. CHAIN RESTRAINT F N REQ S: � L 2x2AI3 CA TOP AND BOTTOM PROVIDE MINIMUM DIA.AS DESCRIBED IN ARTICLE _ TYPICAL WALL CONSTRUCTION ADJACENT W 2#10 SCREWS TO BLOCKING 347 OF THE"NATIONAL ELECTRICAL CODE"TO MEET TO COOLER,IF APPLICABLE-SEE A110. AND STUD,TYP. UL STD.651"NEMA"SPEC.TC-2,ROBINTECH PVC E 4x4 BLOCKING eSTRAPS,TYP. DUCT&SWEEP ELBOWS OR EQUAL.DIAMETER TO BE PVC CAP DURING CONSTRUCTIONSEE FINISH SCHEDULE FOR WALL FINISH GALVALUME WALK-IN PANEL- AS INDICATED WITH MIN.RADIUS OF 24".(PLUMBING PROVIDED BY VENDOR,INSTALLED BY GC ����� SME FACTORY ELLS,ARE NOT ACCEPTABLE) FINISH M-1-WATER PROOFING 12"UP WALL (2)1/4bIAM.x STAG SCREW (MIN). EYE BOLT WITH WASHER I 5/g EACH SIDE,TYP. PROJECT NUMBER: 17-420 5/8"DUROCK CEMENT BOARD UP 2'-0"AFF DENSHIELD 4"VINYL FOAM SCREED-PROVIDED 9 FLAVORS DRAWN BY: RP WALL FRAMING-SEE CONSTRUCTION PLAN BY VENDOR,INSTALLED BY GC CHECKED BY: MP CONTINUOUS BEAD-CLEAR SEALANT 6 / CARD PUMP _ QUARRY TILE O / PVC CONDUIT RUN UNDER FLOOR MUST FINISH MATERIAL TO EXTEND 1"MIN.BELOW T.O.BASE COVE BASE / BE CONSTRUCTED WITH TIGHT, DRINKING WATER SHEET PRE: A = WALL SUBSTRATE, / INTERNALLY SMOOTH JOINTS AND MUST Co2 A MOISTURE SEE WALL TYPES BE LEAK TIGHT. PRESSURE TEST TO 6"COVE BASE-SEE FINISH SCHEDULE RESISTANT TEN(10)PSI PRIOR TO BACKFILLING FLOOR FINISH-SEE FINISH SCHEDULE LUMBER SIKAFLEX 11 FC ---- 24"RADIUS MIN. DETAILS FINISH M-1-WATER PROOFING 12"ALONG FLOOR(MIN) SEALANT/ ®TILE LOCATIONS ONLY ADHESIVE FLOOR FINISH-SEE FINISH SCHEDULE O 0 METAL WALL T FRAMING, APPROXINSTALLATION NOTES: CONDUIT 6"DIAM.PVC SEE WALL TYPES CONDUIT TO BE CAPPED AND SEALED AT BOTH ENDS DURING CONSTRUCTION. SODA&BEER LINE CONDUIT INSTALLERS TO TRIM EXPOSED ENDS TO 7"A.F.F.DURING PRODUCT LINE INSTALLATION. AFTER PRODUCT LINES ARE INSTALLED,THE OPEN ENDS ARE TO BE FILLED&SEALED WITH EXPANSIVE SHEET NUMBER: BUM SEALANT-PROVIDED WITH FOAM(WATERTIGHT)APPROX.2"-4"DEEP AT EACH END,ACCORDING TO NSF SPECIFICATIONS. SYRUP,H2O,&Co2 BUNDLE WALK-IN BY VENDOR,INSTALLED BY Al WATERPROOF DETAIL WALL A2 WALK IN BASE DETAIL GC A3 SEISMIC BRACING AT CO2 CANISTER A4 PVC CHASE-UNDERGROUND A5 DRINK MACHINE BUNDLE CONFIGURATION A600 Scale:3"=1'0" Scale:3"=1'-0" Scale:1112"=1'-0" Scale:N.T.S. Scale:N.T.S FURNITURE LISTDO w o d QTY PLAN DESCRIPTION REMARKS m D Al 14 TYPE 1 CHAIR INSTALL ABOOOTMQUETTES& i ¢ > m m°w E J w O N A2 12 Q TYPE 2 CHAIR INSTALL AFREESTANDING 0'" m w g o m Ul L7 3 o w ED? A3 29 TYPE 1 STOOL INSTALL AT HIGH TOP . DO J DO 1 o¢3 TABLES z M' -z s w 3 SEE PLAN FOR LENGTH- w a 3 B1 6 STRAIGHT BANQUETTE BENCH CONSTRUCTION BY MILLWORK SEE PLAN FOR LENGTH- B2 117 CORNER BANQUETTE BENCH CONSTRUCTION BY p MILLWORK D INSTALL AT ENDS OF Cl 4 FIXED LOW 2-TOP TABLE BANQUETTE,BOOTHS,OR FREESTANDING ADA COMPLIANT-INSTALL C2 10 FIXED LOW 4-TOP TABLE AT ENDS OF BANQUETTE, BOOTHS,OR FREESTANDING ADA COMPLIANT-INSTALL C3 0 0 o FIXED LOW 6-TOP TABLE AT ENDS OF BANQUETTE, BOOTHS,OR FREESTANDING ® $ C4 1 FIXED LOW 4-TOP SQUARE TABLE INSTALL AT INTERIOR O I 0 CORNER OF BANQUETTE WOMEN'S 1 MEN'S RESTROOM L -- - .RESTROOM WALK-IN 111 �O G� 110 � - COOLER CS 0 � FIXED 36"DIAMETER LOW TABLE FREESTANDING �C7C7 _ III III INSTALL AT INTERIOR L-nI a o =� _ _ ` C6 0 ., FIXED 42"DIAMETER LOW TABLE CORNER OF BANQUETTE OR ---- / / — T- FREESTANDING I�Irll o o I1_=111�-I11-111-_I / STORAGE D1 0 FIXED HIGH 2-TOP TABLE FREESTANDING TABLES / \ D2 0 FIXED HIGH 4-TOP TABLE FREESTANDING TABLES ®All DRA'MNGS AND MUM MATEM& CONTAINED HEREIN ARE THE PWR FREESTANDING TABLES- TIE UNGE DESION CROUP,INC.R THEEYTY NAYOF NOT BE REVISED,COPIED,REUSED,OR D3 1 ° u HIGH 6-TOP TABLE-SAWHORSE BASE VERIFY BASE TYPE BEFORE CISCLCBED IN ANY MANNER MTHWT RIM ORDER AUTHORIZATION FROM THE ARCHITECT. B1 / FREESTANDING TABLES- C OFFICE D4 1 ii ii HIGH 8-TOP TABLE-SAWHORSE BASE VERIFY BASE TYPE BEFORE C AUG17 CLEANING ORDER T O HALLWAY 108 AREA ef' `2\OTAR DS 0 FIXED 36"DIAMETER HIGH TABLE FREESTANDING TABLES a 0 CART-L V: V G B1 ® ® D6 3 FIXED 42"DIAMETER HIGH TABLE FREESTANDING TABLES 1 /� O �pXYYATElO UDJ�J E1 0 1 r PATIO CHAIR PATIO USE ONLY O CCOOKING �j � ® -0L LLLJJJ 1 AREA DD� SEE PLAN FOR LENGTH- If--1J E2 0 � EXTERIOR BANQUETTE BENCH CONSTRUCTION BY SERVICE ( / MILLWORK e AREA 1- F1 0 MOVEABLE PATIO 2-TOP TABLE PATIO USE ONLY PR P --T AREA Q G� O F2 0L=d MOVEABLE PATIO 4-TOP TABLE ADA COMPLIUSE ONTY PATIO U) r� C2 r, \ q - - Y o LLJ _ __ f a z B1 0 w\ / C�� - 1 11- III F3 0 PATIO 8-TOP TABLE PATIO USE ONLY-VERIFY O O 0 L J _HII�- BASE TYPE BEFORE ORDER t EE 1 -0 I, 6'-0" F4 0 MOVEABLE PATIO 36 DIAMETER ROUND PATIO USE ONLY n n n L` Q ABLE 5'-0" 1'-6" 4'-0" 6'-0" 2'-0" 5'-0" 3'-6" O Li Q- - z 5. 0„ 5._9�„ 5' 0" 6' 9" 4 p 6._7„ MOVEABLE PATIO 42"DIAMETER ROUND N F5 0 ` TABLE PATIO USE ONLY B1 81 B1 B1 82 B B I-__ _�� I'Ita71'I � 7 1„ r a 2 Ci w C1 p F�T E�T C4 ' a ® Al Ai Ai B 't�7'' t o '`C�7'' • 1• _ DINING AREA 101 ® cm4 Y A3 A3 3 0 ` O - I�I -T III //2// G6 \\ \\ 2 C6 7� //�// GS $i u O, O Sd "'��J"' 'tom' �1./ .. \�� _ Sly E z 6 �1 I I n d� O S T J PROJECT NUMBER: 17-420 DRAWN BY: RP L__ CHECKED BY: MP _. FURNITURE NOTES A. ACCESSIBLE WHEELCHAIR SEATING FOR MIN,5%OF TOTAL SEATS. AT LEAST(1)PER FUNCTIONAL AREA OF THE SHEET 11TLE: 0 RESTAURANT. MIN.36 W CLEAR AISLE&SEATS. SHALL PROVIDE A TABLE OR COUNTER HEIGHT OF 28 TO 34" A.F.F.W/27"H x 30"W x 19"D KNEE SPACE BELOW. A ALL INTERIOR AND EXTERIOR TABLES AND CHAIRS TO BE PROVIDED BY FURNITURE VENDOR. ALL BOOTH BENCHES FURNITURE B. AND BANQUETTE BENCH TO BE PROVIDED BY MILLWORK VENDOR. 10'-2y" 6'-3 q" g_,• g_,^ 18'-11y" C. ALL INTERIOR TABLES THAT ARE NOTED TO BE FIXED WILL BE ANCHORED INTO THE FLOOR SLAB BY THE G.C.'NTH PLAN MASONRY BOLTS,U.N.O. D. ALL PATIO TABLES ARE NOT TO BE FIXED CODED NOTES O1 G.C.TO FIX TABLE TO FLOOR. HOLD TABLETOP 1"OFF WALL SHEET NUMBER: O2 TABLE EDGE TO BE FLUSH WITH BENCH EDGE a FURNITURE PLAN O3 FREE STANDING TABLES TO BE MINIMUM 4'-4"FROM SEATING SIDE TABLE EDGE TO TABLE EDGE A6 1 0 ` SCALE:114"=1'-0" O4 PROVIDE MIN.3"GAP BETWEEN TABLETOPS WHEN INSTALLED IN FIXED SEQUENCE NOTE: GENERAL HEALTH DEPARTMENT NOTES EQUIPMENT LIST EQUIPMENT LIST a w mw m 1. FIRE EXTINGUISHERS MUST HAVE A MINIMUM OF"2A10BC" PROVIDED INSTALL PROVIDED INSTALL v a DO 1. THE GENERAL CONTRACTOR SHALL NOTIFY THE FOOD SERVICE EQUIPMENT CONTRACTOR FOR FIELD INSPECTION FIVE(5)DAYS BEFORE THE EQN QTY DESCRIPTION MANUFACTURER MODEL REMARKS EQ# QTY DESCRIPTION MANUFACTURER MODEL REMARKS rc m❑ m RATING AND CLASS K SHALL BE WITHIN A 30'-0"TRAVEL SLAB IS POURED AND AGAIN BEFORE THE WALLS ARE CLOSED. BY BY BY BY z ❑ 0 IT m DISTANCE OF ALL COOKING SURFACES PER NFPA 10,SEC. WIRE SHELVING,6 TIERS-86"MAX z E w o im6 m 5.7 2002 ED. 2. THE G.C.SHALL CLEAN WHERE EQUIPMENT IS TO BE INSTALLED,AT THE START OF INSTALLATION.THE G.C.SHALL BE RESPONSIBLE FOR PROVIDE 6'FLEXIBLE AIR 41.6 1 METRO 24480RK3 KES G.C. 24"X48" m - r; N HEIGHT POSTS-W DUNNAGE RACK m o 2. FINAL LOCATION&QUANTITY OF FIRE EXTINGUISHERS SHALL SECURITY OF EQUIPMENT ON THE JOB SITE.THE G.C.SHALL BE RESPONSIBLE FOR CLEANUP AND DISPOSAL OF DEBRIS AFTER 1 1 PIZZA DOUGH PRESS-PNEUMATIC DOUGHPRO DP2300BZE KES G.C. HOSE W/QUICK Q 3 0 m-i BE AS DIRECTED BY FIRE MARSHAL. INSTALLATION. DISCONNECT WIRE SHELVING,3 TIERS-34 1 2"MAX 3 w DO w m J 41.7 1 / METRO 1824NK3 KES G.C. m x 3. INSTALL NEW TYPE"K"WALL MOUNTED FIRE EXTINGUISHER. 3. ALL NEW,EXISTING,OR REPLACEMENT EQUIPMENT SHALL MEET NSF AND A.G.A.STANDARDS. HEIGHT POSTS z DO m o a 3 PROTRUSION INTO PATH OF CIRCULATION 4'MAX. 1.1 1 PIZZA DOUGH PRESS-MANUAL DOUGHPRO DP1100BZE KES G.C. j iO z a 3 4. ALL PREP SINKS,CONDENSATE FROM ICE BINS,REFRIGERATORS(OR FACTORY MOUNTED EVAPORATOR)AND SIMILAR EQUIPMENT SHALL BE 4. INSTALL NEW WALL MOUNTED FIRE EXTINGUISHER(MIN.- 1.2 2 DOUGH PRESS CART DOUGHPRO UT1330 KES G.C. 41.8 2 SINGLE SHELF SECURITY CAGE EAGLE SECM1860 KES G.C. TYPE 2A 40BC.)PROTRUSION INTO PATH OF CIRCULATION DRAINED TO A FLOOR SINK AT 1/4"PER 12"SLOPE WITH A LEGAL AIR GAP. AMERICAN SMALL 41MAX. 5. MOP SINK SHALL BE PROVIDED'NTH HOT(120 DEGREE MINIMUM)AND COLD WATER THROUGH A MIXING FAUCET WITH AN APPROVED BACK 2 2 PIZZA PAN RACK METALCRAFT 19030 WARES G.C. 41.9 5 SINGLE SHELF SECURITY CAGE EAGLE SECM2436 KES G.C. FLOW PREVENTION DEVICE. 2.1 2 PIZZA PAN RACK PROLUXE PR6 KES G.C. 42 7 WALL SHELVING ADVANCE TABCO WS-12-36 KES G.C. 6. ALL SINKS,LAVATORIES,AND HAND SINKS SHALL HAVE COMBINATION FAUCETS OR PREMIXING FAUCETS WITH HOT(120 DEGREE MINIMUM) HDE-400 42.1 2 WALL SHELVING ADVANCE TABOO WS-12-48 KES G.C. D AND COLD WATER UNDER PRESSURE. 3 3 HALF HEIGHT DOUGH RACK ALEXANDER IND. KES G.C. W/ALUMINUM TOP p 7. ALL CURB MOUNTED EQUIPMENT SHALL BE SEALED TO THE WALL AND CURB IN APPROVED MANNER. MOD-33BLZ 42.2 2 WALL SHELVING ADVANCE TABOO WS-12-60 KES G.C. 4 0 REFRIGERATED SANDWICH UNIT-27" CONTINENTAL SW27-8-FB KES G.C. W/REMOVABLE LID& 42.3 0 WALL SHELVING ADVANCE TABOO WS-12-72 KES G.C. 8. BUILDING SHALL BE FULL ENCLOSED AND RODENT PROOF. ADAPTER BARS 9. ALL WALLS AND CEILINGS IN THE FOOD PREPARATION AND STORAGE AREAS SHALL BE SMOOTH,DURABLE,AND NON-ABSORBENT. 4.1 2 REFRIGERATED SANDWICH UNIT-60" CONTINENTAL SW60-24M/003P KES G.C. W/REMOVABLE LID& 42.4 0 WALL SHELVING ADVANCE TABOO WS-12-84 KES G.C. TO. ALL EQUIPMENT AND COUNTERS SHALL BE SUPPORTED BY STAINLESS STEEL ROUND,6"HIGH METAL LEGS OR CASTERS, ADAPTER BARS 42.5 0 WALL SHELVING ADVANCE TABOO WS-12-96 KES G.C. 11. TRASH ENCLOSURE WALLS AND FLOORS SHALL BE SMOOTH AND EASILY CLEANABLE AND SEALED WITH AN APPROVED HEALTH 4.2 1 REFRIGERATED SANDWICH UNIT-72" CONTINENTAL SW72-30M/003P KES G.C. W/REMOVABLE LID& 42.6 1 TICKET HOLDER ADVANCE TABOO WS-12-60CM KES G.C. DEPARTMENT APPROVED SEALANT. ADAPTER BARS FIRE EXTINGUISHER DETAIL 5 2 POS PRIN ER EPSON M-88111 VENDOR G.C. 42.7 4 DR ER RACK SPG INT'L 12)OSL1836-E KES G.C. RAX/TRAXSTOPS/RAXTO D1 2)GSS1836-E G PER LAYOUT N.T.S. 5.1 2 LABEL PRINTER EPSON TM-L9O PLUS VENDOR G.C. 42.8 1 UTILITY SHELF ADVANCE TABOO K-245 KES G.C. 6 1 FRONT BREATHING REFRIGERATED DISPLAY CASE W/CASTERS FEDERAL IND. ELPRSS3-BP KES G.C. 42.9 2 WALK-IN WALL SHELVING SPG INT'L MX1842GR KES G.C. MOUNT 6'-6"A.F.F. W/SPARE PARTS KIT, 2 HAND SINK ADVANCE TABOO 7-PS-EC-SP-X KES G.C. FD-9660-RFGLR 7 1 FIRE DECK OVEN,GAS WOODSTONE KES G.C. COVER FORKLIFT HOLES 2 SOAP DISPENSER ECO LAB - VENDOR G.C. -IR W/PROVIDED COVERS 43 M8GLOVE PAPER TOWEL DISPENSER ECO LAB - KES G.C. 7.1 1 EXHAUST HOOD WOODSTONE SG-BDL-O-WS- KES G.C. EXHAUST FAN BY G.C. DISPENSERS-1 BOX HOLDER SAN JAMAR G0801 KES G.C. 4 AT EACH H.SINK 72-F __ FC-3-1824-18R _ 53-BOV� 7.2 1 ANSUL SYSTEM ANSUL R-102 G.C. G.C. 44 1 3 COMPARTMENT SINK W/TRIP LEVERS ADVANCE TABOO L KES G.C. g3 41.5 415 41.6 41 7.3 6 OVEN TOOLS NTH RACK WOODSTONE - KES G.C. MOUNT ON SHROUD 1 FAUCET&SPRAY VALVE COMBO KROWNE 17-109W KES G.C. O O 50 34 41.9 x5 10"HIGH STAINLESS STEEL PLATE(WALL UNIVERSAL 7 7.4 0 PROTECTED) 16 GA 55. STAINLESS STEEL G.C. G.C. 1 MOP SINK STAINLESS MOP-20-12 G.C. G.C. 32 OVE r a � 45 MOP SINK FAUCET-W PAIL HOOK& 31.1 OVE ABOVE 8P _ __ WALK-IN 6 8 1 CAN OPENER EDLUND U-12 KES G.C. INSTALL O.C.OF PREP 1 FILLER HOSE / KROWNE 16-127 KES G.C. _ COOLER ®ALL DRAWINGS AND WRITTEN MATEM& \ / (L= SMALL 46 - WATER HEATER(S) \\ / L---__-- 40.8 47 = f07 9 4 GARBAGE CAN"SLIM JIM" RUBBERMAID FG354000GRAY WARES G.C. - - G.C. G.C. CONTAINED HEREIN ARE THE PROPERTY OF �C7Q WOMEN'S _ L_-J 35 6 RE NNG1 DES CR GROUP,INC.RIEY MAY MEN'S 9 0 NOT BE REUSED,COPIED,REUSED,OR RESTROOM RESTROOM �� ABOVE 48 429 10 1 CAN CART WITH CUTTING BOARD TOP NEW AGE 50194 KES G.C. W/STRIP CURTAIN,4' aSCLOSED IN AxY MANNER WT+DUT RIM // 111 110 12 z2 481 0 0 - - - 47 1 WALK-IN COOLER/FREEZER KOLPAK A034071R2 KES G.C. LIGHT,GLOBES ABOVE pOWOHIZAnON FROM THE ARCIIIRCT. O - 0 11 g 11 1 UTENSIL RACK EDC ED-BLZI KES G.C. DOORS 8 35 35 35 35 41 C --- 40.7 STORAGE t - _ - - 12 2 MAGNETIC KNIFE HOLDER WINCO PMB-18 KES G.C. INSTALL 2"APART W/DRYER&AUTODRAIN, C AUG17 27 105 13 1 TEA BREWER BUNN TB30 COKE COKE 48 1 AIR COMPRESSOR POWEREX SES0308-BP KES G.C. 4-WAY VALVE,& \\`1TIHHII HIfpT17 Ig REGULATORS / \ 14 4 2 412 14 2 TEA DISPENSER BUNN TDO-N-4 COKE COKE ONLY WHEN LOCATION 13 CALIFORNIA AIR 15 1 COKE&ICE DISPENSER LANCER SENSATION COKE COKE 48.1 1 BACK-UP AIR COMPRESSOR TOOLS 10020C-110V KES G.C. USES 2 PNEUMATIC g V4;: CART-L •%nas 5 s 44 x2 16 2 BEVERAGE DISPENSER CRATHCO D25-3 KES G.C. PRESSES o V G o 50 2 LOCKERS NEXEL P6126KD KES G.C. ' ;Ljj T j 17 1 LID DISPENSER SAN JAMAR L3402 KES G.C. 51 1 SAFE SOCAL SAFE F-2820 KES G.C. Z 18 5 STRAW HOLDER SAN JAMAR L320C KES G.C. OFFICE 19 1 TRASH CHUTE SAN JAMAR L360C KES G.C. 52 2 POS TERMINAL SDCR SD_ _ CASH DRAWER MOUNTED CR AT UNDER SHELF Z717E10 I"YYxO HALLWAY 100 .� q q O 20 1 UNDER COUNTER REFRIGERATOR CONTINENTAL UC27 KES G.C. 53 1 AIR CURTAIN 36" MARS N2 36 G.C. G.C. INSTALL AT REAR 109 CLEANING SERVOS DOOR AREA 21 3 DRINK SLEEVES SAN JAMAR C2210SM KES G.C. SMALL 54 2 55 GAL.TRASH DRUM&DOLLY - - G.C. 4 0 106 � 22 2 SPEED RAIL KROWNE RS-18 KES G.C. WARES m m 23 2 BOTTLE CAP CATCHER SAN JAMAR 64300 SMALL G.C. 55 0 REACH-IN FREEZER CONTINENTAL 1F KES G.C. 7 �+ 71 2 5 - - 412 WARES 56 0 ROLL-IN REFRIGERATOR CONTINENTAL DLiRI KES G.C. INSTALL NEAR DOUGH 25 1 DOUGH ROUNDER SOMERSET IND. SDR-400BZ KES G.C. PREP AREA ■ 42 J 60 1 SECURITY CAMERAS AND ALARM SYSTEM - - T T ■ O _ 26 1 FOOD MIXER HOBART HL662-1STD KES G.C. - U) i.,� 80 I DRAFT TOWER-4 FAUCET MICRO MATIC DS-144-PSSKR VENDOR ■ _ _ POT FILLER INCLUDES 6'USE POT W 00 26.1 1 SERVICE FAUCET KROWNE KES G.C. 5 L_ L T= L 20-108L FILLER HOSE 81 1 DRIP TRAY MICRO MATIC DP-1020D VENDOR : a O 0 27 1 WALL HOOK FOR HAND MIXER WOODSTONE 1650100 KES G.C. 82 1 GLYCOL CHILLER-75'LINE OR LESS UBC GROUP TOTTON H-35C VENDOR t C) COOKING z 83 1 NITROGEN TANK VENDOR 0E-3A ■ ® J b- 1 HOT WATER DISPENSER BUNN H5E-18-120 KES G.C. HARDWIRE AT INSTALL _ r 1 40.3 `" >'.; f 28 84 - BEER KEGS VENDOR J e 1 HOT WATER DISPENSER WALL BRACKET - - KES G.C. Li 90 2 TRASH CAN SURROUND MILLWORK MILLWORK G.C. Q O SERVICE 29 2 DOUGH TOTE CART CAMBRO K1874 SMALL G.C. g1 0 HAND RAIL MILLWORK MILLWORK G.C. LC� z WARES N 102 SMALL 92 1 BEVERAGE STATION MILLWORK MILLWORK G.C. 5.1 = = q 30 1 NAPKIN DISPENSER TORK 6332000 G.C. - r PREP WARES 93 I POS COUNTER MILLWORK MILLWORK G.C. / t84 -- 1�_AREAL- B Im \"I�J 40.2 I ® IB 104 � 31 1 WATER FILTER ECOLAB 9320-2266 VENDOR VENDOR INCLUDE CHEMICALS 93.1 2 POS SHROUD MILLWORK MILLWORK G.C. B 66_4- © ® ® ® ® ® 94 1 EXPO STATION MILLWORK MILLWORK G.C. 31.1 1 MODULAR SCALE STICK SYSTEM ECOLAB ECO-SED 10 VENDOR G.C. ICE MACHINE ONLY 95 2 HIGH CHAIRS KOALA RARE KB105-02 SMALL G.C. 32 1 ICE MAKER FOLLETT HCC1410AHS KES G.C. W/MACHINE STAND WARES SMALL 33 1 BAG-N-BOX&CARBONATOR SYSTEM - - VENDOR VENDOR 96 2 BOOSTER SEATS CABMBRO 200BC110 WARES G.C. 34 1 BULK CO2 TANK - - VENDOR VENDOR BULK CO2 PREFERRED 97 I DESK&SHELVES MILLWORK MILLWORK G.C. 35 5 PIZZA TOLE RACK-FULL HEIGHT ALEXANDER IND. HDE-400MOD-7 KES G.C. LOCATE BELOW 98 1 POS SYSTEM SDCR SDCR VENDOR VENDOR 2BLZ CONDENSER FAN WORK TABLE-W/(2)UNDER SHELVES NOTE: FOR VENDOR CONTACT INFORMATION SEE PROJECT TEAM DIRECTORY ON SHEET G003 NO SPLASH GUARD-24"x48" ❑ c==== ❑ 40 1 ADVANCE TABOO MS-244 KES G.C. ADD:US-24-48 O - "EQUIPMENT SCHEDULE IS PROVIDED BY CORPORATE APPROVED KES.CONTRACTOR SHALL CONFIRM MAKE,MODEL,AND SIZE PRIOR TO WORK TABLE-W/(2)UNDER SHELVES ORDERING ANY EQUIPMENT. IF ANY DISCREPANCIES EXIST IN SIZE,MAKE,OR MODEL THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE 19 ❑ ❑ 40.1 0 _NO SPLASH GUARD-NDER36"6" ADVANCE TABOO MS-365 KES G.C. ADD:US-36-60 OWNER AND RISKARCHITECT AND ANY ASSOCIATED AWAIT FOR DIRECTION. SHOULD CONTRACTOR ORDER EQUIPMENT WITHOUT CONFIRMATION,CONTRACTOR DOES SO 18 x4 WORK TABLE-W/(2)UNDER SHELVES 30 T. 40.2 3 ADVANCE TABOO MS-302 KES G.C. ADD: US-30-24 EQUIPMENT NOTES F"' ❑ ❑ DINING -NO SPLASH GUARD-30"X24" AREA WORK TABLE-W/(2)UNDER SHELVES A. ALL MOUNTING HEIGHTS SHALL COMPLY WITH ALL LOCAL AND STATE ACCESSIBILITY AND BUILDING CODE REQUIREMENTS. 16 101 40.3 1 ADVANCE TABOO MS-304 KES G.C. ADD:US-30-48 - -NO SPLASH GUARD-30"X48" THE G.C.SHALL INSTALL ALL SOAP AND PAPER TOWEL DISPENSERS,AS FOLLOWS:SOAP DISPENSERS SHALL BE LOCATED DIRECTLY �' s WORK TABLE-W/(2)UNDER SHELVES B. OVER THE SINK AND PAPER TOWEL DISPENSERS SHALL BE LOCATED TO THE RIGHT SIDE OF THE SINK,WITHIN REACHING DISTANCE, 92 40.4 1 _NO SPLASH GUARD-24"X24" ADVANCE TABOO MS-242 KES G.C. ADD: US-24-24 BUT NOT DIRECTLY OVER THE SINK. 14 ❑ ___m ❑ O (, O O f, O O n O WORK TABLE-W/5"SPLASH GUARD- C. REFER TO THE ENLARGED RESTROOM PLAN FOR RESTROOM FIXTURES/EQUIPMENT. \\ B 40.5 1 W UNDER SHELF-24"X36" ADVANCE TABOO KMS-243 KES G.C. PROVIDEWITHZ-CLIPS D, G.C.TO PROVIDE EPDXY BASED WATERPROOFING AT ALL FLOOR SINKS/FLOOR DRAINS WHEN INSTALLED IN NON-TILE AREAS 15 ❑ ❑ 40.6 1 WORK TABLE-W/5"SPLASH GUARD- ADVANCE TABCO TKMS-305 KES G.C. PROVIDE WITH Z-CLIPS CODED NOTES NO UNDER SHELF-30"X60" PROJECT NUMBER: 17-420 PRO 95 1# O <m O O m O O ue O - O1 METAL CLOSURE PIECE BETWEEN WALK-IN-COOLER&WALL BY KITCHEN EQUIPMENT SUPPDER. DRAWN BY: RP 40.7 1 WORK TABLE-W/5"SPLASH GUARD ADVANCE TABOO TKMS-307 KES G.C. VIDE WITH Z-CLIPS CHECKED BY: MP NO UNDER SHELF-30"X84" MOP SINK TO HAVE A DEDICATED WATER SUPPLY FOR THE CHEMICAL DISPENSER.CHEMICAL DISPENSERS CANNOT BE CONNECTED c=== O DIRECTLY TO THE MOP SINK FAUCET.PROVIDE HANGING MOP HOOKS ON BACK WALL TO ALLOW FOR AIR DRYING OF MOPS. 96 >2 40.8 1 PREP SINK-18"X24"X12" -- -- KES G.C. O SODA MACHINE TO HAVE REDUCED PRESSURE BACKUP DEVICE(REED).NO COPPER,BRASS,OR OTHER CORRODIBLE MATERIALS ARE SHEET 11TLE: 42 x2 WIRE SHELVING,6 TIERS-86"MAX ALLOWED AFTER THE NEED. 41 2 HEIGHT POSTS-W/DUNNAGE RACK METRO 1824DRK3 KES G.C. 18%24" O 4"HIGH CONCRETE PAD FOR SAFE-COORDINATE LOCATION'NTH BLAZE CONSTRUCTION COORDINATOR. A m a " 23 411 0 WIRE SHELVING,6 TIERS-86"MAX METRO 1836DRK3 KES G.C. 18"X36" O EMPLOYEES MUST WASH HAND SIGNAGE(PROVIDED BY G.C.) EQUIPMENT HEIGHT POSTS-W/DUNNAGE RACK ©I la� 41.2 5 WIRE SHELVING,6 TIERS-86"MAX METRO 1848DRK3 KES G.C. 18-48" WALK-IN EVAPORATOR TO BE LOCATED ABOVE DOUGH RACKS PLAN HEIGHT POSTS-W/DUNNAGE RACK O7 T-VALVE TO BE INSTALLED AT BULK CO2 FOR BACKUP TANKS TO BE ATTACHED T B T g WIRE SHELVING,6 TIERS-86"MAX ® 17"MINIMUM CLEAR SPACE BETWEEN BOTTOM TWO SHELVES AT ALL WALK-IN SHELVING UNITS 41.3 6 HEIGHT POSTS-W/DUNNAGE RACK METRO 1860DRK3 KES G.C. 18"X60" WIRE SHELVING,6 TIERS-8 MAX 41.4 0 HEIGHT POSTS-W/DUNNAGE RACK METRO 2424DRK3 KES G.C. 24"x24"WIRE SHEET NUMBER: a TIERS-86"MAX EQUIPMENT PLAN 41.5 2 HEIGHT HPOSTS-6W/DUNNAGE RACK METRO 2436DRK3 KES G.C. 24"X36" Q110 ` SCALE:114'=1'-0' MECHANICAL GENERAL NOTES 15. Provide dielectric unions for connections between dissimilar metals. o if f g y PLUMBING PLAN NOTES PLUMBING LEGEND w 'o �'° BASIC MECHANICAL REQUIREMENTS 16. Test piping systems prior to concealment. n rc v ¢ 1. Furnish all labor and materials and perform all operations necessary for the installation of complete and functioning new and 17. Valves and cleanouts shall be installed as shown on the drawings and as required by code. z m Z m m m existing mechanicalSYMBOL ABBREV DESCRIPTION to systems,as specified and as required by code. 1. SINGLE COMPARTMENT SINK,SODA DISPENSER,AND ICE MACHINES SHALL z CD 18. All valves shall be installed so that valve remains in service when equipment or piping on equipment side of valve is removed. BE INDIRECTLY PLUMBED TO A FLOOR SINK WITH A MIN.1 INCH AIR GAP. SS or W NEW SEWER OR WASTECD w 0 Ci '^ 2. Contractor shall be responsible for verifying operation of all existing equipment and systems to remain.Contractor shall provide (E)SS or W EXIST.SEWER OR WASTE 1e a 3 O m to new or repair existing systems or equipment that are missing or malfunctioning to comply with note#1 above. 19. All balancing valves and butterfly valves shall be provided with position indicators and maximum adjustable stops(memory stops). 2. THREE COMPARTMENT SINK SHALL DRAIN INDIRECTLY.A FLOOR SINK 3 SHALL BE PROVIDED ADJACENT TO THE FIXTURE. V NEW VENT to `o MU MU o¢ 3. Install all mechanical equipment and appurtenances in accordance with manufacturers recommendations and written instructions, 20. All valves(except control valves)and strainers shall be full size of pipe before reducing size to make connections to equipment and ? DD m m x u. ---------------- (E)V EXIST.VENT contract documents,and applicable codes and regulations. controls. 3. HAND SINKS AND MOP SINK SHALL DRAIN DIRECT TO THE SEWER SYSTEM. w a - - CW NEW COLD WATER 4. Coordinate and order the progress of mechanical work to conform to the Owner's schedule and the progress of the work of the 21. Install all piping without forcing or springing. 4. WHEREVER THE SPECIFICATION"ADA COMPLIANT"APPEARS IT SHALL (E)CW EXISTING COLD WATER other trades. MEAN THE PRODUCT SHALL BE COMPLIANT WITH ACCESSIBILITY - - - - HW NEW HOT WATER 22. All valves shall be adjusted for smooth and easy operation. STANDARDS. 5. Coordinate all equipment connections with manufacturers'certified drawings and/or documents.Coordinate and provide all duct (E)HW EXIST.HOT WATER D and piping transitions required for final equipment connections to furnished equipment.Field verify and coordinate all duct and 23. All cleanouts shall be full size of pipe for pipe sizes 6 inches and smaller and shall be 6 inches for pipe sizes larger than 6 inches. 5. PLUMBING CODE USED FOR DESIGN IS 2015 ISPC G G NEW GAS D piping dimensions before fabrication. 24. Provide access panels for installation in walls and ceilings,where required,to service dampers,valves,smoke detectors,and other (E)G EXISTING GAS 6. Apply for and pay for all permits,fees,licenses and inspections for this Division of work. concealed mechanical equipment.Access panels shall be turned over to general contractor for installation. CD cD NEW CONDENSATE DRAIN 7. Comply with state and local code requirements and ordinances.Comply with requirements of the Utility Companies.In the case of 25. All openings in firewalls due to ductwork,piping,conduit,etc.,shall be fire stopped with a product similar to 3M or approved equal. EQUIPMENT RESPONSIBILITY CD (E)CD EXIST.CONDENSATE DRAIN differences between these requirements and ordinances,the most stringent shall govern.Call for inspections required by local CA COMPRESSED AIR building inspection authority. 26. All air conditioning condensate drain lines from each air handling unit and rooftop unit shall be piped full size of the unit drain outlet PROVIDED INSTALLED with a P-trap,and piped to nearest drain.Provide a condensate pump if required,field verify. TAG ITEM BY BY FCO FLOOR CLEANOUT 8. Submit shop drawings for all materials and specified equipment,in addition submit shop drawings showing any changes required in K �a E ff BQ piping,ducting,electrical wiring,space allocation,etc. 27. All piping shall clear doors and windows. WC-1 WATER CLOSET PC PC WCO WALL CLEANOUT L-1 LAVATORY SINK PC PC FD FLOOR DRAIN 9. The location of a istin under round/concealed utilities is shown in an approximate way only.The contractor shall determine the MECHANICAL IDENTIFICATION 'Vy g g pp y y HS-1 HAND SINK OWNER PC FS FLOOR SINK exact location of all existing utilities before commencing work.The contractor shall pay for and repair all damages caused by SK-1 3 COMP SINK OWNER PC failure to exactly locate and preserve any and all underground utilities. 1. Identify piping,ducts and valves above ceilings,as well as exposed to view except in finished areas.Conform to ASME A73.1. Z--�SK-2 1 COMP SINK OWNER PC TP TRAP PRIMER 8.TRAP PRIMER PIPING � 10. Patch and repair to match existing any walls,ceilings,or floors accessed during the installation of ductwork and piping,or during 2. Contractor to label appliances in an approved manner that uniquely identifies the appliance and the area it serves,when appliance MS-1 MOP SINK PC PC SOV SHUT-OFF VALVE c_ the removal of grilles,equipment etc. is remotely located from space it serves. WH-1 WATER HEATER PC PC Tv CV CHECK VALVE 11. Maintain one set of reclined drawings on the job site indicating all changes and deviations from the work shown on the drawings. INSULATION VR-1 VACUUM CONTROL VALVE PC PC p4�1�p4 PRV BACKFLOW PREVENTER W SOWS FS-1 FLOOR SINK PC PC T&P � 12. Prior to final acceptance,thoroughly clean all work. 1. Furnish and install insulation for all piping systems.All cold piping and equipment insulation shall include a vapor barrier. FS-2 FLOOR TROUGH PC PC C DN PIPE DOWN D_ oee�g 13. At completion of Work,deliver completed Project Record Documents marked with field changes to Owner's Representative. 2. Insulate all exposed water supply and waste on all lavatories and sinks. TP-1 TRAP PRIMER PC PC UP PIPE UPo« FD-2 FLOOR DRAIN PC PC ��� HOT WATER CALCULATION Poc POINT OF CONNECTION 14. Provide a written warranty to the Owner covering the entire mechanical work to be free from defective materials,equipment and 3. Piping insulation as indicated in following table. RP-1 REDUCED PRESS BACKFLOW PC PC workmanshipfor eriod of one year after Date of Acceptance. FLOW RATE(SEE SCHED # - PLUMBING NOTE CALL-OUT y P Y P TOTA BF-1 DUAL CHECK VALVE PC PC r, FIXTURE ON P120 FOR MORE QTY L GPM ABV ABOVE INFO. WF-1 WATER FILTER OWNER PC 15. Any substitutions of equipment,including but not limited to RTU's,AHU's,VAV's,VVT's,FPB's,etc.shall be approved by MEA Insulation Schedule ) F-1 DOUGH FAUCET OWNER PC AFF ABOVE FINISH FLOOR Consulting Engineers,Inc.The contractor is responsible for any additional costs incurred by substituting equipment.Cost shall Fluid Run 8" LAVATORY 0.4 2 1 o AIL DRAWNGS AND MIRITIEN MATERIAL Piping System 1-1/4" 2-1/2" 5"to AP ACCESS PANEL include additional cost incurred by other trades associated with the substitution.This shall include,but not be limited to,additional Temperature outs up and GI-1 GREASE INTERCEPTOR PC PC CONTAINED HEREIN A>sE WE RRORraTv a engineering,architectural services,electrical,structural,fire,and general contractor requirements. Types Range to 1" to 2" to 4" 6" larger HAND SINK 0.5 2 1 NOTES: VERIFY W/ARCHITECTURAL DWGS. Nor e[LE DESIGN GROUP,INC.WEY MAY BEL BELOWOR Domestic Cold MOP SINK 2 1 2 PC=PLUMBING CONTRACTOR DISCLOSED IN ANY MANNER IMTNOUT WIITTEN 16. The contractor shall be responsible for familiarizing himself with all field conditions and confirming that the work may be 40-60 1/2 1/2 1/2 1/2 1/2 GC=GENERAL CONTRACTOR BLDG BUILDING ADWORIZATON FROM WE ARCHITECT. Water 3COMP.SINK 1.42 1 1.42 accomplished as shown,prior to proceeding with the construction pricing and/or construction.Should there be any questions OWNER=BLAZE PIZZA C regarding the existing conditions and/or design intent,the contractor shall be responsible for obtaining a clarification from the Domestic Hot 105 or 112 1 1 1/2 1 1/2 1 1/2 1 COMP SINK 1.5 1 1.5 CLG CEILING engineer and/or architect prior to proceeding with the work,or related work,in question. Water greater CONT CONTINUATION C F-1 1.5 1 1.5 EL ELEVATION 17. All reports,plans,specifications,computer files,field data,notes,and other documents and instruments prepared by MEA (Insulation Thickness in Inches for Pipe Size) TOTAL 8.42 FIXTURE UNITS r,SNONAL EN Consulting Engineers,Inc.,as instruments of service shall remain the property of the Consultant.MEA Consulting Engineers,Inc. FIN FINISH �� G15TE t'+iy shall retain all common law,statutory and other reserved rights,including the copyright thereto. DOMESTIC PLUMBING WASTE WATER FL FLOOR 18. If MEA Consulting Engineers,Inc.for any reason is not allowed to complete all the services called for by these documents,MEA 1. Domestic Water Piping Materials: IMPORTANT GR GRADE a 9316 O 9 Consulting Engineers,Inc.shall not be held responsible for the accuracy,completeness or constructability of the construction FIXTURE TOTAL DFU TOTAL WSFU TOTAL Na documents prepared b MEA Consulting Engineers,Inc.if used,changed or completed b the Client or anotherparty. 1.1. Pi In from the service termination throw hout the rest of the building:For buried lines,Type"K",hard drawn co r.Above NTS NOT TO SCALE p99)�of�OPytrr P P Y g g 9 P y Y p g g 9 �� WATER CLOSET 3 6.0 18 2.5 7.5 OC ON CENTER SA Gp• Accordingly,the Client agrees,to the fullest extent permitted by law,to indemnify and hold harmless MEA Consulting Engineers, grade,Type"L",hard crews copper,wrought copper fittings and 9S5(tin/antimony),96�. ELL H• Inc.,its officers,directors,employees and subconsultants(collectively,MEA Consulting Engineers,Inc.)from any damages, LAVATORY 2 1.0 2.0 1.0 2.0 SS=% SLOPE AT A PERCENTAGE 08/30/2017 liabilities or costs,including reasonable attomeys'fees and defense costs,arising or allegedly arising from such use,change or 1.2. All ball,gate,globe and plug valves on hot and cold water domestic plumbing shall meet NSF-61 for lead content on all potable completion by any other party of any construction documents prepared by MEA Consulting Engineers,Inc.. hot and cold applications. URINAL 1 2.0 2.0 20.0 20.0 BHT SHEET TYP TYPICAL 19. Hard-copy construction documents or electronic files furnished by either party shall be subject to an acceptance period of 60 days 2. Sanitary Waste And Vent Materials: MOP SINK 1 3.0 3.0 3.0 3.0 ls: VTR VENT THRU ROOF during which the receiving party agrees to perform appropriate acceptance tests.The party furnishing the hard-copy construction 3-COMP SINK(INDIR) 1 - - 3.0 3.0 documents or electronic files shall correct any discrepancies or errors detected and reported within the acceptance period.After 2.1. Cast iron(below grade),Schad.40 PVC(above grade),and all other piping materials in the 2015 Idaho State Plumbing Coda GW GREASE WASTE the acceptance period,the hard-copy construction documents or electronic files shall be deemed to be accepted and neither party are allowed.Materials used in a return air plenum shall have a Flame-spread index of not more than 25 and a smoke-developed 1-COMP SINK(INDIR) 1 - - 3.0 3.0 0 shall have any obligation to correct errors or maintain hard-copy construction documents or electronic files. index of not more than 50. C HAND SINK 2 2.0 4.0 2.0 4.0 � r� 20. The Client and MEA Consulting Engineers,Inc.agree that any hard-copy construction documents or electronic files furnished by 3. Gas Piping Materials: - - - either party shall conform to the specifications.Any changes to the electronic specifications by either the Client or MEA Consulting FLOOR SINK(15 GPM) 6 3.0 18.0 00SPECIAL NOTICE TO CONTRACTORS `. o Engineers,Inc.are subject to review and acceptance b the otherparty.Additional services i MEA Consulting m Inners,Inc. 3.1. Pipe and Fittings:Schedule 40 black steel pipe and malleable iron fittings. FLOOR SINK 30 GPM 1 4.0 4.0 - - f a 9 I P Y Y 9 9 ( ) made necessary b changes to the hard-ce construction documents or electronic Tile s ecifcations shall be compensated for as ry s. g py p p 4. Water Piping: FLOOR DRAIN 4 3.0 12.0 O O Additional Services. 9� - - 1. ALL CONTRACTORS(GENERAL CONTRACTOR AND SUB-CONTRACTORS)BIDDING THIS 21. Under no circumstances shall delivery of electronic files for use by the Client be deemed a sale by MEA Consulting Engineers,Inc., 4.1. Run piping as direct as possible to required connections,and slope to drain valves at low points for complete draining of system. ICE MACHINE 1 - - 0.5 0.5 PROJECT ARE REQUIRED TO VISIT THE JOB SITE AND VERIFY THE EXISTING CONDITIONS and MEA Consulting onsultin Engineers,Inc.makes no warranties,either express or implied,of merchantability and fitness for an Locate drain valves al accessible points within the system. PRIOR TO SUBMITTING THEIR BID.CONTRACTORS ARE TO CAREFULLY REVIEW ALL n n n Q 9 9 P P lY Y SODA DISPENSER 1 - - 0.5 0.5 particular purpose.In no event shall MEA Consulting Engineers,Inc.be liable for indirect or consequential damages as a result of CONSTRUCTION DOCUMENTS AND NOTE ANY DISCREPANCIES BETWEEN THE O L� the Client's use or reuse of the hard-Copy construction documents or electronic files 5. Sanitary Waste Piping HOT WATER MACH. 1 - - 0.5 0.5 CONSTRUCTION DOCUMENTS AND THE CONDITIONS OBSERVED AT THE JOB SITE PRIOR TO SUBMISSION OF ANY BID.THE BUILDING OWNER REPRESENTATIVE MAY BE CONTACTED FOR CV Z 22. In the event the Client,the Client's contractors or subcontractors,or anyone for whom the Client is legally liable makes or permits 5.1. All sanitary waste piping shall be sloped at a minimum 1/4"per foot. TEA BREWER 2 - - 1.0 2.0 ACCESS TO THE JOB SITE. to be made any changes to any reports,plans,specifications or other construction documents prepared by MEA Consulting Engineers,Inc.without obtaining MEA Consulting Engineers,Inc.'s prior written consent,the Client shall assume full responsibility 5.2. Horizontal vent piping shall be graded to drip back to the soil or waste pipe by gravity. DOUGH FAUCET 1 - - 1.0 1.0 2, PRIOR TO CONSTRUCTION CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THE LOCATION �. for the results of such changes.Therefore the Client agrees to waive any claim against MEA Consulting Engineers,Inc.and to BASED ON 2015 ISPC: TOTAL 63 47 AND CONDITION OF THE FOLLOWING: B release MEA Consulting Engineers,Inc.from any liability arising directly or indirectly from such changes.In addition,the Client 6. Gas Piping: B agrees,to the fullest extent permitted by law,to indemnify and hold harmless MEA Consulting Engineers,Inc.from any damages, A. ALL POINTS OF CONNECTION TO BUILDING UTILITIES AND/OR SYSTEMS INCLUDING,BUT liabilities or costs,including reasonable attomeys'fees and costs of defense,arising from such changes.In addition,the Client 6.1. Support roof-mounted gas piping a minimum of 12 inches above roof on metal stands in pitch pans at 8 feet on center. T NOT LIMITED TO,GAS,WATER,SEWER,VENT,ELECTRICAL,MECHANICAL SYSTEMS, agrees to include in any contracts for construction appropriate language that prohibits the Contractor or any subcontractors of any 6.2. Metallic pipe shall comply with sections 403.4.1 through 403.4.4,and corrugated stainless steel tubing shall be listed in DUCTWORK,EXHAUST/OUTSIDE AIR,SECURITY,FIRE/LIFE SAFETY,DATA,AND PHONE. tier from making any changes or modifications to MEA Consulting Engineers,Inc.'s construction documents without the prior accordance with ANSI LC 1/CSA 6.26. written approval of MEA Consulting Engineers,Inc.and that further requires the Contractor to indemnify both MEA Consulting CHOT WATER SIZING B. ALL REQUIRED CONNECTIONS TO THE BUILDING STRUCTURE Engineers,Inc.and the Client from any liability or cost arising from such changes made without such proper authorization. COLD WATER CALCULATION HOT WATER CALCULATION C. ALL REQUIRED BUILDING PENETRATIONS.IT IS RECOMMENDED THAT THE CONTRACTOR BASIC MATERIALS AND METHODS PIPE X-RAY ALL PENETRATIONS THRU CONCRETE AND MASONRY. BUILDING EXTERNAL PRESSURE LOSS BUILDING EXTERNAL PRESSURE LOSS SIZE 1/2" 3/4" ," 1-1/4" 1-1/2" 2" 2 1. For all removed equipment contractor shall remove all supports,hangers,controls,piping,utilities,etc. 3. ANY DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND THE CONDITIONS ESTIMATED AVAILABLE WATER PRESSURE(VIF): 60 PSI MIN. ESTIMATED AVAILABLE WATER PRESSURE(VIF): 60 PSI MIN. GPM 2.5 6 11 18 25 40 60 OBSERVED SHALL BE BROUGHT TO THE ATTENTION,IN WRITING,TO THE ARCHITECT AND/OR 2. The mechanical drawings indicate the general design and arrangement of piping,equipment,systems,etc.Information shown is N/A TENANT PROVIDED WATER METER(VERIFY INFIELD) N/A PSI N/A TENANT PROVIDED WATER METER(VERIFY INFIELD) N/A PSI ENGINEER PRIOR TO PROCEEDING WITH CONSTRUCTION. diagrammatic in character and does not indicate every required offset,fitting,etc. 2" BLG.BACK-FLOW PREVENTOR -13 PSI 2" BLG.BACK-FLOW PREVENTOR -13 PSI WSFU 0.75 2.5 6.5 16 38 85 175 1-1/4"TENANT PRV(WATTS LFN456) -9 PSI 1-1/4" TENANT PRV(WATTS LFN45B) -9 PSI 4. SEE ARCHITECTURAL PLANS FOR CONTACT INFORMATION. 3. The locations of the items shown on the drawings or called for in the specifications that are not definitely fixed by dimensions are BASED ON PRESSURE LOSS 4.9 PSI PER 100 FT. approximate only.The exact locations necessary to secure the best conditions and results must be determined by the project site PRESSURE AVAILABLE AT BUILDING ENTRANCE 38 PSI PRESSURE AVAILABLE AT BUILDING ENTRANCE 38 PSI MAXIMUM VELOCITY=5.0 FPS conditions and shall have the approval of the engineer before being installed.DO NOT SCALE THE DRAWINGS(unless noted NOTE:HOUSE RPZ IS BY OTHERS,NO INFORMATION AVAILABLE NOTE:HOUSE RPZ IS BY OTHERS,NO INFORMATION AVAILABLE otherwise). TABLE TO CALCULATE DRAINAGE _ BUILDING INTERNAL PRESSURE LOSS BUILDING INTERNAL PRESSURE LOSS z-- 4. Contractor shall field verify locations and sizes of all existing equipment,ductwork,piping,electrical conduit,structuml members, 15 FT. HEIGHT(x 0.434) 6.51 PSI U COLD WATER SIZING FIXTURE UNITS FOR GREASE WASTE - etc.prior to bid.Contractor shall notify engineer of any and all discrepancies between field conditions and contract drawings. 15 FT. HEIGHT(x 0.434) 6.51 PSI PRESSURE REQUIRED AT FIXTURE(FLUSHVALVE UR) 25 PSI PLUMING DRAINAGE FIXTURE TOTAL DRAINAGE IPE ti rn N o 5. All ductwork,piping and equipment supported from structural steel shall be coordinated with the All attachments to steel bar PRESS RE ROD AT TANKLESS WATER HEATERS 15 PSI P SIZE 1/2" 3/4" 1" 11/4" 1-1/2" 2" 2-1/2" FIXTURE UNITS NUMBER OF FIXTURES FIXTURE UNITS joists,trusses,or joist girders,shall be at panel points.Provide beam clamps meeting MSS standards. - s.Welding to structural REMAINING PRESSURE AVAILABLE FOR FRICTION LOSS 6.5 PSI PRESSURE REQUIRED AT FURTHERST FIXTURE(LAY) 10 PSI HAND SINK 2 2 4 - members shall not be permitted.The use of C-Clamps shall not be permitted. 5 GPM REMAINING PRESSURE AVAILABLE FOR FRICTION LOSS 6.5 PSI 3 9 17 30 45 70 117 FLOOR DRAIN 2 2 4 6. Mechanical equipment,ductwork,and piping shall not be supported from metal deck. AVAILABLE PRESSURE FOR FRICTION LOSS FLOOR SINK WSFU 1 4 14 55 115 225 474 (15 GPM) 3 4 12 7. Use adjustable pipe hangers on suspended pipe.Provide hangers to support the systems without sagging.Include hangers at TOTAL LENGTH 133 FT.x 1.2=TOTAL EQUIV.LENGTH(T.E.L.) AVAILABLE PRESSURE FOR FRICTION LOSS PROJECT NUMBER: 1]420 each offset or change in direction and at ends of branches over five feet in length. _ BASED ON PRESSURE LOSS 4 PSI PER 100 FT. MOP SINK 3 1 3 DRAWN BY:160 FT. TOTALLENGTH 110 FT.x 1.2=TOTAL EQUIV.LENGTH(T.E.L.) MAXIMUM VELOCITY=8.0 FPS BASIN CHECKED BY: 8. Contractor to provide and install trap primers for all floor drains and sinks that do receive flow during occupied hours.Where code = 132 FT. TROUGH DRAIN 4 1 4 allows contractor may elect to use a waterless trap primer product. 6.5 PSI/160 x 100 FT.T.E.L.= 4 PSI PER 100 FT. (30 GPM) SHEET TITLE: A 9. Protect all insulated pipe at point of support with a 360-degree insulation insert. MAX aPsl LOSS PER,00FT. 6_5 PSI/ 132 x 100 FT.T.E.L.= 4.9 PSI PER 100 FT. TOTAL DRAINAGE UNITS 27 A 10. Sleeves:Schedule galvanized steel pipe sized large enough to allow for movement and for continuous insulation.Fire stopping sleeves by Pron maa PLUMBING NOTES Prone may b used in ire-rated construction.Sheet metal sleeves are not permitted.Sleeves used below grade and for penetration of water proofed oofed walls shall containn integral MAX q,g PSI LOSS PER 100 FT. gral water stop. INCOMING WATER SERVICE EQUIPMENT,SIZE AND DELIVERY TABLE 10-3 &LEGENDPRESSURES SHALL BE VERIFIED ON SITE PRIOR TO ANY WORK. GRAVITY GREASE INTERCEPTOR SIZING 11. Sleeves and bones shall be provided wherever pipes and ducts pass through Door,wall and roof construction. CONTACT ENGINEER IMMEDIATELY IF ANY DISCREPANCIES ARE INCOMING WATER SERVICE EQUIPMENT,SIZE AND DELIVERY DISCOVERED. PRESSURES SHALL BE VERIFIED ON SITE PRIOR TO ANY WORK. CONTACT ENGINEER IMMEDIATELY IF ANY DISCREPANCIES ARE DFU'S INTERCEPTOR VOLUME 12. Where horizontal pipes pass through walls and vertical pipes pass through floors or roofs,seal off void between pipe and sleeve, DISCOVERED. with an approved non-combustible material. 8 500 GALLONS 13. Install nickel-plated floor,wall and ceiling escutcheons of adjustable type on pipes passing through walls,floor or ceiling in finished 21 750 GALLONS SHEET NUMBER. areas. 14. Provide shut-off valves and unions suitably located to isolate each item of equipment. 35 1,000 GALLONS Pi 0 0 80 1,250 GALLONS p N W N N p ' Km m�p ❑ 0,U Plumbing Fixture Schedule a a ED'D a z o mp m?L� GO z� Zr� Comm Tag Fixture Cold Water Hot Water Waste Trap Vent Water Fixture (E)SAMPLE WELL DID w 0 T w Consumption o 3❑ °p Go 3 (E)1000 GALLON m o x 3 GREASE INTERCEPTOR m E7 a 3 "KOHLER"HIGHLINE MODEL K399916.5"WHITE VITREOUS CHINA j N Z a w 3 FLOOR MOUNTED COMBINATION TOILET WITH ELONGATED O w BOWL OR APPROVED EQUAL.TOILET SHALL HAVE 2"TRAPWAY, CHROME TRIP LEVER,AND 1.28 GPF.ORDER MODEL K-3999 WC WATER CLOSET(ADA /4" - 3" INT. 2" 1.28 GPF WITH LEFT HAND TRIP LEVER OR MODEL K-3999-RA WITH RIGHT O APPROVED HAND TRIP LEVER TO COMPLY WITH ADA FLUSH ACTIVATOR (E)3"VTR REQUIRMENTS.INCLUDE MODEL K-4731 ELONGATED OPEN 3 D FRONT TOILET SEAT.TOILET SHALL BE ADA,ASME Al 12.19.2. E D - PROVIDE WATER HAMMER ARRESTOR WATTS 15M2-FS "KOHLER"GREENWICH MODEL K-2032 VITREOUS CHINA WALL / W MOUNT ADA COMPLIANT LAVATORY WITH 4"CENTERS OR APPROVED EQUAL.INCLUDE"SLOAN"MODEL ETF-600-B-BDM ADA COMPLIANT POLISHED CHROME CENTERSET LAVATORY •� FAUCET OR APPROVED EQUAL.INCLUDE SENSOR OPERATED Lavatory(ADA 0.4 GPM/ METERED FAUCET W/0.5 GPM FLOWRATE,4"CENTERS, Y S Y/ ��=y L-1 1/2" 1/2" 2" 1-1/4" 1-1/2" APPROVED) 0.20GPC VANDAL-RESISTANT120V/2CTRANSFORMER. TOR AND MER.GRIDSET STRAINER,BOX f w �_264 MOUNT 0.20 G4VAC TRANSFORMER.SET METER TO 0.25 MIN/ _ E° ` CYCLE(0.20 GAL/CYCLE)LAVATORY TO BE ADA,IAPMO/UPC, I S ICC/ANSI A117.1,ASME A112.19.2 COMPLIANT.FAUCET TO BE y , • ADA,ASME Al 12.18.1 AND CALIF.GREEN BUILDING CODE I 2^ v COMPLIANT. V 1 "KOHLER"HIGHLINE MODEL K4960.ADA COMPLIANT.PROVIDE I K-13686 0.5GPF FLUSH VALVE,9V LITIUM BATTERY OPERATED, I URA URINAL 3/4" 2" 2" 2" 0.5 GPF ADA COMPLIANT.PROVIDE WATER HAMMER ARRESTOR WATTS \ 1 v 15M2-FS �T\2-112" C RINNAI INSTANTANEOUS GAS WATER HEATER MODEL RUC981. 1 OCD UNIT IS CAPABLE OF PROVIDING 4AGPM AT 80"F RISE.WATER 1 iT 2ii I SHALL BE SUPPLIED AT 120"F.CITY OF 2.NATURAL GAS INPUT n (E)FCO m oR OF 199,000 BTU INPUT COMPLETE WITH ALL STANDARD WHA WATER HEATER 1" 1" - - - - ACCESSORIES REQUIRED FOR OPERATION,INCLUDING FS TEMPERATURE AND PRESSURE RELIEF VALVEAND DRAIN ��///I 1 \1� 1 1 1 2 �" VALVE SIZED MULTI APPLICATION EXPANSION TANK.PROVIDE 2-1/2"��'WCO I \ / i�/ e 4"VTR V UR FS WITH MULTI UNIT CONNECTOR.PROVIDE ISOLATION KIT PER FS e "A MANUFACTURERS MANUFACTURERS RECOMMENDATIONS. JIB WC 1 \\�2- 1 3" RHEEM/RUUD"THERM-X-GUARD"POTABLE WATER EXPANSION 4" \ 2"i�/// HS FS 3 1 / ®ALL DRAWNCS AND WRITTEN MATERIAL ET-1 EXPANSION TANK 1/2" - - - - - TANK,MODEL#RRT-5.5 GALLON TANK VOLUME,STD FACTORY 3" 1 1 1 1 FS CONTAINED DESIGN ARE THE INC.THEY M OF 2' sir/ q^ THE LINGLE DESIGN C�PZD, C.THEY MAY PRE-CHARGE AT 40 PSI,PROVIDE STRAP AND SUPPORT. \ Y FD 1 e GIS 0 R IN M COPIED.REWFD,OR ��� pISCLOSED IN ANY MANNER W1THWi WRITTEN WATER HEATER "WATTS REGULATOR"WATER SERVICE VACUUM RELIEF VALVE, T / FD / / 4^\\ 1 j j 1 ADMORIZATION FROM ME ARCHITECT. MODEL#N36 Mi,ORDER#138458-3/4"NPT.OPENS @ LESS THAN 2" I� VR-1 VACU VALVE 112" - - - - - - 1/2"VACUUM.TESTED&RATED UNDER"ANS1221.22.CGA WC \�� e L �12- CERTIFIED2 C OR APPROVED l e r� 2" e 4\ C "PRO FLO"MODEL PF4285812N12"PVC RECEPTOR W/NICKEL 1 j 3 1 4" NAL FS-1 FLOOR SINK - - 2" 2" 1-1/2" - BRONZE STRAINER W/1/2"OPENING IN GRATE SEDIMENT CO 4" /�� 4" 1 HS Q�' OISTFp_n'i2 BUCKET. 2" 1 2" e O Q4r'rtZ F TRENCH DRAIN:ADVANCED TABCO FTG-1224 STAINLESS STEEL (E)FCO /\�� MS 1 1 1 a g3t11 p FS-2 FLOOR TROUGH - - 4" 4" 2" - FLOOR RECEPTOR WITH REINFORCED STAINLESS STEEL / \ 1 N O SLOTTED GRATE.SIZE 12"X24". 4" Q 2^ TRAP PRIMER:(SINGLE DRAW DISTRIBUTION),"PRECISION 4„ I� FDOF\GP54r PLUMBING PRODUCTS,INC."OREGAN#1 PO-500 TRAP PRIMER, 1/I e 3" 1 F9FLL R. TP-1 TRAP PRIMER 1'.. - - - - - PISTON OPERATED(TO OPERATE @ LESS THEN 1 PSI i� I/U 1 3„ 08/30/2017 PRESSURE DROP),ISOLATION VALVE,&STAINLESS STEEL Tj ACCESS PANEL. WC FS "J.R SMITH"MODEL#2005 FLOOR DRAIN W/5"POLISHED \ 1 BRONZE SQUARE TOP STRAINER.INCLUDE DUCO CAST IRON 1 FDA FLOOR DRAIN - - 2" 2" 1-1/2" - L BODY WITH FLASHING COLLIER,ADJUSTABLE STRAINER HEAD, 1/2"TRAP PRIMER CONNECTION,AND NO HUB CONNECTION. 1 1 CARBONATED "WILKINS"MODEL 740 3/8"CARBONATED BEVERAGE BACKFLOW 3" 1 BF-1 BEVERAGE 1/2" PREVENTER.STAINLESS STEEL BODY,SILICONE&BUNA WASTE & VENT ISOMETRIC 9 � - - - - - � I"O BACKFLOW NITRILE ELASTOMERS AND INTEGRAL STAINLESS STEEL 9 I••7 PREVENTER SPRING.ABBE 1022 COMPLIANT FS e 00 "WILKINS"MODEL 975XLST 1/2"REDUCED PRESSURE PRINCIPLE 1 o W PRINCIPLE REDUCED BACKFLOW PREVENTER.STAINLESS STEEL MAIN BODY WITH 1 1 a a C[ 0 PRESSURE TO INLINE INDEPENDENT CHECK VALVES SEPERATED BY AN 3" RP-1 1/2" O - - - - - 11 BACKFLOW INTERMEDIATE CHAMBER FOR RELIEF VENTING TO THE Q ® _j (n PREVENTER ATMOSPHERE. SHALL COME WITH TWO FULL PORT III ^ g BALL VALVES ANDND MODEL MODEL AG AIR GAP. / _ L_ J "SLOAN"MODEL BDM THERMOSTATIC MIXING VALVE.VALVE 1/2" / Li MV-1 MIXING VALVE 1/.. 1'.. - - - - SHALL PROVIDE TEMPERED HOT WATER(95-F-110-F)AT POINT /� / z OF USE.VALVE SHALL COMPLY WITH ABBE 1070 UNIVERSAL STAINLES"MODEL EHS-IRL WALL MOUNTED HAND SINK WITH GOOSENECK FAUCET AND 1.5"BASKET DRAIN \ HS-1 HAND SINK(ADA 1/2" 1/2" 1-1/2" 1-1/2" 1-1/2" 0.5GPM SUPPLIED BY OTHERS AND INSTALLED BY PLUMBING r1CF COMPLIANT) CONTRACTOR.SEE EQUIPMENT SCHEDULE IN ARCHITECTS / B DRAWINGS FOR ADDITIONAL INFORMATION.PROVIDE A DIRECT e TER ' \� / �� B CONNECTION PER NOTE#3 WC I BF-1 3/4" / \ I \ "ADVANCE TABCO"MODEL FC-3-1824-18RL THREE 1 COMPARTMENT SINK.INCLUDE"T&S"MODEL B-2299 WALL 3/4" 3-COMPARTMENT MOUNT FAUCET AND"T&S"MODEL B-0133 SPRAY NOZZLE(1.42 \ `\ / I I -� 3�q- 3/4'� SK-1 1/2" 1/2" 2" 1-1/2" 1-1/2" 1.42 GPM "C UR I \ 4' SINK GPM)SUPPLIED BY OTHERS AND INSTALLED BY PLUMBING \ CONTRACTOR.SEE EQUIPMENT SCHEDULE IN ARCHITECTS i 1 DRAWINGS FOR ADDITIONAL INFORMATION. \ I // I /\\Y' R7 \\ 1/2 SK I I 1/2" V'\ / BF-1 / \\\ DOUGH "ADVANCE TABCO"MODEL TA-1 to DROP IN PREP SINK.INCLUDE 3/4" � 3/4" / / / \ \ \ e I I FAUCET "T&S"MODEL B-0232 DECK MOUNT FAUCET PROVIDE WITH 1.5 r114„ / \ C\' I TEA 1-COMPARTMENT GPM AERATOR SUPPLIED BY OTHERS AND INSTALLED BY , I BREWER / ' �\\�3/4" 3/4- - I I 112' SK-2 1/2" 1/2" INDIRECT - - 1.5GPM I` SINK PLUMBING CONTRACTOR.SEE EQUIPMENT SCHEDULE IN ARCHITECTS DRAWINGS FOR ADDITIONAL INFORMATION. J I\ / PROVIDE INDIRECT CONNECTION TO FLOOR SINK PER NOTE#1. 3/4 � V � 1"DOWN 1 z / TO GWH-1 3/4" 1/2" "UNIVERSAL"MODEL MOP-20-12 MOP SINK OR APPROVED \ 1 z EQUAL.INCLUDE"KROWNE"MODEL 16-127 SERVICE FAUCET, I WC MS-1 MOP SINK 112" 112" 3" 3" 2" 2 GPM HOSE AND BRACKET,AND MOP HANGER.FAUCET TO INCLUDE I \vn(�/ VACUUM BREAKER,PAIL HOOK,INTERGRAL STOPS,AND FOUR \/ 3/q^ 112" I I HOT WATER - ARM HOT/COLD HANDLES.SEE NOTE#3 I Ir/ \1 HS DISPENSOR - I/ WC I C L (� WATER -- "ECOLAB"MODEL 932 OTHERS TWIN DUAL OUTLET HC WATER J e 1-1/q" \`\ FILTER 1 FILTER.SUPPLIED BY OTHERS AND INSTALLED BY PLUMBING 1 I I `\ 1 1/2- I �N z CONTRACTOR.SEE EQUIPMENT SCHEDULE IN ARCHITECTS WF-1 WATER FILTER 3/4' - - - - - I MS I mZ� DRAWINGS FOR ADDITIONAL INFORMATION.INCLUDE I I _ CARTRIDGE TYPE FILTERS W/3/4"INLET/OUTLET.CERTIFIED 1;2^ \\`3'4 1 I I - UNDER NSF/ANSI STANDARDS 42&53, I 1.7/4 I I "T&S BRASS"MODEL B-0674-BSTP SERVICE SINK FAUCET \\ `\\ a SUPPLIED BY OTHERS AND INSTALLED BY PLUMBING I CONTRACTOR.SEE EQUIPMENT SCHEDULE IN ARCHITECTS PROJECT NUMBER: 17-420 F-1 FAUCET 1/2" 1/2" - - - 1.5 GPM DRAWINGS FOR ADDITIONAL INFORMATION.INCLUDE POLISHED \\ I'I RPZBFP DRAWN BY: EBH CHROME PLATED FINISH,VACUUM BREAKER NOZZLE,PAIL \ I \/ CHECKED BY: NJH HOOK AND 3/4"GARDEN HOSE THREAD-6'NSF FILLER HOSE. ADA COMPLIANT. A* 3/4" ZURN MODEL NO.Z1446 CLEANOUT TEE,DURA-COATED CAST \�\'LO SHEET TITLE: A WCO WALL CLEANOUT IRON BODY,GAS AND WATERTIGHT ASS TAPERED THREAD / A PLUG,AND ROUND,SMOOTH STAINLESS STEEL WALL ACCESS 1/2" COVER WITH SECURING SCREW. 1/2" SPECIFICATIONS I < I BF-, &ISOMETRICS TEA I BREWER INSSODA SHEET NUMBER: WATER ISOMETRIC Pi 10 U F m W W0 mM p Z �❑ N U 1"CW,SEE PLANS FOR CONTINUATION LOW PRESSURE NATURAL GAS SUPPLY, u G m m 7 z SENSOR ACTIVATED —SEE PLANS FOR CONTINUATION 0 m❑ m❑ o`? METERED FAUCET 1"HW,SEE PLANS FOR CONTINUATION COLD WATER SUPPLY ��PIPE HANGER m ¢ Q m m w FLUE AND INTAKE UP THROUGH ROOF TO WATER HEATER NEXT TO PIPE TEE 1/2"C.W.SUPPLY VALVED z � m w SECURE TO WALL PER �� SEE PLAN 1"BALL VALVE INACCESSIBLE LOCATION PIPE UNION: 41 m a 3 p m i MANUFACTURER'S RECOMMENDATIONS DIELECTRIC IF ow w 3 ..OD J DISSIMILAR METALS �' ii AGA RATED GAS VALVE IN ACCESSIBLE SENSOR SENSOR CONTROL WIRE/CONDUIT i Mmi J m LO 2 4�+ THERMOMETER LOCATION TRAP PRIMER VALVE WITH INTEGRAL ^w a 3 INSTANTANEOUS GAS WATER HEATER VACUUM KFLOW FAKERPREVE TOR AND 2 GALLON THERMAL EXPANSION TANK WH-1 CONTROL BOX f/ VACUUM BREAKER PORT.PRECISION WITH NSF LINER. ( ) PLUMBING PRODUCTS#P1-500 WELDED STEEL SEE DETAIL 2/P720. BUTYL DIAPHRAGM EXPANSION TANK NOTE: Cl m - WITH POLYPRO- THIS DETAIL IS ONLY USED FOR REDUCER,LOCATE WITHIN 3"OF WATER --- PYLENE LINING J-BOX W/ AG-500 AIR GAP FI p D HEATER CONNECTION(TYP X 3) AIR CHARGING VALVE TANK-TYPE WATER HEATER. T�N�� 1„ FILL TANK WITH AIR TRANSFORMER \ SECURE DISTRIBUTION UNIT TO ASME RATED TEMPERATURE& PRESSURE TO MATCH SOLENOID \` BACKING SHEET BETWEEN PRESSURE RELIEF VALVE.EXTEND WALL MOUNTED WATER HEATER WATER PRESSURE, CONTROL VAVLE DISTRIBUTION UNIT STUDS. THEN OPEN VALVE LOW VOLTAGE FULL-SIZED DISCHARGE TO SPILL CONTROLLER.LOCATE ON WALL NEAR WIRE/CONDUIT NEAREST INDIRECT RECEPTOR --- WATER HEATER.PROVIDE ALL PIPING ARRANGEMENT SHOWN IS SCHEMATIC.ADJUST TO SUIT (POWER) CONTROL WIRING PER FIELD CONDITIONS.MAKE PIPE SAME SIZE AS TANK FITTING. MANUFACTURER'S RECOMMENDATIONS. FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION PROCEDURE.VERIFY PROPER OPERATION WHEN INSTALLED. PRESET SOLENOID TEMP. 38 bs ' -2 3/4"DRAIN VALVE NION(TYP X 3) EXPANSION TANK INSTALLATION SHALL OCCUR ONLY WHEN THERE (MIXED) CONTROL WIRFJCONDUIT / ,w AID U V,A BACK FLOW PREVENTION DEVICE INSTALLED WITHIN THE T NOTE: E TENANT SPACE WATER SYSTEM OR BUILDING WATER SYSTEM. DETAIL ONLY USED WHERE �LONGED DIRT LEG FIELD VERIFY BACKFLOW PREVENTION DEVICE. HOT O COLD 1/2"COPPER TUBING CODE REQUIRED. ROUTED BELOW FLOOR TO \/ MIXING VALVE TRAP ON FLOOR DRAIN. INSTANTANEOUS GAS WATER HEATER NOT TO SCALE 1 EXPANSION TANK NOTTOSCALE 2 ANTI-SCALD MIXING VAVLE NOT TO SCALE 3 TRAP PRIMER NOT TO SCALE 4 M� �v NOTE:PLUMBING CONTRACTOR TO BLOW OUT ALL TYPICAL GAS FIRED ROOFTOP PIPE REDUCER FROM O®W � e AIR LINES BEFORE MAKING FINAL CONNECTIONS. o AIR CONDITIONING UNIT BRANCH PIPE SIZE TO UNIT PROVIDE CLEANOUTS IN G__„.. CONNECTION SIZE,AT UNIT PRIMARY AIR TURNS ENDS OF PIPE.USE DISCHARGE INTO CENTER HOLE OF SILICONE SEAL AROUND PROVIDE V ELASTOMERIC INSULATION OVER CONNECTION COMPRESSOR DWV FITTINGS IF SIZE IS GRATE OF WASTE RECEPTACLE WITH f mm 8 PIPE PENETRATION CONDENSATE LINE. F m MMc DO NOW PROVIDE TRAP ON LARGER THAN 1" —� AIR GAP SUFFICIENT TO REMOVE 19 �'E UNITS WHICH HAVE AN GROUND JOINT PIPE UNION �S TANK DRAIN LINE W/ GRATE AND STRAINER.MINIMUM GAP INTERNAL TRAP.DRAIN BRANCH PIPE. AUTO TRAP EXTEND =TWO PIPE DIAMETERS DX COIL. y CONDENSATE DISHARGE TO AN SEE PLAN FOR SIZE FULL SIZE TO INDIRECT SLOPE PIPE AS MUCH 3/4" APPROVED PLUMBING RECEPTOR. MANUAL DIVERTING 00 coOUNT ABOVE VALVE IN AS POSSIBLE \ DOUGH CARTS GAS SHUT-OFF COCK PROVIDE TRAP AT BOTTOM TOWARD DISCHARGE ®ALL DRANiNGS AND Y.RITIEN MATERIAL OF RISER AND DISCHARGE CO NOT ABOVE CONTAINED HEREIN ARE ME PROPERLY OF CONDENSATE TRAP 8 DRAIN BRANCH PIPE. 4y 1 INTO FLOOR DRAIN OR PROVIDE CLEANOUT IN SHELVING ME UNCLE DE90 GROUP,INC.MEY MAY SEE PLAN FOR SIZE MAKE CONNECTION TO FLOOR SINK WITH AIR GAP NOT BE REUSED,COPIED,REUSED,OR DRAIN CONDENSATE AT SECONDARYAIR TURNS AND ENDS OF PIPE 1/8"PER FT.SLOPE TO AN� EQUIPMENT AS OF TWO PIPE DIAMETERS DISCLOSED IN ANY MANNER 1MMoui WRIi1EN APPROVED PLUMBING 2 MIN' BRANCH OFF TOP OF GAS DOUGH PRESS COMPRESSOR REQUIRED � MAKE CONNECTION TO COIL AUMORIZAPON FRgA ME ARCHITECT LOCATION 1-1Y2"MIN. PIPE MAIN TABLE VERIFY WITH LOCAL CODS AS REQUIRED MAKE PIPE MINIMUM ONE SIZE IF/W TRAP AND/OR FLOOR LARGER THAN EQUIPMENT VENT ARE REQUIRED FOR NO INSULATION ON PIPE RISER C CONNECTION,MINIMUM 3/4".USE"M" THE LENGTH OF DRAIN PIP WALK-IN COOLER OR FREEZER BOX OR 1"HARD COPPER UP TO 1"AND INSTALLED \ONAI FAy TYPE DWV FOR LARGER �4. 0\STE CQy EQUIPMENTCURB (n PIPE SUPPORT 18" SEE FLOOR PLAN FOR RECEPTACLE LOCATION. a Q 9 fi"LONG DIRT LEG FULL SEE DETAIL NO SHUT-OFF VALVES SHALL ROUTE PIPE INCONSPICUOUSLY AND UNOBTRUSIVELY.HANG PIPE 9316 SIZE OF BRANCH PIPE TYPICAL PRESSURE REGULATOR BE LOCATED ON THIS LINE. N 0 FF AS REQUIRED.DO NOT INSULATE INDIRECT DRAIN PIPE WHEN INSTALL PIPE HIGH AS POSSIBLE,ANCHORED TO WALL OF BOX .� PIPING ARRANGEMENT SHOWN IS SCHEMATIC.ADJUST AS REQUIRED. TYPICAL SHUT OFF VALVE INSTALLED EXPOSED IN FOOD SERVICE FACILITY.REFER TO LOCAL WITH SUPPORTS AT MAXIMUM SIX FOOT CENTERS.USE TYPE"M" O97FOF�OPg4 GAS CONNECTION AND PIPING NOT REQUIRED ON ELECTRIC HEAT UNITS. WITH QUICK DISCONNECT CODES FOR FURTHER INFORMATION. HARD COPPER TUBE AND FITTINGS WITH LEAD-FREE SOLDER 'C9FlL R•Oq JOINTS.SLOPE HORIZONTAL PIPE AT MINIMUM TWO PERCENT. REFER TO LOCAL CODE FOR INDIRECT DRAIN REQUIREMENTS. 08/30/2017 DETAIL REQUIRED ONLY IN DUAL PNEUMATIC DOUGH PRESS LOCATIONS ROOF TOP UNIT NOTTOSCALE 5 COMPRESSOR PIPING DETAIL NOTTOSCALE 6 INDIRECT DRAIN NOT TO SCALE 7 WALK-IN COOLER CONDENSATE NOT TO SCALE F8 NOTE: p _ NOTE:ALL FLEXIBLE CONNECTION LINES SHALL BE THE DECK PLATE SHALL BE STEEL MADE OF COPPER. COMPATIBLE WITH THE ROOFING DECK t PIPE SIZE AS REQUIRED SE MATERIAL FI Cn DRAWINGS TOP BEAM ALL-THREAD ROD. L u Incoming Water F110lICd W81lr CENTER DECK PLATE BELOW PIPE C STEEL LENGTH AS REQUIRED F STEEL Iced Tea STAND FOR PIPE SLOPE F Brewer DECK PLATE,RIGID 18 GA. STEPPED FLEXIBLE PVC BOOT CLAMPED 70 FLASHING BASE AND BAR JOIST . � STAINLESS STEEL,MIRO PIPE WITH STAINLESS STEEL SCREW CLAMPS PROVIDE COPPER INDUSTRIES MODEL DP-12, DRAINAGE PORTS ON TWO SIDES OR NON-METALLIC L J CJ SIZE 12"SO. OF PIPE STAND BASE �—GROUND-JOINT PIPE UNION ADJUSTABLE COATING WHERE J BAND HANGER HANGERS CONTACT CLEVIS HANGER FOR n n n LL_ J¢ ELBOWS TO PIPE OVER FOUR INCH FOR PIPING BARE COPPER PIPE Hot Water COMPENSATE FOUR INCH 0 O L� DI$en5er PROVIDE SPUN ROOFING OVER FOR PIPE 11�J L.(7 P METAL FLASHING EXPANSION OR LESS Q N Z ALUMINUM BASE IN O O Pizza Dough PROVIDE ALUMINUM PIPE BED OF MASTIC BY ROOFING PIPE SUPPORT PILLOW BLOCK PIPE STAND OF STRAPS.FASTEN TO PIPE COORDINATE WITH CONTRACTOR POLYCARBONATE RESIN STAND WITH STAIN STEEL ROOFER REFER TO DETAIL MATERIAL,MIRO INDUSTRIES PLAN SCREWS —y MODEL 24-R DO NOT HANG PIPE PROVIDE GALVANIZED STEEL SADDLE FOR ALL B Soda ROOF INSULATION LARGER THAN 3"FROM INSULATED PIPE LARGER THAN 314'.VERIFY H PIPE SHALL REST FIRMLY ON PIPE BOTTOM OF JOISTS. INSULATION THICKNESS WHEN SIZING HANGERS. PILLOW BLOCK PIPE STAND WITHOUT GAPS ROOF DECK r _ STAND PIPE STANDS ARE STACKABLE FLREQUIREDEEVE F �ANCHOR PIPE TO ROOF DECK OR JOISTS PROVIDE UPPER ATTACHMENT AS REQUIRED FOR CASES SHOWN HERE.DO NOT INSTALL HANGER INSIDE FOR PROPER ELEVATION OF INSULATION OR OTHERWISE PENETRATE VAPOR BARRIER.DO NOT HANG ONE PIPE FROM ANOTHER DECK PLATE VARIOUS SIZE PIPE TO MAINTAIN EXCEPT IN CHASES.TRAPEZE HANGER MAY BE USED FOR MULTIPLE PARALLEL PIPES.HANGER SPACING Ice LEVEL PIPING.NO SHIMS OR FOR PIPE SIZE: ROOFING MATERIAL BLOCKS ARE ALLOWED COPPER:4"=12' 3"=12' 2-1/2"=10' 2'=9' 1-1/2"=8' 1-1/4"=7' 1"=6'3/4"=S 1/2"=5' Machine REFER TO PLANS FOR PIPE SIZES)AND LOCATION(S).USE WELDED CAST IRON:WAND ONE NEAR ALL JOINTS OR SCREWED FITTINGS AS SPECIFIED FOR PIPE SIZE.LOCATE STEEL:4"=14' T=12' 2-1/2"=11' 2"=10'1-1/2"=9' V=7' 3/4"=6'1/2"=5' �IJI PENETRATION MINIMUM 18"FROM ADJACENT WALLS. LOCATE HANGERS AS CLOSE AS POSSIBLE TO TURNS AND TEES OF PIPE.PROVIDE SUPPLEMENTARY ELEVATION STEEL STRUTS BETWEEN JOISTS IF REQUIRED,LOCATE HANGERS TO TAKE LOAD OFF OF EQUIPMENT ECO TOZO ECPSED 10 Scale Cont of CONNECTIONS.ANCHOR WATER PIPE AGAINST SWAYING DUE TO CHANGES IN WATER VELOCITY. PIPE STAND GOOD FOR 1/2"TO 3 1/2"STEEL PIPE SIZES ONLY. PPROVI DE SEISMIC BRACING IF/AS REQUIRED BY LOCAL AUTORITIES.CHAINS OR PERFORATED STRAP carbidge Ice machine only IRON OR STEEL IS NOT ACCEPTABLE.REFER TO CODES FOR FURTER INFORMATION. From oftheho cabinet NOTE:MOUNT WITHIN 5'-0" L SUPPORT SPACING FOR PIPE SIZE:1/2"=6';3/4"-1";1 1/4"AND LARGER=10';PLACE OF THE ICE MACHINE DECK PLATES ON ROOFING,SET PIPE STAND FREE ON DECK PLATES.STACK PIPE STAND WHERE REQUIRED TO ELEVATE PIPING.INSTALL GAS PIPE TO ALLOW FOR ROOF PENETRATION NOT TO SCALE 11 PIPE HANGER NOTTOSCALE 12 EXPANSION AND CONTRACTION.PRIMER COAT AND PAINT EXTERIOR GAS PIPE LIGHT GREEN COLOR. WATER FILTER NOTTOSCALE 9 ROOF PIPE SUPPORT NOT TO SCALE 1p 4'-D" EQ. EQ. HOSE HOOK TO BE INSTALLED AT A+SPOUT,B.-CE HEIGHT 2"LESS THAN FAUCET OUTLET AND SHALL BE POSITIONED TO DRAIN EQ INTO MOP SINKSPOUT WITH HOSE END HOSE HOOK TO BE SPOUT BRACE PROJECT NUMBER: ]EH AND PAILHOOK INS TALLEDATAHEIGHT T — FLOORD IN STAINLESSSTEELDRAWNBY:LESS THAN FAUCETOUTLET 4'-0" = 3-COMPARTMENTSINKSERVICE FAUCET WITH SPOUT WITH HOSE END — CHECKED BY:VACUUM BREAKER AND PAILHOOK LINE E SLOPE-TYP. MOP SINK(MS-1) EQ SHEET TITLEA A SERVICE FAUCET WITH NEW SLAB 38"ROUGHIN HEIGHT PLUMBING POTFILLER VACUUM BREAKER TO FAUCET VERIFY DRAIN 44 AFF HOSE SLOPEO BFROM EDGE EX15TING 51A5 HEIGHT WITH EQUIPMENT OF SAW CUT TO DRAIN,REFER TO PLAN MANUFACTURER DETAILS DRAIN FOR CONTINUATION 4'-0"SQ. NOTE:FLOOR FINISH 2 yA• (TILE)TO BE CUT TO ACCEPT SLOPE Yz"SLOPE SHEET NUMBER: NEW SLAB POUR-BACK-Y" 3"DIA.P-TRAP SLOPE FROM EDGE OF SAW P 12 0 — CUT TO DRAIN MOP SINK NOT TO SCALE 13 POT FILLER FAUCET NOTTOSCALE 14 FLOOR DRAIN DETAIL NOT TO SCALE 12 3-COMP SINK DETAIL NOT TO SCALE 15 0 z w w o NN N p j F a m Z O m pa 6 mp pa Lf C7 Z� ZU •0m III a D ¢ m o LI EJ W 00 N� N N Q 3 O m J EXISTING O 3 w m w ..m SAMPLE WELL u DO J o a 3 Z N m Z a 4 3 w D o D _ EXISTING 1000 GALLON GREASE INTERCEPTOR 13 PLAN NOTES pF�111 Eu C 1. COORDINATE ROOF PENETRATIONS WITH THE LANDLORD'S ROOFING CONTRACTOR(IF J r REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED ROOFING BY LANDLORD'S ROOFING CONTRACTOR. C AJI o O b0 2. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING STRUCTURE OR O CBUILDING UTILITIES CAUSED AS RESULT OF THE CONTRACTOR'S WORK UNDER THIS WC FD CONTRACT.IT IS RECOMMENDED THAT MASONRY/CONCRETE FLOORSANALLS BE X-RAYED I 1 3 ---___--PRIOR TO ANY PENETRATIONS.3. CONTRACTOR SHALL INSULATE ALL INDIRECT DRAIN LINES(INCLUDING CONDENSATE LINES) E FC FROM ALL MECHANICAL COOLING&REFRIGERATION EQUIPMENT,COLDWELLS,ICETRAYS I _ (�_____JT====I `o I�__= IE:97.6 _ ANDANYFIXTURE/EQUIPMENT ITEM THAT MAY CONVEY WASTE UNDER 65'F AND/OR CAUSES 1 I N (EJ4"GW --- -- - I ........ Y7"GW f (EY7"GW ypeO^� CONDENSATION ON PIPING SURFACES.INSULATION SHALL BE 1/2"THICK CLOSED CELL Z (Ekl"SAN Q (E)FCO �„0.,0., ELASTOMERIC(RUBATEX OR EQUAL). WC ? --- 0 2 - 1 __-- FS 4. VERIFY WITH GENERAL CONTRACTOR AND KITCHEN EQUIPMENT VENDOR FINAL LOCATION �� L- UR I 8 12 IN y " OF ALL FLOOR SINKS AND FLOOR DRAINS.LOCATE FLOOR SINKS AND FLOOR DRAINS TO IE:96.7' =_J AVOID LEGS OF KITCHEN EQUIPMENT. FD 5. REFER TO ARCHITECTURAL PLANS AND KITCHEN VENDOR DRAWINGS FOR DIMENSIONAL I I I I CONTAINED ALL HER AND MITTEN MATERIAL ALLDRA HEREIN PRE ITT PROPERTY OR INFORMATION. e e - THE UNCLE DESIGN GROUP,INC.THEY MAY NOT BE DISCLOSED IN A,COPIED,REUSED,OR 6. ALL NEW CONCRETE AT TRENCHED AREAS TO MATCH EXISTING THICKNESS AND TO BE I 1 1 I AUTN IN ANY MANNER ARCHITECT 45RIi1EN PINNED TO EXISTING SLAB. I I FD AUTHIXtIZAiION FROM THE ARCHITECT. C I I. C � i i ii ySNO�AL FN p O L_ _LJ---_�I 11a I FCO 2 N m WASTE&VENT PLAN KEYED NOTES® I_ r FS 0.N� B31B 9 09-96 I MSS 1 9 P 1. SANITARY WASTE POINT OF CONNECTION:POINT OF CONNECTION TO EXISTING 4"SANITARY OF\Q yW WASTE LINE IN THIS VICINITY-FIELD VERIFY.MAKE NECESSARY CONNECTIONS AS 7 ie 9SgE11 N-pP REQUIRED.PLUMBING CONTRACTOR SHALL FIELD VERIFY INVERT ELEVATION PRIOR TO 11 10 1 L - DB�JO�POI� SANITARY WASTE LINE INSTALLATION. - -�-- - 2. GREASE WASTE PIPING:POINT OF CONNECTION TO EXISTING 4"GREASE WASTE LINE IN THIS b ¢ VICINITY-FIELD VERIFY.MAKE NECESSARY CONNECTIONS AS REQUIRED.PLUMBING O li CONTRACTOR SHALL FIELD VERIFY INVERT ELEVATION PRIOR TO GREASE WASTE LINE INSTALLATION. �nn H3 L L 46" 3. VENT:PROVIDE AND INSTALL 4"SANITARY VENT THRU THE ROOF IN THIS VICINITY.FIELD o VERIFY PRIOR TO INSTALLATION. IL- �-Ji "FS p Q O e 14 I`(J 4. SODA DISPENSER:PROVIDE DRAIN LINE FROM SODA DISPENSER DRAIN TO APPROVED � RECEPTOR.PROVIDE INDIRECTCT CONNECTION WITH MINIMUM 1"AIR GAP PER DETAIL 7/P120. FS F� FS FD & L LI �J 00 S. ICE MACHINE:PROVIDE 3/4"DRAIN LINE FROM ICE MACHINE DRAIN TO APPROVED RECEPTOR. 2 LLJ PROVIDE INDIRECT CONNECTION WITH MINIMUM 1"AIR GAP PER DETAIL 7/P120. O 1 1 f a O 6. RP VALVE DRAIN:PROVIDE 3/4"DRAIN LINE FROM REDUCED PRESSURE PRINCIPLE I li BACKFLOW PREVENTION ASSEMBLY TO APPROVED RECEPTOR.PROVIDE INDIRECT n O _ L CONNECTION WITH MINIMUM 1"AIR GAP PER DETAIL . ®® ® I O 7. BACKFLOW VALVE DRAIN:PROVIDE 3/e"DRAIN LINE CARBONATED BEVERAGE BACKFLOW AI. LLWWJJ LLWWJJ LL WW__JJ__JJ__JJ PP�� IJ�J PRE ENTER TO APPROVED RECEPTOR.PROVIDE INDIRECT CONNECTION WITH MINIMUM 1" AIR GAP PER DETAILS 7/P120. RR N Z 8. COMPRESSOR DRAIN:PROVIDE 3/4"DRAIN LINE FROM AIR COMPRESSOR TO APPROVED FF:100.0' RECEPTOR.PROVIDE INDIRECT CONNECTION WITH MINIMUM 1"AIR GAP PER DETAIL 7/P120. O 9. PREP SINK:PROVIDE 1-1/2"DRAIN LINE FROM PREP SINK TO FLOOR SINK.PROVIDE INDIRECT B CONNECTION WITH MINIMUM 1"AIR GAP PER DETAIL 7/P3.0. I B 10. WATER HEATER:PROVIDE 314"DRAIN LINE FROM WATER HEATER DRAIN TO APPROVED RECEPTOR.PROVIDE INDIRECT CONNECTION WITH MINIMUM 1"AIR GAP PER DETAILS 11P120 I aee e e e AND 7/P120. I ❑ o ❑ O ze O O O ze O ze O ze 11. T 8 P VALVE:PROVIDE 3/4"DRAIN LINE FROM T&P VALVE TO APPROVED RECEPTOR. I PROVIDE INDIRECT CONNECTION WITH MINIMUM I"AIR GAP PER DETAILS I/P120 AND 7/P120. I 88O ❑ ❑ R 12. WALK-IN UNIT CONDENSATE:PROVIDE AND INSTALL 3/4"CONDENSATE DRAIN LINE FROM WALK-IN FREEZER/COOLER TO INDIRECT DRAIN AT FLOOR SINK.MAINTAIN 1/4"PER FT.SLOPE ❑ ❑ ON DRAIN LINE AND MIN.1"AIR GAP AT TERMINATION.SEE DETAILS 7/P120 AND 8/P120. I INSULATE DRAIN FROM COOLER/FREEZER WITH 1"ELASTOMERIC INSULATION.SEAL PENETRATIONSAT COOLER/FREEZER FOR A WEATHERPROOF SEAL.PROVIDE TAPE ON CONDENSATE LINE WITHIN THE FREEZER SECTION UNDERNEATH THE ELASTOMERIC INSULATION. I ❑ ❑ ❑ ❑ ❑ O 13. GREASE WASTE PIPING TO CONNECT TO EXISTING 1000 GALLON EXTERIOR BELOW GRADE INTERCEPTOR.FIELD VERIFY EXACT SIZE AND LOCATION.MAKE NECESSARY CONNECTIONS o AS REQUIRED.PLUMBING CONTRACTOR SHALL FIELD VERIFY INVERT ELEVATION PRIOR TO FS o 0 0 0 0 0 SANITARY WASTE LINE INSTALLATION. O O O 1 14. CONTRACTOR TO MAINTAIN 2"FROM EDGE OF TROUGH TO EDGE OF LEG ON FOOD MIXER (EQUIPMENT tF26). NOTE: G` s - VERIFY INVERT ELEVATION OF EXISTING SANITARY PIPING IN FIELD.IF INVERT ELEVATION IS NOT O SUFFICIENT CONTACT ENGINEER.PROVIDE ALTERNATE PRICING FOR PUMP STATION IF O O O PROJECT NUMBER: 17-420 REQUIRED. DRAWN BY: EBH CHECKED BY: NJH A O B O B O A SHEET TITLE: o WASTE&VENT PIPING PLAN SHEET NUMBER 0 1' 2' 4' 8' 12' O O OSCALE: 1/4" = 1'-0" 0 N ? W N,II p rcDO mv >o -m❑ v am z ❑ mm BACK FLOW PREVENTER ASSEMBLY REQUIREMENTS ED ¢ Qm m w f�'J EJ W O Nm w 0 N 9 TYPE OF EQUIPMENT METHOD OF CROSS CONNECTION MANUFACTURE AND MODEL REMARKS w z ED ED 3 ON SYSTEM CONTROL NUMBER 3 ��� ® STAINLESS STEEL BODY WITH �^ m m 4 3 CARBONATE w a 3 SODA SYSTEM DUAL CHECK VALVE WITH WATTS QUARTER TURN VALVE SS ATMOSPHERIC PORT ASSE 1022/10222/1024 CERT STRAINER. kPz PM h - "(15mm LF0090T STAINLESS STEEL BODY WITH t]2 25 ICE MACHINE REDUCED PRESSURE ZONE WATTS LF009-QT-S 3a z0 ASSEMBLY QUARTER TURN VALVE BRONZE t03 is WATTS SD3-QT D TEA MACHINE DUAL CHECK VALVE WITH STAINLESS STEEL BODY WITH D 69 10 ATMOSPHERIC PORT ASSE 1022/1024 CERT QUARTER TURN VALVE BRONZE STRAINER. s WATER SERVICE REDUCED PRESSURE ZONE LAD FREE CAST COPPER WITH AP 0 t 2.5 5 ].5 t0 t25 t5 ppm WATTS LF-919-OT 0 3.6 9.5 f9 26.5 3B n.5 5]Ipm ASSEMBLY QUATER TURN 5 7.5 1.5 2.3 4.6 fps 1.CONTRACTOR SHALL PROVIDE INDIVIDUAL BACKFLOW PREVENTERS FOR EACH PIECE OF EQUIPMENT. mps 2.EACH BACKFLOW PREVENTER MUST HAVE TESTING PORTS. 3.BRONZE BODIED BACKFLOW PREVENTERS ARE PERMISSABLE IF ALLOWED BY LOCAL CODES. - —• �- Py vWWArM ICE MACHINE $n o C Qeeg$6tHs AIR COMPRESSOR �N SK2 C 0IIIIIIIIIIIIIIIIIIIIII C. S IS -- A P. F_----� �61,I�� ��ee �9tY 2p eye,, e Rm. B TEAO w DISPENSER DOMESTIC WATER PIPING PLAN NOTES ®AEL DRANINOS AND WRITTEN MATERIAE _ I 5 L COIJiAINED HERDN ARE THE PRDPERTIMAMY Of 1. COORDINATE ROOF PENETRATIONS WITH THE LANDLORD'S ROOFING THE SINGLE DE90x ORWP,wc.IN MAY 1 I CONTRACTOR(IF REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED ROOFING BY NOT BE RENSED,COPIEq REUSED,OR LF-919-QT pA.[a." c I LANDLORD'S ROOFING CONTRACTOR.SEE DETAIL 11/P120 OFR SIMILAR CONDITION. DISCLOSED Iry ANv MANrvER vn>HouT MITTEN ADTHORIZATON PROM THE ArecwlECT n L I I I 2. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING STRUCTURE C OR BUILDING UTILITIES CAUSED AS RESULT OF THE CONTRACTOR'S WORK UNDER C 'o I THIS CONTRACT.IT IS RECOMMENDED THAT MASONRY/CONCRETE FLOORSNVALLS - BE X-RAYED PRIOR TO ANY PENETRATIONS. ONA1- - - - - - - yS� FH O �FW - o _ - L- _u_-_J _ o - x s - 3. CONTRACTOR SHALL INSULATE ALL INDIRECT DRAIN LINES(INCLUDING CONDENSATE LINES)FROM ALL MECHANICAL COOLING&REFRIGERATION a v MS _ EQUIPMENT,COLD WELLS,ICE TRAYS AND ANY FIXTURE/EQUIPMENT ITEM THAT 9310 0 a a a xc oM i." 09-96 t HS - MAY CONVEY WASTE UNDER 65°F AND/OR CAUSES CONDENSATION ON PIPING 09 Q; SK \ / \ / SURFACES.INSULATION SHALL BE 1/2"THICK CLOSED CELL(RUBATEX OR EQUIV.). RPZBFP 1 /l}{(\ /1}{(\ �9FLLH•GP 2 4. VERIFY WITH GENERAL CONTRACTOR AND KITCHEN EQUIPMENT VENDOR FINAL O8/30/2017 LOCATION OF ALL FLOOR SINKS AND FLOOR DRAINS.LOCATE FLOOR SINKS AND 4 FLOOR DRAINS TO AVOID LEGS OF KITCHEN EQUIPMENT. O O O �oli 5. REFER TO ARCHITECTURAL PLANS AND KITCHEN VENDOR DRAWINGS FOR L L � DIMENSIONAL INFORMATION.WATER METER SHALL BE PROVIDED AND INSTALLED 9 ="^ BY TENANT.COORDINATE WITH DEPARTMENT OF WATER AND POWER 1800-342-5397 6 ] 1 FAUCET 6. ALL WATER OUTLETS OR DIRECT-CONNECTION OF WATER TO AN APPLIANCE SHALL ® E� O BE PROTECTED AGAINST BACKFLOW. ■ 00 LLJ O O I D nHOISPENSER T WATER DOMESTIC WATER PIPING PLAN KEYED NOTESiii O ® O q � LL I - Iuul Iii 1. DOMESTIC WATER:POINT OF CONNECTION TO EXISTING 2"DOMESTIC IL ® J VALVED AND CAPPED WATERLINE IN THIS VICINITY-FIELD VERIFY.MAKE Li J NECESSARY CONNECTIONS AS REQUIRED.PLUMBING CONTRACTOR SHALL O Q FIELD VERIFY POINT OF CONNECTION PRIOR TO WATER PIPE INSTALLATION. 2. WATER FILTER:INSTALL WATER FILTER PROVIDED BY OWNER PER DETAIL N 9/P720.WATER FILTER TO SERVE ICE MACHINE,TEA BREWER,BAG-N-BOX STATION AND HOT WATER DISPENSER. �. 3. RP VALVE:PROVIDE AND INSTALL A 1/2"STAINLESS STEEL PRINCIPLE B I REDUCED PRESSURE BACKFLOW PREVENTER(RP-1)IN FILTERED WATER B LINE AT THE ICE MACHINE PER PLAN.THE RELIEF VALVE SHALL DRAIN ❑ o Eleseo < < < INDIRECTLY TO AN APPROVED INDIRECT WASTE RECEPTOR(FLOOR SINK OR OLZOZ O O O e>e O e>e O rnz MOP SINK)WITH AN AIR GAP OF TWICE THE DIAMETER OF THE PIPE DIAMETER OR PER LOCAL CODE. o°Oo� I 4 1CARBONATED VENTED CARBONBEVERAGE TED BEVERAGE PREVENTER: BACKFLOW PREVENTER PROVIDE RAND(BFNSTNLL A FILTERED WATER LINE AT THE BAG-N-BOX,ICE TEA BREWER AND HOT WATER ❑ ❑ DISPENSER PER PLAN.THE VENT SHALL DRAIN INDIRECTLY TO AN APPROVED INDIRECT WASTE RECEPTOR(FLOOR SINK OR MOP SINK)WITH AN AIR GAP OF TWICE THE DIAMETER OF THE PIPE DIAMETER OR PER LOCAL CODE. CARBONATED BEVERAGE BACKFLOW PREVENTER SHALL BE ASSE 1022 ❑ ❑ O 5 COMPLIANT PER 20151DAH0 STATE PLUMBING CODE. QTFJ DISPENSER 5. MIXING VALVE:PROVIDE AND INSTALL ANIT-SCALD MIXING VALVE AT o O4 SODA o 0 0 0 0 o O LAVATORY TO TEMPER HOT WATER AT FOR PUBLIC USE.SET VALVE FOR HOT WATER DISCHARGE AT LAVATORY TO 110"F MAXIMUM. DISPENSER O O - O 0 6. WATER HEATER SHUT-OFF:INSTALL COLD WATER FEED SHUT-OFF VALVE - O o� O(E)2"CW a O FOR HOT WATER HATER IN 12"x12"FLUSH MOUNTED ACCESS DOOR.MOUNT VALVE 48"A.F.F. O o 7. WATER HEATER:PROVIDE 1"CW+1"HW DOWN TO WATER HEATER PER DETAIL 1/P120. - s 8. PROVIDE 1/2"CW LINE DOWN TO ICE MACHINE PROVIDE T010S FILTER WITH O SCALE CONTROL.NOT ALWAYS USED. O O O O 9. COMPRESSEDAIR:INSTALL 114"PEX COMPRESSED AIR PIPING FROM AIR PROJECT NUMBER: 17-420 COMPRESSOR TO PIZZA DOUGH PRESS.PROVIDED THREADED HOSE WALL DRAWN BY: Ell PLATE W/PRESSURE GAGE AND THREADED CONNECTION.PROVIDE 6 FT. CHECKED BY: NJH FLEXIBLE HOSE W/QUICK RELEASE DISCONNECT BETWEEN TOP AND BOTTOM SHELF OF CART AT PIZZA DOUGH PRESS.VERIFY EXACT O a -. 0 O a REQUIREMENT WITH OWNER.SEE DETAIL 6/P120 FOR POSITION OF SHUT SHEET TITLE: A OFF VALVE AND QUICK DISCONNECT. A DOMESTIC WATER PIPING PLAN SHEET NUMBER: 0 1' 2' 4' 8' 12' 10 SCALE: 1/4" = 1'-0" P210 w - w w >❑ ;mo j f a Q m O V z m on m ED ED z- z❑ mmm a n ¢ n o w >-J W an ED NAD w N In 313 m = 3Z ow to U J W 3 z ImnJ mGO a43 Gas Demand Schedule J w Equipment CFH RTU-1 80 RTUJ RTU-2 80 D (60 MBH) D &!� RTU-3 60 12" PIZZA OVEN 350 (60 MBH) WH QTY2 398 1/2" ROOF (458 MBH) PENETRATION Total Demand 968.00 3/4" `Bb Bat Total Developed Length:114'-0" N 8v na� J Fla 2e � E � 3/4" ROOF (458 MBH) PENETRATION i 1 RTU-2 GAS PIPING PLAN NOTES qp (80 MBH) 1. F -1 rc--� 1. COORDINATE ROOF PENETRATIONS WITH THE LANDLORD'S ROOFING (199WH-1 MBH EA.) 1/2" O i o CONTRACTOR(IF REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED C ROOFING BY LANDLORD'S ROOFING CONTRACTOR. ijp III (808 MBH) ,� L J III /q^ 1^ (80 MBH) ____________9 _ - 2. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING ��w ?bo$�; STRUCTURE OR BUILDING UTILITIES CAUSED AS RESULT OF THE -8. 3/4" 1/2" CONTRACTOR'S WORK UNDER THIS CONTRACT.IT IS RECOMMENDED THAT 2z ee 3 MASONRY/CONCRETE FLOORSIWALLS BE X-RAYED PRIOR TO ANY t e TTS 1^ PENETRATIONS. „ (888 MBH) y (968 MBH) 3. REFER TO ARCHITECTURAL PLANS AND KITCHEN VENDOR DRAWINGS FOR DIMENSIONAL INFORMATION. 0 ALL DRANIN11 AND WRITTEN MATERIAL PIZZA 1 `s `s GAS PIPING INSTALLATION NOTES caNTAINEo HEREIN ARE THE PROPERTY Of (350 MBH) V2" / m THE LINGtE DESIGN GROUP,INC.THEY MAY G NOT BE REUSED,COPIED,REUSED,OR \��1 1. GAS SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH 2012 DISCLOSED Iry ANY MANNER MTHWT WITTEN IJ p p �_ _Lj____� INTERNATIONAL FUEL AND GAS CODE.SUBMIT SHOP DRAW STO AuwoRlzanoN RROM mE ARCHITECT. (800 M MBBH) ENGINEER SHOWING FINAL ROUTING,MATERIALS,SHUT-OFFS,DETAILS,LINE C WH ----- SIZES FOR A COMPLETE GAS SERVICE TO THIS PROJECT. C ROUTE TO NEW GAS METER REGULATOR,VALVES,WALL, 09-98 1 - 2. THE GAS SYSTEM HAS BEEN DESIGNED USING THE LONGEST LINE METHOD BRACKETS,ETC.AS REQUIRED RTU-3 \ / WITH THE FOLLOWING CRITERIA: �455AD$TE FNC BY LOCAL UTILITY.SIZED FOR 2 G �.0 GASA,000 BUT/HR=1 CFH PSI SYSTEM UNDER IFGC. 2 1 ® I --- - INLET PRESSURE:2L�TA�TE a 9316 6 3 2 PRESSURE DROP:1O THIS PROJECT REQUIRES 968 CFH OF GAS CAPACITY AT 114'FT.T.D.L. Of�OPy4r o C CONTRACTOR SHALL VERIFY EXACT GAS REQUIREMENT WITH S9F(L P•GP 44 TENANT PRIOR TO CONSTRUCTION. 08/30/2017 L_____J 3. CONTRACTOR SHALL PROVIDE AND PAY FOR ANY REQUIRED UPGRADE OF EXISTING GAS SERVICE AND METER. 22'10. 4. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING STRUCTURE OR BUILDING UTILITIES CAUSED BY SLAB PENETRATIONS.IT IS O O --- - RECOMMENDED THAT THE FLOOR BE X-RAYED PRIOR TO ANY SLAB __ = PENETRATIONS. EQET O 1 n O I- 5, COORDINATE ROOF PENETRATIONS WITH LANDLORD'S ROOFING - 00 CONTRACTOR(IF REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED L W eM. uem ROOFING BY LANDLORDS ROOFING CONTRACTOR. a 0 TABLE mz.4tx1Ae""e RTU-1 2-3 6. VERIFY ALL GAS CONNECTIONS WITH MANUFACTURE'S INSTRUCTIONS PRIOR scHMULE 40 METALLIC PIPE n..... xzee TO CONSTRUCTION.PROVIDE CABLE RESTRAINTS FOR ALL GAS FIRED _J VJ EQUIPMENT ON MOVABLE EQUIPMENT. R L_ J O E4 O Amro aazz a.n4 Ian Lsn 1ao :za's z4rA z0ee ams GAS PIPING PLAN KEYED NOTES ® Z emp0 V9 C.' r,Tnee.riee a9 perlw 1 '-11 '• Q cV zew sssa Iosao nm0 Jzao a 9+m0 IxAnO asa.9aa e e e e 1. POINT OF CONNECTION TO EXISTING 1"CAPPED AND VALVED 2 PSI GAS m Lwa s.ua il.M usw0 zx.Jm 4x.0m W4..ou In.am z.zm0 O O O oz O zoz O zrz PIPING ON ROOF.ROUTE TO NEW GAS METER.NEW METER DEMAND:968 s0 I.IWO s.0m sdm u.v00 n.w0 ssm xsm 9r.lm 19am0 p CFH AT 114'-0"TOTAL DEVELOPED LENGTH.INSTALL NEW GAS LINE SIZED PER B Wa PLAN IN CEILING SPACE TO PIZZA OVEN AND WATER HEATERS.VERIFY WITH zJa -1. m100 °1'0°e _ iw.o�OW ®oCO ❑ ❑ LANDLORD EXACT ROUTE.se B No 1.010 2.1m 4nm az la Izlm zs.110 31.Tm .'We IJ Tqc 2. GAS LINE PENETRATION:INSTALL NEW GAS LINE DOWN FROM ROOF INTO Je 9so ® J..mo 6'-2' TENANT SUITE.COORDINATE WITH GENERAL CONTRACTOR AND LANDLORD so wA I 1 1.130 AJz.Jm1 17.1. AG LOCATION OF PENETRATION. Me a'S I.tm JSIO 3o_wo ,s u _ ❑ �, ❑ 4'-1 3. ANSUL R-102 CONTROL 8 CHEMICAL BOX ABOVE OVEN(BY OTHERS). ❑ ❑ O zAm _ _ _ _ 4. EMERGENCY SHUT-OFF:OVEN VENDOR PROVIDED 1-1/2"GAS AUTOMATIC EMERGENCY SHUT-OFF VALVE CONTROLLED BY HOOD FIRE SUPPRESSION In sm L.I. z140 4.em - I- vim n..00 'I- SYSTEM LOCATED IN OVEN.VERIFY LOCATION PRIOR TO INSTALLATION. zan .swl � (E)1'GAS O COORDINATE INSTALLATION WITH ELECTRICAL AND MECHANICAL Im s•.em "''°° azrao O CONTRACTORS. wa Ass enn INTO s.uo s.lw avm ISJm n.nm 57- 11. Jso xl an la.o J.Im ..Tm 1- A- x.zm sz.00 5. PULL STATION:FIRE SUPPRESSION SYSTEM PULL STATION INSTALLED BY aov w. Teo I,sso z.9m .1m a.so u�oo x.9m a4m O O O OTHERS. sm zzz w. Isro z,m0 x910 Tdm IzmO zLmW A1o01. O 6. PIZZA OVEN:PROVIDE 1-1/2"GAS SHUT-OFF VALVE WITH DIRT LEG AND GAS - I�lo ..a alo IIAao .Im CONNECTOR TO PIZZA OVEN(350 CFH @(VERIFY LENGTH PER PROJECT) _ z3m 3Jm _ m� Ic T.D.L.).VERIFY E MANUFACTURE NO FLEXIBLE CONNECTION ALLOWED FOR PIZZA OVEN. es0 20J SBS I.I. 2140 JJ'm aJ'n I- I.." flJm Inu zlm mam O lym son O O O \\ Sxl 98n z.m - J.W - IeAOe 11409 - \\ S 2,9b S,eea -A- 32.o9 zxla JAte 9!M >b �i6 M 1.6.0 - S.JIa WW1 Is.- leJOM IJIOU EL Ihl !J3 I.Tm Zhaa 1.1m 0110 14.ba P.lm O a O a O 121 0 DRAAWN BY:UMBER: 17-EBH uzm CHECKED BY: NJH IJdI 1. dUx Tn1 I.- M. AA. M. M- xSJaa eam 1Jao z1m aem SHEET TITI F. A ao a ax9 v.eoo A I. I.- zu'. 1.1110 °IOU iu,9w „w, GAS PIPING 4am iW um PLAN zxm IQ oM em 1100 1.tl1p 1- 52m 1..- SHEET NUMBER 0 1' 2' 4' 8' 12'O SCALE: 1/4" = 1'-0" P//�2^/(O ❑ w m s MECHANICAL GENERAL NOTES AIR DISTRIBUTION SYSTEMS 7 w o N Rooftop Unit Schedule �m a m BASIC MECHANICAL REQUIREMENTS 1. Sheet metal duct systems shall be fabricated and installed in accordance with SMACNA HVAC Duct Construction Standards Manual. rc rn 0 al❑ m?u Min Total SEN E.A.T. E.A.T. L.A.T. O.A.T. HTG Motor Data z- Z ro r0 m rn Supply ductwork shall be low pressure(2"w.g.). Nominal D ign E Elec. Elec. E.E.R./ Weight [0 Q m w 1. Furnish all labor and materials and perform all operations necessary for the installation of complete and functioning Item Manufacturer Model O.A. CAP CAP DB WE DB Input (MBH) z a w p p ry p g new and existing Tonnage C M CFM (I ) (MBH) (MBH) DEG F DEG F DEG F ('F) IN/OUT HP V/PH MCA MOCP S.E.E.R. (Lbs) r7 E w O rn w w mechanical systems,as specified and as required by code. 2. All round and flat oval duds exposed to view shall be spiral seam.Concealed round and flat oval ducts may be fabricated with lock type m F- ❑ in or welded longitudinal seams. RTU-1 Trans YSC072 6 2 00 550 0. 72.0 57.6 80 62 55 95 80/53 - 208/3 36.5 50 11.2 750 p w W 3❑ m m Z 2. Contractor shall be responsible for verifying operation of all existing equipment and systems to remain.Contractor shall provide new or 3 ❑w w repair existing systems or equipment that are missing or malfunctioning to comply with note#1 above. 3. If ductwork is to be painted,ductwork shall be paintlock type. RTU-2 Trans YSC072 6 2 0 550 0. 72.0 57.6 80 62 55 95 80/53 - 208/3 36.5 50 11.2 750 m J m to­10 a 3 z ut IE 3. Install all mechanical equipment and appurtenances in accordance with manufacturers'recommendations and written instructions, 4. Suspend duds from structure with proper hangers at a maximum of V-0"intervals,at each floor,change of direction and wherever ^Lu a 3 contract documents,and applicable codes and regulations. necessary. RTU-3 Trane YSC048 4 1 0 400 0." 48.0 38.4 80 62 55 95 60/40 - 208/3 25.4 35 414.0 550 4. Coordinate and order the progress of mechanical work to conform to the Owner's schedule and the progress of the work of the other 5. All duct connections to motor driven equipment shall be with flexible connections. E::::: KS: trades. rooftop units with economizer and barometric relief to remain.Verify location and proper operation infield.Contractor to verify orientation of existing rooftop6. All ductwork to be of sheet metal construction per SMACNA standards for low pressure distribution.Provide volume dampers at eachd location of supply and return drops.Notify tenant's engineer with any questions prior to bidding.No extras or change orders shall be given for contractor'sD 5. Coordinate all equipment connections with manufacturers'certified drawings and/or documents.Coordinate and provide all duct and round duct and 45 degree duct take-off to allow complete balancing of all branches and diffusers. verify site conditions prior to bidding. D piping transitions required for foal equipment connections to furnished equipment.Field verify and coordinate all duct and piping tor to verify orientation of existing rooftop units and location of supply and return drops.Notify tenant's engineer with any questions prior to bidding.No dimensions before fabrication. 7. Coordinate diffuser and grille locations with ceiling and lighting layout to avoid conflicts. r change orders shall be given for contractor's failure to verify site conditions prior to bidding. 6. Apply for and pay for all permits,fees,licenses and inspections for this Division of work. 8. Make all radius elbows with radius of one and one half times the diameter or width of duct and an inside throat radius of one times the condensate and condensate overflow protection to remain.Contractorto verify proper operation andexactlocation infield. diameter or width.Radius elbows are the preferred method for 9W dud turns. 7. Comply with state and local code requirements and ordinances.Comply with requirements of the Utility Companies.In the case of differences between these requirements and ordinances,the most stringent shall govern.Call for inspections required by local building 9. Attach flexible duct inner liner to duct connectors,diffuser necks,or ductwork with stainless steel worm driven clamp.Tape outer vapor inspection authority. barrier securely war clamp with vapor barrier tape. MUA TO BE PROVIDED BY RTU UNITS. RTU WWS 8. Sping,dshop drawings for all rng,sp spls ace anon,edequipment,inadditionsubmitshopdrawingsshowinganychangesrequiredin 10. Low and eairdu tandc complyure ing with uct shall FPAStan ards90 listed 90B.Du Underwriters llbeGLaboratories,GUARInc. tested andnder UL d 181 as a Class UNITS TO BE INTERCONNECTED WITH HOOD piping,ducting,electrical wiring,space allocation,etc, flexible air duct and complying with NFPA Standards 90A and 908.Duct shall be GREENGUARD tested and certified.Low permeability E � outer vapor barierof fiberglass bi-directional reinforcedmetalizedlaminatefilmshallcompletethecomp°site. EXHAUST FAN TO RUN WHILE OPERATING. 9. The location of existing underground/concealed utilities is shown in an approximate way only.The contractor shall determine the exact location of all existing utilities before commencing work.The contractor shall pay for and repair all damages caused by failure to exactly 11. Flexible ductwork hanger supports shall be constructed of durable composite material and shall be 1-1/2"wide to prevent any restriction locate and preserve any and all underground utilities of the internal diameter of the ductwork when the weight of the supported section rests on the hanger.Hanger supports shall be UL listed for use in return air plenum spaces. UO 10. Patch and repair to match existing any walls,ceilings,or floors accessed during the installation of ductwork and piping,or during the removal of grilles,equipment etc. 12. Maximum length of any section of flexible duct shall be eight feet. N 11. Maintain one set of reclined drawings on the job site indicating all changes and deviations from the work shown on the drawings. 13. Certain items such as rises and drops in ductwork,access doors,volume dampers,etc.,are indicated on the contract document Ventilation Schedule c drawings for clarity for a specific location requirement and shall not be interpreted as the extent of the requirements for these items. Required Required Breathing Zone Air Zone Supplied Floor Area Maximum upply Air Exhaust Airflow Exhaust Airflow Exhaust Airflow q 12. Prior to final acceptance,thoroughly clean all work. Space Name Outdoor Air Outdoor Air Zone Outdoor Distribution Outdoor Outdoor Air O �E (tt') Occupants (CFM) Rate CFM/FT' Required CFM Supplied CFM 14. All ductwork dimensions,as shown on the drawings,are internal clear dimensions and duct size shall be increased to compensate for (CFM/Person) (CFMttt') Air(CFM) Effectiveness (CFM) (CFM) ^^^ 13. At completion of Work,deliver completed Project Record Documents marked with field changes to Owner's Representative. duct lining thickness. E� k Dining 101 1769 123 7.5 0.18 1240.92 0.80 1551.15 550.00 6000 - - - 14. Provide a written warranty to the Owner covering the entire mechanical work to be free from defective materials,equipment and 15. Locate all mechanical equipment(single duct,dual dud,variable volume,constant volume and fan powered boxes,fan coil units, Service/Cooking Area 102/103 462 - - - - - 200.00 1100 0.70 224 1050 ." workmanship for a period of one year after Date of Acceptance. cabinet heaters,unit heaters,unit ventilators,coils,steam humidifiers,etc.)for unobstructed access to unit access panels,controls and valving. Prep Area 104 114 1 5.0 0.12 18.68 0.80 23.35 250.00 200 15. Any substitutions of equipment,including but not limited to is inc rred by V substituting tang e FPms,etc.shall be approved by Engineer of Storage/Cleaning Area 105/106 370 3 5.0 0.12 59.40 0.80 74.25 400.00 900 Record,The contractor is responsible for any additional costs incurred by substituting equipment.Cost shall include additional cost 16. Smoke detectors shall be furnished and wired by the electrical contractor.The mechanical contractor shall be responsible for mounting incurred b other trades associated with the substitution.This shall include,but not be limited to,additional engineering,architectural the smoke detector in ductwork in accordance with manufacturer's printed instructions. T 0 1 .0 8200 ®Ali DRAmM AND wxITtEN MATERIAL YP CONTAINED HEREIN ARE THE PROPERW OF services,electrical,structural,fire,and general contractor requirements. THE LINGIE DESGN GNUIP,INC.THEY MAY FIRE PROTECTION NOSBS BALANCE REPORT NOT BE OSED IN ED,COPIED,RED NUT BASIC MATERIALS AND METHODS 1. Ventilation Schedule is based on 2012 IMC chapter 4-Use local codes and amendments for ventilation requirements. ,�640 DISCLOSED IN A>✓v MANNER vnntoui wRITTEx 1. The fire sprinkler system shall be designed and installed by an approved design build contractor. 2. Balance to CFM's indicated in this schedule.Minimum OSA for building is set to 20%OSA. REQUIRED AT FINAL AUTHORIZATION FROM THE ARCHITECT m 1. For all removed equipment contractor shall remove all supports,hangers,controls,piping,utilities,etc. 3. Restroos require 100 CFM exhaust each,amount supplied is 100 CFM each. C 2. Modify the existing automatic wet pipe sprinkler system throughout the entire building,complete in all respects and ready for operation. C 2. The mechanical drawings indicate the general design and arrangement of piping,equipment,systems,etc.Information shown is diagrammatic in character and does not indicate every required offset,fitting,etc. 3. Coordinate sprinkler head locations with the architectural reflected ceiling plans,lighting,and other ceiling items and make minor TONAL F modifications to suit project Exhaust Fan Schedule Air Balance Schedule 3. The locations of the items shown on the drawings or called for in the specifications that are not definitely fixed by dimensions are approximate only.The exact locations necessary to secure the best conditions and results must be determined by the project site 4. Sprinklers installed in ceilings of finished areas shall be symmetrical in relation to ceiling system components and centered in the ceiling 1 0: Q•(s/+"� rn E.S.P. Operating Power a_ 9 conditions and shall have the approval of the engineer before being installed.DO NOT SCALE THE DRAWINGS(unless noted tile. Mark Model No. CFM (in W.C.) B.H.P. (watts) Voltage Location Weight Equipment Supply Air Return Ai Outside Air xhaust Air Balance 9316 otherwise). N� O O 9)� yOP 4. Contractor shall field verify locations and sizes of all existing equipment,ductwork,piping,electrical conduit,structural members,etc. REFRIGERANT PIPING EF-1 Loren Cook 165VCR-HP 1050 1.0 .6 1/2HP 208/60/1 Roof 149 RTU-1 2400 -1850 550 550 9q OF p5 prior to bid.Contractor shall notify engineer of any and all discrepancies between field conditions and contract drawings. 1. Slope refrigerant piping one percent in the direction of oil return.Liquid lines may be installed level. EF-2 Loren Cook GGi62 100 0.375 - 71 115/60/1 Ceiling 17 RTU-2 2400 -1850 550 Sso -9FLL F-G 5. All ductwork,piping and equipment supported from structural steel shall be coordinated with the GC.All attachments to steel bar joists, 2. Install horizontal refrigerant hot gas discharge piping with 1/2"per 10 feet downward slope away from the compressor. NOTES RTU-3 1600 -1200 400 400 08/30/2017 trusses,or joist girders,shall be at panel points.Provide beam clamps meeting MSS standards.Welding to structural members shall not be permitted.The use of C-clamps shall not be permitted. 3. Install horizontal refrigerant suction lines with 1/2"per 10 feel downward slope to the compressor,with no long traps or dead ends which 2. EF-2 is a new ceiling mounted exhaust fans that are contractor furnished and contractor installed.Units to serve resirooms.Fans EF-1 -1050 -1050 may cause oil to separate from the suction gas and return to the compressor in damaging slugs. switched on with restroom lights. 6. Mechanical equipment,ductwork,and piping shall not be supported from metal deck. 3 EF-1 s all e U 76 Its ed,with facto vents cur,hi ge ase kit, rea a dr in. EF-2(Oty 2) -200 -200 4. Provide line size liquid indicators in main liquid line leaving condenser or receiver.Install moisture-liquid indicators in liquid lines between 4. F- she be proved withex sus air grille an c ra damper. Total 250 7. Boxes shall be provided wherever ducts pass through floor,wall and roof construction. filter dryers and thermostatic expansion valves and in liquid line to receiver. 5. Install EF-1 per typical detail 3/M300. G 6. Install EF-2 per typical detail 6/M300.Install controls per typical detail 4/M300.7. Q 8. Where horizontal ducts pass through walls and vertical ducts pass through floors or roofs,seal off void between opening and duct,with 5. Provide line size strainer upstream of each automatic valve.Provide shutoff valve on each side of strainer. Total Store Pressure �9 an approved noncombustible material. Should Be Between 200 ~ I� 6. Provide permanent filter dryers in low temperature systems and systems using hermetic compressors. And 400 CFM Positive � CO 9. Furnish and install all foundations,bases and supports. � W 7. Provide replaceable cartridge filter dryers with three-way valve bypass assembly for solenoid valves,adjacent to receivers. f a � = 10. Test ductwork systems prior to concealment. O 8. Provide refrigerant charging valve connections in liquid line between receiver shutoff valve and expansion valve. l., Diffuser Schedule < � 11. Provide vibration isolation for all mechanical equipment to prevent transmission of vibration to building structure. Air Distribution Schedule J J SPECIAL NOTICE TO CONTRACTORS Li_ J 12. Valves and cleanouts shall be installed as shown on the drawings and as required by code. CFM Neck 0 n n n O 1. All contractors(general contractor and sub-contractors)bidding this project are required to visit the job site and verify the existing 0-125 6" L17 13. Provide access panels for installation in walls and ceilings,where required,to service dampers,valves,smoke detectors,and other conditions prior to submitting their bid.Contractors are to carefully review all construction documents and note any discrepancies Tag Manufacturer Model CFM Neck Size Pattern Damper Mounting Finish Type 126-2r50 8. z concealed mechanical equipment.Access panels shall be turned over to general contractor for installation. between the construction documents and the conditions observed at the job site prior to submission of any bid.The building owner 251-350 10" G N representative may be contacted for access to the job site. 351-550 12" 3: 14. All openings in firewalls due to ductwork,piping,conduit,etc.,shall be fire stopped with a product similar to 3M or approved equal. 1 Metal Aire 9000 Series Not.2 Note 2 Adjust,4-way MVD @ Duct T-bar See Notes Supply Air Supply 551-700 14" I- 2. Prior to construction contractors are responsible for verifying the location and condifion of the following: 2 Metal Aire 9000 Series 0-100 8'x8":6"0 Adjust,4-way OBD in Diff. Surface See Notes Supply Air Supply 701-850 16" 15. All air conditioning condensate drain lines from each air handling unit and rooftop unit shall be piped full size of the unit drain outlet,with B a P-trap,and piped to nearest drain.Provide a condensate pump if required,field verify. A. All points of connection to building utilities and/or systems including,but not limited to,gas,water,sewer,vent,electrical,mechanical 3 Metal Aire 4000 Series 201-500 16"x8" Adjust,4-way OBD in Diff. Duct See Notes Supply Air Supply For any run-out over 20'in length, B systems,ductwork,exhaust/outside air,security,freAife safety,data,and phone. Be next size up on this schedule. 16. All ductwork shall clear doors and windows. Determine length in field. . B. All required connections to the building structure JA Metal Aire RH 2,000 36"x24" None None Surface See Notes Return Air Grille MECHANICAL IDENTIFICATION ING C. All required building penetrations.it is recommended that the contractor x-ray all penetrations thru concrete and masonry. Metal Aire RH 1,500-2,000 30"x20" None None Surface See Notes Return Air Grille 1. Identify piping,ducts and valves above ceilings,as well as exposed to view except in finished areas.Conform toASMEA13.1. Metal Aire RH 1,400-2,000 18"x18":20"0 None MVD @ None T-bar See Notes Return Air Grille 3. Any discrepancies between the construction documents and[he conditions observed shall be brought[o[he attention,inwriting,to the2. Contractor to label appliances in an approved manner that uniquely identifies the appliance and the area it serves,when appliance is architect and/or engineer prior to proceeding with construction. Metal Aire RH 600-900 14"x14":14"0 None MVD @ None T-bar See Notes Return Air Grille remotely located from space it serves. 4. See architectural plans for contact information. Notes: INSULATION 1. See Architectural plans for painting. 2. See Diffuser Schedule this sheet. 1. Furnish and install insulation for all ductwork systems that are not within the space the duct is serving.All equipment insulation shall include a vapor barrier. 2. Ductwork insulation:1-1/2"exterior duct wrap or 1"duct liner.Minimum R-value shall be R-5,except where local jurisdiction states otherwise. TEMPERATURE CONTROLS SYSTEMS �+ _ 1. All control work to be per the mechanical equipment list.Provide all necessary transformers for low voltage control circuits.Low voltage City Note (24 V)wiring to be by this contractor.Provide all motor disconnects and contactors. CEInspectoruire a light capture and containment test. 1 2. Install all thermostats and switches where shown on plans at 54 inches A.F.F.Coordinate locations with the electrical contractor. 3. All control wire and conduit shall comply with the National Electric Code. s \\\ TESTING,ADJUSTING,AND BALANCING 1. Test and balance the environmental systems including but not limited to air distribution systems,hydronic distribution systems,and the PROJECT NUMBER: 17-420 equipment and apparatus connected thereto. DRAWN BY: 'IV 2. The Mechanical Contractor shall procure the services of an independent testing and balancing firm certified and specializing in this work. CHECKED BY: )RC 3. Air inlets and outlets shall be balanced to within 10 percent of the air quantity specified on the drawings. SHEET TITLE: A 4. At completion of Work,deliver three copies of the Test and Balance Report to the General Contractor.Report shall list all supply,return, A SPECIFICATIONS and exhaust air flows,elecrcal data,temperatures,and pressure drops.G.C.shall deliver one copy to MFA Consulting Engineers,Inc. for review and approval.One copy shall be for landlord records.One copy shall be on site for final inspection. SHEET NUMBER: M100 LEGEND HVAC KEYED NOTESO z w Nm� 1. A/C UNIT:EXISTING ROOFTOP PACKAGE GAS/ELECTRIC A/C UNIT ON FACTORY CURB PER o F j v a DO °'a q AxB DUCT WORK(WIDTHxDEPTH) DETAIL 1/M300.SEE EQUIPMENT SCHEDULE ON SHT.M100 FORADDITIONAL INFORMATION. 10 Z 0 `0 m PROVIDE DUCTWORK,PLENUMS,AND AIR DISTRIBUTION DEVICES PER PLAN.INSTALL i Q Q m�0 w LINED DUCT WORK(WIDTHxDEPTH DIMENSIONS ARE FOR I.D.) CONTROL WIRE FOR CONTROLS AS REQUIRED.ELECTRICAL CONTRACTOR TO INSTALL 17 E w o N N w CONDUIT FOR CONTROL WIRE.VERIFY AND COORDINATE CONDENSATE AND GAS PIPING m m DOto 8 SUPPLY DUCT, SECTION WITH PLUMBING CONTRACTOR.VERIFY AND COORDINATE POWER,CONTROL CONDUIT, IF 2' `' O 3 W Q w DO m J AND DISCONNECT LOCATIONS WITH ELECTRICAL CONTRACTOR.START-UP,TEST,AND EF 2 --- - / x 0 RETURN DUCT, SECTION BALANCE FOR PROPER OPERATION. 6' 6"0 1z \- _ _ i N J m i 4 3 EXHAUST DUCT, SECTION 10 11 -w a 3 2. ROOFTOP EXHAUST FAN:PROVIDE AND INSTALL NEW ROOFTOP UP-BLAST BELT DRIVE C 160 RISE OR DROP IN DIRECTION OF AIR FLOW EXHAUST FAN ON FACTORY CURB PER DETAIL 3/M300.SEE FAN SCHEDULE ON SHT.M100 - j FOR ADDITIONAL INFORMATION.VERIFY PITCH OF ROOF AND LEVEL CURB FOR PROPER II -- -- - 6 - I � FLEX. CONN. FLEXIBLE CONNECTION OPERATION.PROVIDE AND INSTALL TYPE I DUCTWORK PER PLAN.INSTALL CONTROL WIRE _ /.' D O 4 T FOR CONTROLS AS REQUIRED.ELECTRICAL CONTRACTOR TO INSTALL CONDUIT FOR 1 DUCT TRANSITION,ROUND AND RECTANGULAR CONTROL WIRE.VERIFY AND COORDINATE POWER,CONTROL CONDUIT,AND DISCONNECT "rl 3 3so D SPUTTER DAMPER LOCATIONS WITH ELECTRICAL CONTRACTOR.START-UP,TEST,AND BALANCE FOR PROPER D OPERATION. �,_-/ EXTRACTOR AT BRANCH DUCT - J - -'-J -- + 3. REFRIGERANT LINES:PROVIDE AND INSTALL NEW DX REFRIGERATION LINE-SETS FOR -:'- ;. TURNING VANES WALK-IN/FREEZER COOLER AND ICE MACHINE.LINES SHALL BE SIZED AND INSTALLED IN ,---- ----- ----- ---- ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.VERIFY - FLEXIBLE DUCT INSTALLATION OF VAPOR LINE ACCESSORIES(SHUT-OFF VALVE,ACCESS PORT,SUCTION LIE FILTER,FROSTAT)AND LIQUID LINE ACCESSORIES(SHUT-OFF VALVE,FILTER DRIER, 2 -i SINGLE LINE DUCT WORK ACCESS PORT,SOLENOID VALVE,MOISTURE AND LIQUID INDICATOR AND THERMOSTATIC T� EXPANSION VALVE).PROVIDE AND INSTALL ALL MANUFACTURER RECOMMENDED AVID AUTOMATIC VOLUME DAMPER COMPONENTS.INSULATE VAPOR LINE IN 1"THICK ELASTOMERIC INSULATION(RUBATEX ORe l--I� MVD MANUAL VOLUME DAMPER EQUIV.).SECURE REFRIGERANT LINES TO AVOID VIBRATION F--� / R2� BDD BACKDRAFT DAMPER 4. SMOKE DETECTOR:PROVIDE AND INSTALL 120V DUCT MOUNTED SMOKE DETECTOR IN THE RETURN AIR SYSTEM IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE.MD MODULATING DAMPER DETECTOR INSTALLATION SHALL COMPLYWITH UL286AANDNFPA72.INTERLOCK 350 DETECTOR TO SHUT DOWNALL AIR DISTRIBUTION EQUIPMENT IN ACCORDANCE WITHAFD AUTOMATIC FIRE DAMPER INSERT LOCAL CODE SECTION HERE UPON THE DETECTION OF SMOKE.IF THE BUILDING IS AD ACCESS DOOR ROVIDED WITH AFIRE DETECTION ORALARM SYSTEM,THE SMOKE DETECTOR SHALL BESUPERVISED AND MONITORED BY SUCH SYSTEM. AT �SD SUPPLY DIFFUSER2017 5. THERMOSTAT:PROVIDE AND INSTALL 7 DAY PROGRAMMABLE THERMOSTAT WITH REMOTE EF-1 Z -� RR RETURN REGISTER SENSOR CAPABILITY AT MANAGER'S DESK.MOUNT THERMOSTAT 48"A.F.F.COORDINATE EXACT LOCATION WITH OWNER. a, 13 - ® �Ar ER EXHAUST REGISTER 6. REMOTE SENSOR:PROVIDE AND INSTALL REMOTE SENSOR FOR THERMOSTAT IN THIS - SWR SIDE WALL SUPPLY REGISTER O 2 LOCATION. 3 rt 16 -P - ---- - - - �e LJI $ SWE SIDE WALL RETURN OR EXHAUST °1 7. DEMAND CONTROL VENTILATION:INSTALL CO2 SENSOR FOR DEMAND CONTROL - '-- LID LINEAR DIFFUSER VENTILATION: -- - 1 1 1 CAL_ A"" AND WRITTEN MATERIAL -D.L. DL DOOR LOUVER 8. SUPPLY/RETURN DUCT PLENUMS:PROVIDE AND INSTALL SUPPLY AIR AND RETURN AlR 300 300 300 CONTAINED HEREIN ARE THE PROPERTY OF THE UNGIE DESIGN CNWP,INC.THEY MAY DUCT PLENUMS L REQUIRED.LINE INTERIOR OF PLENUM WITH 1 INCH,1.5 TO 3 LB./CU.FT. ie p G NOT BE REUSED,COPIED,REUSED.OR -U.C. UC UNDER CUT DOOR MINERAL FIBER BLANKED DUCT LINER. DISCLOSED IN MY MANNER vaTHOUT WRITTEN ADTHORIZARON FROM THE ARCHITECT VAV VARIABLE AIR VOLUME 9. AIR DISTRIBUTION SYSTEM:PROVIDE AND INSTALL AIR DISTRIBUTION DUCT,DIFFUSERS, \ 22"xi 6" - C OT THERMOSTAT REGISTERS,GRILLES PER PLAN.SEE SHT.M100 FOR AIR DISTRIBUTION SCHEDULE. O PROVIDE FLEXIBLE TAIL PIECE AND MANUAL VOLUME DAMPER AT EACH DIFFUSER FOR AIR e Q DUCT SMOKE DECTECTOR BALANCE. 7 O p , ' - .,;22'X1, yS�QNAL FH ® THERMOSTAT REMOTE SENSOR 10. RESTROOM EXHAUST FAN:PROVIDE AND INSTALL CEILING MOUNTED RESTROOM EXHAUST ® CARBON DIOXIDE SENSOR FAN WITH FAN SPEED CONTROL PER DETAIL 6/M300.ELECTRICAL CONTRACTOR TO - ® g _ _ N4' m INTERLOCK FAN WITH LIGHTSWITCH PER DETAIL 4/M300 AND ELECTRICAL PLAN. 9316 " 0 11. EXHAUST DUCT:PROVIDE AND INSTALL ENVIRONMENTAL EXHAUST DUCT FOR RESTROOM EXHAUST SYSTEM.SEE DUCTWORK SPECIFICATIONS ON SHEET M100 FOR ADDITIONAL 21 DUCTWORK SPECIFICATIONS INFORMATION. -. O m 20 300 3009FLL Fi•�A 1. ALL DUCTWORK SHALL CONFORM TO THE REQUIREMENTS OF THE INSERT LOCAL CODE SECTION HERE. 12. ENVIRONMENTAL EXHAUST TERMINATION:TERMINATE RESTROOM EXHAUST AIR DUCT UP O OB/30�2017 THRU ROOF IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE TERMINATE 9 2. ALL SUPPLY AND RETURN AIR DUCTS IN UNCONDITIONED SPACES SHALL HAVE R-8 INSULATION. OUTLET A MINIMUM 3 FT.FROM PROPERTY LINES AND OPERABLE OPENINGS INTO THE BUILDING AND 10 FT.AWAY FROM MECHANICAL AIR INTAKES. 200 3. ALL CONCEALED LOW PRESSURE(<2"WG)COOLING&HEATING DUCT 20"DIA.OR LESS SHALL BE UL 181lij ®z7 1:1 ®z ez CLASS I FACTORY MADE FLEXIBLE ALUMINUM DUCT INSULATED WITH R-81NSULATION AND SHEATHED 13. EXHAUST HOOD:PROVIDE AND INSTALL TYPE I EXHAUST HOOD.INSTALL STAINLESS STEEL o WITH A VAPOR PROOF POLYETHYLENE SLEEVE. WRAPPER PANELS AT TOP PERIMETER OF HOOD TO ABOVE T-BAR CEILING.SUPPORT �o HOOD AND DUCT PER MANUFACTURER'S INSTRUCTIONS.PROVIDE AND INSTALL 3 0 Q 4. ALL ROUND FLEXIBLE SUPPLY TAIL PIECES SHALL BE UL 181 CLASS I FACTORY MADE ACOUSTICAL TRANSITION FROM HOOD CONNECTION TO TYPE I DUCT.SEE HOOD SCHEDULE ON SHEET ■ O FLEXIBLE DUCT WITH NYLON LINER AND INSULATED WITH R-8 INSULATION SHEATHED WITH A VAPOR M100 FOR ADDITIONAL REQUIREMENTS.SEE SHEET M410 FOR HOOD MANUFACTURER'S ®880 O ■ �u � � PROOF METALIZED POLYESTER SLEEVE. SHOP DRAWINGS.HOOD TO SERVE GAS FIRED PIZZA OVEN. ` � 00 5. ALL EXPOSED LOW PRESSURE(<2"WG)COOLING&HEATING 20"DIA.OR LESS SHALL BE FACTORY MADE 14. GREASE DUCT:PROVIDE TYPE I GREASE DUCT WITH CONTINUOUS LIQUID TIGHT EXTERNAL El 1:1 GALVANIZED 4-PLY SPIRAL LOCK SEAM DUCT LINED WITH R-8 INSULATION. WELDED IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE.SIZE DUCT PER PLAN. 30o F a O SEE SHEET M100 FOR DUCTWORK SPECIFICATION.DUCT SHALL BE WRAPPED WITH TWO ■ 6. ALL CONCEALED INTERIOR RECTANGULAR COOLING&HEATING DUCT SHALL BE GALVANIZED METAL LAYERS OF FIREMASTER FASTWRAP XL DUCT ENCLOSURE SYSTEM PROVIDING 2-HOUR E ❑ ❑ ❑ ❑ ®� ` ® J WRAPPED WITH R-8 INSULATION IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE. FIRE RESISTANT PROTECTION.WRAP SHALL CONSIST OF W PERIMETER AND LONGITUDINAL Li J OVERLAPS WITH ZERO CLEARANCE TO COMBUSTIBLES.DUCT WRAP SHALL COMPLY WITH 7. ALL EXPOSED INTERIOR AND EXTERIOR RECTANGULAR COOLING&HATING DUCT SHALL BE THE REQUIREMENTS OF NFPA 96 AND ICC ES EVALUATION REPORT NO.ESR-2213.DUCT 3 O L- GALVANIZED METAL LINED WITH R-8 DUCT LINER IN ACCORDANCE WITH INSERT LOCAL CODE SECTION WRAP IS UL LISTED.DUCT WRAP SHALL BE INSTALLED IN ACCORDANCE WITH THE O 3 m O O O O O O HERE. MANUFACTURER'S INSTALLATION INSTRUCTIONS.REFER TO DETAILS ON SHEET M410. ® ® ® 3 G N Z WRAP MAYBE OMITTED WHEN DUCT IS LOCATED WITHIN A 2-HR RATED ASSEMBLY.SLOPE 8. ALL ROUND ENVIRONMENTAL EXHAUST AIR DUCT AND OUTSIDE AIR DUCT SHALL BE SMOOTH ROUND GREASE DUCT AT 1/4"INCH PER FOOT TO THE HOOD OR APPROVED GREASE COLLECTION ase aze GALVINIZED PIPE INSTALLED IN ACCORDANCE WITH CHAPTER INSERT LOCAL CODE SECTION HERE. RESERVOIR IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE.WHERE HORIZONTAL DUCTS EXCEED 75 FT.SLOPE DUCT AT 1"INCH PER FT.B 9 ALL RECTANGULAR DUCTWORK STEEL(16 GA.)OR 0 043 STAINLESS R TIEEL(1 NG TYPE I HOODS SHALL BE CONSTRUCTED OF 0.054 IN CARBON 200 8 GA.)WE DED FORA LIQUID TIGHTS AL IN ACCORDANCE 15. ACCESS PANELS:PROVIDE AND INSTALL APPROVED PROTECTED ACCESS PANELS IN TYPE I O O O O O 00 O B WITH INSERT LOCAL CODE SECTION HERE. GREASE DUCT IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE AT EACH 9 16"e CHANGE IN DIRECTION OF THE DUCT. 10. DUCTWORK SHALL BE CONSTRUCTED AND SUPPORTED IN ACCORDANCE WITH THE LATEST EDITION OF200 3 200 3 200 THE HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE BY THE SHEET METAL AND AIR 16. GREASE DUCT EXHAUST TERMINATION:TERMINATE GREASE DUCT EXHAUST AIR DUCT UP + + O a CONDITIONING CONTRACTORS NATIONAL ASSOCIATION INC.(S.M.A.C.N.A.) THRU ROOF IN ACCORDANCE WITH INSERT LOCAL CODE SECTION HERE TERMINATE O O ic O OUTLET A MINIMUM 10 FT.FROM PROPERTY LINES AND OPERABLE OPENINGS INTO THE 11. NO EXPOSED FLEXIBLE DUCTS SHALL BE USED. BUILDING AND 10 FT.AWAY FROM MECHANICAL AIR INTAKES. 12. NO RETURN AIR REGISTERS SHALL BE LOCATED W-O"OF A SUPPLY AIR DIFFUSER THAT DIRECTS SUPPLY 17. FIRE SUPPRESSION SYSTEM:PROVIDE AN INSTALL ANSUL R-102 FIRE SUPPRESSION AIR IN THE DIRECTION OF THE RETURN AIR REGISTER. SYSTEM FOR TYPE I KITCHEN HOOD.SYSTEM TO INCLUDE ANSUL AUTOMAN REGULATED O g O O GREASE DUCT FIRE PROTECTION RELEASE ASSEMBLY W/WET CHEMICAL STORAGE TANK,WET CHEMICAL AGENT, DISTRIBUTION PIPING,GAS SOLENOID VALVE AND PULL STATION ASSEMBLY.LOCATE I O ALL TYPE I GREASE DUCT SHALL BE WRAPPED WITH TWO LAYERS OF FIREMASTER FASTWRAP XL DUCT AUTOMAN REGULATED RELEASE ASSEMBLY ABOVE OVEN.PROVIDE ALL MANUFACTURER ENCLOSURE SYSTEM PROVIDING 2-HOUR FIRE RESISTANT PROTECTION.WRAP SHALL CONSIST OF 3"PERIMETER RECOMMENDED COMPONENTS AND ACCESSORIES FOR A COMPLETE AND OPERABLE AND LONGITUDINAL OVERLAPS WITH ZERO CLEARANCE TO COMBUSTIBLES.DUCT WRAP SHALL COMPLY WITH THE SYSTEM.TYPE I HOOD COMES PRE-PIPED WITH ANSUL DISCHARGE NOZZLES.COORDINATE REQUIREMENTS OF NFPA 96 AND ICC-ES EVALUATION REPORT No.ES-2213.DUCT WRAP IS UL LISTED.DUCT WRAP INSTALLATION WITH ELECTRICAL AND PLUMBING CONTRACTORS.LOCATE GAS SOLENOID SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.REFER TO VALVE PER GAS PIPING PLANS.VERIFY EXACT LOCATIONS WITH OWNER.SYSTEM SHALL BE DETAILS ON SHEET M300. U.L.LISTED AND BE U.L.300 COMPLIANT. 18. FIRE SUPPRESSION PULL STATION:PROVIDE AND INSTALL ANSUL R-102 PULL STATION FOR MANUAL ACTIVATION OF HOOD FIRE SUPPRESSION SYSTEM.LOCATE IN READILY ACCESSIBLE LOCATION IN PATH OF EGRESS. AIR FLOW DIRECTION LEGEND \\\ 19. HOOD DIFFUSER:PROVIDE METAL AIR,PERFORATED FACE DIFFUSER MODEL 7550 WITH 1 HVAC Plan PATTERN CONTROLLER REMOVED.NECK SIZE PER DIFFUSER SCHEDULE ON SHEET M100. M200 Scale:1/4"=V-O" s_ 20. INTERLOCK:ELECTRICALLY INTERLOCK SUPPLY FANS OF ROOFTOP UNITS AND EXHAUST f ( ) y FAN EF-1 FOR SIMULTANEOUS OPERATION TO PROVIDE MAKE UP AIR TO HOOD HDA.WHEN IILi "��II 4 WAY THROW OVEN IS INITIALIZED SUPPLY FANS AND EXHAUST FAN SHALL INITIALIZE.COORDINATE PROJECT NUMBER: 17-420 INTERLOCK WORK WITH ELECTRICAL CONTRACTOR.SUPPLY FANS TO RUN CONTINUOUSLY 1 DURING OCCUPIED HOURS TO MAINTAIN BALANCE.HEATING COOLING SECTION SHALL DRAWN BY: JJV OPERATE BASED UPON SET POINT OF THERMOSTAT. HECKED BY: DRC FIRE SUPPRESSION NOTES MECHANICAL PLAN NOTES S U N I S 10 S T SHEET TITLE: 3 WAY THROW 1. INSPECTION:HOODS,GREASE REMOVAL DEVICES,FANS AND APPURTENANCES SHALL 1. COORDINATE ROOF PENETRATIONS WITH THE LANDLORD'S ROOFING CONTRACTOR(IF A , 1 y 1. CONTRACTOR SHALL ARRANGE AND PAY FOR THE INSTALLATION OF AN ANSUL R-102 RESTAURANT FIRE BE CLANED AND INSPECTED AT INTERVALS AS LISTED IN INSERT LOCAL CODE REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED ROOFING BY LANDLORD'S ROOFING A HVAC PLAN SUPPRESSION SYSTEM.SYSTEM SHALL BE INSTALLED BY A FACTORY AUTHORIZED INSTALLER.SYSTEM SHALL SECTION HERE AND IN INSERT LOCAL CODE SECTION HERE. CONTRACTOR. PROVIDE AUTOMATIC MANUAL DETECTION 2. GREASE FILTERS:GREASE FILTERS SHALL BE CLASS I AS REQUIRED BY THE STATE FIRE 2. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING STRUCTURE OR 2. SYSTEM TO INCLUDE REGULATED RELEASE ASSEMBLY ENCLOSURE W/REGULATED RELEASE MECHANISM AND MARSHAL AND INSERT LOCAL CODE SECTION HERE. BUILDING UTILITIES CAUSED AS RESULT OF THE CONTRACTOR'S WORK UNDER THIS IIII������IIII WET CHEMICAL STORAGE TANK,CHEMICAL AGENT,DISTRIBUTION PIPING,REMOTE MANUAL PULL STATION, CONTRACT.IT IS RECOMMENDED THAT MASONRY/CONCRETE FLOORSNVALLS BE X-RAYED �y 2 WAY THROW ELECTRICAL SWITCHES FOR AUTOMATIC EQUIPMENT AND ELECTRICAL GAS SHUT-OFF VALVE.INCLUDEALL 3. PORTABLE FIRE EXTINGUISHER:PORTABLE FIRE EXTINGUISHING EQUIPMENT SHALL BE PRIOR TO ANY PENETRATIONS. MANUFACTURER REQUIRED AND RECOMMENDED SYSTEM COMPONENTS FOR A COMPLETE OPERABLE FIRE PROVIDED AS SECONDARY PROTECTION AS REQUIRED BY INSERT LOCAL CODE SUPPRESSION SYSTEM. SECTION HERE. 3. PRIOR TO CONSTRUCTION THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING MECHANICAL EQUIPMENT THAT SERVING THIS AND NEARBY ADJACENT SPACES 3. TYPE I HOOD IS FURNISHED BY THE MANUFACTURER PRE-PIPED FOR ANSUL R-102 SYSTEM.SEE HOOD 4. MANUAL ACTIVATION:MANUAL ACTIVATION DEVICE OF THE PRIMARY FIRE AND IS TO REMAIN.CONTRACTOR SHALL VERIFY THE PROPOSED LOCATIONS OF NEW I MANUFACTURER'S SHOP DRAWINGS ON SHEET M4.1 FOR ADDTIONAL INFORMATION.PROVIDE AND INSTALL EXTINGUISHING SYSTEM SHALL BE PROVIDED IN COMPLIANCE WITH INSERT LOCAL MECHANICAL EQUIPMENT AND DETERMINE IF ANY CONFLICTS(CLEARANCES,ETC.)EXIST SHEET NUMBER: I T�I MANUFACTURER REQUIRED AND RECOMMENDED COMPONENTS NOT FURNISHED BY MANUFACTURER. CODE SECTION HERE AND WITHIN DISTANCE AND HEIGHT AS INDICATED IN THAT INSERT BETWEEN EXISTING EQUIPMENT AND NEWLY INSTALLED EQUIPMENT.CONTRACTOR SHALL' /� 1 WAY THROW LOCAL CODE SECTION HERE. NOTIFY THE ENGINEER IF EQUIPMENT EQUIPMENT CANNOT BE SUBSTANTIALLY INSTALLED n n' J 0 O 4. SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTION AND U.L.LISTING. AND LOCATED AS INDICATED BY THESE DRAWINGS. I\Y/I INSTALLATION SHALL MEET THE REQUIREMENTS OF INSERT LOCAL CODE SECTION HERE 5. FUEL SHUT-OFF:PROVIDE FOR AUTOMATIC SHUT-OFF OF SOURCES OF FUEL AND L ELECTRIC POWER TO COOKING EQUIPMENT UPON ACTIVATION OF THE FIRE 4. REFER TO ARCHITECTURAL PLANS AND KITCHEN VENDOR DRAWINGS FOR DIMENSIONAL 5. SYSTEM SHALL BE U.L.LISTED AND U.L.300 COMPLIANT. SUPPRESSION SYSTEM AS REQUIRED BY INSERT LOCAL CODE SECTION HERE. INFORMATION. 0 z w 10 w >o Nm c1 OIL ,a 3m mvz MECHANICAL PLAN NOTES rj z Z U N�m m a s a m o 1. COORDINATE ROOF PENETRATIONS WITH THE LANDLORD'S ROOFING CONTRACTOR(IF m E w 0 N N w REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED ROOFING BY LANDLORD'S ROOFING Ow m a 3 O m m CONTRACTOR. w 3 w 0 w w X ED 3 2. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING STRUCTURE OR z IT J m LID BUILDING UTILITIES CAUSED AS RESULT OF THE CONTRACTOR'S WORK UNDER THIS ^z a 3 CONTRACT.IT IS RECOMMENDED THAT MASONRY/CONCRETE FLOORS/WALLS BE X-RAYED PRIOR TO ANY PENETRATIONS. 3. PRIOR TO CONSTRUCTION THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING MECHANICAL EQUIPMENT THAT SERVING THIS AND NEARBY ADJACENT SPACES AND IS TO D REMAIN.CONTRACTOR SHALL VERIFY THE PROPOSED LOCATIONS OF NEW MECHANICAL e D EQUIPMENT AND DETERMINE IF ANY CONFLICTS(CLEARANCES,ETC.)EXIST BETWEEN EXISTING EQUIPMENT AND NEWLY INSTALLED EQUIPMENT.CONTRACTOR SHALL NOTIFY THE ENGINEER IF EQUIPMENT EQUIPMENT CANNOT BE SUBSTANTIALLY INSTALLED AND LOCATED AS INDICATED BY THESE DRAWINGS. O 4 4. REFER TO ARCHITECTURAL PLANS AND KITCHEN VENDOR DRAWINGS FOR DIMENSIONAL INFORMATION. O O W WALK-IN COOLER WALK-IN FREEZER COMPRESSOR COMPRESSOR -------------------- MY N C HVAC KEYED NOTESO 1. A/C UNIT:EXISTING ROOFTOP PACKAGE GAS/ELECTRIC A/C UNIT ON FACTORY CURB PER EF-1 DETAIL .SEE EQUIPMENT SCHEDULE ON SHT.M100 FOR ADDITIONAL INFORMATION. 3 PROVIDEE DUCTWORK,PLENUMS,AND AIR DISTRIBUTION DEVICES PER PLAN.INSTALL ❑ i/ I °e9 CONTROL WIRE FOR CONTROLS AS REQUIRED.ELECTRICAL CONTRACTOR TO INSTALL CONDUIT FOR CONTROL WIRE.VERIFY AND COORDINATE CONDENSATE AND GAS PIPING 10 O III WITH PLUMBING CONTRACTOR.VERIFY AND COORDINATE POWER,CONTROL CONDUIT,AND DISCONNECT LOCATIONS WITH ELECTRICAL CONTRACTOR.START-UP,TEST,AND BALANCE RTU-3 FOR PROPER OPERATION. ___-_____ I ®ALL'EA"" AND VIM MATERIAL I CONTAINED HEREIN ARE THE PROPERTY 9 2. ROOFTOP EXHAUST FAN:PROVIDE AND INSTALL NEW ROOFTOP UP-BLAST BELT DRIVE �I THE IINGIE DED, GNp1P,INC. OR MAY EXHAUST FAN ON FACTORY CURB PER DETAIL 3/M300.SEE FAN SCHEDULE ON SHT.M100 FOR NOT O REUSED,COPIED,REUSED,OR j DISCLOSED IN ANY MANNER 4MTHODT WRITTEN ADDITIONAL INFORMATION.VERIFY PITCH OF ROOF AND LEVEL CURB FOR PROPER I �� AuiHORIZAnoN FROM THE ARCHITECT OPERATION.PROVIDE AND INSTALL GREASE DUCTWORK PER PLAN.INSTALL CONTROL WIRE FOR CONTROLS AS REQUIRED.ELECTRICAL CONTRACTOR TO INSTALL CONDUIT FOR C CONTROL WIRE.VERIFY AND COORDINATE POWER,CONTROL CONDUIT,AND DISCONNECT C LOCATIONS WITH ELECTRICAL CONTRACTOR.START-UP,TEST,AND BALANCE FOR PROPER OPERATION. yS�ONAL FH rt4. OISTf O'�Z 3. REFRIGERATION COMPRESSOR:INSTALL OWNER PROVIDED ROOFTOP REFRIGERATION COMPRESSOR PER MANUFACTURER'S INSTRUCTIONS.SEE ARCHITECTURAL PLANS FOR i I i/ I a 9 9316 ADDITIONAL INFORMATION.PROVIDE REFRIGERATION LINE-SETS(SEE NOTE#4.),PLATFORM, AND CONTROLS AS REQUIRED.ELECTRICAL CONTRACTOR TO INSTALL CONDUIT FOR CONTROL WIRE.VERIFY AND COORDINATE POWER,CONTROL CONDUIT,AND DISCONNECT I 10 1 RTU-1 II -- �9q�OF�OPy4r LOCATIONS WITH ELECTRICAL CONTRACTOR.START-UP,TEST,AND BALANCE FOR PROPER 1 10 I T9 Op' OPERATION. I 1 FLL F- RTU-2 I OB/30/2017 4. REFRIGERANT LINES:PROVIDE AND INSTALL NEW DX REFRIGERATION LINE-SETS FOR I I WALK-IN COOLER/FREEEZER AND ICE MACHINE.LINES SHALL BE SIZED AND INSTALLED IN IT i I1 ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.VERIFY INSTALLATION OF VAPOR LINE ACCESSORIES(SHUT-OFF VALVE,ACCESS PORT,SUCTION LIE FILTER, FROSTAT)AND LIQUID LINE ACCESSORIES(SHUT-OFF VALVE,FILTER DRIER,ACCESS PORT, SOLENOID VALVE,MOISTURE AND LIQUID INDICATOR AND THERMOSTATIC EXPANSION VALVE).PROVIDE AND INSTALL ALL MANUFACTURER RECOMMENDED COMPONENTS. 0 INSULATE VAPOR LINE IN 1"THICK ELASTOMERIC INSULATION(RUBATEX OR EQUIV.).SECURE Q O REFRIGERANT LINES TO AVOID VIBRATION. I 5. SUPPLY AIR INTERLOCK:ELECTRICALLY INTERLOCK SUPPLY FANS OF RTU'S AND EXHAUST L Do FAN EF-1 FOR SIMULTANEOUS OPERATION TO PROVIDE MAKEUP FOR HOOD HDA IN o W ACCORDANCE WITH SEC.511.3 NCMC.COORDINATE INTERLOCK WORK WITH ELECTRICAL f a CONTRACTOR. / • (D 6. ENVIRONMENTAL EXHAUST TERMINATION:TERMINATE RESTROOM EXHAUST AIR DUCT UP L J THRU ROOF IN ACCORDANCE WITH SEC.504.5 N.C.M.0 TERMINATE OUTLET A MINIMUM 3 FT. Li J FROM PROPERTY LINES AND OPERABLE OPENINGS INTO THE BUILDING AND 10 FT.AWAY n n n CDL— FROM MECHANICAL AIR INTAKES. LCC 7. GREASE DUCT EXHAUST TERMINATION:TERMINATE GREASE DUCT EXHAUST AIR DUCT UP N Z THRU ROOF IN ACCORDANCE WITH LOCAL CODE TERMINATE OUTLET A MINIMUM 10 FT.FROM PROPERTY LINES AND OPERABLE OPENINGS INTO THE BUILDING AND 10 FT.AWAY FROM MECHANICAL AIR INTAKES. LTnJ B 8. NO EXHAUST TERMINATIONS OR PLUMBING VENTS SHALL BE WITHIN THIS MINIMUM OF B 10'-0"AREA. 9. WATER HEATER INTAKES. __T_ _T_ 10. MPS :ELECTRICALLY INTERLOCK SUPPLY FANS OF ROOFTOP UNITS AND EXHAUST FAN MULTANEOUS OPERATION TO PROVIDE MAKE UP AIR TO HOOD HDA.WHEN OVEN D SUPPLY FANS AND EXHAUST FAN SHALL INITIALIZE.COORDINATE INTERLOCK ELECTRICAL CONTRACTOR.SUPPLY FANS TO RUN CONTINUOUSLY DURING OURS TO MAINTAIN BALANCE.HEATING COOLING SECTION SHALL OPERATE N SET POINT OF THERMOSTAT. E 1. HOODS,GREASE REMOVAL DEVICES,FANS AND APPURTENANCES SHALL BE CLEANED AND INSPECTED AT INTERVALS AS LISTED IN TABLE. 2. GREASE FILTERS SHALL BE CLASS I AS REQUIRED BY THE STATE FIRE MARSHAL AND LOCAL 0 _ CODE. —— 3. PORTABLE FIRE EXTINGUISHING EQUIPMENT SHALL BE PROVIDED AS SECONDARY PROTECTION AS REQUIRED BY LOCAL CODE. 4. MANUAL ACTIVATION DEVICE OF THE PRIMARY FIRE EXTINGUISHING SYSTEM SHALL BE PROVIDED IN COMPLIANCEWITH LOCAL CODEANDWITHIN DISTANCEAND HEIGHTAS 1 HVAC Roof Plan s INDICATED IN LOCAL CODE. M210 Scale:1/4"=1'-0" 5. INTERLOCK OF THE COOKING EQUIPMENT WITH ALL VENTILATION AND FIRE SUPPRESSION SYSTEMS SHOULD BE PROVIDED AS REQUIRED BY LOCAL CODE. PROJECT NUMBER: 17-420 DIAWNPlacement of roof CHECK BY: Rc CHECKED BY: DRC top units will be A inspected by City PROVIDE ROOF ACCESS TO ROOF VIA A A SHEET TITLE: staff to ensure HVAC ROOF PLAN compliance with LADDER OR ROOF HATCH IF ROOF OR PUD and PARAPET IS >16' ABOVE FINISHED GRADE. obscured from Roof top ui view of parking lot and adjacent road SHEET NUMBER: and properties. n A^1 0 UPBLAST EXHAUST FAN WITH p FACTORY CURB.FAN SHALL BE w N W NOIS UL LISTED FOR RESTAURANT a a m Inv i AC ELECTRICAL POWER& z_W Z LD �0 0 m USE AND SIZED IN TO PROVIDE 0 m W. m p Ln?u _ DISCONNECT(BY OTHERS) 115V 1 PHASE THE EXHAUST CAPACITY [B CONTROL CONDUIT& POWER SOURCE ❑ ut WIRE(CONDUIT BY FRESH AIR INTAKE OR NE ACCORDANCE FOR AW THELOCOALD m m a 3 ED m m z ELEC.CON7R.) D ECONOMIZER MECHANICAL CODE.PROVIDE 9 3 W ED w m- PACKAGED HVAC EQUIPMENT SECURE EXHAUST AND INSTALL A TOGGLE SWITCH DID- AIR CONDITIONING 2 FAN HINGED BASE TO WITH PILOT LIGHT AT HOOD z m m LID x 4 3 B FACTORY ROOF ROOFCURBAS CONDENSATE UNIT FOR ON/OFF CONTROL. J w D. CURB _ UNIT BASE RAIL REQUIRED.(MINIMUM OVERCURRENTO _ TRAP d DRAIN GAS(BY OTHERS) #8 TEK SCREW 2 FASTENERS PER COUNTER FLASHING SIDE) Z PROTECTION ROOF FELT,CANT GASKET 18 GAUGE TIE ROOF STRIP(BY OTHERS) #8 TEK SCREW DOWN RESTRAINT D ROOF BEAM71 COUNTERFLASHING FLASH AND COUNTERFLASH INTERLOCK WITH LIGHT SWITCH EE D TREATED WOOD NAILER SECURED TO CURB ROOFING ROOF CURB ON/OFF OCCUPANCY SENSOR DUCT MOUNTED S OKE so SUPPLY AND RETU N AIR PLENUM (LINED) 73 MINIMUM ED HIGH FACTORY DETECTOR IN SUP Y AIR ROOF CURB CANT STRIP SEAL ALL FABRICATED INSULATED ROOF SNSTEM SUPPLY R DUCT a JOINTS RETURN AIR DUCT CUR COMPATIBLE WITH ROOF. DISCONNECT INSULATION /-ROOFING WW.S€ O=INSTALLED BY ELECTRICAL CEILING I N En aa� CONTRACTOR. 3/8"LAG SCREW W/ HER, 2 MINIMUM EACH SIDE. 3/8"LAG SCREW W/ ♦y m WASHER,2 MINIMUM OM=INSTALLED BY MECHANICAL V SUPPLY AIR 6 b RETURN AIR 2-1/2"MIN.PENETRATION ROOF DECK EACH SIDE.2112" DIFFUSER qY ql GRILLE CONTRACTOR. TYPE DUCT MIN.PENETRATION ENCLOSED IN FIREMASTER FASTWRAP XL DUCT C T MOUNT THERMOSTAT ENCLOSURE SYSTEM FOR w 48"ABOVE F.F. FRAME OPENING WITH 2-HR RATED PROTECTION jC 4x8 BLOCKING FAN MOTOR MO s� C 6 AIR DISTRUBUTION ��c o2-� DUCTWORK E�^^ �ymm TYPICAL A/C SYSTEM N.T.S. I FACTORY CURB N.T.S. 2 ROOF EXHAUST FAN N.T.S. 3 RESTROOM EXHAUST CONTROL N.T.S. 4 EXHAUST ®ALL DRAINGS AND WRITTEN MATERIAL CONTAINED HERDN ARE THE PROPERTY OF ME LINGIE DESIGN GROUP,INC.THEY MAY NOT BE REUSED,COPIED,REUSED,OR DISCLOSED IN MY MANNER—OUT WRITTEN AUTHORMARON FROM ME ARCHITECT GALV.METAL DUCT oN C STRAP(TYP.) yS�QNAt FH MANUAL VOLUME DAMPER GREASE DUCT ROOF �4. OISTf Gii CLASS I FLEXIBLE AIR � N m DUCT UL 181 a 9316 3/8"0 THREADED N O EF CEILING ROD a ACOUSTICAL CLASS���IH-----��� B.D.D. RND,GALV,DUCT FLEXIBLE AIR DUCT \ - FN I SIZE PER PLAN 9R.9 OF GP5 UL 181 \1\ rll LL R• OB/30/2017 4"CONCENTRIC VENT(TYP.) z CONDENSATE DRAIN � 0 Q- o O GALV.METAL DUCT I Cn SQUARE TO ROUND FITTINGS(TYP.) I N11 o W 00 ADAPTER JI ANGLE SEISMIC BRACE CEILING CEILING CEILING GRILLE � f a cje� t] VENTS PROVIDED AND INSTALLED BY ■ Cj FIREMASTER HVAC CONTRACTOR < L2x2x1/8GALV. FASTWRAP XL DUCT L "� J _J STEEL SUPPORT ENCLOSURE SYSTEM Li J (2-HR RATED) WATER WATER --IL- < T-BARCEILING HEATER HEATER Li CEILING DIFFUSER OR GRILLE i=iiilTliiiiHili=iiilTl N Z =iii?_i i'!=iii?_! iii=ri i=!i i F_ TYPICAL DUCTWORK N.T.S. 5 RESTROOM EXHAUST FAN N.T.S. 6 DUCT TRAPEEZE N.T.S. 7 B MIN.WIRE SIZE OF 18 GA.AWG WIRE NOTES: SHOULD BE USED FOR ALL FIELD INSTALLED 24 VOLT WIRE 1. DETAIL FOR REFERENCE ONLY.INSTALL PER MA UFACTURIER'S MINIMUM THERMOSTAT DIMENSONS CLEARANCES AND A/C UNIT RECOMMENDATIONS AND AS PER CODE. 2. INSTALL WATER HEATERS AS CLOSE AS POSSIBLE TO CEILING GRID,MAINTAIN ALL Y1 - y1 UNIT TERMINAL STRIP MANUFACTURER'S RECOMMENDED CLEARANCES. 3. PIPING UNDERNEATH WATER HEATER MUST HAVE A CLEARANCE OF 8'-0'MINIMUM A.F.F. R R TYPICAL GAS FIRED ROOFTOP AIR CONDITIONING UNIT G G L-VOLT DO NOT PROVIDE E AN ON PIPE REDUCER FROM = -- TRANSFORMER UNITS WHICH HAVE AN BRANCH PIPE SIZE TO UNIT FLOOR UPROGRAMMAB,LE C INTERNAL TRAP.DRAIN CONNECTION SIZE,AT UNIT - CONDENSATE DISHARGE TO AN CONNECTION APPROVED PLUMBING RECEPTOR. GROUND JOINT PIPE UNION CONTACTORBRANCH PIPE.SEE PLAN FOR SIZE WATER HEATER DETAIL N.T.S. 1QGAS SHUT-OFF COCK GROUNDL'G THERMOSTAT ONLY a CONDENSATE TRAP&DRAIN BRANCH PIPE. DRAIN CONDENSATE AT A IOJECT UMBER: S 1/8"PER FT.SLOPE TO AN EE PLAN FOR SIZE DAWN By 1`11�11 APPROVED PLUMBING 2"MIN. BRANCH OFF TOP OF GAS RFIELD-SUPPLIED LOCATION 1-1/2"MIN. PIPE MAIN CHECKED BY: DISCONNECT (BY OTHERS) SHEET TITLE'. POWER WIRE& CONDUIT BY OTHERS A DETAILS THREE PHASE EQUIPMENT CURB POWER SUPPLY 6"LONG DIRT LEG FULL PIPE SUPPORT _50— (BY OTHERS) SIZE OF BRANCH PIPE SEE DETAIL PIPING ARRANGEMENT SHOWN IS SCHEMATIC.ADJUST AS REQUIRED. REFER TO GAS CONNECTION AND PIPING NOT REQUIRED ON ELECTRIC HEAT UNITS. MANUFACTURERS INSTRUCTION FOR DISCONNECT SIZE SHEET NUMBER" : A/C UNIT CONTROL N.T.S. 9 CONDENSATE/GAS CONNECTION N.T.S. 8 300 0 w >ED Non L❑ �a am mvz Sheet III Item/ Description W.O./ Rev. ❑ m❑ a 0 FP a, u OR SNEEI NDEx a GENERAL NOTES [0 a xa Q V m w 02 GENERAL&APPROMAE NOTES 08 [a9 E J >O N t7 w 03 SG-BOL-0-w5 SERIES(IIEVAMIN MEW/SECRON NEs)) OB E%HAT]ST WLIIYE REOINREYEH75 FINE EXTINGIIISIDNG SYSTEM Iq F- W❑ -N 1.Exhaust volumes,as shown on this drawing,ore determined by 1.The Hood is Factory Pre-Piped fa as Ansll R-102 an¢ 3 0 33 Z a (�WEN) a established engineering or tez and in accordance with Fire Extinguishing System. DaI.MST g1Pi Ww �' W C]3 ..m J 06 tENNILVAR MIN MT FAINT DEINL 06 the terms of the UL listing. 2 The Chemical Une Pre-Piping indudes Duct Cella they NCLUOED)�I 0 Lu W K 3 05 IENIUIYt MM CANOED FRONT D❑NL(OmI01AL) 06 2.Hood static preasum is wg t the duct takeoff collar. and Plenum Protection with Nosdn stubbed out to OUCi 1 Z GO J m C7 2 4 3 Refer to drawing. Total duct system and other external statics must be a ��nnecl'lan t ND22 I M to R 3 added to above fa determining proper exhaust fan static Pressure drop. single point. 4Nau I, PIENaw I W Static based an operation at mean sea level. 3.Deleclian Line Pre-Piping includes a Fax Link ulses 3.Duct size based an 1800 fpm. Bracket located at the Duct Collor and EMT Conduit Fix stubbed cut to a single connection Pont.One(1) BME MN Mtgai YAId''-UP AIR REOUNtEYENTS 450T Fun Unk is Provided,rite tied to the Fun pEWRAIIW MODEL NUMBER SEQUENCE 4.Make-up air 21,i be applied fa replaoernmt of IT exhausted Link Bracket The Detection Cable and other Hard— NER6 through all kitchen exhaust systems. Make-up air should be Is Not Provided GREASE (Ton) gel GRI gp delivered through l% tha a NOTE u eMwl Parts,Plans and D SG—BDL—O—WS-72—FF—CF—BT—PPA throughout the A generalruleof thumb'is t 75% Permits am Not Provided. Nc Ova I,n.hNN.M D D to 80%of tha replacemant air should be bash,cmditiand I (heated a coded)air brought into the kit hen Aron-with the renaming 20%to 25%allowed to Row into the kitchen from WDODSTONE adlocent areas FIRE DECK OVEN ANSUL PRE-PIPE STANDARD INSTALLATION HOOD TESTING, LISTG AND W$-FD-9660&11260 ( ) IN 5.Hood to be installed in accordance wKh this drawing,NFPA-96 COUPIdANCE REFERENCES: I OPTIONAL and ell other mom mpliI codes. Sncid attention most be given BRASS TRIM (OPTIONAL) to code regulations relative to demance,from aurraundmg The exhaust hood eet ell equir--is of I buatible and Imhited combustible con}rvcllan(w Its,telling,eta). the latest edition of NFPA-96. CURVED FRONT(OPTIONAL) 6.NI duMwork beyond the hood duct take-off collar la be I 'S5 E PI and installed by others,in accordance with applicable NATIONAL SANITATION FOUNDATION i ,w c8 n 6a1 codes. Exhaust ducts must be grease and water tight with conlinuaus The exhaust hand's NSF listed under vl�e, E FLAT FRONT(STANDARD) Do Li O temal welds. me exhaust duct mast be aontinuoudy welded Standard h1 2- Food Service Equipment 1 I e a V to the hood duct calla. IINDERIPRITERS LAHORATORTE4-ING j�.i/ LENGTH OF HOOD IN INCHES CONSTRUCTION The exhaust hood has been tested under 7.Hoods are an factured In strict accordance elth aapp Ificatlone. tandard U.L.710'Exhaust Honda for I WOOD STONE &Honda constructed of 18 Ga.stainless algid.Type 4.T0, Commercial Cooking Equipment.It la U.L I No.4 finish unless otherwise noted an drawmge, listetl antler fie number MH13522. I bC0 STYLE-CANOPY FOR OVEN INTmEeI RNexAnTauuat hood!meet. ANICAL CODE I II[ )1� all roqukemant 9.Fi tere are Stainless Sted U.L dassified and meet NFPA-96 requirement. of the Intamalim al Mechanical Code C SERIES PREFIX O N. ELEVATION VEE SECTION VIEW �• O_aA =o§Mo 10111 JA 2/13/10 IDD YOGBB FD-91i8q-11�,-11 BP 0e 6-11-01 06 CIA 3 0 ND FD-91i6q FD-11260,.ND Fblt 6-11-U 6-11-01 m x n/9/Ge NO CHANCE MODEL SG-BDL-O-WS SERIES EXHAUST HOOD per �S t o n e,n e NONE ge J n s NO CHANGE MODEL SG-BDL-O-WS SERIES EXHAUST HOOD �S t O n el a E NONE MODEL SG-BDL-O-WS SERIES EXHAUST HOOD AN �S t O n el D a a JA lo-N-a No awNf FOR FlRE DECK OVEN MODELS WS-FD-9690 MN M a JA lo-n-ro aAx¢To 4N sh FOR FlRE DECK OVEN MODEL VS-FD-9690 _ FOR FlRE DECK OVEN MODEL WS-FD-9690 M �e�1•-rc OJ AN 10-zia WDIh1E NOIX,FDIT M6JL PRI:-BPE a x® -��-B N AH Io-2Fa EMT OL1FR N01[ADO F.P.NOff rq.n a w® xano.:ll-12a6i1-B 08 A4 3 0 ND SIT f0 M.-11 -12a60-B 19 FD-9660,FD-11260,AND FD-11290 � ', FD-9660,FD-11260,AND FD-11290 3 No o-Bz90 FD-9660,FD-11260,AND FD-11290 ean^°' °®° N. ; 'a`:"a xO.:Ofi xo:02 x'erax:06 xo:03.1 x'�o.:06 ®ALL"A""AND WRITTEN MATERIAL CONTAINED HERON ARE THE PROPERTY OF ME UNGIE DESIGN GROUP,INC.THEY MAY NOT BE PEASED,COPIED,REUSED,OR DISCLOSED IN MY MANNER MMOUT WRITTEN AUTHORIZATION FROM ME ARCHITECT F1N.WST WLT (xm NCLWFD)11 I 11 I C I Irl NENN vlr i WOODSTONE I; FIRE DECK AL D¢aknnM Ir file eels uN NLwar WS-FD-96 0&1111P0 0 S�GIN �e (DP) °W" IMr•=aP i FD-11260 i Fo-ssso FlNEW OD�NE i OVEN a Q(9y3•A16 9 MIa BANr< t ,,K Iwuxnxc rLAxIE j WS-FD-9660&11260 N� O FlREOODST OVEN I i i mD,ly D. i 9�9FLL P.GPy WS-FD-9690&11290 FBINIsr gggT aBx laxel' NET 08/30/2017 I I �:YxYP CHINK MA. RAE us, NETS NNptlGL i J --- ` l�aPi r AND 1W Mrs. e O O FAa BM ANI AM I P,r afll (n I'7 o I MM HS-MNIIFD _ ______`____________ _ E �� TT I❑ � SAM NOTES I iW _ - � o LLJ P,r NUIE �aMlm FnaR F a C f11 I I 1E _ I (OP110NM) CD ■ O I PLAN VIEW t0P1gXW—T PLAN VIEW L its LL J ELEVATION VIEW SECTION VIEW n n n C ) Lam_ to N Z 1L.1 F. 2/13/10 i-m-%60,Eo-N260,ANl Fo-N W 6-11-01 M JA 2/h3/10.NO Ng5li0,N,h260.ANO N,h BP 6-n-01 BP II 1_01 os LJI n/ha/OB REwsm ro hr RUEAS MODEL SG-BDL-O-WS SERIES EXHAUST HOOD per �S t o n el osh/4._I,_o, 0 bN 11/191 No cNANBE MODEL SG-BDL-O-WS SERIES EXHAUST HOOD _ �S t o n el a"�/4._I,_o. MODEL SG-BDL-O-WS SERIES EXHAUST HOOD NN �S t o n el FOR FIRE DECK OVEN MODEL WS-FD-9690 FOR FIRE DECK OVEN MODEL WS-FD-9690 a,Ma wN�x FOR FIRE DECK OVEN MODEL WS-FD-9690 °Etl e:ahZ alma TZ n. V. wo:Y-t2a4e-B x.�n re rh. wu: N2a4e-B hwh w e..r n µ n. m coo.: -N2ae-B g FD-9660,FD-11260,AND FD-11290 F „e sect FD-9660,FD-11260,AND FD-11290 e++^^•vox aeNe �m E „tl sc�T m JA zA3Ao Ana sect FD-NM0.-nz5q-n2Be FD-9660,FD-11260,AND FD-11290 �°^•r"°1N° s¢T ocamennowxw 03 x�o.:06 b rho.:p4 xpi 06 rw hn.:Da.t x�o:08 B FP W&T IEMRT IEtbPSµea NpPRT --- o w w w 0 0 o a r1 x�w o r r r -- MU55 mN n,Ls TIY PROJECT NUMBER: 17]121 STANDARD FLAT FRONT STANDARD FLAT ADD SUFFl%_IF 1E THE A00 SUFFIX -FF-Bi AT THE OPTIONAL CURVED FRONT OPTIONAL CURVED FRONT WITH BRASS TRIM DRAWN BY:MODEL NUMBER. MODEL NUMBER. ADD SUFFIX-CF TO THE ADD SUFFIX-CT-BT TO THECHECKED BY: REFER TO THE INDEX SHEET. REFER TO THE INDEX SHEET. MODEL NUMBER. MODEL NUMBER. REFER TO THE INDEX SHEET. REFER TO THE INDEX SHEET. SHEET TITLE'. A A DETAILS we a JA 2A3A0 ADD iD-9860,FD-11250,AND N-II BP rt:fi-Il-m ce JA zA3/10/1D FD-SBBO,N-11250,NO Ntl F 6-hh-U os IAt D/le/m No aIANGE MODEL SG-BDL-O-WS SERIES EXHAUST HOOD PN �$t O n el aa+e. os I,N Bh9/De No aIANC£ MODEL SG-BDL-O-WS SERIES EXHAUST HOOD NN �$t O n el eche. a AA lo-N-a No awNE FOR FIRE DECK OVEN MODEL WS-FD-9690 _ NONE a aA lo-0-a xo a1u+cE FOR FIRE DECK OVEN MODEL WS-FD-9690 NONE a AH lo-aa xo alu+re 'e„yw,,,,a,w„ -1za"-B a AN lo-z9-a xo afeel 'e°N,.ew„„a -lzase-B FD-9660,FD-11260,AND FD-11290 w i 'ass sN 05 0..E FD-9660,FD-11260,AND FD-11290 .� ^a wa":os w�a os SHEET NUMBER: M400 z w N >❑ m K Thermal Ceramics FastWrap®XL v a m z LOmmercial Nitchen Grease Duct EDOIOSufe System 6.Store or 3 sitles d the tlud as d.-idad in one of Ill.immulatiw he hollow steel tubes to seal the..IN cover ® ® 0 DO N❑ al O N..,ago against i Z Z L3 r0 N Air Ventilation Duct Enclosure System CO Insulating Our World Y FastWrap XL mull be mores I. d Gibed. Ouse environment the I.described in so he cou,r a with ost lading edga d Flale m me eted FireMaster FastWrap XL a to a p3 aD w F/Rfi{/AC/fA on pallets.Pallets sM1oule not be stacked. the blanket anached b the mncrele°r CMU assembly one 2)Field InauleteU DuciMete Aece&&Doare(FlBule 3)- ran seeta, ere �,Sw,�,�rtmm'vim IJ E J >O N m w Men d round the duct..It the she,and can be DudMab Ulthem snit F2 do,,are a d for use with n mr` Grease and HVAC Duct Enclosure System w 7.m.tauattn wrappa a pvrome Nrwrc m F- ❑ rn Protlud Data d Inatellailon Goal u`Vii FastWrap XL shall be installed by a qualifies bly,11-dror in attached to the other concrete or CMU assem thus eh.W- FastWrap XL.and shall be installed according to DWMate I in.Is wee van 1 or 2 Hour Shaft Alternative/Zero Clearance to Combustibles ch a 3❑ In z 1 I�y� acwmanca with manubdurer's Insirudions and design let- cuts IT the tlud with Insulation arountl all accessible sides. Indamies installation Instructions. A lfi gaga(1.4mm) (a mm.I'syc zr:nl W 3 ..m 1.PYOeud Oeedipnon �L L� � ingo.Sea figures 1 to 5 for complete details. Tne blanket is to range out onto the concrete or CMU awe,- outer Inver plate is required.which is 6'1152mm)verger in x(a11.21sIi.re tau i„a,ale 3 ❑W w buy. It shall be secured to the P ining assembly wire min width and ten M1 11m,the U N ate door,ane which M1as necaxw,m d 2(m).2ta11.reNliesaic Ij Ip J ED J 0O Q 3 FlraMealerM FeefWrep XL is a ilexiple Dlenkat composed of NMeHels and EOu'omeni "nil il.mam sal flax sae 2(5U.2 1'wta)n.agk z N m LD Z 3 Hill 1 Moore clasellled I.,application.t0 2192'F _ 3118"(5mm)drrnall,d•(ld2mm)long concrete anchors,hoot- holes Milletl to match iM1e Mr`.=roc on the DudMate 4 3 g emperdture pp .- •FastWrap XL blanket ed to a minimum 1-12"(38mm)old.x 3116"(5mm)thick steel door. Four 12 wHt as Is W R ( ) y encepauleted in°durable glass IIOer rate �'-- •Aluminum loll tape gage(3mm)tee latn0e pins are wdtletl to 1rced f and lull 1 XL I loll.nosh for and LC..l and Installation,PoBIWrap •Olass filament reinhorcetl tape(bpibnaq MripJMtap with-The holes spaced l maximum 10" 1, outer cover plate,and three layers of FBS 8,Y)%L ere 2)HVAC un,So Trapeze support hangers shall be spaced On (25ire Pon center.The steel strip h m be placed around the Impeded antl he hNfl bong minimum 1-1It,(them)ctMa- maximum 60 in.d with rame remora.Harger roes or straps XL Is UL r file lied and ULC nuetl dmotions deduced for 1 �, •Carbon steel N s sinless steal 5'(0ing material,_Sr_ entire Perimeter t the dud In the exposure a Tha door clips.The Insulation layer and each to the DudMate shall be..chorea with steel drop In or wedge axpagloo 8 tl2n0ut lien N,hNNSIStiW antl03 I promotion,feuwe eland a tom(13mm)witle.lminimum 0.015'(0.4mm)thick,witM1sleal FastWrapXL insulation wrapilseared to 0-Ina duct(270hetn mini- Booris cut to o-lthef1-11 the door and in toylayer typem nary anchors. NO edemeeti protection is ••1\\\ ce for kitchen exhaust duct.,electrical circuit protectlon,and Deneing clipx e9O \\\ °mp...ni In various UL WIN,designs for fire resist. •Hand bantling tensi0ner and crimping tool mum The and, of the steel Denning p I to'ad ,,)den- he,,,an overlap tt e fir.(38mm)Duet in.ed)acent Myer.a tea..o for hangere and suppods meeting the require- \\\\ traled floors,ceilings,end wells. The core fibers in •Minimum 12 M.N. enet steel insulation tars.The ones d Ma bentllnB era to bop Into antl eroune the is asoantal that the first and..contl layer fit 11BMIy e9elnM malls d the Table below. ae a ga( pins;steal speetl steel strips/Mraps that bot Ma blanket to Me concrete floor or the surrountline wrap with no through openings.All edges 1 ••\�\\ 1 FeetWrop XL ere menulanured using TNBrmal Ceramics t•a� clips,minimum l-12"(3hmm)square or l-1/2"(38mm)dam- g u ep¢a Smlwnl>eeulvwnr "\\ � D wall,and lightened gown. 01 insulMlYn blanked halt be..led with minimum 3" rknwn ponnhol SuperwooNs fiber wnten is an elkalina-°anti silicele elel,or equivelem.izad cup-heed pins; D.Maehenieel AtleehmaM Mrhotle br Ineulellon WreO ()5mm)wive aluminum fill tope.Tine Iroularod cover plate °'r f'Oii 4iY0n Mlmry Yre arronser,n lrou '\\\\\\ wool with low bi0per.I.iBncO ane Ineralore Incrae..e solely for _ y_s� •..Pacil°r tlischat,..'it gun s inslalletl over the Duolm°le thnuumd,did,and held tight in3tallars. Fa XL Is under U A Follow-Up Service _ D� •FireMaster F2-HT-XL3 Prefebrlcatee Door or Fleld Fabricated 1)Ears ilq(Figure 1)-Minimum 1/2"(Item)witle c°Non B \ FOPS-t0 ensure the°onslstenl quality essential to this life. DOD,Hold- steel Or stainless Novel bantling,0.015"D0.4ri thick,is 3 FBreilN Cher dFederh Both t.and SD Door, Fi 9 - "�'e l�vvremm) IN 90'8I 3 el a e' •An approved fires op NNINM plaeetl arountl ins emlro pedmebr d Me lnflubroe�an o ) Y I Sure 1 l4mte mm3 ilw.mnma llso lxlaer.U ael.stetsre"pa Porn nonce Specifications axirnurn l0--(270mm)..lets aedl-1oT'(38mm)from FireMaster doors or.tested per ASTM E23S6 and ere rein tlOmm)Iheeaearm tM treat txraNa udNaate(Nenpe PIOeMCt F.Mufm analoo.-ad.. Stan No. Melarnomw � earn bleek.t aege or 112"(35mm)imm each caller edge intended for um in two layer inmelletlOns. FireMaster lei"flea mmlamaeaa,m ten lNlfll ttsn vxtsn.ddl e,ge •Zero clearance combustibles el any locetian To minimise waste,FastWrap%L blanket shoultl bit rollae ous when using ire burl joint and collar method.When ban ding. cress tloors wee complete and ready br InstallMlon with a,ml'n,rka roe sl2 nspao3 slasl.slwl.se llm Sure •Thin ane Ughl"'gnt et 1-112"(38mm)tnlek.6 psi(98 kg/m") rosyebm As Molly bdore measuring. Cm etlgas d the blanRat shell bit filemem tape ten be dead to tempororlly hold the blanket In a DuciMete®F2 ewer tloor,cut-out template,en oubitla ae tlensiry E23� tepee with aluminum fell tape to prevent exposed eegea Of the lace until the banding M lied.The bendin laced vet plate with proper aigni an 11 tested MISOPY p XL / _ •Contours easil lax dun tlesi Gon la1- nsulation absorbin tl oisiu n Me event d e p g flap g Is p r 8.Maintenance earl Repair - -- y to comp Bns 1M Ef 38 g gum..en m re around the blankel and ti Maned to fi hold the nsulation package,antl Installation Insirudions. 18 IBM 5 on-CpnpoSorry c d dun t Overle ee to block q rely No maintenance is required when installed i.acwrtl°Me with y" •Optimized Installation won Ina109 layer bun jaunts on Breese Berl R ref ompromise grease join. are us FastWrap XL in pace against the dull,but not cease arty F.Through Paromme 1.Mmetop System(Figure 2)-When Thermal Ceramic°insalldion imtrudi-.It damage is lima- ° 5 E d° tlud enclosures per ABTM E 2336 0 re ea eqa heat trensfaBeisn erne event of tlue s sct Por etion resulting ferolm cutting or tlamage to In.blanket. ire duct fire rated as..nib tl fire etl to the toil fact. aluminum fail i -Fully foil encapsulated for fast and clean I,billedi III n Iharmal a.p .Filament tap gg Med to tamp° ly p Pinning Fi 0 It the how.in F" 4 re penetrates a ty an approve g, ape can be used to repair f N E •Com IMOI rebilM Tact hold the blanket lace until s eel bending ) g I aura 1- pin pattern s gore Mop system must be employed.Figure 2 m-id-atom- iha mil facing. Ii an area d blanket is bond to be do-,. _ p yin." is and nOn-wmbuslibb CS1B n p i g or pinning is used on ell races IN the dun,Men 12 Gage(0.4mm)in au- b lid d UL/ULC tireslo designmin nicM1 Inn be Ina f011owin tlure must be inIn te0.It iM1e damaged •COntalne 2192"F(1200"C)rated fibers to,added Safely TM E23]B ins tied to permaeroly secure the blanket. leti°n pins may bit used In lieu d dnl bantling.To prevent NI'di in the Ced'rfiwtions Direne I g°Isom for US is tar.p hen S"-him S"203mm he entire wrap \ //\�\v No Nun t8.5 Flre Ergupmanl As Pre A.Fist Lai Single I I-miletioh blanket Ni Ge UOAIN de instailetl es shown In ry ei www.0 �,r i ( )x ( )i ASTM E91NE119 Par 9� 9° )p systems and www.ulc.ca for Canadian systems. Prior t ..dime m be removed and mpl.owl according to Thermal 1 Fw•.L�'/ •Will veriely of through panelrelloe fII systems 1 11 Bun JOiM lol ASTM U336 compliant greeae dui Figure 4 are required in eddition to banding on the boom installing any f ostop aym.m the su,m-of all opening, Ceramics inamilalion immudiws. n Me damaged a •fleelaMnt lO moldrpsor LC Greece OUG irl Pndwal Per ehoomm(Figure l)-TM1efirstlayerd FastWrap XL is cus of horix°mal duct.where the boom dimensim,is larger and penetrating Gems must be clean and tlry.The FastWrap ,.It Des,than 8"C,thum)x8-(203mm)f,the damaged arm•Good sound absorption UL lom 11 completely wrap around the panne-r of the tlue with than 24'(610nnui or on one side of medical ducts wlrere XL core blanket(or rn oral wool where e11I by the mud be cut away and repbcetl with a new sedign 1"(25mm) gW JokW/IMhp Opbnll eun.bim a coney Opaon 3"rid)Owilap l3•(Is)ovwp Do I ISO- enough exw..to provitle a light bust pi where the blan- a dimensbn is larger than 24"(B10mm). Pins that fireshp design lidin 1ed be Sum ed Into the annular la length and width than the cut out are,Such that the C Grease OUG Cleerenga sat sees meet.The joints of adj..nt blankms are firmty antl b d the outer blanket la hall be turned i.. 9)mu press larger iP gl Repulretl br ULC Green Duct 6ystena •1 and 2 ium, encl08ulB and 11lesl0p system IOf kitchen SuMce wins". nlrp Chanclenabq °y°" y°f a spat°.Tha packing material must be recessed a minimum new se ten can be wmectim. lightly IMO the cut Out area. 1W0LAYER INSTALLATION OPTIONS exneuat tlpde Pam Olteeagai,q each toner. orihehxcess plus length cut onto prevent shed edges. depth from the sudaceMMec°nods or gypsum assembly. All cut edges If the new canton must be tapatl are amletl wlh `VIVN •Zero clearance fmm enclosure to combustibles for kitchen flame BPeatl(bll/blerika11 ASTM E. Se 2)Overlaps requiretl lOr ISO 6941 complieM single IeYe! Shoot through pins(cup need pins)may be used in Inn- Tha races-opening must be filled with a minimum thick- aluminum mil nip°.The now sedio^must be hold in place with C_ Smoke DSUGagd ilonbinkdl ASTM EBI tOm -nation tlud enclosure and two layer greeea duet pric m,with steal bending to prevent blanket sag. nesa d an a p flea pat g me pinning Or g per exnaun dune air pproved findO lent.The kin lariat N- Innis banal. Thermal Ceramics ImmilMlo •1 and 2 hour en,l,,u,,and flhum rem for hezaenou3 Therm.)NoM.nc. ;.I.S.rm inealled in Canada(Figure 1)-I layer d E.Fieltl FebNceted Awm6 Doon type ane wmproflfli0n,minimum races II t/d" inMfuGione. C p P°Y° A9TM C51a 7.3 per layer FesiWre XLe fled tllrenl to the Oun recut to tom fete- .(typicay 'emust ducts,pressurizallon duns,ddhm tlry°,exhaust rR-value til lM P PP Y P 1)Fieltl FabHwbtl Accma Doors(Figure 3) Each access (6rnm)),and appioned Rest,sealant and thickness(typi- (�-� OI_N c 3'�•'E ducts,trash and linen charm,end other Mrs,ratite HVAC MOM Ornwn ty wrap arountl the parlmder d the tlud wkh enough tloor esxmbly M1as bur Mraeeetl mtl.rod inch(emm)in tally 1/4"(BmmH snarl be as specified in an approved UL/ 9.Limibtione \ ASTM 0032R RaaWM Suss to overt. Itself I 1e tluc18 I75T AST numratryl ax p by e m n mum o (TSmml.Tha diam.or and 5"(127mm)in length,with ono welled to ULC IireMop tlesign listing. WM1en(here is not.unicient Thermal Ceremica FaatWrep%L shell be Installed In •1 hour clenull Inl 101nia Of eejacenl blonkata must overlap each Older bye dance with these InaMlletlon Instructions. Tne Integrity of Njfiry prolectlOn for cable treys and steel minimum 3"75mm. each wrnerot the door alled ute Hollow heeltubes,owe,plot, nnular space eroune the duct to the FaatWrep XL Fm1Wm XLsstems is limited h the Ill fthe Installation. L ® a L fee wntluits S.Listings/BuiMing Code Reports ( ) (114mm)lone era Installed ousalea ire awes.rover puree enclosure ayMem wntinuoua through ins Ilre trait maem- P Y qua y o •Im Imuh.eW.U.n.nit Mstatl It nNns for ill° tecllon a.Sewntl Layer Where Required-(Figure 1) and over the threaded rods.Four 12 3mm)ere 4- bl,the enclood, terminate above end below the Far rvenel o-nenae eaaemr,"ur,emeee.wh Now TNwap w1rr31wm too-desm3 dwWimnwry Opur B Y Pro gaga( Y mat, e' If structural steel Deems antl wlumns,and MoreBe vessels Lhba Uwe Apanty Loanp Tna socon0 layer d FastWrap XL is cut m wmplMely wrap 112"(114mm)long Mae Inoulat-pine aro welded to Me 11--clung assembly Or on either side of a well assembly es " ASTM Ell9.ISO 8S4,and UL1709 ....nd Me perimeter of the first layer,with enough.xces.h SNGLE LAYER OR OUTSIDE LAYER INSTALLATION OPTIONS pen Greve nod Endmuregr ASTM UL G18 g Inver plate to allow for I,of F tiOn dine inroe ley- anew.in Fig.,2.When this red o Ifl then the FastWrap w ver,S Ii..M a less then 3"(75mm).Saints in the.acne Q336 ere ACt01 ° rs olSFaslWrap XL.One layer of FastWrap%L is cut to %L moat be mecnenically attached on either Glee Of ins fire "'°�"ai"iarea wTM'es 3.Physical OharoieHstlOe ICC F.4,1 Idyl,snouts 1, t.Adj,eda minimumd he Nhom)from trims approximately the some si As Ina ad ss panel,and rated assembly using o no of the attachment methods •'mien lean"a a,.eMneaw es a,euamea,neuac °"too,pL�� J. F.4.>] on the inner lsyar.Atljacent blankets on the sawntl letter mull impaled I-the i-Nion pin.on the panel.A..cane do,,bad in Such-D.spaced.maximum of l-12"(%ern) O�iva.a.e.a."na°.aea..«una.". LEGGEND Product Una SM crease oualullmwM�i°" 2 -dep each her by not lens than 3"(75mm).As an aibrne- layer rdlni,d FastWrap XL is cut so as to overlap the Dist Myers from ins fire rated assembly. ®ALL OAAMNGS AND Vim MATERIAL *�l Greau ouG imuiation(2003IMC) OPL TC411 t200t1 live to overlaps on atllaceni blankets installed on iM1e..wntl 1 Too LayemdFueMrlar FaMwrap XL NweelbOra�Dad Enamor CONTAINED HERON ARE THE PROPERTY OFll ttl2'x24'xT5 um of l-12•(38mm).It is essemial that the fired antlThmuph Pemeri FiSbp UL layer,atljecemblenkets can be tightly buttl.intetl antlwreppetl 1 taligMtyagainsithe surrounding wrap w6M1no G.SuPpoG Hanger Syslema On dFkeMeeMrFadWro%LMenlmlfarNrVpMdm Gap Emba�r ME UNGIE DESIGN CNWP,INC.THEY MAY gee Fl9ure2 td2 et,,4.UL1479 with a F(152mm)wide FastWrap%L collar centeretl over Me through openings.Tne iniM and outside layer should be 11 Graeae ducts:Trapeze supPod hangers shell be spacetl 2 BbM bend minimm 12 13 rdde 0.015' .4 Mir*. NOT BE REUSED,COPIED,REUSED,OR Dun joint. tO on maximum SU in.(1500 ram)centers. Hanger mde or 3 butl 0Yew tL Career DC ulreeS DISCLOSED IN MY MANNER uUNOUT WRITTEN tt/YxB•x25' HN fi Overlap the...it Insulation toyer by a minimum Of sl nail be..-wit.Meal dro d 4 Mn.T m 'nwrrrur Dmr^a^ad'®aLN"Fe1^"wrbBe Al1iHORIZAIION FROM THE ARCHIIECi w Duct Encbaure SM. wV12 C.2 S 3&tied Wrap lnetellotbn(Figure 5) 112'Ntub . Minimum l-VT Beene)round Or sgWre ,°pas pin orwe ge expen- 5 0 CFYeMeWrF %L muttCob ISO ee4 l9 1 2. on type maaomry anchors. No eddituni protection is 4-te05 When space does not allow ere wmplete wrap applied biM1e nsulation slips are indalledwihe insulation posh secure required for has and Ns dre tin the require- 1 -ebe Md aeemMhae[SeWdr Wnst„ lFa 5,h,1 tlud on all bur Sides,the FSAWrap XL is approved for 2 or 3 the three layers d insulation to the across cover pleb.All gars suppo a g i -magm.Mon Mreran aq tlebtlwMBe Yen C uL sided indalho...with mechanical emclumnl to a r.t.d Inn- cut edges d the insulation shall be taped wall minimum 3' meets d the Table below. Elad-Cllcua Inslows Symem ULC FNIi.S 2 crate or CMUassembly.The FeMWrap XL is i ratirt-on the2 (75mm)witle aluminum loll tape.Wing nuts and washers '�*'^^°r'r^•""a°u^u's'ae.'°i"'n` are nN.ued oe m.hour Mreatlaa rude,sae tightened Flmml. ys�p{NAL F o s le�i�y��ryC,�Zm ¢ Q'� m o_ 9316 ❑'] N� • FireMastelrFastWI FireMaste®FastWrap XL FireMaster FastWrap XL FireMasteIFastWrap®XL OF Commercial Commercial Kitchen Grease Duct Enclosure System Access Door Systems TYPICAL INSULATION PIN LAYOUT Commercial Kitchen Grease Duct Enclosure System 9F�L A•° Air Ventilation Duct Enclosure System Commercial Kitchen Grease Duct Enclosure System FOR DUCT SPANS> 24"(610)WIDE Air Ventilation Duct Enclosure System 08/30/2017 Through Penetration Firestop Systems To Prevent Blanket Sag 1 Or 2 Hour Shaft Alternative/Zero Clearance to Combustibles a-o.) 2 and 3 Sided Wrap Detail for Attaching to Walls and/or Ceilings 5 1 2 3 FireMaster F2-HT-XL3 Roof System NOTE SIDE ELEVATION END ELEVATION Fi 4 ow,Dotab iron 1-1anul Cammio _ / 1 2 2 F-L+/ gMeeler Dibrlm. I ��� Note 5 >• 1 >• `' a \ LaDeT�ulred " S Cn (b Accessb tr Wp S L DD Not OSQ g r Z� ® < O o 0 i 5 nit n n L1 < -- 4all ,Nicol m 3 4 O Li end) G N z 4 6 FrlwrximMHmm.mMSYhrw.er....n, Frywl XLmek,broth-orel.ertmrladem.e.nmy aster Field Fabricated Door System BOTTOM VIEW 7 B z 6 e 2 is Qt 7 1. B 2 N16 6 3 Label-Ran ad 'j4Frel 'A D I' Nob:Duche W mdpnbnW WNalled pr code Ferryarm »aweemm.-Imeso«iciew, "ry `r Imrl I _gl FIGURE 5 1 1 or 2 Hour Rated C-..Door telly .'"it 2 Two Byers ofFulthall FastWrap XL fcr Grease Dud ErdoMXss Firestop Design, S Oro ot FireMaster FeSlWre%L he An V.WW Dap EndBRew 3 COndebfn"' tam Par ASTM E814/UL 1479 4 3118.5 Mirdr x 2'50 a' S wide Dr SONS 17 FIGURE 3 5 1(203)nlexin um AS Gap FIGURE 2 RD] 6 Ina 1 Rated Fbdlceilin dwallassembl L-N7018 GA3-102t FRDS 7 Sbat bantli n.12.13)wtda 0.015'D.I tllidt. 2 Dud C-u.7w7 C.a-flogs FROB �.�rO°ddte 1s Fre FedvreeA®Oa. FIGURE4 B Standing,cq 3 Two Layers of Fraud-FaatWrep XL he Grew Dud Endoaures �osid � �1B ryw.d Fieselbr M.", aarArwen Lt'xwrwrn l•(25)Pwty Minimwn l2 3 Welir4asn mwP., mvaa w.n".awr wryeryaea"rrm Ore La of FireMaster F...XL for Art VenMation DUG E. tree F cos _ 4 L "-...,",✓•�.+mn•..ea.w.nweaw.ro - 4 Sled bondin m um 12'13 wideb 0.015'15 Mickel in FL7037 Wi-700a B and wq.bTtxw.e leap -- 5 Forest!....r FastWra XL mabdel µy.7i2f W.L-T145 1 s ILbentl VAWrrR xkm6-7 8 raved Imo n nelrelbnfireel lent WJ 70m b 130W ai,WM lldwe4 MDGfh6 DOOR DO NOT OBSTRUCT' FMMe9r.i S PROJECT NUMBER: 17-420 DRAWN BY: JJV CHECKED BY: DRC SHEET TITLE: A A DETAILS SHEET NUMBER: M410 LIGHT FIXTURE SCHEDULE 2 w M SYMBOL MANUFACTURER&MODEL* DESCRIPTION LAMPING v a m m v z ED N 0 M 0 m O USPENDED PENDANT WI METAL REFLECTOR SHADE-MOUNT @ [0 z G mONw -LITE#H-921603G8K01CCB/CGU-RIB/C814BK01/GU24 (1)GREENCREATIVE 9.6W 9.5A19G4DIW8271GU24 z a PAi -0'AF.F.,U.N.O.-WFLEX CORD In E ED PP2 RTCO#IEL8R-25W-PM18-BL USPENDEDPENDANIWITBGELSLEEVE-ROSCOLENEORANI (1)25WT8 0 0 0 0 0 0 HOOD TO BE INTERLOCKED WITH RTU N wa 30 mm= �� ENTEROVER POS Ow 3 W ❑w w ®pqS I-LITE#H-FGU-BK0I-AMICBB-BK011GU24 USPENDED PENDANT WI BLACK LAMP GUARD&AMBER GLASS- (11 GREENCREATIVE 9.SW 9.SA19G4DIMI8271GU24 �_, a. �., �. O TI.-SWITCH UNITS TO PROVIDE MAKE UP AIR i �J mp i43 OUNT@B'-0"A.F.F.,U.N.O-B'BLACK CORD coVERPLATE _ -z a 3 ALL MOUNTED WI FLUSH DRYWALL FEED BOXIMOUNTING PLATE- 0 • 0 0 0 • _ WHILE HOOD IS IN OPERATION w RTCO#BZG-28W-0-U-PRS-SIN-CF-BL-OR ON DIMMING-MOUNT IN HALLWAY CORNER @10'-0"A.F.F.-BLACK FRONT FRONT ancH sncH Tlan�.H evaAss PA4 owwc Dwwc owwc Dwwc ucnrs nMER WISH,ORANGE GEL LTA USPEND WI JUNO T90 PENDANT STEMS(48"MAX)-MOUNT @ 9'-0- LT, END TRAC-LITES SINGLE CIRCUIT TRACK R4BL&R8BL 012'-0'AEF,U.N.O.-SEE SHEET A300 0 UNO TRAC-LITES R60OL127KIFIBL RACK MOUNTED WITH IOW INTEGRAL LED LIGHT (1)1OW INTEGRAL LED • • • 0 0 U TLi +46"AFF <TL2 JUNO TRAC-LITES R7IBE ED MRI6 MENU BOARD TRACK LIGHTING (1)SCRAP,7.5W#SM16GA-07E0D-927-03 <TMIS JUNOTRAC-LITESR60OL127KIFIBUI40N-BLMONOPOINT ED LAMP-MOUNT @9-0"TO10'-0"A.F.F.,U.N.O. (1)10W INTEGRAL LED f 09 0h BATH FANS TO BE INTERLOCKED WITH ■ Q OUSING:ELITELED#LD61G14W-DIMTR-120 0 0 • • • LIGHTS TO RUN WHILE RESTROOM IS R AVE A 90 MIN.BATTERY BACKUP-CENTER IN 2x CEIRING THLEL KITCH N KITCH N LIGHTS KITCHEN KITCHEN OCCUPIED C U P I E D DDULE:ELITE LED#RL607-14W-0MITR-1 -MB-BK (1)14W LED INCLUDED QRi-EM SOLITE INVERTER:#IMI-12-V10R#IMI-25-V1 OUSING:LITON#LH71CA-GU24-LBL1328 'RECESSED HOUSING DOWNLIGHT,BLACK RING FINISH-INSTALL Q, 5-GANG LIGHT SWITCH COVER PLATE(TYP.) (1)CREE14WLEDLRP3&iL-27K-25D-GU24 ♦A �v 6� MODULE:LITON#LH7A-LBL151LRS40B-B ENTERED ABOVE FOOD TRAYS PROVIDE PERMANENT,TYPED LABELS AS SHOWN. o ♦V e 'x4'RECESSED FLUORESCENT TROFFER WI0.125'THICK OOPERIMETALUX#2GR8332A-UNV-EB81-U A Switchin Detail FR6 ATTERNEO ACRYLIC SHIELD.FIXTURES DESIGNATED FOR (3)F32T81835 y f ' OOPERIMETALUX#2GR&332A-UNV-EL-EB81-U MERGENCY LIGHTING SHALL HAVE 90 MIN.BATTERY BACKUP (P rt) �■/ E300 Scale:No Scale 13 -3ij 'x2'RECESSED FLUORESCENT TROFFER W10.125'THICK 00 OOPERIMETALUX#2GR&2U6T8A-UNV-EB81-U ATTERNEDACRYUCSHIELD.FIXTURES DESIGNATED FOR (2)F32T81SP351ECO 105 MERGENCY LIGHTING SHALL HAVE 90 MIN.BATTERY BACKUP 7 N URFACE MOUNT BLACK TEXTURE VAPOR JAR WI LAMP GUARDS- GENERAL NOTESMET : EMi N ®SA1 -LITE#H-FGU-FB-BK0I-RIBIGU24 (1)GREENCREATIVE 9.SW 9.SA19G4DIM18271GU24 LISTED FOR OUTDOOR USE �C ALL MOUNT SCONCE BLACK TEXTURE WI LAMP GUARDS-MOUNT T-0"AF.F„U.N.O 1. UPPER CASE LETTER DESIGNATES LUMINAIRE TYPE,LOWER CASE LETTER IISCi I-LITE -FGU-HB-BK0I-RIBIGU241101LBL (11 GREENCREATIVE 9.5W 9.5A19G4DIMIB271GU24 DESIGNATES SWITCH LEG.THREE LAMP TROFFERS WITH TWO LOWER RI R1 EXTERIOR WALL MOUNT BLACK TEXTURE SCONCE WI LAMP GUARDS • Jm ^g CASE LETTERS INDICATE SWITCHING FOR OUTER AND INNER LAMPS o ee ?� -LITE -FGU-iB-BK0I-AMIGU241101LBL (1)GREENCREATIVE 9.SW 9.SA19G4DIM18271GU24 RESPECTIVELY.TWO LAMP TROFFERS WITH TWO LOWER CASE LETTERS EEC, MOUNT @ T-0-A.F.F.,U.N.O INDICATED SWITCHING FOR INDIVIDUAL LAMPS.SINGLE LOWER CASE NTERIOR WALL MOUNT ORANGE FINISH SCONCE W125D LAMP- LETTER INDICATES SINGLE SWITCH FOR ALL LAMPS IN LUMINAIRE. _------ - I-LITE#H-922046444441 (1)SORAA SAW MR16-GU10 SM16GA-05.25D-927-03 SC3 OUNIF3"A.F.F.,U.N.O a e-28(art) f° 2. FULLY SHADED OR HALF SHADED LUMINAIRES INDICATE NIGHTLIGHT TO BE 2 2 ERIOR MOUNT SCONCE WIMETAL REFLECTOR SHADE- CIRCUITED AHEAD OF SWITCHING. R1 Ri e , I-LITE#9216036-BK01-CCBICGU-RIBIIB-1-BK01GU24I101LBL (1)GREENCREATIVE 9.SW 9.SA19G4DIM18271GU24 EF-2 EF-2 0 a 0 ®nu oenvnNcs nNg vnslnEN unrzxlnl �SC4 OUNT@7-0"A.F.F.,U.N.O �� O O 3. INSTALL 2X4 TROFFERS IN SUSPENDED CEILING PER DETAIL C SHEET E400. CONTAINED HEREIN ARE ME PROPERtt OF NTERIOR WALL MOUNT ORANGE FINISH SCONCE W125D LAMP- --- 11 ME UNCLE DEscN GROUP,INC.MEY MAY SC�� -LITE H-922048136-1-141 OUNT@6'3'A.F.F.,U.N.O (1)SORAA 5.4W MR16-GU108M16GA-OS-25D-927-03 4. REFER TO ARCHITECTURAL SET FOR ADDITIONAL INFORMATION. O DNOT I5CLOE RMSANYCMANNFR SEE,OWAlilEx NTERIOR WALL MOUNT ORANGE FINISH SCONCE W125D LAMPS- KA-3 7 - Kn-3 AUTHORrznnoN MOM THE ARCHITECT. SC6 I-LITE H-9220461SP4116-14112-LITE OUNT@6'3"A.F.F.,U.N.O (2)SORAA SAW MR16-GUIO SM16GA-0S25D-927-03 5. EXISTING EXTERIOR LIGHTS AND EMERGENCY EGRESS LIGHTING TO SC1 (part) (part) SCi 11 C EMi ITNNIT COMBO EMERGENCY LIGHT WITH 90 MIN.BATTERY REMAIN. R1-EM Ri-EM O7 C ITRONIX#VEX.U-BP-WB-WH.EL90 CKUP INCLUDED O NA ITRONIX#LL50H ORIZONTALLYONCEILING-BLACKFINISH TOBEUSED IF INSTALLED INCLUDED KA1c KA-5e"o �� 05�015 FNG�m O ROVIDED AND INSTALLED BY DMX ROVIDEDANDINSTALLED BY DMX /41(part) ---- RTCO CB5.54-U-PRS-CM96-SIN-BL-BLACK EXTERIOR CCENT LIGHTING-LENGTH,ORIENTATION,&GEL COLOR VARIES- 1 54W TS SC3 THIS EM3 b 7 a 93�6 v c LFi INISH OORDINATE WITH BLAZE CORPORATE O O SAi KA 6a 1 L O AMERICAN LIGHTING COMMERCIAL GRADE LIGHTSTRING: - O'9TF XQP 4i EXH- US MS, 24'BULB SPACING,SUSPENDED MEDIUM EXTERIOR COMMERCIAL GRADE LED LIGHT STRING,EDISON DROP AMERICAN LIGHTING PS14E26-WW 9'�9OF 0 BASE,LAMP:S14-LED-WW-PREM FLL R• U.N.O.ALL FIXTURES ARE CONTRACTOR FURNISHED,CONTRACTOR INSTALLED 4 AR 48A017 KEYED NOTES:O# VENDOR CONTACT INFORMATION VILLA LIGHTING SUPPLY,INC. 1. PROVIDE OCCUPANCY SENSOR,GREENGATE ONW-D-1 00 1-MV OR EQUAL WALL MOUNTED OCCUPANCY SENSOR. $C3 O TM15 e 5 ANNE VOELKER 2. APPROXIMATE LOCATION OF RESTROOM EXHAUST FAN TO BE PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR. 2929 CHOUTEAU 7 0 ST.LOUIS,MO 63103 COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT LOCATION AND REQUIREMENTS.FAN TO BE CIRCUITED AND (P)314833-0554(F)314-0-0537 SWITCHED WITH LIGHTS. O EM3 g,Ri I R1 9 R1 R1-EM R R1 f R1 a R1 R1 ` i� (n � 3. PROVIDE 120 WATT CURRENT LIMITER FOR TRACK LIGHTING. 7 LLJ f a � � 4. J-BOX FOR HOOD LIGHTS.HOOD LIGHT FIXTURES BY HOOD SUPPLIER,WIRED BY THE ELECTRICAL CONTRACTOR. Ri-EM R1 . O ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL 1DOW A-19 LIGHT BULBS IN FIXTURES AS REQUIRED. SC3 J J 5. HOOD LIGHTS AND SWITCH FACTORY PRE-WIRED WITH SWITCH MOUNTED ON FRONT OF HOOD WITH HOOD CONTROLS. TM15 e - ,g,h h TL2 9 R1 R1 'phi '�h� 1hi 1hi 9 Li J ELECTRICAL CONTRACTOR SHALL VERIFY WITH EQUIPMENT SUPPLIED FOR POWER REQUIREMENTS AND LOCATION OF 3 RI CONNECTION POINT. Pll 9- c11 il� O Li Z 6. PROVIDE AND INSTALL J-BOX,SWITCH AND ADDITIONAL VAPOR-PROOF LIGHT FOR FREEZER/COOLER INTERIOR LIGHTING. I R2 R2 0 R2 M R2 f R2 M R2 R2 0 R2 I R2 Q N � COMPLETE CIRCUITING AS SHOWN. 7. CIRCUIT ALL NIGHT LIGHTS AND EGRESS LUMINARIES FROM HOT LEG OF CIRCUIT OR UNSWITCHED LEG OF CIRCUIT. E B 8. SEE DETAIL C THIS SHEET FOR AUTOMATIC TIME SWITCH INTERIOR LIGHTING CONTROL.VERIFY ALL LIGHTING CONTROL SC3 TMiS a TMIS a TM78 a TM78 a TMiS TMiS TM1S B 0-2HR OVERRIDE SWITCH WITH LANDLORD AND TENANT. . PANEL"KA" LOCATE ADJACENT TO MAIN LIGHTING SWITCH BANK 9. APPROXIMATE LOCATION OF SWITCH BANK.SEE ALSO DETAIL A THIS SHEET.LOCATION SHOULD GENERALLY BE BEHIND KA-ia,b,c SEE E2.0 FOR LOCATION POS STATION WHERE LUMINAIRES BEING OPERATED CAN BE OBSERVED.VERIFY EXACT LOCATION WITH OWNER. (pan) PNL"KA" 10. EXTERIOR SIGN:PROVIDE WEATHER-PROOF HBOX AND 20A 1-POLE TOGGLE DISCONNECT FOR EXTERIOR SIGN. C COORDINATE EXACT LOCATION PRIOR TO ROUGH-IN.ROUTE CIRCUIT THRU TIMECLOCK.SEE STOREFRONT SIGNAGE PAS AND BID. DETAIL B THIS SHEET.CONCEAL CONDUIT IN WINDOW MULLION.VERIFY EXACT LOCATION PRIOR TO ROUGH-IN ppi Ai Al Al AlPAS PA3 3 5 1 TS TM1S 11. INVERTER:ISOLITE IM112V1.VERIFY EXACT LOCATION OF R1-EM INVERTER WITH TENTANT.EM LIGHTING TO BE SWITCHED IN SERVICEICOOKING/PREP AREAS AND CONSTANT ON IN RESTROOMS. LF1 e PROVIDE A 7 12. EC SHALL INSTALL"LIGHT STRING"FROM COLUMN TO COLUMN AND CONNECT TO LIGHTING CIRCUIT SHOWN.PROVIDE 3 C ;4 DAY MOUNTING TO COLUMN PER MANUFACTURERS INSTRUCTIONS AND VERIFY LOCATION PRIOR TO ROUGH IN z PROGRAMMABLE 1 UP CLOCK. i 13. EC TO VERIFY EXISTING EXTERIOR EMERGENCY LIGHT AND PROVIDE NEW AS REQUIRED.VERIFY LOCATION PRIOR TO - 1 LOCATE NEXT TO C T ROUGH-IN. Al PANEL "KA'. -- 7-DAY TIME a d PAi LTG.CONTACTOR CLOCK NEUTRAL c LOCATE IN PAi Al Al SEPARATE - INTERIOR LIGHTING LOAD ENCLOSURE ON 120 VOLT KA-7(part) T TMiSa LFie 1 s TOP OF PANEL "KA" PROJECT NUMBER: 1]42 PNL"KA" J 'Al DRAWN BY:SPARECHECKED BY: SPARE 9 SHEET TITLE: A 120 VOLT KA-41 ,J b b pqS PAS PAS a PA3 PA3 Pq3 A3 LIGHTING PLAN EXTERIOR SIGN KA31 C FM1 7 O EM1 SPARE J 1 LTG.CONTACTOR SPARE 13 10 LOCATE IN SEPARATE SHOW WINDOW LIGHTING LOAD ENCLOSURE ON SPARE ,f TOP OF PANEL SHEET NUMBER: SPARE E 1 0 0 "KA• Store Lighting Detail 1 Lighting Plan E300 Scale:No Scale � Ext Ltg&Signage Control E100 Scale:1/4"=V-0" E100 Scale:No Scale O GENERAL NOTES,POWER PLAN: 6. ALL 125 VOLT,SINGLE PHASE 15 AND 20 AMP RECEPTACLES INSTALLED IN N 1. DO NOT SCALE DRAWINGS. KITCHEN AND BAR SHALL HAVE GFI PROTECTION.USE HOSPITAL GRADE(GREEN 7 4". �' z DOT)TYPE FOR MOTOR LOADS.ALL GFI RECEPTACLES ARE TO HAVE DEDICATED rc z o z❑ m 2. EQUIPMENT,EXHAUST FANS,AND UTILITY VENTS CANNOT BE HIGHER THAN THE NEUTRALS.ALL GFI CIRCUITS THAT ARE NOT"READILY ACCESSIBLE"ARE TO USE ED a,0 Q O m a w PARAPET WALL. A GFI BREAKER SUPPLIED BY E.C..VERIFY WITH KITCHEN EQUIPMENT DRAWINGS E >d 0 m w AND SUPPLIER. m F W O 10 9 3. CONTROL CIRCUIT AND SHUNT TRIP BREAKER(S)TO FIRE CONTROL SYSTEM p w 3 W Dom? CONTROL MICRO-SWITCH SHALL BE FURNISHED AND INSTALLED BY ELECTRICIAN. 7. RECEPTACLES TO BE MOUNTED AT 24"AFF UNLESS OTHERWISE NOTED. J KB-40,42 KB-34,36 J �O G 3 GENERAL NOTES,ROOF POWER PLAN: SHUNT TRIP BREAKER(S)TO BE UNDER EXHAUST HOOD.IN CASE OF FIRE,ALL m Z LF EO x Fi 3 POWER TO EQUIPMENT UNDER HOOD OR PARTIALLY UNDER HOOD WILL BE SHUT 8. RECEPTACLES SHALL BE BLACK AT THE FRONT OF HOUSE AND WHITE AT THE -Z a 3 1. DO NOT SCALE DRAWINGS. OFF.ALL GAS EQUIPMENT LOCATED UNDER HOOD WILL ALSO BE SHUT OFF IN BACK OF HOUSE. ED © O CASE OF FIRE.MUST BE WIRED THAT IN THE EVENT OF POWER FAILURE,FIRE 2. COORDINATE ROOF PENETRATIONS WITH THE LANDLORD'S ROOFING CONTRACTOR(IF CONTROL SYSTEM WILL NOT BE ACTIVATED AND WHEN POWER IS RESTORED, 9. VERIFY ALL POWER REQUIREMENTS,RECEPTACLE TYPES,CONNECTION TYPES, REQUIRED).PROVIDE AND PAY FOR ANY REQUIRED ROOFING BY LANDLORD'S ROOFING FIRE SYSTEM WILL NOT DISCHARGE. LOCATIONS AND ELEVATIONS WITH KITCHEN EQUIPMENT DRAWINGS AND CONTRACTOR. SPECIFICATIONS AND OWNER. 4. ALL 120 VOLT OUTLETS NOT DESIGNATED WITH SPECIFIC LOADS TO BE RATED AT D 3. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING STRUCTURE OR 20.0 AMPS. 10. NO ELECTRICAL TO BE INSTALLED UNDERGROUND UNLESS NO OTHER ACCESS D BUILDING UTILITIES CAUSED SLAB PENETRATIONS.IT IS RECOMMENDED THE FLOOR BE TO EQUIPMENT IS AVAILABLE. KA-23(part) S. ELECTRICIAN TO CONNECT ALL ELECTRICAL EQUIPMENT AND FIXTURES AND DO -23(paw) X-RAYED PRIOR TO ANY FLOOR SLAB PENETRATION. ANY INTERNAL WIRING REQUIRED IN THE FIXTURES AS REQUIRED.ALL 11. E.C.TO VERIFY ALL CIRCUITS RELATED TO THIS PROJECT AND ADJUST AS 2 2 cI ELECTRICAL OUTLET COVER PLATES ARE TO BE FURNISHED BY THE REQUIRED. W ❑ 0 1 ELECTRICIAN,AS WELL AS THE RECEPTACLE,UNLESS OTHERWISE SPECIFIED IN PTcOKA-16,18,20 KEYED NOTES,ROOF POWER PLAN:O THE ITEM SPECIFICATIONS.ALL DISCONNECT SWITCHES,CORDS AND PLUGS 12. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION. 5 3 REQUIRED ARE TO BE FURNISHED AND INSTALLED BY THE ELECTRICIAN AT TIME KA-19,21 OF INSTALLATION. KA 1012 14 1. EXISTING ROOFTOP UNIT TO REMAIN.EC TO VERIFY EXISTING CONDITION AND REPLACE DEVICES AS REQUIRED FOR A COMPLETE WORKING SYSTEM v a� KA-23(Part) o E O 2. EQUIPMENT RECEPTACLE:PROVIDE WEATHERPROOF GFCI RECEPTACLE FOR WITHIN 25 FT. OF MECHANICAL EQUIPMENT. y f ' KA-4.8,8 7 1 3. A/C CONTROL CONDUIT:PROVIDE CONDUIT WITH PULL STRING FROM FOR THERMOSTAT �/ TO A/C UNIT ON ROOF FOR CONTROL WIRE.CONTROL WIRE BY OTHERS 110� 4. EXHAUST FAN EF-1:PROVIDE A WEATHERPROOF 20A 1-POLE NON-FUSED DISCONNECT SWITCH FOR ROOFTOP EXHAUST FAN. N ABOVE 5. IINTERLOCK:ELECTRICALLY INTERLOCK RTUa AND EXHAUST FAN EF-1.COORDINATE 53 C INTERLOCK WORK WITH MECHANICAL CONTRACTOR.LOCATE INTERLOCK ON/OFF 0w SWITCH NEAR HOOD HDA PER OWNER.SEE INTERLOCK DIAGRAM SHEET E400. 0 2� 6. WALK-IN COOLER/FREEZER COMPRESSOR:PROVIDE A WEATHERPROOF 20A 2-POLE KB-31,33,35 82 NON-FUSED DISCONNECT SWITCH FOR WALK-IN COOLER REMOTE COMPRESSOR UNIT. $� KL INSTALL 3/4"C,2#10,1#10GND CU THWN. o o KA-24,2fi A V aN = 7. SMOKE DETECTOR:PROVIDE 120V POWER FOR DUCT MOUNTED SMOKE DETECTOR 32 15 KAJ2,34,38 5 INSTALLED BY MECHANICAL CONTRACTOR.INTERLOCK DETECTOR TO PROVIDE FOR 20 19 0,32 AUTOMATIC SHUT-OFF OF AIR MOVING EQUIPMENT. /F a\ 48 47 Lf ®ALL DAAmNGS AND MRITIEN uAIERIAL ABOVE 22 CONTAINED HEREIN ARE THE PROPERTY OF --��Q - - 31 K O NOT BECLE RENDEDG CROUP,INC. THEY,OR MAY - 48' DISCLOSED IN ANY MANNER WITHOUT WRITTEN o L y 21 KA-W 3 22 AUTHORIZAHON FROM THE ARCHITECT. - KA-1s(part) C o 46C1 ---J GFCI 30 0 o C O _ +48 ------------------ 51ONALF B-23 2 KBA1 �k.5 O\STE N0''2 2 Roof Power Plan J GFCI pp pp E200 Scale:1/8"=V-O" GFCI 13 a v UV --- - 2 f� O 09FTF OF`Q Aye (Part) 13 B 9FLO C, KB-19 /KA-15(part) KA-15(part) 017 L -] 30 V 30 O 9g 33 J -- - KB-3 KA-22 IG4 5A_3 1 KB-17 28 7.2 26 \ / 7.1 1 T 12 10 KA-17 7 -69 2 / iE; 2 ® LG� � 00 ul 46 KA 3141 ll-ll �❑ 1 ' I� 8 � o U ll A L J 23 i J 5(part) 5.1 LKA-39 J 24 pq 25 26 n n n Q KB-20,22 KB-18,18 6 O i O D KA-15(part) 78 KB-37,39,41 O z Q N � 30 17 28 Kg_1 O KEYED NOTES,POWER PLAN:O 19. EQUIPMENT PLATFORM:GENERAL CONTRACTOR TO PROVIDE EQUIPMENT PLATFORM ABOVE WALK-IN FOR#48 AIR COMPRESSOR. O -2 KA-REFER ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.B ON 1STANDARD CONVENIENCE DUPLEX RECEPTACLE WITH TWO USB CHARGING PLUGS,COOPER ARROWHART TR7746 OR EQUAL:INSTALL1120V DUPLEX RECEPTACLE @ 18"A.F.F.U.N.O. 20. AIR COMPRESSOR:PROVIDE A 20A 3-POLE NON-FUSED DISCONNECT SWITCH FOR#48 AIR COMPRESSOR.PROVIDE 3/4"C,3#10.1#10 GND O I-_+� -_ B 2. GFCI RECEPTACLE:INSTALL GFCI 120V DUPLEX RECEPTACLE @ 18"A.F.F.U.N.O. CU THWN. I _ L--- 21. AIR COMPRESSOR DRIER:INSTALL J-BOX W/DUPLEX NEMA 5-20R GFCI RECEPTACLE FOR AIR COMPRESSOR CORD&PLUG -- 3. LAVATORY:PROVIDE W.P.J-BOX WITH 120V POWER FOR LAVATORY FAUCET SENSOR.VERIFY EXACT REQUIREMENT WITH PLUMBING DRIER/AUTODRAIN.MOUNT J-BOX ADJACENT TO COMPRESSOR.VERIFY REQUIREMENT W/VENDOR. 8 fi 20 CONTRACTOR PRIOR TO CONSTRUCTION. g 10 4.1 4.2 22. WALK-IN COOLERIFREEZER EVAPORATOR:PROVIDE AND INSTALL WEATHERPROOF 20A 1-POLE NON-FUSED DISCONNECT l�1 5 23 5.1 4. QUAD-PLEX RECEPTACLE:INSTALL NEMA QUAD-PLEX RECEPTACLE @18"A.F.F.AT POS FOR NON-POS POWER. SWITCH FOR COOLER EVAPORATOR.PROVIDE 1/2"C,2#10,1#10 GIRD. O 52 5 KA-7 KA-B 8-12 KA-37 5. CORD CONNECTION:GENERAL CONTRACTOR TO PROVIDE CORD HOLE WITH GROMMET IN COUNTERTOP FOR POWER CORD 23. PRINTER POWER/DATA:INSTALL 1201.G.DUPLEX RECEPTACLE FOR PRINTER POWER AND J-BOX WITH ONE RJ-45 CATSE FEMALE CONNECTION TO UNDER-COUNTER RECEPTACLE CONNECTOR FOR PRINTER @ 18"A.F.F.INSTALL 1/2"CONDUIT WITH ONE CATSE 24AWG SOLID COPPER CABLES(EIA/TIA 568E PAIRI=BLUE, PAI R2=ORANGE,PAIR3=GREEN,PAIR4=BROWN STRAIGHT THROUGH-NO CROSS-OVER)FROM PRINTER TO PATCH PANEL LOCATED AT 6. MAIN ROB WORKSTATION POWER:PROVIDE NEMA QUADPLEX ISOLATED GROUND RECEPTACLE FOR POS EQUIPMENT ON DEDICATED MANAGERS DESK.RECEPTACLES TO BE LOCATED ON PONY WALL OR INTERIOR WALL.NOT ON EXTERIOR OR DEMISING WALL. CIRCUIT.MOUNT RECEPTACLE @ 18"A.F.F.AND WITHIN 3 FT.OF ROB STATION.RECEPTACLE SHALL BE ORANGE AND LABELED"FOR POS 1 ❑ o ❑ ONLY".VERIFY WITH OWNER POS REQUIREMENTS PRIOR TO CONSTRUCTION. 24. DOUGH PRESS:PROVIDE 208V NEMA 6-30R RECEPTACLE AND DEDICATED 30A CIRCUIT(FOR PNEUMATIC PRESS)AND ONE 208V NEMA (part) O O O O O O O 6-15R RECEPTACLE AND DEDICATED 15A CIRCUIT(FOR MANUAL)FOR FUTURE USE/REDUNDANCY.OUTLETS MOUNTED AT 18"AFF AT 7. MAIN POS WORKSTATION DATA:PROVIDE J-BOX WITH TWO RJ45 CATSE FEMALE CONNECTORS UNDER COUNTER AT AT EACH ROB EACH DOUGH PRESS LOCATION. TERMINAL.INSTALL 3/4"CONDUIT WITH TWO CATSE 24AWG SOLID COPPER CABLES(EIA/TIA 568E PAIRI=BLUE,PAIR2=ORANGE, �880 ❑ ElPAIR3=GREEN,PAIR4=BROWN STRAIGHT THROUGH-NO CROSS-OVER)FROM ROB WORKSTATION TO PATCH PANEL LOCATED AT 25. APPROXIMATE LOCATION OF#46 WATER HEATER.PROVIDE RECEPTACLE FOR IGNITION.VERIFY LOCATION AND REQUIREMENTS WITH _ MANAGERS DESK.GENERAL CONTRACTOR TO PROVIDE ACCESS HOLE IN MILLWORK SURFACE WITH GROMMET. PLUMBING CONTRACTOR. _ KB-5 ❑ El -- 8. INTERNET:INSTALL INTERNET RECEPTACLE PER OWNERS REQUIREMENT. 26. PIZZA OVEN:PROVIDE DISCONNECTING MEANS FOR#7 PIZZA OVEN.CONNECT POWER CORD TO DISCONNECT AND TO PIZZA OVEN TERMINAL STRIPPER MANUFACTURER'S INSTRUCTION.PROVIDE FOR AUTOMATIC SHUT-OFF OF POWER UPON ACTIVATION OF KITCHEN 16 9. MANAGER'S DESK DATA:INSTALL CATSE PATCH PANEL WITH RJ-45 CATSE FEMALE CONNECTORS AT MANAGERS STATION.VERIFY PATCH HOOD FIRE SUPPRESSION SYSTEM. PANEL REQUIREMENT AND MOUNTING HEIGHT W/ROB VENDOR AND OWNER. ❑ o ❑ ❑ ❑ ❑ O 27. EXHAUST SYSTEM CONTROL&INTERLOCK:INTERLOCK RTUa WITH EXHAUST FAN EF-1 FOR SIMULTANEOUS OPERATIONS.INTERLOCK 10. MANAGER'S DESK POWER:PROVIDE ONE QUAD-PLEX ISOLATED GROUND RECEPTACLE FOR POS EQUIPMENT ON DEDICATED CIRCUIT OVEN TO ALLOW OPERATION ONLY WHEN EXHAUST FAN IS ON.COORDINATE INTERLOCK WITH MECHANICAL CONTRACTOR AND tjK. AND ONE QUAD-PLEX NEMA GFCI RECEPTACLES AT MANAGERS DESK.MOUNT RECEPTACLES 36"A.F.F.ON BACK WALL OF MANAGER'S KITCHEN EQUIPMENT SUPPLIER.ALL FANS/HOODS SHALL BE ACTIVATED BY A WALL MOUNTED TOGGLE SWITCH.VERIFY WITH OWNERDESK AREA. EXACT LOCATION. KA 911. PHONE BOARD:PROVIDE 24"X12"X3/4"PLYWOOD BOARD FOR PHONE/DATA SERVICE.SECURELY MOUNT TO WALL.PAINT TO MATCH 28. FIRE SUPPRESSION:PROVIDE J-BOX W/1-POLE TOGGLE DISCONNECT SWITCH WITH 120V POWER TO KITCHEN HOOD FIRE PROJECT NUMBER: 11-42ADJACENT SURFACE.PROVIDE 1"EMPTY CONDUIT WITH PULL-STRING FORM PHONE BOARD TO MANAGER'S DESK AND FRONT SERVICE SUPPRESSIONS SYSTEM CONTROL BOX LOCATED ON TOP OF OVEN AND ELECTRIC GAS SOLENOID VALVE/MANUAL VALVE RESET RELAY ❑ ❑ 29 DRAWN BY: LBW POS STATIONS.INCLUDE ONE DUPLEX NEMA GFCI RECEPTACLE FOR PHONE/DATA PHONE SYSTEM POWER.VERIFY MOUNTING HEIGHT LOCATED IN OVEN.PROVIDE ALL ELECTRICAL CONDUIT,WIRE AND COMPONENTS REQUIRED BY THE MANUFACTURER FORA COMPLETE WITH OWNER,PROVIDE 1-1/2"CONDUIT FROM PHONE BOARD TO MAIN BUILDING PHONE DISTRIBUTION CENTER.INSTALL BONDING AND OPERABLE POWER SYSTEM FOR THE FIRE SUPPRESSION SYSTEM.VERIFY W/MECHANICAL CONTRACTOR EXACT REQUIREMENT. CHECKED BY: BMG JUMPER#6 MINIMUM PER NEC 800.100(D).VERIFY REQUIREMENT WITH OWNER AND LANDLORD. � ❑ o ❑ O 29. SHOW WINDOW RECEPTACLES TO INSTALLED PER N.E.C.ROUTE CIRCUIT THROUGH CONTACTOR FORON/OFF CONTROL WITH 12. TIME CLOCKS:PROVIDE AND INSTALL TIME CLOCKS.SEE DETAILS ON SHEET E700 FOR ADDITIONAL INFORMATION.PROVIDE ONE DUPLEX INTERIOR LUMINAIRE CIRCUIT.SEE LIGHTING LIGHTING CONTROL DETAIL C,SHEET E100 SHEET TITLE: A NEMA GFCI RECEPTACLE FOR TIME CLOCKS.VERIFY MOUNTING HEIGHT W/OWNER. �30. CAMERA SYSTEM:PROVIDE AND INSTALL J-BOXES AND CONDUIT AS REQUIRED BY OWNER FOR CLOSED CIRCUIT CAMERA SYSTEM. A POWER PLAN 13. APPROXIMATE LOCATION OF NEW ELECTRICAL PANELS.VERIFY WITH OWNER AND ARCHITECT. PROVIDE 120V POWER CIRCUITS POWER AS REQUIRED BY OWNER,ROUTE ALL POWER TO CIRCUIT KB-1 14. A/C CONTROL CONDUIT:PROVIDE 1/2"CONDUIT WITH PULL STRING FROM FOR THERMOSTAT TO A/C UNIT ON ROOF FOR CONTROL WIRE. 31. RECEPTACLE FOR BACK-UP COMPRESSOR#48.1,IF REQUIRED. O O O CONTROL WIRE BY OTHERS. 15. ICE MACHINE:PROVIDE DISCONNECTING MEANS FOR#32 ICE MACHINE.PROVIDE ALL CONDUIT AND WIRE FOR POWER AND CONTROL. MOUNT @48"A.F.F.OR PER MANUFACTURER.VERIFY EXACT ELECTRICAL REQUIREMENTS WITH EQUIPMENT MANUFACTURER. O O 16. DOUGH ROUNDER:PROVIDE A J-BOX WITH 20A 1-POLE TOGGLE DISCONNECT SWITCH FOR#25 DOUGH ROUNDER.PROVIDE 1/2"C,2#10, 1 1 O 1#10 GND CU THWN. _�7"l I 0 I1 SHEET NUMBER: 17. HOT WATER:PROVIDE DISCONNECTING MEANS FOR#28 HOT WATER. /\ ��O O 18. FOOD MIXER:PROVIDE A 20A 3-POLE NON-FUSED DISCONNECT SWITCH FOR#26 FOOD MIXER.PROVIDE 3/4"C,3#10,1#10 GND CU THWN. i Power Plan E200 Scale:1/4"=V-0" BASIC ELECTRICAL REQUIREMENTS W O W N m p 1. Furnish all labor and materials and perform all operations necessary for the installation of complete 36. Empty conduits shall be complete with pull-string.Conduit shall be EMT thinwall with steel setscrew w m Q m m v z and functioning new and existing electrical systems,as specified and as required by code. couplings and connectors unless othewise notedconduits shall he run perpendicular and parallel to Existing AIC Rating l8,000 Ra,ed Panel Wiring Schedule(3-Phase) _ Rated o m v v Ls building walls,beams and joists when not concealed behind walls or ceilings. Panel Wiring Schedule(3-Phase) AIC Rating o m❑ Ir Fed fmm UTILITY V 2. COnlreetc shall be responsible for Verifying operation of all existing equipment and systems to PanelboaM KA Voltage 208VI120 Phase 3 Options/No,es PenelboaN KB Voltage 208V/120 Phese 3 Options/Ne,es Fed from PA,NEL.- ED Z m )N m Z Q`D Q m DD p remain.Contractor shall provide new or repair existing systems or equipment that are missing or 37. Provide hangers,inserts(of a lead shield type)and supports,as required.Support all branch Panel Type PB OCPO 400A MLO wire 4 Panel Type NOOD OCPD 200A MCB wire 4 J ED 0 i0 N malfunctioning to comply with note#1 above. conduits for power and communications from building structure;do not caddie clip to ceiling hangers. NEMA Type 1 Mounxng FLUSH Buss 400A NEMA Typa 1 Mounting FLUSH Buss 200 m N O m L9 a 3 z 3. Install all electrical equipment and appurtenances in accordance with manufacturers' 38. Pull boxes shall be provided for all conduit runs of 50'and/or more than the equivalent of 2-9W Ckt. Brkr. Brkr. N.E.C. N.E.C. Brkr. Brkr. Ckt. Ckt. Brkr. Brkr. N.E.C. N.E.C. Brkr. Briar. Ckt. 3 J 0 w i.i m 7 3 recommendations and written instructions,contract documents,and applicable codes and bends. No. Load Description Size Opts. VA Phase VA Opts. Size Load Description No. No. Load Description Size Opts. VA Phase VA Opts. Size Load Description No. z MM, m m i 4 3 regulations. * ** ** * ** ** - Z a 39. Protection of wiring and equipment shall be by means of circuit breakers,fuses and switches and of w 4. Coordinate and order the progress of electrical Work to conform to the Owner's schedule and the types antl ratings acceptable to the inspection department.For protection of the primary side of dry 1 LIGHTING-DINING 20/1 200 A 500 20/1 #52 POS 2 1 #28 HOT WATER DISPENSER 20/1 1500 A 1656 eon #25 DOUGH ROUNDER 2 progress of the work of the other trades. type transformer and electric motors use Time Delay fuses,HRCI type,unless indicated otherwise. 3 LIGHTING-KITCHEN,REST. 20/1 825 B 4380 EXISTING 4 3 #46 WATER HEATER IGNITION 2011 98 B 1800 25/1 #82 GLYCOL CHILLER 4 5 LIGHTING-HALLWAY,TRACK 20/1 426 C 4380 HACK 50/3 RTU-1 6 5 2011 720 C 1080 2011 #4.1 REFRIGERATED TABLE 6 5. Coordinate all equipment connections with manufacturers'certified drawings and/or documents. 40. Grounding Provide all equipment grounding as required to confirm with the applicable safety code. 7 TIME CLOCKS 2011 300 A 4380 8 7 #4.1 REFRIGERATED TABLE 2011 1080 A 1080 2011 #4.2 REFRIGERATED TABLE 8 Coordinate and provide all conduit and transitions required for final equipment connections to Arrange grounds so under normal operating condifions no injurious amount of current will flow in any 9 SHOW WINDOW REC. 2011 360 B 4380 EXISTING 10 9 SPARE 2011 - B 1080 20/1 16 DISPLAY CASE 10 D furnished equipment. grounding conductor.Ensure continuity of equipment grounding(conductors,connectors, 11 SPARE eon C 4380 HACK 50/3 RT11 12 11 #13 ILA LIKEWILK 2011 1680 C 1200 20/1 CONVENIENCE RECEPTACLE 12 D accessories)and connect to the existing building system at the nearest location.Conform to the 13 SPARE 2011 A 4380 14 13 #7 PIZZA OVEN 2011 480 A 480 20/1 #20 UNDERCOUNTER REFRIGE 14 6. Apply for and pay for all permits,fees,licenses and inspections for this Division of work. requirements of the local authority having jurisdiction.Insulated grounding conductors shall be green. 15 CAMERA SYSTEM 2011 320 B 3050 EXISTING 16 15 SHUNT TRIP B 1150 15/2 #1 DOUGH PRESS.MANUAL 16 7. Cora with state and local code requirements and ordinances.Cora with requirement.of the 41. Lighting system Temporary lighting hall be provided throughout project in both hard ceilings and in 17 #7.2 ANSUL SYSTEM 2a1 540 C 3050 HACR 40/3 RTU-3 18 17 #33 BAG IN BOX 2011 900 C 1150 18 ■ Comply wi q Comply q b g sng p ry g g s iced g actor. 9 19 1587 A 3050 20 19 CONVENIENCE REC.DINING 2011 720 A 2300 30a #1 DOUGH PRESS.PNEUMATIC 20 Utility Companies.In the case of differences between these requirements and ordinances,the most T-bar ceiling areas,by this trade where required by general contractor.All new and/or relocated light HOOD EXHAUST FAN 15/2 stringent shall govern.Call for inspections required by local building inspection authority. fixtures must be independently supported from structure per code. 21 1587 B 98 20/1 #46 WATER HEATER IGNITION 22 21 CONVENIENCE REC.BACK 2011 720 B 2300 22 23 ROOF MAINT.REC. 2011 360 C 1445 2orz #3210E MAKER CONDENSER 24 23 RESTROOM REC.AUTO FAU 2011 600 C 360 20/1 #15 COKE AND ICE DISPENSER 24 8. Submit shop drawings for all materials and equipment showing any changes required in electrical 42. Circuitry shown on plans is for grouping purposes only.Exact circuits are to be determined on site 25 SMOKE DETECTOR 2a1 250 A 1445 26 25 #48.1 BACK UP COMP. 2011 1680 A 360 2o/1 EXHAUST HOOD LIGHTS 26 wiring,space allocation,etc. based on availability.Record on panel directory and on"as-built"drawings.Circuitry shown on plans 27 #52 POS 2011 500 B - 2011 SPARE 28 27 SPARE 2011 -- B 968 2011 WALK IN LTS,DOOR HTR COND. 28 V//� B� ° as existing shall be verified for continuity on site by this contractor prior to commencing new work. 29 REC.AT POS 2a1 360 C 400 20/1 AIR COMPRESSOR 30 29 SPARE 2011 C 707 15/2 WALK IN FREEZER EVAP&HTR 30 t 1 9. The location of existing underground/concealed utilities is shown in an approximate way only.The Verify that not more than six duplex receptacles are connected to any one circuit.Record existing 0 o /r�■ E contractor shall determine the exact location of all existing utilities before commencing work.The circuitry on panels and on"as-built"drawings. 31 PHONE BOARD 2a1 200 A 1321 32 31 #53 AIR CURTAIN 20/3 300 A 707 32 ,V cent rector shall pay for and repair all damages caused by failure to exactly locate and preserve any 33 REC.-MANAGER OFFICE 20/1 360 B 1321 20/3 #48 COMPRESSOR 34 33 300 B 1310 2orz WALK IN FREEZER COMP 34 and all underground utilities. 43. Contractor to verity and make necessary adjustments to ensure that loading on each phase is 35 #113 POS SYSTEM REC. 2011 400 C 1321 36 35 300 C 1310 36 V balanced.(unbalanced load shall be less than 10%).Provide a typed circuit directory in each panel. 37 #5.1 PRINTER 2a1 200 A 13759 38 37 #26 FOOD MIXER 2. 1200MB 216 1 1 38 10, Patch and repair to match existing any walls,ceilings,or Floors accessed during the installation of 39 #5.1 PRINTER zo/1 200 B 10979 200/3 PANEL'KS' 40 39 1200 1133 2orz WALK IN COOLER COMPRESSOR 40conduitand wiring. 44. Provide lock-on devices on fire alarm,emergency lighting,night-lights,security and exit light circuits, 41 EXTERIOR SIGNAGE eon 1200 C 1234042 41 1200 1133 42 as required. PHASE A 3157PHASE1375911, Maintain one set of redlined drawings on the job site indicating all changes and deviafions from the PHASE B 28360 PHASE10979 work shown on the drawings. 45. When a 15A or 20A circuit breaker is used as the only switching device for fluorescent luminariesPHASE C 30602 PHASE12340the circuit breaker shall be suitable for switching duty and shall be marked"SWD".12. Prior to final acceptance,thoroughly clean all work. TOTAL90534 TOTAL37078 Jm ^ 46. Life safety systems work shall be performed by the contractor.Where existing emergency lighting is o ee 13, At completion of Work,deliver completed Project Record Documents marked with field changes to not shown,verify on site and revise as required to conform to the new layout shown on plans. SERVICE LOAD SUMMARY f m Owner's Representative. 47. Electrical Contractor shall test all emergency lighting and submit letter of certifications,listing the SERVICE LOAD SUMMARY LOAD DESCRIPTION DEMAND FACTOR VOLT-AMPS 14. Pro a written warranty to the Owner covering the entire electrical work to be free from defective floor,and the date tested. D.F. CONNECTED DEMAND vide u, materials,equipment and workmanship for a period of one year after Date of Acceptance. LOAD DESCRIPTION DEMAND FACTOR VOLT-AMPS LIGHTING&SIGNS 1.25 1328 1660 48. Smoke detectors shall be furnished and wired by the electrical contractor.The mechanical contractor D.F. CONNECTED DEMAND RECEPTACLES REMAINDER O 150% 3240 3240 LIGHTING&SIGNS 1.25 33tt 4t 3B 15. All reports,plans,specifications,computer files,field data,notes,and other documents and shall be responsible for mounting the smoke detector in ductwork in accordance with manufacturer's MOTORS ALL O t00% 7466 812t 0 ALL DRALMNcs ANO 1L91TMN MATERIAL instruments prepared by MEA Consulting Engineers,Inc.,as instruments of service shall remain the printed instmctions. RECEPTACLES 1st 10KVA O t50R 6470 6470 PLUS 25%OF LARGEST CONTAINED HEREIN ARE ME PROPERTY OF P 9 9 REMAINDER O SOR ME UNCLE DE9GN CROUP,INC.MEY MAY property of the Consultant.MEA Consulting Engineers,Inc.shall retain all common law,statutory MOTORS ALL O 100% 16543 20678 MISC.EQUIPMENT 1.00 9310 9310 NOT BE REUSED,COPIED,REUSED,OR and other reserved rights,including the copyright thereto. 49. Final inspection certificate shall be submitted upon completion of contract Final payment shall be PLUS 25%OF LARGEST KITCHEN E UIPMENT N.E.C.65% 15734 15718 DlscLosED IN ANY MANNER MMoui MITTEN subject to receipt of this certificate. MISC. EQUIPMENT 1.00 -- -- HVAC E UIPMENT 1.00 -- -- Au1HORF2AVON FROM mE ARCHITECT. 16. If MEA Consulting Engineers,Inc.for any reason is not allowed to Complete all the services Called KITCHEN E UIPMENT N.E.C.65% 28780 18707 - 37078 38047 C for by this Agreement,MEA Consulting Engineers,Inc.shall not be held responsible for the 50. Identification shall include provision of a lamacoid label on each enclosure,relay or other device. HVAC E UIPMENT 1.00 35430 36144 PANELBOARD LOAD= 35047 V.A. accuracy,completeness or constructability of the construction documents prepared by MEA Color and format are to match base-building.Provide a typed circuit directory in each panel.Tag all TOT - 90534 86137 FULL LOAD AMPS 106 A. C Consulting Engineers,Inc.if used,changed or completed by the Client or by another party. cabling. PANELBOARD LOAD 86137 V.A. Accordingly,the Client agrees,to the fullest extent permitted by law,to indemnify and hold harmless FULL LOAD AMPS= 239 A g5\ONALgF�N MEA Consulting Engineers,Inc.,its officers,directors,employees and subconsultants(collectively, 51. Contractor shall provide shop drawings. MEA Consulting Engineers,Inc.)from any damages,liabilities or costs,including reasonable attorneys'fees and defense costs,arising or allegedly arising from such use,change or completion 52. Alternatives to the materials specified herein and/or on the drawing may be submitted separately a 93�6 v by any other party of any construction documents prepared by MEA Consulting Engineers,Inc.. showing any change to the base contract price for their substitution. p 17. Hard-copy,construction documents or electronic files furnished by either party shall be subject to an 53. Operating&maintenance instruction prepared by manufacturers shall be as indexed in 3-ring �9q OF acceptance period of 60 days during which the receiving party agrees to perform appropriate binders for submission in triplicate. 9FLL R-O acceptance tests.The party furnishing the hard-copy construction documents or electronic files shall 017 correct any discrepancies or errors detected and reported within the acceptance period.After the 54. Landlord's guidelines for tenant construction shall be strictly adhered to by this contractor. acceptance period,the hard-copy construction documents or electronic files shall he deemed to be accepted and neither party shall have any obligation to correct errors or maintain hard-copy FIRE PROTECTION construction documents or electronic flies. The fire alarm system shall be designed and installed by an approved design build contractor.All 18. The Client and MEA Consulting Engineers,Inc.agree that any hard-copy construction documents or construction documents shall be submitted to MEA Consulting Engineers,Inc.for review and approval electronic flas furnished by either party shall conform to the specifications.Any changes to the prior to submission for permit and construction.electronic specifications by either the Client or MEA Consulting Engineers,Inc.are subject to review Q and acceptance by the other party.Additional services by MEA Consulting Engineers,Inc.made BASIC MATERIALS AND METHODS ■ necessary by changes to the hard-copy construction documents or electronic file specifications shall [ ~ be compensated for as Additional Services. 1. The electrical drawings indicate the general design and arrangement of conduit and wiring, - F-,zo 00 equipment,systems,etc.information shown is diagrammatic in character and does not indicate ■ LLJ 19. Under no circumstances shall delivery of electronic files for use by the Client be deemed a sale by every required offset,fitting,etc. MEA Consulting Engineers,Inc.,and MEA Consulting Engineers,Inc.makes no warranfies,either F a C:) express or implied,of merchantability and fitness for any particular purpose.In no event shall MEA 2. The locations of the items shown on the drawings or called for in the specifcations that are not ■ Consulting Engineers,Inc.be liable for indirect or consequential damages as a result of the Client's definitely fixed by dimensions are approximate only.The exact locations necessary to secure the ® J use or reuse of the hard-copy construction documents or electronic files. best conditions and results must be determined by the project site conditions and shall have the [ Li J approval of the engineer before being installed.DO NOT SCALE THE DRAWINGS(unless noted 20, General:Refer to the architectural specifications,The general conditions,bid form,schedule of otherwise). O completion,etc. 3. Contractor shall field verify locations and sizes of all existing equipment,electrical conduit,structural Q z 21. Electrical contractor shall be responsible for submitting construction documents to the local utility members,etc.prior to bid.Contractor shall notify engineer of any and all discrepancies between field N company for review and approval prior to ordering equipment. conditions and contract drawings. 22. Scope of work includes but is not limited to,the furnishing of labor,material,tools and equipment 4. Where beams are indicated to be penetrated with conduits and wiring,coordinate duchvork and B required to complete installation and testing of all systems shown on the drawings and specified piping layout with beam opening size and opening locations.Coordination shall be done prior to B herein,including: fabrication of beams. • Lighting EXISTING • Power 5. All conduit,wiring and equipment supported from structural steel shall be coordinated with the GC. EXTERIOR TENANT SPACE • Data Conduit All attachments to steel bar joists,trusses,or joist girders,shall be at panel points.Provide beam DISCOPH/3R/4SER • Telephone Conduit clamps meeting MSS standards.Welding to structural members,shall not be permitted.The use of DISCONNECT SERVICE ENTRANCE RATED • Life Safety Systems C-clamps shall not be permitted. EXISTING CT AND 23. No extra charge for material and labor shall be added to the contract for outlets moved within 10 ft. 6. Electrical equipment,conduit and wiring shall not be supported from metal deck. METER from the location shown on the plans prior to mugh-in. BY LANDLORD BY EC 7. Use adjustable pipe hangers on suspended conduit.Provide hangers to support the systems 'I KA KB GENERAL NOTES: 24. Unless instructed otherwise,electrical contractor is responsible for removal of all wiring,cables and without sagging.Include hangers at each offset or change in direction and at ends of branches over - 400A 200A electrical devices existing in walls to be demolished and removal of all other redundant electrical five feet in length. EXISTING UTILITY EXISTING NEW 42 POLE 42 POLE 1. E.C.TO VERIFY ALL EXISTING EQUIPMENT,INCLUDING METER SECTION,AND devices not shown on plans.Cut back and Cap unused raceways and outlets and remove unused TRANSFORMER PROVIDE REQUIRED EQUIPMENT TO HAVE A COMPLETE AND OPERATING wiring back to panel board. 8. Sleeves and boxes shall be provided wherever conduits pass through floor,wall and roof SYSTEM. construction. 120/208V 120/208V 25. Where the distribution of power and communication is through a floor system electrical contractor 9. Where horizontal Conduits and wiring ass through walls and vertical ducts and es ass through floors or EXISTING(DIR4)#3LIT/0,(1)#6G IN 2. ALL ELECTRICAL TO BE IN ACCORDANCE WITH THE NEC AND ALL LOCAL shall ensure access at handholes at all times.Provide Floor pan covers throughout the premises. 9 P 9 pipes P 9 ORDINANCES. roofs,seal off void between opening and duct or pipe and sleeve,with an approved non-combustible material. 26. Coordination of work shall be done with all other trades on the site to the extent of properly locating 3. E.C.TO COORDINATE WITH LOCAL UTILITY FOR INSTALLATION OF NEW _ all devices,fixtures,equipment,piping,ductwork,etc.This contractor shall be responsible for 10, Install nickel-plated floor,wall and ceiling escutcheons of adjustable type on conduits passing through walls, METER AND SERVICE TO TENANT SPACE. -- obtaining accurate dimensions from the architectural drawings and at the si te. floor or ceiling in finished areas. EXISTING BY EXISTING EXISTING LANDLORD 27. Electrical Division shall supply all starters and do all control wiring unless otherwise noted. 11. Provide all excavating and backfilling required by the work in this division. CONDUIT AND WIRE TO Mechanical Division to install starters and line side wiring and provide all required isolating REMAIN disconnects switches 12. Furnish and install all foundations,bases and supports. 05 28. Base-building systems shut down or affected in any way must be coordinated with building's 13, Concrete housekeeping pads to suit electrical equipment shall be sized and located by the electrical operating staff to obtain landlord's approval. contractor.Minimum concrete pad thickness shall be 6 inches.Pad shall extend beyond the 1 OneLlne Diagram equipment a minimum of 6 inches on each side.Concrete housekeeping pads shall be provided by 29. Access doors&panels are to be supplied by others and located on the site by this trade where the general contractor(GC).It shall be the responsibility of the size and location of concrete E300 Stale:No Scale PROJECT NUMBER: ].MG requiredtoservicenew or existing equipment and/or systems.Coordinate to ensure installation of housekeeping pads with general contractor.electrical contractor to coordinate. DRAWN BY: same. 14. Reinforcement,detailing,and placement of concrete shall Conform to ASTM 315 and ACI 318. CHECKED BY: 30. Core drilling of concrete structure is permitted only with use of x-raying to detect embedded Concrete shall conform to ASTM C94.Concrete work shall conform to ACI 318,part entitled materials.Perform x-raying outside normal Working hours in coordination with building management "Construction Requirements". and tenants. SHEET IL: A UNAUTHORIZED CHANGES A ONE LINE 31. Materials required for the performance of the work shall be new,of uniform pattern throughout, except as noted otherwise,all materials shall be equal to the base-building materials. In the event the Client,the Client's contractors or subcontractors,or anyone for whom the Client is legally liable makes or permits to be made any changes to any reports,plans,specifications or other NOTES 32. Approvals shall be provided by the manufacturer where required by federal,provincial or local construction documents prepared by MEA Consulting Engineers,Inc.without obtaining MEA Consulting authorities. Engineers,Inc.'s pnorwritten consent,the Client shall assume full responsibility for the results of such &SCHEDULE changes.Therefore the Client agrees to waive any claim against MEA Consulting Engineers,Inc.and to 33. Conductors shall be copper,to suit load or breaker size indicated on plans,but not less than#12 release MEA Consulting Engineers,Inc.from any liability arising directly or indirectly from such changes. AWG.For electric motors(air conditionings,heat pumps,etc.)minimum Conductor size shall be#10 In addition,the Client agrees,to the fullest extent permitted by law,to indemnify and hold harmless MEA AWG. Consulting Engineers,Inc.from any damages,liabilities or costs,including reasonable attomeys'fees and costs of defense,arising from such changes.In addition,the Client agrees to include in any contracts for 34. All conductors shall be installed in EMT conduit except for branch wiring to fixtures,which shall not construction appropriate language that prohibits the Contractor or any subcontractors of any tier from SHEET NUMBER: exceed 1 OR in length.Except that,branch wiring to fixtures and devices not exceeding 10'in length making any changes or modifications to MEA Consulting Engineers,Inc.'s construction documents ///��� may be installed in armoured sheathing. without the prior written approval of MEA Consulting Engineers,Inc.and that further requires the )O O Contractor to indemnify both MEA Consulting Engineers,Inc.and the Client from any liability or cost 35. Connections to equipment that produce noise and or vibrations(transformers,motors,generator set, arising from such changes made without such proper authorization. 3 dimming rack,etc.)Shall be made with flexible conduit.Use minimum 3 feet of flexible cable with slack at each device. EQUIPMENT LIST w w 01NAm CAT Be(or 6) F BT 3 m 01 z ETHERNET ELECTRICAL 0 OR ao OR m y PROVIDED INSTALL C.B. z- Z Eo `0 0 m CAT 5e(or 6) EQq QTY DESCRIPTION MANUFACTURER MODEL FLA VA CONNECTION MI HT.A.F.F. NOTES EO# i a 4 m�o w ETHERNET BY BY V B AMPSIPOLES LD w o N Ln ❑ n a aQ 30 m z 1 1 PIZZA DOUGH PRESS-PNEUMATIC DOUGHPRO DP23009ZE KES GC 208 1 60 22.1 4600 3012 NEMA6.30R 18" 1 1 3 W ❑w - m w K 1.1 1 PIZZA DOUGH PRESS-MANUAL DOUGHPRO DP1100BZE KES GC 208 1 60 11.05 2300 1512 NEMA6-15R 18" 1 1.1 i N J m LJ7 3 1 4 0 REFRIGERATED SANDWICH UNIT-2T CONTINENTAL SW'27-B-FB KES GC 120 1 60 8.2 984 2011 NEMA S20R 18" 1,2 4 J ^ED O a CABLE/S 4.1 1 1 1 REFRIGERATED SANDWICH UNIT-60' CONTINENTAL $W60-24MIOOBP KES GC 120 1 60 9 1 1080 1 2011 NEMA6-20R 18" 1,2 4.1 4.2 1 REFRIGERATED SANDWICH UNIT-72' CONTINENTAL SW'72-30MIOOBP KES GC 120 1 60 7.3 876 2011 NEMA S20R 18" 1,2 4.2 CONDUIT BUSHING WITH TERMINATION Oi PATCH PANEL AT BACK OFFICE ro AT6"ABOVE FINISHED CEILING. ® ® ® ® 4.3 0 REFRIGERATED SANDWICH UNIT-32 CONTINENTAL SW32-12MMBP KES GC 120 1 60 6.3 756 2011 NEMAS20R 18" 1,2 4.3 D 314"CONDUIT WITH CEILING GRID O2 POSTERMINALS O O O (a) 5 2 PRINTER EPSON TM-88111 VENDOR GC 120 1 60 1.6 200 2011 NEMA5.20R 18" 1 5 D MRIL PULL STRING AS NOTED. 4 1 O3 REMOTE PRINTERS 5A 2 LABEL PRINTER EPSON TM-L90 PLUS VENDOR GC 120 1 60 1.6 200 2011 NEMA6-20R 18" 1 6.1 RECESSED SINGLE GANG 4E ELECTRICAL BOX. FRONT BREATHING REFRIGERATED DISPLAY Morem 6 1 FEDERAL IND. ELPRSS3-BP KES GC 120 1 60 ifi 1920 2011 NEMA 520R 18" 1,2 8 m p ALL CAT- OR CAT-6 CABLE SHALL BE IN CONDUIT PUNCHED CASE W/CASTERS DOWN WITH RJ45'S USING B CONFIGURATION.TERMINATIONS BY DUAL my SYMBOL ON DRAWING TELECOM CONTRACTOR. 7 1 FIRE DECK OVEN,GAS WOODSTONE FD-9660-RFGLR-IR KES GC 120 1 60 4 480 2011 J-BOX 2P DISCONNECT VERIFY 1,6 7 FINISHED FLOOR LV Cablin 7.1 1 TYPE 1 HOOD WOODSTONE SG-BOLOWS-72-F KES GC 208 1 60 5.4 1123 15/2 J-BOX 2P DISCONNECT VERIFY 1,5 7.1 Detail A a Detail 7.2 1 ANSUL SYSTEM ANSUL R-102 GC GC 120 1 60 1.5 180 2011 J-BOX IF DISCONNECT VERIFY 1,5 7.2 �° •A v 6 E400 Scale:NT$ E400 Scale:NT$ 13 1 TEABREWER BUNN TB3Q COKE COKE 120 1 60 14 1680 2011 NEMA5-20R 1. 1 13 a V/'!!• E 15 1 COKE B ICE DISPENSER LANCER IBD4500 COKE COKE 120 1 60 3 360 2011 NEMA5.20R 18" 1 15 16 2 BEVERAGE DISPENSER CRATHCO D253 KES GC 120 1 60 6 720 2011 NEMA5-20R 1. 1 16 �r OB 20 1 UNDERCOUNTER REFRIGERATOR CONTINENTAL UC27 KES GC 120 1 60 6.3 758 2011 NEMA 620R 18" 1 20 2 25 1 DOUGH ROUNDER SOMERSET IND. SDR400BZ KES GC 120 1 60 13.8 1656 2011 J-BOX,1P DISCONNECT IF 1 25 V y EXISTING STRUCTURE � 26 1 FOOD MIXER HOBART HL862-1STD KES GC 208 3 60 10 3800 2013 J-BOX,3P DISCONNECT 48' 1 28 OD C 28 1 HOT WATER DISPENSER BUNN H5E-18-120 KES GC 120 1 60 12.5 1500 2011 J-BOX,2P DISCONNECT 48' 1 28 0 w or$Ra o 32 1 ICE MAKER MANITOWOC IY-1196N KES GC 208 1 60 13.9 2891 2011 J-BOX,2P DISCONNECT 48' 1 32 of^^� 33 1 BAG-N-BOX SYSTEM - - Venda Vendor 120 1 60 5 900 2011 NEMA 520R VERIFY 1 33gMM� ---- HILTI CC27 CLIP OR EQUAL 46 1 WATER HEATER GC GC 480 3 60 24,000 4013 J-BOX,3P DISCONNECT 18" 1 4fi u, SEISMIC RESTRAINT 1 WALK-IN FREEZERICOOLER COMPRESSOR KOLPAK A034071R2 KES GC 208 1 60 10A 2163 20C2 J-BOX,2P DISCONNECT VERIFY 1,3,4 47 #12 SAFETY WIRE TIED TO 47 CLIP MINIMUM (4) 1 WALK-IN FREEZERICOOLER EVAPORATOR KES GC 120 1 60 1.8 216 1511 J-BOX2P DISCONNECT VERIFY 1,3 SAFTEY WIRE SUPPORT HOLES ®Au NED HERE AND MEEK MAIEBIAL & FASTENED TO BLDG. PER LIGHT FIXTURE, 48 1 AIR COMPRESSOR POWERE% SES030&BP KES GC 208 3 60 11.0 3963 2013 J-BOX,3P DISCONNECT VERIFY 1 q8 corvraweD xe6ery ARE ME PROPERtt OF STRUCTURE. MINIMUM (2) SEC PLY ATTACHED ME UNCLE DE9CN CROUP,INC.THEY MAY SAFETY WIRES PER LIGHT '� Q� TO CEILING CALIFORNIAAIR NOT BE REMSED,COPIED,REuseD,OR FIXTURE PLACED AT DIAGONAL '� GRID-TYPICAL 48.1 1 BACK-UP AIR COMPRESSOR TOOLS 10020C-110V KES GC 120 1 W 14 1680 2011 NEMA S20R VERIFY 1 48.1 ISCLOOED IN ANY Aumoarzanon HeoMANNER AMON mn6cxllEcrxxl7lEx CORNERS .1 EXPOSED T-BAR CEILING 52 2 POSTERMINAL SDCR SDCR VERIFY 52 C / C 53 1 AIR CURTAIN MARS N236 GC GC 208 3 60 2.5 900 2013 J-BOX 3P DISCONNECT VERIFY 55 NO 55 0 REACH-IN FREEZER CONTINENTAL IF KES GC 120 1 60 8.7 1044 2011 NEMA&20R 18, 1 53 g`'\ONAL FN NOTE LIGHT FIXTURES •FIXTURE INSTALLATION TO COMPLY 55.1 0 REACH-IN REFRIGERATOR CONTINENTAL 1R-GD KES GC 120 1 60 10.7 1284 2011 NEMA 520R 18" 1 55,1 SAFETY WIRE WITH ASTM C 635 AND ASTM C 636. a p SUPPORT HOLE, 60 1 SECURITY CAMERAS AND ALARM SYSTEM - - T T 120 1 80 2011 NEMA&20R 18" 1 58 9316 •ALL WIRES ARE TO BE TAUT WITH A Ord O TYPICAL MINIMUM OF 3 TIGHT TURNS AROUND 82 1 GLYCOL CHILLER UBC GROUP TOTTON H-35G VENDOR 120 1 60 3 360 2011 NEMA 5.20R I 1 82 �q p SELF - TYPICAL y,� OF\04g4i 98 1 POS SYSTEM SDCR SDCR Vendor Vendor 120 1 60 3.5 420 20/1 NEMA 5.20R VERIFY 1 113 9FLL V%. �c� Recessed Light Fixture Support "tee AR 48A 017 E900 Sole:No Scale 1.VERIFY EXACT CORD AND PLUG REQUIREMENTS AND MOUNTING HEIGHT FOR ALL EQUIPMENT WITH EQUIPMENT VENDORIOWNER PRIOR TO COMMENCING ROUGH-IN. 2.MOUNT ELECTRICAL DEVICE IN CASEWORK,RACEWAY TO BE MOUNTED WITHIN CASEWORK(OR WALL)SO AS TO BE CONCEALED FROM VIEW. 3.ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL ALL POWER AND CONTROL WIRING NECESSARY FOR A COMPLETE INSTALLATION OF WALK-IN COOLER$AND FREEZERS.THIS INCLUDES WIRING AND CONNECTIONS TO LIGHTS,SWITCHES,EVAPORATORS,CONDENSING UNITS, DEFROST TIMERS,DOOR HEATERS,ETC.COORDINATE INSTALLATION WITH KITCHEN EQUIPMENT SUPPLIER.ALL PENETRATIONS INTO UNITS SHALL BE WATER TIGHT AND PROPERLY SEALED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION.ALL ELECTRICAL DEVICES WITHIN WALK-IN UNITS SHALL BE WEATHERPROOF. 4.WALK-IN COOLER IS A SPLIT SYSTEM WITH COMPRESSOR LOCATED OUTDOORS. O HOOD MAX MICROSWITCH STATUS WITH 5.PROVIDE ELECTRICAL POWERICONTROL CIRCUITS TO EXHAUST FANS,MAKE-UP AIR FAN,AND A/C UNIT.INTERLOCK FOR SIMULTANEOUS OPERATION.SEE MECHANICAL PLANS FOR ADDITIONAL INFORMATION.COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT REQUIREMENTS. L H- r7 LIGHTS 1400 WATTS BLU FIRE SYSTEM ARMED L �9 INPUT POWER TOTAL INPUT POWER 120 VAC 6.PROVIDE INTERLOCK WITH KITCHEN HOOD ANSUL FIRE SUPPRESSION.PROVIDE FOR SHUT-OFF OF ALL AIR MOVING EQUIPMENT AND TO ELECTRICAL OUTLETS SERVING EQUIPMENT UNDER HOOD. (n 00 LIGHT CONTROL 7.PROVIDE FT.MOLDED CASE RECEPTACLE AND PLUG OF NEMA CONFIGURATION LISTED.PLUG TO BE WIRED DIRECTLY TO EQUIPMENT TERMINAL STRIP.RECEPTACLES RATED OVER 20A SHALL HAVE TWIST LOCKS. L L CIRCUIT CIRCUIT ANsuL or YROCHEM AN BUL or YROCHEM "EQUIPMENT SCHEDULE IS PROVIDED BY CORPORATE APPROVED KES.CONTRACTOR SHALL CONFIRM MAKE,MODEL,AND SIZE PRIOR TO ORDERING ANY EQUIPMENT.IF ANY DISCREPANCIES EXIST IN SIZE,MAKE,OR MODEL THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER o W *S2 MICROSWITCH MICROSWITCH AND ARCHITECT AND AWAIT FOR DIRECTION.SHOULD CONTRACTOR ORDER EQUIPMENT WITHOUT CONFIRMATION,CONTRACTOR DOES SO AT OWN RISK AND ANY ASSOCIATED COST. f a CTERMINALS OC-NO-NC.2 FOR SHUTDOWN FOR FIELD"BRN11I WIRING TO L J BUILDING FIRE x x z PANELO DRY CONTACTS Il� L<J FOR SIGNAL ONLY BRN Lu N BILK NC 1 BLK R L_ BILK NO 1 RED C 1 BRN LU/WHT NC 2 B NO2 BM B WHT C 2 RED LKNJHT ORG YEL ®®®®® Al NC- 0 o THIS IS A GENERIC WIRING DIAGRAM AND IS NOT SPECIFIC TO 0 m 0 m NO- ANY RTU OR MUA. ®®®®® ®®®®o C- E.C.TO VERIFY CONNECTIONS WITH ACTUAL EQUIPMENT USED TO PERFORM THE FOLLOWING BASIC SEQUENCE: COIL ®R R ,1 R1 WHEN FAN SWITCH IS ACTIVATED,EXHAUST FAN AND RTU(S) _ -- �TJ �J RUN. SPARE si osp se oe vT Al AN AN DRY EXHAUST HOOD HAS AUTOSTART WHICH AUTOMATICALLY CONTACTS STARTS THE EXHAUST FAN IF COOKING STARTS WITHOUT THE PC ACTIVATED EXHAUST FAN SWITCH BEING TURNED ON,VIA HOOD WHT BYMOUNTED THERMOSTAT AND CONTROLLER. MICROSWITCH21 22 24 25 26 DRY CONTACTSNCTO BE USED FOR WHEN FIRE SUPPRESSION IS ACTIVATED RTU(S)STOP,GAS HUNT TRIP DEVICE VALVE TOOVEN SHUTS OFF,BUT EXHAUST FAN CONTINUES NOCONTROL TO RUN.CCONTACT RELAY PROJECT NUMBER: 17-420 BY: LSW EXHAUST SUPPLY DKFAN FAN1 cOILLT.BLUCCHECKED BY: BMG LT.BLU R2 SHEET TITLE: A �GROUND� WIRING FOR APPROXIMATELY 12" X 18" X 6" HINGED A ELECTRICAL _ COVERED ELECTRICAL BOX EQUIP.SCHED. &DETAILS Generic Exhaust Hood Wiring Diagram E400 Scale:No Scale SHEET NUMBER: E400